RS-485: Wiring, Termination and Biasing

Lesson 1 of 10 24 min read
Found this useful?

An energy meter answers every request on the bench, through two metres of cable. On site, at the end of 180 m of cable beside a variable speed drive, the same meter answers nine requests in ten, and the missing readings appear as gaps in the energy record that nobody can explain. The meter is not faulty and the software is not faulty. The cable, its two ends and the state of the lines when nobody is sending decide whether the bytes arrive. This lesson shows how an RS-485 bus is wired, terminated and biased, and how to check each of these with a short calculation. #RS485 #IndustrialCommunication #SerialBus

Learning Objectives

By the end of this lesson, you will be able to:

  1. Explain why a differential pair rejects electrical noise that a single wire cannot
  2. Identify the A and B lines of a device whatever letters its maker has printed
  3. Calculate the idle voltage of a terminated bus and choose bias resistors that hold it above the receiver threshold
  4. Compare the delay of a reflection with the bit time and decide whether termination is needed
  5. Check the node count, the stub length and the baud rate of a bus against the usual guidelines

Real-World System Problem: Six devices on 180 m of cable



A cold store has a compressor on a variable speed drive, an energy meter on the compressor feeder, and three more energy meters on other feeders. A small gateway in the control room reads all of them over one RS-485 segment: 180 m of shielded twisted pair with a characteristic impedance of 120 Ω (the resistance that a long cable presents to a fast edge, set by the size and spacing of its wires; an ohmmeter cannot measure it). The gateway is at one end. The compressor meter (address 5), the drive (address 10) and the three other meters are connected along the cable: six nodes in total.

RS-485 runs all six devices on one pair of wires, over hundreds of metres in the electrical noise of a plant room. Its standard defines only the electrical signals. The cable layout, the termination and the idle state are left to the installer, and left to chance they let a bus work at first and fail when a drive starts or the baud rate is raised.

6801201206805 Vbiasline Bmeter 5, drive 10 and twometers connect along hereline AbiascommonGateway end180 mlast meter
The bus of this course: a line with a termination at each end

Fundamental Theory: Two wires, one line, two ends



Differential signalling

A simple serial link sends each bit as a voltage on one wire against a common wire, so any noise on that wire is added to the bit. Over a few metres this is acceptable. Over 180 m beside power cables it is not.

RS-485 sends each bit as the difference between two wires: the driver pushes one up and the other down, and the receiver looks only at the difference. The wires are twisted together, so a nearby power cable or drive induces almost the same noise voltage in both, and their difference does not change.

bitB less ADriverReceiverline B plus noisebitline A plus noise
Noise that is equal on both wires leaves the difference unchanged

The standard states the levels. A driver must produce at least 1.5 V between the lines into its rated load. A receiver must decide correctly when the difference is at least 200 mV in either direction. The space between the two values is the allowance for cable loss and noise.

Write the difference as

where and are the voltages of the two lines against the common wire. A receiver reads a 1 when is above and a 0 when is below . Between those two values the output of a standard receiver is not defined. That undefined region is the reason for bias resistors.

The names A and B

The standard names the lines A and B and says that A is negative with respect to B when the bus carries a 1, which is also the idle state. Many makers of transceiver chips print the letters the other way round. Device makers add more names: D+ and D-, or D0 and D1 (in the Modbus serial line guide D0 is A and D1 is B).

This lesson uses the definition of the standard: B is the line that is more positive when the bus is idle, and A is the line that is more negative. The bias resistor to the supply goes on B, and the bias resistor to common goes on A.

One line, not a star

An electrical edge travels along the cable at a finite speed, so the cable behaves as a transmission line: one continuous path with two ends. The cable goes into each device and out again to the next one (a daisy chain).

TTCorrect: one line, a termination (T) at each endnodenodenodenodenodeWrong: a star has five ends and no place toput two terminationsnodenode●nodenodenode
Topology: a line with short stubs, never a star

A short branch from the line to a device is a stub: a small extra line with an open end, so it must be short (Application 2 gives the rule). A star is a set of long stubs. Where the plant layout looks like a star, run the cable out to each device and back, so that the electrical path is still one line.

Reflections and termination

An edge that reaches an open end travels back, as a wave on a rope tied to a wall returns to your hand. This reflection adds to the signal: the level at a receiver rings up and down for a short time after each edge.

The termination, a resistor equal to the characteristic impedance of the cable (here 120 Ω) between A and B at the end, absorbs the edge. Every device may send, so the line needs one termination at each end and none anywhere else.

Whether the reflection matters depends on time. Let be the cable length and the delay per metre, about 5 ns/m for common twisted pair. A reflection from the far end returns to the sender after one round trip:

One bit lasts , where the baud rate is the number of bits sent on the line each second, and the receiver samples near its middle. If the round trip is a significant part of the bit, the level may still ring at that moment.

When termination matters

The usual rule: termination matters when the round-trip delay is a significant part of one bit time. An unterminated line rings for several round trips.

one bit at 9600 baud: 104 µsround trip on 180 m: 1.8 µs (drawn wider than scale)
A bit at 9600 baud against the round trip on 180 m

Every edge makes a reflection, so an unterminated long line rings even at 9600 baud. At low rates the ringing ends long before the sampling point.

Termination has a cost. Two 120 Ω resistors in parallel put 60 Ω between the lines, so the driver supplies more current and the idle bus is pulled towards a difference of 0 V. On 180 m in a plant room, fit both terminations and solve the idle state correctly.

The idle state and biasing

Only one device sends at a time, so between frames every driver is off and the terminations pull the difference to 0 V, inside the undefined region. Noise can then switch a receiver to 0, which looks like a start bit: receivers see characters that nobody sent, and the next real frame loses its first byte.

Bias resistors (also called fail-safe resistors) hold the idle line, as a light spring holds a door shut while nobody pushes it. pulls line B towards the supply , and an equal resistor pulls line A towards common. With no driver active, a small current flows through this chain, and the voltage across the terminations is the idle voltage.

Let be one termination resistor. Two of them in parallel give . The three parts form a voltage divider:

Idle voltage of a biased, terminated bus

The idle voltage must be above the receiver threshold of 200 mV with a margin for noise, a low supply and resistor tolerance. A common design target is 300 mV or more.

The bias network is fitted at one place on the bus only, here at the gateway. Bias resistors at several devices act in parallel, and nobody then knows the real value. Do not take a value from a manual without the calculation: the Modbus serial line guide gives 450 to 650 Ω, with 150 Ω terminations, and 650 Ω on that bus idles at only 273 mV.

A smaller gives a larger idle voltage, but the bias network is also a load on every driver. The standard specifies the driver output of 1.5 V into 54 Ω, and the terminations, bias resistors and receivers together must not present less.

Unit loads and node count

Each receiver draws a small current from the line. The standard defines one unit load as the load of a standard receiver, about 12 kΩ from each line to common, and a standard driver must drive 32 unit loads together with the two terminations. So a bus of standard devices holds 32 nodes.

Many modern transceivers are a fraction of a unit load: 1/2, 1/4 or 1/8. A bus of 1/8 unit-load devices holds nodes electrically. Add the unit loads of every device from its data sheet. The total must not pass 32. When it does, a repeater divides the bus into two segments, each with its own two terminations.

The common wire and the shield

The receiver looks at the difference, but each line must also stay within a range against the receiver’s own common: from to in the standard. Two devices on different supplies can have grounds that differ by more than this. For this reason a “two-wire” RS-485 bus needs a third conductor: a common (reference) wire that joins the signal common of every device.

The shield has a different task: it surrounds the pair and carries noise current away. Connect it to protective earth at one end only, normally at the gateway. Earthed at both ends, it joins two earth points that may be at different potentials, and the current that then flows in it puts noise into the pair it should protect.

Isolation

Where devices are in different buildings or close to large drives, the ground difference can exceed what a common wire can control. An isolated transceiver has no electrical connection between its bus side and the device’s own electronics, so the bus side follows the bus common freely. Isolation at the gateway and at the drive removes most ground problems on a bus of this kind.

Application 1: Is the bias of the cold store bus enough?



Step 1: The idle voltage as built

Click to reveal the idle voltage
  1. Terminations in parallel. Both resistors are between the same two lines.

    The lines see 60 Ω between them. ✅

  2. Idle voltage. The supply drives the series chain of 680 Ω, 60 Ω and 680 Ω.

    The idle voltage is 211 mV. ✅

  3. Margin. above the threshold. A noise pulse of 11 mV between the lines is enough to make a receiver uncertain. ✅

  4. Worst case. Use the low supply and bias resistors that are 5 percent high, .

    At 192 mV the bus idles inside the undefined region. The bias is not enough. ✅

Step 2: Choose the bias resistors

Click to reveal the choice
  1. Largest resistor for the target. Set and solve the divider for .

    A value of 470 Ω gives exactly 300 mV with no margin, so the choice must be lower. ✅

  2. Compare the standard values. Calculate the nominal idle voltage, and the worst case with and resistors 5 percent high.

    Idle, nominalIdle, worst case
    470 Ω300 mV272 mV
    430 Ω326 mV296 mV
    390 Ω357 mV324 mV
    330 Ω417 mV379 mV

    The largest value that stays above 300 mV in the worst case is 390 Ω. ✅

  3. Selected value. gives 357 mV nominal. That is 57 mV (19 percent) above the 300 mV target and 157 mV above the receiver threshold. In the worst case it still gives 324 mV. ✅

Step 3: Check the load on a driver

Click to reveal the load check
  1. What a sending driver sees. Between the lines there are three paths in parallel: the terminations (60 Ω), the two bias resistors in series through the supply (), and the six receivers (). ✅

  2. Total load.

    The load is 54.9 Ω, above the 54 Ω at which the driver output is specified. ✅

  3. How far the bias can go. With the load set to 54 Ω, the same calculation gives as the smallest bias resistor for this bus. So 390 Ω is close to the strongest bias that this terminated bus accepts. ✅

Step 4: Check the answer a second way

Click to reveal the check by current
  1. Bias current. With no driver active, one current flows through the whole chain.

    The network takes 5.95 mA from the supply continuously. ✅

  2. Voltage across the terminations. , the same as the divider result. ✅

  3. Script. The Python script below prints 211.3 mV for 680 Ω, 357.1 mV for 390 Ω, a worst case of 324.2 mV and a driver load of 54.95 Ω. ✅

Check it on the bus. The calculation is only a prediction until the electrician measures it at commissioning.

  1. With every device on the bus switched off, the resistance between A and B at the gateway terminals is about 55 to 67 Ω: the 60 Ω of the terminations, a little less through the bias resistors and receivers, a little more through the cable. About 100 to 120 Ω means one termination is missing. Under 40 Ω means a third termination is switched on (three of 120 Ω in parallel are 40 Ω).
  2. With the devices on and the gateway not polling, the DC voltage from B to A at the gateway is about 0.36 to 0.39 V (the higher value on a long cable). Near 0 V means the bias is not fitted or not powered. A negative value means A and B are swapped at the gateway. A value well above the calculation means another device has its own bias switched on.
  3. Measure again at the last meter. The calculation treats the cable as having no resistance, but 180 m of a 24 AWG pair adds about 30 Ω in series with the far termination. The far end then idles at about 315 mV, lower than the gateway, and about 286 mV in the worst case. This is still above 200 mV, and it is one more reason to keep the margin.

Application 2: Stub length and baud rate for 180 m



Step 1: Round trip against bit time

Click to reveal the timing
  1. One-way delay.

    An edge takes 0.9 µs to travel the length of the bus. ✅

  2. Round trip. . ✅

  3. Bit times and ratios. The bit time is the inverse of the baud rate.

    Baud rateBit timeRound trip as part of a bit
    9600104 µs1.7 percent
    1920052.1 µs3.5 percent
    1152008.68 µs20.7 percent

    At 9600 and 19200 baud the middle of the bit comes 29 and 14 round trips after the edge. At 115200 baud it comes only about 2.4 round trips after the edge. ✅

  4. Decision. At 115200 baud this bus must be terminated. At the two lower rates an unterminated bus would probably pass data, but the bus may be run faster later, so both terminations stay. ✅

Step 2: Longest stub

Click to reveal the stub lengths
  1. Rule as a formula. The stub delay is its length times , and it must be below , where is the driver rise time.

    The limit depends on the driver edge, not on the baud rate. ✅

  2. Fast transceiver. . The cable must go into and out of the device terminals, with almost no branch at all. ✅

  3. Slew-rate limited transceiver. . A drop of a few metres from a junction box to a meter is acceptable. ✅

Step 3: Baud rate that 180 m supports

Click to reveal the rate
  1. Which part of the guideline applies. 180 m is far below 1,200 m, so the bus is in the region where rate times length stays near bit·m/s. ✅

  2. Guideline rate.

    All three baud rates of the problem are below it, and 115200 is below it by a factor of 4.8. ✅

  3. Check a second way. The bit time at 556 kbit/s is , exactly the round-trip delay of Step 1. With , the guideline and the timing argument say the same thing: a bit must last at least one round trip of the cable. ✅

Verify It in Python



The script repeats both applications: the idle voltage as built, the four candidate bias resistors and the timing on 180 m. It then builds the 11 bits of one real character on the wire (the byte 0x05, the address of the compressor meter, with 8 data bits, even parity and 1 stop bit) and saves a plot of idle voltage against bias resistance. The script calls the cold store bus “bus C”.

rs485_bias_and_timing.py
"""RS-485 bus C: idle voltage, bias choice, driver load, reflection timing, one character."""
import numpy as np
import matplotlib.pyplot as plt
VCC = 5.0 # V, transceiver supply
VCC_LOW = 4.75 # V, supply at its lower limit
R_TERM = 120.0 # ohm, one termination resistor
N_TERM = 2 # one at each end of the line
V_THRESHOLD = 0.200 # V, receiver threshold of the standard
V_TARGET = 0.300 # V, design target for the idle voltage
R_LOAD_MIN = 54.0 # ohm, load at which the driver output is specified
N_NODES = 6 # nodes on bus C, each taken as one unit load
R_NODE_DIFF = 24e3 # ohm between the lines for one unit load (2 x 12 kilohm)
LENGTH = 180.0 # m of cable
DELAY = 5e-9 # s per metre of cable
def parallel(*resistors):
"""Resistance of several resistors in parallel."""
return 1.0 / sum(1.0 / r for r in resistors)
def idle_voltage(r_bias, vcc=VCC, r_between=R_TERM / N_TERM):
"""Idle voltage V_B - V_A with one bias resistor to each rail."""
return vcc * r_between / (2.0 * r_bias + r_between)
def driver_load(r_bias):
"""Load between the lines that an active driver must drive."""
return parallel(R_TERM / N_TERM, 2.0 * r_bias, R_NODE_DIFF / N_NODES)
# ---------- Part 1: the bus as built ----------
r_tt = R_TERM / N_TERM
v_680 = idle_voltage(680.0)
print("Bus C as built")
print(f" terminations in parallel: {r_tt:.1f} ohm")
print(f" idle voltage with 680 ohm bias: {1e3 * v_680:.1f} mV")
print(f" margin above the {1e3 * V_THRESHOLD:.0f} mV threshold: "
f"{1e3 * (v_680 - V_THRESHOLD):.1f} mV")
print(f" at {VCC_LOW:.2f} V and bias 5 % high: "
f"{1e3 * idle_voltage(680.0 * 1.05, VCC_LOW):.1f} mV")
print(f" bias current: {1e3 * VCC / (2 * 680.0 + r_tt):.2f} mA")
# ---------- Part 2: choose the bias resistors ----------
r_max = (VCC * r_tt / V_TARGET - r_tt) / 2.0
print("Choosing the bias resistors")
print(f" largest value for {1e3 * V_TARGET:.0f} mV: {r_max:.0f} ohm")
for r in (470.0, 430.0, 390.0, 330.0):
print(f" {r:.0f} ohm: idle {1e3 * idle_voltage(r):.1f} mV, "
f"worst case {1e3 * idle_voltage(r * 1.05, VCC_LOW):.1f} mV, "
f"driver load {driver_load(r):.2f} ohm")
r_min = parallel(R_TERM / N_TERM, R_NODE_DIFF / N_NODES)
r_bias_min = 1.0 / (1.0 / R_LOAD_MIN - 1.0 / r_min) / 2.0
print(f" smallest value that keeps the load at {R_LOAD_MIN:.0f} ohm: {r_bias_min:.0f} ohm")
print(f" bias current with 390 ohm: {1e3 * VCC / (2 * 390.0 + r_tt):.2f} mA")
# ---------- Part 3: reflections against the bit time ----------
t_one_way = LENGTH * DELAY
t_round = 2.0 * t_one_way
print("Reflection timing on 180 m")
print(f" one way {1e6 * t_one_way:.2f} us, round trip {1e6 * t_round:.2f} us")
for baud in (9600, 19200, 115200):
t_bit = 1.0 / baud
print(f" {baud:>6} baud: bit time {1e6 * t_bit:.2f} us, "
f"round trip is {100.0 * t_round / t_bit:.1f} % of a bit")
# ---------- Part 4: stubs and the length against rate guideline ----------
print("Stub length (one tenth of the rise time)")
for t_rise in (10e-9, 250e-9):
print(f" rise time {1e9 * t_rise:.0f} ns: stub up to {t_rise / 10.0 / DELAY:.1f} m")
rate_max = 1e8 / LENGTH
print(f"Guideline rate for {LENGTH:.0f} m: {rate_max / 1e3:.0f} kbit/s "
f"(bit time {1e6 / rate_max:.2f} us)")
# ---------- Part 5: one character on the wire (0x05, 8E1) ----------
byte = 0x05
data_bits = [(byte >> i) & 1 for i in range(8)] # least significant bit first
parity = sum(data_bits) % 2 # even parity
bits = [0] + data_bits + [parity] + [1]
print(f"Character 0x{byte:02X} at 8E1: {''.join(str(b) for b in bits)} "
f"({len(bits)} bits, {1e3 * len(bits) / 9600:.3f} ms at 9600 baud)")
# ---------- Plot ----------
r_axis = np.linspace(200.0, 1000.0, 400)
fig, ax = plt.subplots(figsize=(8, 4.5))
ax.plot(r_axis, 1e3 * idle_voltage(r_axis), label="5.00 V supply")
ax.plot(r_axis, 1e3 * idle_voltage(r_axis * 1.05, VCC_LOW), "--",
label="4.75 V supply, resistors 5 % high")
ax.axhline(1e3 * V_THRESHOLD, color="gray", linewidth=0.8)
ax.axhline(1e3 * V_TARGET, color="gray", linewidth=0.8, linestyle=":")
ax.plot([680.0, 390.0], [1e3 * v_680, 1e3 * idle_voltage(390.0)], "o")
ax.set_xlabel("each bias resistor (ohm)")
ax.set_ylabel("idle voltage between the lines (mV)")
ax.set_title("Bus C: idle voltage with two 120 ohm terminations")
ax.legend()
fig.tight_layout()
fig.savefig("rs485_bias_and_timing.png", dpi=120)
print("Saved rs485_bias_and_timing.png")

Expected output

Bus C as built
terminations in parallel: 60.0 ohm
idle voltage with 680 ohm bias: 211.3 mV
margin above the 200 mV threshold: 11.3 mV
at 4.75 V and bias 5 % high: 191.5 mV
bias current: 3.52 mA
Choosing the bias resistors
largest value for 300 mV: 470 ohm
470 ohm: idle 300.0 mV, worst case 272.2 mV, driver load 55.62 ohm
430 ohm: idle 326.1 mV, worst case 296.0 mV, driver load 55.31 ohm
390 ohm: idle 357.1 mV, worst case 324.2 mV, driver load 54.95 ohm
330 ohm: idle 416.7 mV, worst case 378.5 mV, driver load 54.25 ohm
smallest value that keeps the load at 54 ohm: 312 ohm
bias current with 390 ohm: 5.95 mA
Reflection timing on 180 m
one way 0.90 us, round trip 1.80 us
9600 baud: bit time 104.17 us, round trip is 1.7 % of a bit
19200 baud: bit time 52.08 us, round trip is 3.5 % of a bit
115200 baud: bit time 8.68 us, round trip is 20.7 % of a bit
Stub length (one tenth of the rise time)
rise time 10 ns: stub up to 0.2 m
rise time 250 ns: stub up to 5.0 m
Guideline rate for 180 m: 556 kbit/s (bit time 1.80 us)
Character 0x05 at 8E1: 01010000001 (11 bits, 1.146 ms at 9600 baud)
Saved rs485_bias_and_timing.png

Read the character from left to right: a start bit (0), the eight data bits of 0x05 with the least significant bit first, the parity bit (0, because the byte already has an even number of ones), and the stop bit (1). For every 1 the line B is more positive than A, and for every 0 the line A is more positive. After the stop bit the driver switches off, and only the bias resistors keep the bus at 1.

Common Mistakes



  • Switching on the termination in every device. Only the two ends of the line are terminated.
  • Connecting A to A and B to B by the printed letters. Makers disagree. Match the lines by their idle polarity as given in each manual.
  • Running only two wires. The devices also need a common wire so that the lines stay inside the receiver’s range.
  • Earthing the shield at both ends “to be safe”. Earth it at one end, so that no current flows along it.
  • Wiring a star from a junction box. Run one line in and out of each device.
  • Fitting bias resistors without calculating. With two terminations, 680 Ω on a 5 V supply gives only 211 mV, which is not a safe idle state.

Summary



  • RS-485 sends each bit as the difference between two twisted wires, so noise that reaches both wires equally does not change the bit. A receiver needs at least 200 mV.
  • The bus is one line with a 120 Ω termination at each end and nowhere else. Termination matters when the round trip of the cable is a significant part of a bit time.
  • Bias resistors at one place hold the idle voltage at , which should be 300 mV or more. The cold store bus has 211 mV with 680 Ω and 357 mV with 390 Ω.
  • A standard driver supports 32 unit loads. A common wire, a shield earthed at one end and isolated transceivers control ground differences.
  • For 180 m the commonly quoted guideline allows about 556 kbit/s, and the stub limit comes from the driver rise time.

Exercises



1. A technician finds that the cold store bus has only one of its two 120 Ω terminations fitted. The bias is 680 Ω to each rail on 5.0 V. Find the idle voltage. Explain why this healthy idle voltage is not good news.

Answer

Now 120 Ω is between the lines: . The idle state looks better only because a termination is missing. The open end reflects every edge.

2. A bus has 20 devices of one unit load each. How many more devices of 1/8 unit load can be added before the bus reaches 32 unit loads?

Answer

unit loads remain, and each new device takes 1/8, so more devices.

3. A gateway uses a 3.3 V transceiver on a bus with two 120 Ω terminations. Find the largest bias resistor that gives an idle voltage of 300 mV. Then find the load between the lines made by the terminations and that bias network alone, and compare it with 54 Ω.

Answer

, so . The load is 60 Ω in parallel with 600 Ω, which is 54.5 Ω. That is only just above 54 Ω before any receiver is counted, so transceivers with a built-in fail-safe receiver are the usual answer at 3.3 V.

4. A transceiver has a driver rise time of 50 ns, and the cable delay is 5 ns/m. Find the longest stub by the one-tenth rule. A meter must be connected by a 3 m drop cable: what is the shortest rise time that permits it?

Answer

. For 3 m the stub delay is 15 ns, so the rise time must be at least .

References



  • Telecommunications Industry Association, TIA/EIA-485-A: Electrical Characteristics of Generators and Receivers for Use in Balanced Digital Multipoint Systems, 1998.
  • Modbus Organization, MODBUS over Serial Line Specification and Implementation Guide V1.02, 2006.
  • H. W. Johnson and M. Graham, High-Speed Digital Design: A Handbook of Black Magic, Prentice Hall, 1993.


© 2021-2026 SiliconWit®. All rights reserved.
5 V680 Ω bias120 Ω680 Ω biascommon120 Ωline Bline Ameter 5, drive 10 and two metersconnect along here180 mgateway endlast meter
The bus of this course: a line with a termination at each end
DriverbitReceiverB less Abitline B plus noiseline A plus noiseThe same noise rides on both lines, so B less A keeps only the bit.
Noise that is equal on both wires leaves the difference unchanged
Correct: one line, a termination (T)at each endTTnodenodenodenodenodeWrong: a star has five ends andno place to put two terminationsnodenodenodenodenode
Topology: a line with short stubs, never a star
one bit at 9600 baud: 104 µsround trip on 180 m: 1.8 µs, 1.7 % of the bitBoth bars are to the same scale.
A bit at 9600 baud against the round trip on 180 m
Predict first

Six devices on one RS-485 cable each have a switch for a 120 Ω termination resistor. Which switches should be on?

See it: an edge on 180 m of cable, and what comes back

Round trip of the cable
Round trip as a part of one bit
Middle of the bit comes after
Level at the sample
Highest overshoot
Driver edge (rise time)

One edge leaves the device that sends and travels along the cable at 5 ns/m. At an open end it comes back. At the sending driver it is sent back again, smaller and inverted, so the level at the receiver rings up and down and slowly settles. A 120 Ω termination at an end absorbs the edge there. The receiver samples the middle of the bit, marked by the dashed line. The model has no cable loss and takes the driver as a source of about 40 Ω, so read the shape, not the exact percentages.

open end120 Ω at the end 120 Ω edge returnsedge absorbed
See it: the idle voltage that two bias resistors give

Idle voltage, nominal
Idle voltage, worst case
Bias current
Load on a sending driver
Unit loads this bias allows
Between the lines at idle

With no driver active, one small current flows from the supply through a bias resistor, the terminations and the second bias resistor to common. The voltage across the terminations is the idle voltage between B and A. The worst case takes the supply 5 percent low and both bias resistors 5 percent high. As in the lesson, each unit load is taken as 24 kΩ between the lines, and the receivers are left out of the idle voltage. The driver output is specified into 54 Ω or more.

0undefinedreads 1 no bias: 0 mV680 Ω: 211 mV390 Ω: 357 mV Two resistors hold the silent line at 1

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. A new gateway has a 3.3 V transceiver. It keeps the 390 Ω bias resistors that gave the cold store bus 357 mV, and the bus keeps its two 120 Ω terminations. What is the idle voltage now?

2. A bus is 600 m long, with a delay of 5 ns/m, and runs at 38400 baud. The gateway at one end polls meters along the cable. Where should it be terminated?

3. The cold store bus has six nodes of one unit load each and the 390 Ω bias. Can you add 20 new meters of 1/2 unit load each to the same segment?

Watch it build: check the bus with a multimeter
gatewaybias120 Ω lastmeter120 Ω BA 180 m of pair predicted: 60 Ω and 357 mV power off: ohms from A to B ≈ 60 Ω 120 Ω: one missing40 Ω: one too many power on, idle: volts B − A 0.36 to 0.39 V negative: A and Bare swapped ≈ 0.315 V the same check at the last meter 30 Ω of cablestill above 0.2 V
  1. The calculation predicts about 60 Ω between the lines and 357 mV at idle. Now measure it.
  2. Power off, at the gateway: about 55 to 67 Ω. 120 Ω means a termination is missing, 40 Ω one too many.
  3. Power on, polling stopped: B minus A is 0.36 to 0.39 V. A negative reading means A and B are swapped.
  4. At the last meter: about 0.315 V, lower through 30 Ω of cable, still above the 0.2 V threshold.