Sampling Intervals and Aggregation

Lesson 2 of 10 23 min read
Found this useful?

Two loggers are fitted to the same compressor, and both read the power every 15 minutes. At the end of the day one reports 6.9 kWh and the other reports 9.6 kWh. Neither logger is faulty. They started at different seconds, and a compressor that runs for 8 minutes at a time can be missed completely between two readings. In the same building, a cold room report built from hourly averages shows no hour above 5.0 °C, although the air passed 5.0 °C on 676 occasions. This lesson shows what a logged value really means, how the sampling interval and the method of aggregation change the answer, and how to choose them so that the stored data can still answer the question. #DataLogging #Sampling #EnergyMetering

Learning Objectives

By the end of this lesson, you will be able to:

  1. Identify whether a logged value is instantaneous, an interval average or a counter
  2. Choose a sampling interval from the shortest event that must be seen
  3. Calculate the false period that appears when a cycling signal is sampled too slowly
  4. Compare the energy found from instantaneous samples, from interval averages and from a counter, with the error of each
  5. Select the statistics to keep when readings are aggregated to hours and days

Real-World System Problem: An energy total that depends on the logger



A site wants to know how much energy its refrigeration compressor uses in a day. The logger was set to one reading every 15 minutes, which is common in energy work. The total calculated from the log does not agree with the energy meter of the supplier, and it changes from one day to the next for no visible reason.

The logger stores the power at the moment of each reading, and the compressor runs for 6 to 10 minutes, then rests for 10 to 30 minutes. Whether a run is caught or missed depends on the second at which the logger started. The supplier’s meter adds energy continuously, so it does not have this problem.

So before any statistics, you must know what each stored value means, how far apart the values are, and how they were aggregated.

MeterMachineLoggerinterval: 15 mininstantaneousaveragecountervalue nowof intervaltotal so far
From the machine to the stored value

Fundamental Theory: What a logged value means



Three kinds of logged value

Every value in a log is one of three kinds. They can have the same column name and the same unit, so read the manual of the meter.

KindWhat is storedGood forWeakness
InstantaneousThe value at the moment of the readingShape, states, peaks, limitsSees nothing between readings
Interval averageThe mean of the signal since the last readingEnergy, totals, loadHides peaks and short events
CounterA total that only increases (kWh, m³, starts)Totals across any period, across gapsSays nothing about the shape between readings

Take one 15 minute interval in which a compressor is stopped at 0.014 kW, runs at 1.16 kW from minute 4.0 to minute 11.8, and is stopped again when the reading is taken.

Power1.16 kW0.014 kW04.011.815 minInstantaneous at 15 min:0.014 kWAverage of the interval:0.610 kWCounter, end minus start:0.152 kWh
Three ways to log the same 15 minutes

The interval average is . The counter rises by . The instantaneous value is 0.014 kW, and energy calculated from it is , which is 44 times too small.

How fast to sample

Let be the sampling interval, the time between two readings. The interval is chosen from the shortest event that the data must show.

  • To see every event at least once, must be no longer than the shortest event.
  • To count the cycles of a repeating signal, every on period and every off period must hold at least one reading: no longer than the shortest on time and the shortest off time. For an even square wave this is the rule of more than two readings in each cycle, shorter than half the cycle. For an uneven one it is stricter: this compressor runs for as little as 6.0 minutes in a cycle of at least 16.0 minutes, and readings every 8 minutes (half the cycle) see only 44 to 51 of its 52 starts.
  • To measure how long an event lasted, or its shape, plan for 5 to 10 readings inside it.

A compressor run of 6 minutes is seen at least once with . To time the run within about a minute, must be near 1 minute. A fast log can always be reduced to a slow one, and a slow log can never be made fast.

Aliasing: a false slow pattern

When a repeating signal is sampled too slowly, the readings do not look random: they show a slow, regular pattern that is not in the machine, called an alias. It is the wheel in a film that seems to turn slowly backwards, because the camera looks too seldom.

Let the signal repeat with period , so its frequency is . The sampling frequency is .

Apparent frequency of an undersampled signal

Here is the whole number that makes smallest. The alias appears whenever is less than , which means is longer than . With more than two readings in each cycle, and the true frequency is seen.

Take a square wave that is on for 3 minutes and off for 3 minutes, so , and read it every .

The readings repeat every 30 minutes. The log describes a machine that runs for 15 minutes and rests for 15 minutes.

ONOFFmin0510152025301000111The readings 1 0 0 0 1 1 repeat every 30 min.
A 6 minute cycle read every 5 minutes

The worst case is a sampling interval equal to the period: every reading falls at the same point of the cycle. A square wave of period 5 minutes read every 5 minutes gives “always on” or “always off”, depending on the second at which the logger started, while the true mean is one half.

Energy from power samples, from averages and from a counter

Energy is power multiplied by time. From instantaneous readings at a fixed interval, the usual calculation is

This is an estimate: it assumes that each reading describes its whole interval. That is good for a slow, smooth signal and poor for a machine that switches inside the interval, as the 0.0035 kWh above shows.

If each stored value is the average of its interval, the same sum is exact, because the average contains everything that happened in the interval.

Three routes to the energy of a period

is the reading of an energy counter in kWh. The second and third routes do not depend on the interval. The first does.

A counter that reads 12,480.6 kWh at midnight and 12,611.9 kWh at the next midnight has measured , however many readings were taken between the two.

On a real site, check every difference of a counter before you use it. A counter can roll over to zero at its largest value, and some meters reset it after a power cut or a replacement. Either gives a negative difference, or one far too large. Mark that interval and take its energy from another source, never from the subtraction.

A counter across a gap

Suppose the logger on the compressor of data set D is silent from 09:00 to 11:00, and the meter continues to run. The last power reading before the gap is 1.166 kW, because the compressor was running, and the first reading after it is 0.013 kW. The true energy of the day is 8.081 kWh. If you add only the readings that exist, the total is 7.588 kWh, which is 6.1 percent low. If you draw a straight line across the gap, you add and reach 8.767 kWh, which is 8.5 percent high. If you hold the last value across the gap, you reach 9.920 kWh, which is 22.8 percent high. None of the three knows what the compressor did in those two hours. The energy counter does: it read 3.138 kWh at 09:00 and 3.630 kWh at 11:00, so the gap contained 0.492 kWh, and the counter at the end of the day minus the counter at the start gives 8.081 kWh. A counter loses the detail inside a gap and keeps the total. Power readings lose both.

Aggregating to hours and days

Aggregation replaces many readings with one row for each hour or day. Each statistic in the row keeps a different part of the truth.

meanmaximumminimumminutes abovecountenergy, load, slow trendswas the upper limit passed?was the lower limit passed?how long the limit was passedhow much of the hour exists60 one-minute readings in the hour
What one hourly row should keep

Some statistics can be combined again later and some cannot.

  • The maximum of the hourly maximums is the true maximum of the day. The same holds for the minimum.
  • Counts and sums add. The minutes above a limit in 24 hourly rows add to the minutes above the limit in the day.
  • The mean of hourly means is the true daily mean only when every hour holds the same number of readings. If not, weight each hourly mean by its count.
  • Medians and percentiles cannot be combined. The median of 24 hourly medians is not the median of the day.

A mean hides anything shorter than its own interval. An hour with 54 minutes at 4.0 °C and 6 minutes at 7.0 °C has a mean of , which is below a limit of 5.0 °C.

Time zones and the daily boundary

A daily total depends on where the day begins. Store time in UTC, which has no clock changes, and calculate daily totals in the local time of the site. A site at UTC+3 that is aggregated by UTC days has “days” that run from 03:00 to 03:00 local time. For the compressor of data set D, the energy from 00:00 to 03:00 is 1.064 kWh, which is 13.2 percent of the day and would be given to the wrong date. Where clocks change for summer time, one local day in the year has 23 hours and one has 25. For a steady load, the 25 hour day uses about 4 percent more energy than its neighbours (25 hours divided by 24 is 1.042) and the 23 hour day about 4 percent less, with no change in the machine. A logger that stores local time without its offset writes one hour twice in autumn and skips one in spring; two readings with the same time stamp are the sign. Store UTC, convert once, and divide a daily total by the hours in that day when you compare days.

What a missing interval does to a sum

If readings are missing at random moments, the mean of the readings that remain is still a fair estimate. The sum is not: every missing interval removes its energy, so a sum with gaps is always too low. In the gap example, two missing hours in 24 removed 6.1 percent of the day’s energy.

Store the count of readings beside each aggregated value, and report the coverage: the readings that exist as a fraction of the readings expected. A daily total with a coverage of 91.7 percent is not a daily total.

Application 1: The day’s energy at four sampling intervals



Step 1: The truth and the length of the events

Click to reveal the reference values
  1. True energy. The sum of the 8,640 readings multiplied by 10 s gives . ✅

  2. Runs. With a threshold of 0.5 kW there are 52 runs. The on runs last 6.0 to 9.8 minutes, with a mean of 7.8 minutes. The off periods last 10.0 to 29.8 minutes, with a mean of 20.3 minutes. ✅

  3. Cycle. The time from one start to the next lies from 16.0 to 38.7 minutes, with a mean of 28.0 minutes. ✅

  4. What the rules predict. The shortest on run is 6.0 minutes. An interval of 1 or 5 minutes puts at least one reading in every run. An interval of 15 minutes is longer than every run, so some runs must fall between two readings. ✅

Step 2: Instantaneous samples

Click to reveal the energy estimates
  1. 1 minute. Across the 6 phase offsets the estimate lies from 8.020 to 8.139 kWh. The error is to percent. Every offset sees all 52 starts. ✅

  2. 5 minutes. Across the 30 offsets the estimate lies from 7.563 to 8.660 kWh. The error is to percent. Every offset still sees all 52 starts, as Step 1 predicted, but 5 of the 30 offsets are wrong by more than 5 percent. Seeing a run once does not measure its length. ✅

  3. 15 minutes. Across the 90 offsets the estimate lies from 6.879 to 9.588 kWh.

    The worst error is 18.6 percent, and only 44 of the 90 offsets are within 5 percent of the truth. ✅

  4. Starts at 15 minutes. The 15 minute samples show 22 to 30 starts, where the machine made 52. About half of the runs were never seen. ✅

Step 3: Interval averages

Click to reveal the averaged result
  1. Energy. The interval averages give 8.081 kWh at 1 minute, at 5 minutes and at 15 minutes. The error is zero at every interval. ✅

  2. Reason. When the averages are added and multiplied by the interval, every 10 s reading is counted exactly once, so the total is the same sum as in Step 1. ✅

  3. What the averages lose. The largest 15 minute average is 0.753 kW, although the compressor draws 1.16 kW. Of the 15 minute averages, 76.0 percent lie from 0.03 to 1.00 kW, a range in which the machine never operates. At 5 minutes the share is 28.8 percent and at 1 minute it is 6.3 percent. ✅

  4. Consequence. Averaged data give the right energy and a wrong picture of the states. A threshold applied to 15 minute averages cannot find the duty. ✅

Step 4: Check the result a second way

Click to reveal the check
  1. Average the estimates over all offsets. Each 10 s reading belongs to exactly one phase offset. So the mean of the estimates from all offsets must equal the truth. ✅

  2. Result. The mean of the 6, the 30 and the 90 estimates is 8.081 kWh in each case. Instantaneous sampling has no bias: it is not wrong in one direction. It is uncertain, and the uncertainty grows as the interval approaches the length of the runs. ✅

  3. Compare with aliasing. This compressor’s cycle varies from 16.0 to 38.7 minutes, so the 15 minute readings give no clean false period. The same effect appears as an irregular error. ✅

Application 2: A cold room record reduced to hourly values



Step 1: The hourly mean

Click to reveal what the mean keeps
  1. Range of the hourly means. The 336 hourly means lie from 3.84 to 4.21 °C. ✅

  2. Excursions that survive. The number of hourly means above 5.0 °C is 0. Of the 676 excursions in the one minute data, none survives. ✅

  3. Reason. No hour holds more than 6 minutes above the limit, and the other 54 minutes or more keep the mean near 4 °C. ✅

  4. What the mean does keep. The mean of the 336 hourly means is 4.013 °C, the same as the mean of the 20,160 readings, because every hour holds 60 readings. The hourly mean is a correct record of the average and no record at all of the limit. ✅

Step 2: The hourly maximum and minimum

Click to reveal what the extremes keep
  1. Maximum. The hourly maximum is above 5.0 °C in 332 of the 336 hours, and above 5.2 °C in 34 hours. The largest hourly maximum is 5.44 °C, the true maximum of the record. ✅

  2. What the maximum hides. By the maximum, 98.8 percent of the hours passed the limit. The air was above the limit for 4.35 percent of the time. The maximum says that the limit was passed and says nothing about for how long. ✅

  3. Minimum. The hourly minimum is below 3.0 °C in 316 of the 336 hours, and the smallest is 2.66 °C. It shows the bottom of the thermostat cycle in the same way. ✅

Step 3: Store the time above the limit

Click to reveal the statistic that answers the question
  1. Count in each hour. Count the readings above 5.0 °C inside each hour before the raw data are discarded. The count lies from 0 to 6 minutes in an hour. ✅

  2. Check by adding. The 336 hourly counts add to 877 minutes, exactly the count from the one minute data. A count is a sum, so it survives aggregation without loss. ✅

  3. One spot reading an hour. If the logger had stored only one instantaneous reading in each hour, the fraction of readings above 5.0 °C would lie from 1.79 to 8.33 percent, depending on which minute of the hour was read. The true value is 4.35 percent. ✅

Verify It in Python



The script constructs the clean square wave and confirms the false period of 30 minutes. It then samples the compressor power at every interval and phase offset, forms the interval averages, compares the counter with power readings across a gap, and reduces the cold room record to hourly rows.

sampling_and_aggregation.py
"""Sampling interval, aliasing, interval averages, counters and hourly aggregation."""
import numpy as np
import matplotlib.pyplot as plt
def compressor_power(seed=41, seconds=86400, step=10):
"""Data set D: compressor electrical power in kW, one reading every 10 s."""
rng = np.random.default_rng(seed)
n = seconds // step; p = np.empty(n); on = False; left = 0
for i in range(n):
if left <= 0:
on = not on
left = rng.integers(36, 60) if on else rng.integers(60, 180) # in steps of 10 s
p[i] = (1.16 + rng.normal(0, 0.02)) if on else (0.012 + abs(rng.normal(0, 0.002)))
left -= 1
return p # kW
def cold_room_minutes(seed=11, days=14):
"""Data set A: cold room air temperature in degC, one reading a minute."""
rng = np.random.default_rng(seed)
n = days * 1440
t = np.empty(n); temp = 4.0; on = False; out = []
for i in range(n):
minute = i % 1440
# door openings are more likely in working hours
door = (480 <= minute < 1020) and (rng.random() < 0.035)
if temp >= 5.0: on = True
if temp <= 3.0: on = False
temp += (-0.30 if on else 0.10) + (0.35 if door else 0.0)
t[i] = temp + rng.normal(0.0, 0.05) # sensor noise, 0.05 degC
return t
def count_runs(flags):
"""Number of separate runs of True values."""
f = np.asarray(flags, dtype=int)
return int(f[0] + np.sum(np.diff(f) == 1))
def repeat_period(x):
"""Smallest shift (in samples) after which the series repeats exactly."""
for lag in range(1, x.size // 2):
if np.array_equal(x[lag:], x[:-lag]):
return lag
return None
# ---------- Part 1: aliasing with a clean square wave ----------
t = np.arange(0, 6 * 3600, 10) # 6 hours in steps of 10 s
square = ((t % 360) < 180).astype(float) # period 6 min, on for 3 min
spot = square[::30] # one sample every 5 min
print("Aliasing: square wave of period 6 min sampled every 5 min")
print(f" true period {repeat_period(square) * 10 / 60:.0f} min, "
f"period seen in the samples {repeat_period(spot) * 5} min")
print(f" first 13 samples: {' '.join(str(int(v)) for v in spot[:13])}")
print(f" formula 1 / (1/5 - 1/6) = {1.0 / (1.0 / 5.0 - 1.0 / 6.0):.0f} min")
same = ((t % 300) < 150).astype(float) # period 5 min, on for 2.5 min
print(f" period 5 min sampled every 5 min: mean of samples "
f"{same[0::30].mean():.2f} at offset 0 s, {same[15::30].mean():.2f} at offset 150 s "
f"(true mean {same.mean():.2f})")
# ---------- Part 2: compressor energy against sampling interval ----------
STEP = 10.0
p = compressor_power()
truth = np.sum(p) * STEP / 3600.0 # kWh in the day
running = p > 0.5
edge = np.diff(np.r_[0, running.astype(int), 0])
begin, end = np.where(edge == 1)[0], np.where(edge == -1)[0]
on_min, off_min = (end - begin) / 6.0, (begin[1:] - end[:-1]) / 6.0
print("Compressor, one day")
print(f" truth from 10 s readings: {truth:.3f} kWh, {begin.size} runs")
print(f" on runs {on_min.min():.1f} to {on_min.max():.1f} min (mean {on_min.mean():.1f}), "
f"off runs {off_min.min():.1f} to {off_min.max():.1f} min (mean {off_min.mean():.1f})")
cycle = np.diff(begin) / 6.0
print(f" cycle, start to start: {cycle.min():.1f} to {cycle.max():.1f} min "
f"(mean {cycle.mean():.1f})")
print(" instantaneous samples, every phase offset:")
spread = {}
for label, k in (("1 min", 6), ("5 min", 30), ("15 min", 90)):
est = np.array([p[o::k].mean() * 24.0 for o in range(k)])
err = 100.0 * (est - truth) / truth
starts = [count_runs(running[o::k]) for o in range(k)]
spread[label] = est
print(f" {label:>6}: {k:2d} offsets, energy {est.min():.3f} to {est.max():.3f} kWh, "
f"error {err.min():+.1f} to {err.max():+.1f} %, "
f"starts seen {min(starts)} to {max(starts)}")
print(f" mean of the {k} estimates {est.mean():.3f} kWh, "
f"within 5 % of the truth: {np.sum(np.abs(err) <= 5.0)} of {k}")
print(" interval averages:")
for label, k in (("1 min", 6), ("5 min", 30), ("15 min", 90)):
avg = p.reshape(-1, k).mean(axis=1)
middle = np.mean((avg > 0.03) & (avg < 1.00))
print(f" {label:>6}: energy {np.sum(avg) * k * STEP / 3600.0:.3f} kWh, "
f"largest average {avg.max():.3f} kW, "
f"{100.0 * middle:.1f} % of averages between 0.03 and 1.00 kW")
# ---------- Part 3: a counter against power samples across a gap ----------
counter = np.cumsum(p) * STEP / 3600.0 # kWh since midnight
a, b = 9 * 360, 11 * 360 # logger silent 09:00 to 11:00
kept = np.ones(p.size, dtype=bool); kept[a:b] = False
e_kept = np.sum(p[kept]) * STEP / 3600.0
e_line = e_kept + 0.5 * (p[a - 1] + p[b]) * 2.0
e_hold = e_kept + p[a - 1] * 2.0
print("Gap from 09:00 to 11:00")
print(f" power before the gap {p[a - 1]:.3f} kW, after the gap {p[b]:.3f} kW")
for name, value in (("sum of the readings that exist", e_kept),
("straight line across the gap", e_line),
("last value held across the gap", e_hold)):
print(f" {name}: {value:.3f} kWh ({100.0 * (value - truth) / truth:+.1f} %)")
print(f" counter at 09:00 {counter[a - 1]:.3f} kWh, at 11:00 {counter[b - 1]:.3f} kWh, "
f"energy in the gap {counter[b - 1] - counter[a - 1]:.3f} kWh")
print(f" counter at 24:00 minus counter at 00:00: {counter[-1]:.3f} kWh")
print(f" energy from 00:00 to 03:00: {counter[3 * 360 - 1]:.3f} kWh "
f"({100.0 * counter[3 * 360 - 1] / truth:.1f} % of the day)")
# ---------- Part 4: cold room temperature aggregated to hours ----------
temp = cold_room_minutes()
hourly = temp.reshape(-1, 60)
h_mean, h_min, h_max = hourly.mean(axis=1), hourly.min(axis=1), hourly.max(axis=1)
h_above = (hourly > 5.0).sum(axis=1)
above = temp > 5.0
print("Cold room, 14 days")
print(f" minute data: mean {temp.mean():.3f} degC, maximum {temp.max():.2f} degC, "
f"{above.sum()} min above 5.0 degC ({100.0 * above.mean():.2f} %) "
f"in {count_runs(above)} runs")
print(f" hourly mean: {h_mean.size} values from {h_mean.min():.2f} to {h_mean.max():.2f} degC, "
f"{np.sum(h_mean > 5.0)} above 5.0 degC, mean of them {h_mean.mean():.3f} degC")
print(f" hourly maximum: {np.sum(h_max > 5.0)} of {h_max.size} hours above 5.0 degC, "
f"{np.sum(h_max > 5.2)} above 5.2 degC, largest {h_max.max():.2f} degC")
print(f" hourly minimum: {np.sum(h_min < 3.0)} of {h_min.size} hours below 3.0 degC, "
f"smallest {h_min.min():.2f} degC")
print(f" hourly minutes above 5.0 degC: 0 to {h_above.max()} in an hour, "
f"total {h_above.sum()} min")
frac = [100.0 * np.mean(temp[o::60] > 5.0) for o in range(60)]
print(f" one spot reading an hour: {min(frac):.2f} to {max(frac):.2f} % above 5.0 degC, "
f"by the minute chosen")
# ---------- Plot ----------
fig, ax = plt.subplots(3, 1, figsize=(9, 9))
window = slice(0, 4 * 360) # first 4 hours
minutes = np.arange(p.size) * STEP / 60.0
ax[0].plot(minutes[window], p[window], linewidth=0.8, label="10 s readings")
for offset, mark in ((0, "o"), (45, "s")):
idx = np.arange(offset, 4 * 360, 90)
ax[0].plot(minutes[idx], p[idx], mark, label=f"15 min samples, offset {offset * 10} s")
ax[0].set_xlabel("time (min)"); ax[0].set_ylabel("power (kW)")
ax[0].set_title("The same compressor, two 15 min sampling phases")
ax[0].legend(loc="center right", fontsize=8)
for pos, label in enumerate(("1 min", "5 min", "15 min")):
ax[1].plot(np.full(spread[label].size, pos), spread[label], "_", markersize=14)
ax[1].set_xticks([0, 1, 2]); ax[1].set_xticklabels(["1 min", "5 min", "15 min"])
ax[1].set_xlim(-0.5, 2.5)
ax[1].axhline(truth, color="tab:red", linewidth=0.8)
ax[1].set_ylabel("energy estimate (kWh)")
ax[1].set_title("Day's energy from instantaneous samples, all phase offsets")
day2 = slice(24, 48)
hrs = np.arange(24)
ax[2].plot(np.arange(1440) / 60.0, temp[1440:2880], linewidth=0.5, color="0.6",
label="1 min readings")
ax[2].step(hrs, h_mean[day2], where="post", label="hourly mean")
ax[2].step(hrs, h_max[day2], where="post", label="hourly maximum")
ax[2].axhline(5.0, color="tab:red", linewidth=0.8)
ax[2].set_xlabel("hour of day 2"); ax[2].set_ylabel("temperature (degC)")
ax[2].set_title("Cold room: what the hourly mean hides")
ax[2].legend(fontsize=8)
fig.tight_layout()
fig.savefig("sampling_and_aggregation.png", dpi=120)
print("Saved sampling_and_aggregation.png")

Expected output

Aliasing: square wave of period 6 min sampled every 5 min
true period 6 min, period seen in the samples 30 min
first 13 samples: 1 0 0 0 1 1 1 0 0 0 1 1 1
formula 1 / (1/5 - 1/6) = 30 min
period 5 min sampled every 5 min: mean of samples 1.00 at offset 0 s, 0.00 at offset 150 s (true mean 0.50)
Compressor, one day
truth from 10 s readings: 8.081 kWh, 52 runs
on runs 6.0 to 9.8 min (mean 7.8), off runs 10.0 to 29.8 min (mean 20.3)
cycle, start to start: 16.0 to 38.7 min (mean 28.0)
instantaneous samples, every phase offset:
1 min: 6 offsets, energy 8.020 to 8.139 kWh, error -0.8 to +0.7 %, starts seen 52 to 52
mean of the 6 estimates 8.081 kWh, within 5 % of the truth: 6 of 6
5 min: 30 offsets, energy 7.563 to 8.660 kWh, error -6.4 to +7.2 %, starts seen 52 to 52
mean of the 30 estimates 8.081 kWh, within 5 % of the truth: 25 of 30
15 min: 90 offsets, energy 6.879 to 9.588 kWh, error -14.9 to +18.6 %, starts seen 22 to 30
mean of the 90 estimates 8.081 kWh, within 5 % of the truth: 44 of 90
interval averages:
1 min: energy 8.081 kWh, largest average 1.185 kW, 6.3 % of averages between 0.03 and 1.00 kW
5 min: energy 8.081 kWh, largest average 1.166 kW, 28.8 % of averages between 0.03 and 1.00 kW
15 min: energy 8.081 kWh, largest average 0.753 kW, 76.0 % of averages between 0.03 and 1.00 kW
Gap from 09:00 to 11:00
power before the gap 1.166 kW, after the gap 0.013 kW
sum of the readings that exist: 7.588 kWh (-6.1 %)
straight line across the gap: 8.767 kWh (+8.5 %)
last value held across the gap: 9.920 kWh (+22.8 %)
counter at 09:00 3.138 kWh, at 11:00 3.630 kWh, energy in the gap 0.492 kWh
counter at 24:00 minus counter at 00:00: 8.081 kWh
energy from 00:00 to 03:00: 1.064 kWh (13.2 % of the day)
Cold room, 14 days
minute data: mean 4.013 degC, maximum 5.44 degC, 877 min above 5.0 degC (4.35 %) in 676 runs
hourly mean: 336 values from 3.84 to 4.21 degC, 0 above 5.0 degC, mean of them 4.013 degC
hourly maximum: 332 of 336 hours above 5.0 degC, 34 above 5.2 degC, largest 5.44 degC
hourly minimum: 316 of 336 hours below 3.0 degC, smallest 2.66 degC
hourly minutes above 5.0 degC: 0 to 6 in an hour, total 877 min
one spot reading an hour: 1.79 to 8.33 % above 5.0 degC, by the minute chosen
Saved sampling_and_aggregation.png

In the top panel of the saved plot, two sets of 15 minute samples from the same four hours catch different runs. The middle panel shows the estimates spreading as the interval grows. In the bottom panel the hourly mean stays near 4 °C while the one minute readings touch the limit line in almost every cycle.

Common Mistakes



  • Treating a column named “power” as if its kind were known. Confirm whether it is instantaneous or averaged before you add it to make energy.
  • Multiplying instantaneous power samples by a long interval to get the energy of a machine that switches inside the interval. Use the counter, or interval averages.
  • Reading a slow, regular pattern in a coarse log as the behaviour of the machine. Compare the sampling interval with the real cycle time first.
  • Keeping only the mean when data are aggregated. Store the minimum, the maximum and the time beyond the limit with it.
  • Adding the readings of a day with gaps and reporting the result as the day’s total. Report the coverage, and take the total from a counter.

Summary



  • A logged value is instantaneous, an interval average or a counter. The three answer different questions, and the column name does not say which one you have.
  • The sampling interval must be shorter than the shortest event that the data must show. To count cycles, it must be no longer than the shortest on time and the shortest off time, which for an even square wave is half the cycle.
  • A signal read too slowly gives an alias, a false slow pattern that no later calculation can remove.
  • Energy from instantaneous samples is an estimate whose error grows with the interval: for the compressor it reached 18.6 percent at 15 minutes. Energy from interval averages or from a counter is exact at any interval.
  • An aggregated row must store what the question needs: the mean for totals, the extremes and the time beyond the limit for limits, and always the count. A sum with missing intervals is always too low.

Exercises



1. An energy counter reads 12,480.6 kWh at 00:00 and 12,611.9 kWh at 24:00. Find the energy of the day and the mean power.

Answer

kWh. The mean power is kW. The number of readings taken between the two does not matter.

2. A fan cycles with a period of 7 minutes. Its state is logged every 6 minutes. What period appears in the log? What is the longest interval that shows the true period?

Answer

per minute, so the log shows a period of 42 minutes. To see the true period the interval must be shorter than minutes.

3. A power log has one reading a minute. On one day 3 hours are missing. The readings that exist add to 41.2 kWh over 21 hours. The energy counter shows 49.0 kWh for the full day. Find the energy in the gap, the mean power in the gap, and the error of an estimate made by scaling the 21 hours to 24.

Answer

The gap holds kWh, a mean of kW. The mean of the existing readings is kW, so scaling gives kWh, which is 3.9 percent low. The gap fell on a period of higher load than the rest of the day, which scaling cannot know.

4. Change the script to sample the compressor of data set D every 30 minutes (one reading in every 180). Find the range of the energy estimate across the 180 phase offsets and the worst error.

Answer

Add ("30 min", 180) to the list of intervals. The estimate lies from 5.465 to 12.345 kWh, an error of to percent. There are only 48 samples in the day and the interval is longer than the mean cycle of 28.0 minutes.

References



  • A. V. Oppenheim and R. W. Schafer, Discrete-Time Signal Processing, 3rd edition, Pearson, 2010.
  • R. J. Hyndman and G. Athanasopoulos, Forecasting: Principles and Practice, 3rd edition, OTexts, 2021.
  • D. C. Montgomery and G. C. Runger, Applied Statistics and Probability for Engineers, 7th edition, Wiley, 2018.


© 2021-2026 SiliconWit®. All rights reserved.
Machine Meter Logger interval: 15 min instantaneous value now average of interval counter total so far
From the machine to the stored value
average reading 1.16 kW 0.610 kW 0.014 kW Power energy 0.152 kWh 0 4.0 11.8 15 min Instantaneous at 15 min: 0.014 kW Average of the interval: 0.610 kW Counter, end minus start: 0.152 kWh
Three ways to log the same 15 minutes
60 one-minute readings in the hour 3 4 5 limit minute 0 59 readings above the limit in gold, the mean dashed mean energy, load, slow trends 4.07 maximum was the upper limit passed? 5.27 minimum was the lower limit passed? 3.00 minutes above how long the limit was passed 6 count how much of the hour exists 60
What one hourly row should keep
Predict first

A compressor runs for 3 minutes and rests for 3 minutes, again and again. A logger stores its state once every 5 minutes. What does the log show?

See it: one machine, read at a chosen interval

True energy, 3 hours
From the samples
Error of the samples
From interval averages
Samples, across all phases
Period seen in the samples

The faint shape is the true power: an exact square wave of 1.16 kW and 0.014 kW, made for this figure. It is an illustration, not the lesson's data. Each dot is one instantaneous reading, and the stepped line holds it until the next reading. The solid bars under the plot are the same held readings alone: this is all that the log knows, and it is the machine that the log suggests. The phase is the moment of the first reading, as a percent of one interval: two loggers that start at different seconds have different phases. Energy from the samples is the mean of the readings multiplied by 3 hours. Energy from interval averages adds the true mean of every interval, so it is exact at any interval and any phase. The range across all phases uses 100 phases, from 0 to 99 percent. Below one minute the dots are not drawn.

Watch it build: a false slow cycle
machine log 015304560 min on 3 min, off 3 min: T = 6 read every 5 min: 1 0 0 0 1 1 the log: a 30 min cycle T = 5, read every 5: always on
  1. The machine runs 3 minutes, rests 3 minutes: one cycle every 6 minutes, ten in the hour.
  2. A logger reads it every 5 minutes, fewer than two readings in each cycle: 1 0 0 0 1 1.
  3. Joined up, the readings show a machine that runs 15 minutes and rests 15: a false 30 minute cycle.
  4. Read once per cycle, every reading falls at the same point: the log says always on; the truth is half.
0 min5 min10 min15 min20 min25 min30 min the wheel turns once in 6 minutes; we look every 5 It seems to turn backwards, once in 30 minutes.
6 min at 7.0 °C limit 5.0 °Chourly mean 4.3 °C 0 min3060 Keep the maximum and the minutes above the limit too.

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. A fan cycles with a period of 10 minutes. Its state is logged every 8 minutes. What period appears in the log?

2. A load is on for 2.5 minutes and off for 2.5 minutes. Two loggers read its power every 5 minutes. One reports that the load was on all day. The other reports that it was off all day. Which logger is faulty?

3. A meter stores the average power of each 15 minute interval. In one interval the compressor is stopped at 0.014 kW, except for a run of 7.8 minutes at 1.16 kW. The stored value is 0.610 kW. What can you take from this value?