4 to 20 mA current loop
On this page
In one pipe with no branches, the water that enters one end each second leaves the other end, however long the pipe is. Electric current in a single loop of wire behaves the same way. A 4 to 20 mA current loop uses this to send a measurement over a long cable: the transmitter sets the current, 4 mA for the bottom of its range and 20 mA for the top.
See it
A pressure transmitter has a range of 0 to 10 bar and an output of 4 to 20 mA. It sends 12 mA. What is the pressure?
The upper scale is what the transmitter measures. The lower scale is the current it sends, which a resistor in the panel turns into a voltage. The bottom of the range is 4 mA, not 0 mA, so a current of zero can mean only one thing: no signal is arriving.
The idea
A voltage falls along a cable, by an amount that depends on its length and temperature. A current does not: the current that leaves the transmitter is the current that arrives at the panel. The panel passes it through a resistor and reads the voltage there.
The bottom of the range is 4 mA, called a live zero. It lets the panel separate a low measurement from a missing signal, and the 4 mA that always flows also powers the transmitter.
x is the measured value, xlo the value at 4 mA and xhi the value at 20 mA. The signal is 16 mA wide.
Many transmitters report their own failure by sending a current outside the measuring range: at or below 3.6 mA, or at or above 21 mA. These levels are a recommendation (NAMUR NE 43), and a datasheet says whether a transmitter follows it.
The current stays correct only while the transmitter has enough voltage. The cable and the resistor both take voltage from it, so a loop has a limit of length.
One worked number
A transmitter with a range of 0 to 10 bar sends 10.4 mA. What is the pressure?
Show the worked solution, 3 steps
- Subtract the live zero
10.4 mA − 4 mA = 6.4 mA above the bottom of the range.
- Find the share of the range
6.4 mA ÷ 16 mA = 0.40, which is 40%. It is not 52%, which is 10.4 as a share of 20.
- Take that share of the range
0.40 × 10 bar = 4.0 bar. Check it in the figure: set the pressure to 4.0 bar and read 10.4 mA.
The mistake to avoid
A second trap: software that turns the current directly into a pressure, and limits a negative result to zero, shows a broken wire as 0.0 bar. Test the current first. 0 mA means an open loop or no supply. About 3.6 mA means that the transmitter reports a failure.
Check yourself
A level transmitter on a water tank has a range of 0 to 4 m. It sends 16 mA. What is the level?
A screen shows 0.0 bar for a pump line. A check of the signal shows that the loop current is 0 mA. What does that tell you?
A transmitter is 400 m from its panel, and the cable has a resistance of 28 Ω. Why does this resistance not change the reading?
Where you meet it
- Pump stationsA pressure transmitter on a pump line sends its reading to a panel hundreds of metres away.
- Tanks and boreholesLevel transmitters report the depth of water as a current.
- Flow and temperature transmittersMost industrial instruments offer this output, so one kind of input reads them all.
- Current is equal at every point of a loop, so the cable does not change the signal.
- 4 mA is the bottom of the range and 20 mA is the top. The signal is 16 mA wide.
- Subtract 4 mA, divide by 16 mA, then multiply by the range.
- 0 mA is never a measurement. It means a broken loop or no supply.
Discussion
No comments yet. Questions, results from your own build, a better way to explain it: all welcome.
My notes on this page
Kept on this device only. Nothing is sent anywhere.
Tip: select words in the lesson, or tap a figure or an equation, to put a note right there.
Notes on earlier wording
The lesson has changed and these words are no longer in it. Your notes are kept, with the words you chose.