Current transformer
On this page
A clamp meter reads the current in a cable without touching the copper, because a current makes a magnetic field round its wire. A current transformer (CT) is a steel ring with a winding, placed round one conductor. It gives a meter a small, exact copy of a large current, such as 5 A for every 100 A.
See it
A class 1 CT of 100 A : 5 A may drive at most 2.5 VA. The meter takes 0.2 VA. The meter is moved 10 m away, with 2.5 mm² copper leads. Is the CT still within its rated burden?
Leads of 2.5 mm² copper, out and back. The burden is compared at the rated secondary current, because that is how the maker states it. The open secondary is shown here only so it is never done on site.
The idea
The conductor through the ring is the primary. The winding is the secondary, closed through the meter. The ratio is written as two rated currents, such as 100 A : 5 A, and the secondary current is the primary current divided by it: 62 A ÷ 20 = 3.10 A. The meter is told the ratio and multiplies back.
The secondary must drive its current through the leads and the meter. Together they are the burden, stated in volt-amperes at the rated secondary current.
Sb is the burden in VA, Isn the rated secondary current (5 A or 1 A), Rb the resistance of both leads and the meter in Ω
The CT keeps its class only within its rated burden. A 1 A secondary takes 25 times less burden from the same lead, so it suits long distances.
A split core CT opens round a conductor that stays connected, so it suits an existing panel. Its joint makes its error larger, mostly at low current. Billing meters use solid core CTs.
One worked number
A 100 A : 5 A CT, rated burden 2.5 VA, measures a compressor at 62 A. The meter takes 0.2 VA. The leads are 2.5 mm² copper (0.0175 Ω mm² per metre), 4 m each way. What current reaches the meter, and is the burden within the rating?
Show the worked solution, 3 steps
- Secondary current
Ratio 100 ÷ 5 = 20, so 62 ÷ 20 = 3.10 A.
- Resistance of the leads
Out and back is 8 m: 0.0175 × 8 ÷ 2.5 = 0.056 Ω.
- Burden at 5 A
5² × 0.056 = 1.40 VA, plus 0.2 VA = 1.60 VA, 64% of 2.5 VA. It is within the rating. Check it in the figure at 4 m.
The mistake to avoid
Some small monitoring CTs have a built in resistor and give a low voltage, such as 0.333 V; the resistor keeps the secondary closed. Read the label.
Check yourself
A 300 A : 5 A CT is on a feeder carrying 240 A. What current flows in its secondary?
A meter is set to a ratio of 200 : 5, but the CTs fitted are 100 : 5. What does the meter show?
Someone wants to take a meter away for repair while the compressor runs, leaving the CT leads loose. Why must this not happen?
Where you meet it
- A compressor or pump feederSplit core CTs let an electrician add a sub-meter without disconnecting the conductors.
- The utility billing meterLarge supplies are metered through solid core CTs of a high class.
- A generatorCTs on its output feed its meter and its overload protection.
- A distribution boardSmall CTs with a voltage output measure each circuit for an energy monitor.
- Secondary current = primary current ÷ ratio. Tell the meter the ratio.
- Burden = Isn2 × resistance of leads and meter. Keep it within the rating, counting the leads out and back.
- Split core CTs fit round a live conductor, with a larger error.
- Never open the secondary of a CT while the primary carries current.
Discussion
No comments yet. Questions, results from your own build, a better way to explain it: all welcome.
My notes on this page
Kept on this device only. Nothing is sent anywhere.