RTD and thermocouple

One idea Beginner 5 min read
Found this useful?

A thermometer in a glass tube works because a liquid grows when it warms. Industrial sensors use two other effects. A platinum wire's resistance rises with temperature: that is a resistance temperature detector (RTD), such as the Pt100. Two different metals joined at a tip give a small voltage when the tip is hotter than the other end: that is a thermocouple.

A broken sensor?The reading is steady and believable. A broken sensor is usually not.Unlikely
A bad controller?It holds the reading at 4 °C, as it was told to.Not the cause
The cable is in the reading?Two wires add their resistance to the sensor.This is the trap

See it

Predict first

A Pt100 measures a cold room at 4 °C. It has two wires through 30 m of cable, and each wire has 1.05 Ω. A Pt100 changes by 0.39 Ω for each degree. What does the controller show?

See it: a sensor, its cable and its instrument

True temperature
Instrument shows
Error

Copper cable of 0.035 Ω per metre in each wire. The thermocouple's instrument measures a voltage and draws almost no current, so the cable's resistance does not matter to it; the temperature of its terminals does.

The idea

A Pt100 has 100 Ω at 0 °C and gains about 0.39 Ω for each degree. A common industrial grade, class B, is within ±0.32 °C at 4 °C, and platinum sensors cover about −200 to 850 °C. The trap is the cable: with two wires, the instrument measures the sensor and both wires as one resistance.

error = (RL1 + RL2) ÷ (dR/dt)

RL1 and RL2 are the resistances of the two wires; dR/dt is the sensor's change in ohms for one degree, 0.39 Ω per °C for a Pt100

A third wire lets the instrument measure one lead and subtract it. Four wires remove the leads completely.

A thermocouple's voltage depends on the difference between its tip and the instrument terminals, the cold junction. Type K gives about 41 µV per degree and works from about −200 to 1,200 °C, but a new one may be 1.8 °C wrong at 450 °C. The instrument must measure its terminal temperature and add the matching voltage before it converts.

E(thot) = V + E(tterm)

V is the measured voltage, E(t) is the standard table voltage at temperature t, tterm is the terminal temperature

One worked number

The question

A two-wire Pt100 in a cold room at 4 °C has 30 m of cable, 0.035 Ω per metre in each wire. Near 4 °C the sensor changes 0.390 Ω per degree. What does the instrument show?

Show the worked solution, 3 steps
  1. Resistance of the two wires

    30 m × 0.035 Ω = 1.05 Ω each, so 2 × 1.05 = 2.10 Ω.

  2. Turn it into degrees

    2.10 ÷ 0.390 = 5.38 °C, always in the warm direction.

  3. Read the result

    The instrument shows 4 + 5.38 = 9.38 °C. A controller that holds 4 °C on its display keeps the real air near −1.4 °C. Check it in the figure at 30 m.

The mistake to avoid

A thermocouple does not report the temperature at its tip. It reports the difference between the tip and its terminals. A type K at 450 °C, with terminals at 35 °C and no compensation, reads 416.8 °C: 33.2 °C low, steady and believable.

The short cure is also wrong. Converting the voltage first and then adding 35 °C gives 451.8 °C, because the curve is not straight. Add voltages, never temperatures.

Check yourself

Question 1

A two-wire Pt100 at 4 °C has 50 m of cable, 0.035 Ω per metre in each wire. About how large is the error?

Question 2

A type K thermocouple on a generator exhaust at 450 °C reads 416.8 °C. The instrument terminals are at 35 °C. What is the most likely cause?

Question 3

A vaccine store must be held within a few tenths of a degree. A generator exhaust runs near 450 °C. Which sensors fit?

Where you meet it

  • A cold room or vaccine storeA Pt100 or Pt1000 with three wires, where a few tenths of a degree decide whether the product is safe.
  • A diesel generatorA type K thermocouple in the exhaust shows the engine's health at a given load.
  • A bakery ovenEither sensor can work at 200 °C; the choice depends on the accuracy needed and the cable route.
  • A kiln or furnaceAbove the range of platinum sensors, thermocouples are the only practical choice.
Key points
  • Pt100: resistance rises 0.39 Ω per degree. Exact, for about −200 to 850 °C.
  • Two wires put the cable in the reading. Use three or four wires.
  • Thermocouple: a voltage from the difference between tip and terminals. Wide range, less exact.
  • Compensate the cold junction by adding voltages, never temperatures.