Skip to content
You Start with one site
Amounts in Start with one site
Heat & Refrigeration · Concept

Thermal resistance

One idea Beginner 5 min read
Found this useful?

One blanket keeps you warm, and two keep you warmer. Each blanket holds back some of the heat that flows from your body to the cold room. Thermal resistance is the number that says how strongly a layer holds back heat, and it is used in the same way as electrical resistance in a circuit.

Exactly half?Only if the foam were the whole resistance. It is nearly all of it, not all.Very close
A quarter?Heat flow follows the resistance, not its square.Too hopeful
How do we count it?Add the resistance of every layer, then divide the temperature difference by the total.This is thermal resistance

See it

Predict first

A cold room wall has 80 mm of foam insulation. It is 30 °C outside and 4 °C inside. The foam is changed to 160 mm. What happens to the heat that flows in through the wall?

See it: a wall as three resistances in a row

Total resistance
Heat flow on each m²
Through 35 m² of wall

The upper drawing is the wall, with a line for the temperature on the way through. The two narrow strips are the still air that clings to each face, which also resists heat. The lower drawing is the same wall as a circuit. The temperature difference plays the part of the voltage, and the heat flow plays the part of the current.

The idea

Heat flows from the warm side of a wall to the cold side. A larger temperature difference drives more heat, and a larger resistance passes less. This has the form of Ohm's law, with the temperature difference in place of the voltage.

heat flow on each m² = ΔT ÷ (R1 + R2 + R3)

ΔT is the difference between the air temperatures on the two sides, in kelvin (K). For a layer, R = L ÷ k: the thickness L in metres divided by the thermal conductivity k. For an air film, R = 1 ÷ h

The thermal conductivity k says how easily a material passes heat. Steel is about 50 W/(m·K) and dry polyurethane foam is 0.023, about two thousand times less.

Heat must cross every layer in turn, so the resistances are in series and they add. The temperature falls across each layer in proportion to its resistance. You will often see the U-value: it is 1 divided by the total resistance, so a low U-value is a good wall.

The sum describes the flat middle of a wall in steady conditions. A steel fixing or an open joint is a path around the insulation, and it passes far more heat.

One worked number

The question

A cold room wall has 80 mm of foam with k = 0.023 W/(m·K). The air film inside has a resistance of 0.125 m²·K/W and the film outside 0.050. The air is at 30 °C outside and 4 °C inside. How much heat enters through 35 m² of wall?

Show the worked solution, 3 steps
  1. Resistance of the foam

    R = L ÷ k = 0.080 ÷ 0.023 = 3.478 m²·K/W.

  2. Add the layers

    0.125 + 3.478 + 0.050 = 3.653 m²·K/W.

  3. Divide the temperature difference by the total

    ΔT = 30 − 4 = 26 K. Heat flow = 26 ÷ 3.653 = 7.12 W on each m². For 35 m²: 7.12 × 35 = 249 W. The figure opens on this case.

The mistake to avoid

U-values of layers do not add. Two layers that each have U = 0.5 W/(m²·K) do not make a wall of U = 1.0. That would mean that a second layer lets more heat through. Change each U-value to a resistance (1 ÷ U), add the resistances, and take 1 ÷ the total at the end: here 2.0 + 2.0 = 4.0, so U = 0.25.

Insulation slows heat and never stops it. The lesson on conduction, insulation and the envelope turns the watts into energy and cost.

Check yourself

Question 1

A wall has a total resistance of 4.0 m²·K/W and an area of 30 m². The air is at 34 °C outside and 2 °C inside. How much heat flows through the wall?

Question 2

A wall is built from two layers, one behind the other. Each layer alone has U = 0.5 W/(m²·K). What is the U-value of the two together?

Question 3

The air outside a cold room is at 30 °C and the room is at 4 °C. You touch the outside face of a sound panel and it feels almost as warm as the air. Why?

Where you meet it

  • A cold room or a refrigerated truckThe panels set a heat load that the cooling plant must remove for all 8,760 hours of the year.
  • A heat sink on a drive or a power supplyIts resistance is given in K/W for the whole part: each watt of loss raises the temperature by that many kelvin.
  • A hot water tank and its pipesTheir insulation is a resistance between the hot water and the room.
Key points
  • Heat flow = temperature difference ÷ thermal resistance, as current = voltage ÷ resistance.
  • For a flat layer, R = thickness ÷ conductivity. Layers in series add.
  • The largest resistance takes the largest share of the temperature fall.
  • U-values do not add. Add resistances, then take 1 ÷ the total.
Practice

Found this useful?

Discussion

    Comments show your name. Be kind, stay on the topic.