Control Systems · Concept

Time constant and dead time

One idea Intermediate 5 min read
Found this useful?

Turn the hot tap of a shower. For some seconds nothing changes: the hot water is still in the pipe. Then the water warms, fast at first and then more slowly. Dead time is the wait before anything moves, and the time constant says how fast the process moves once it has started.

Yes, same time?The total is the same. What happens inside it is not.Not enough
The slow climb is harder?A slow climb can be watched and corrected on the way.Slow, but safe
The long wait is harder?During the wait, nothing you do can be seen.This is dead time

See it

Predict first

The heater of a tank is turned up. In tank A the sensor shows nothing for 40 s, and the climb is 63% complete at 340 s. In tank B the sensor shows nothing for 240 s, and the climb is also 63% complete at 340 s. Which tank is harder to control?

See it: one step of the heater, and the answer of the tank

First movement at θ
63.2% reached at θ + τ
Settled (98%) at θ + 4τ

The first band is the dead time: the heater has changed and the sensor shows nothing. The second band is one time constant, measured from the moment the temperature starts to move. The two sliders are independent. One moves the start of the curve and the other changes its steepness.

The idea

Change the input of a process in one step and watch the measured value. Three numbers describe what you see.

The process gain, K, is how far the value moves in the end for each unit of input. The dead time, θ, is the time from the step to the first movement. It comes mostly from transport: water must travel along a pipe to the sensor. The time constant, τ, is the time from the first movement until 63.2% of the change is complete. It comes from storage: a large mass of water warms slowly.

y(t) = K × Δu × (1 − e−(t − θ) ÷ τ)

for t later than θ. y is the change of the measured value, Δu is the size of the input step and t is the time since the step. Before θ, y = 0

The climb is 95% complete at three time constants and 98% at four. The ratio θ ÷ τ says how hard the loop will be: below about 0.3 it is easy, and above about 1 it is difficult. The three numbers hold near one operating point only: a different flow in the pipe gives a different dead time.

One worked number

The question

A tank is steady at 45.0 °C with its heater at 40%. The heater is stepped to 60% and held. The temperature first moves 40 s after the step, passes 51.3 °C at 340 s, and settles at 55.0 °C. Find K, θ and τ.

Show the worked solution, 3 steps
  1. Process gain from the two ends

    The temperature moved 55.0 − 45.0 = 10.0 °C for a step of 60 − 40 = 20%. K = 10.0 ÷ 20 = 0.50 °C per percent.

  2. Dead time from the first movement

    Nothing moved for 40 s, so θ = 40 s.

  3. Time constant from the 63.2% point

    63.2% of 10.0 °C is 6.3 °C, so the level is 45.0 + 6.3 = 51.3 °C. It was reached at 340 s. τ = 340 − 40 = 300 s. The figure opens on this case.

The mistake to avoid

A late process and a slow process are not the same. A long time constant makes a loop slow and safe: the controller can watch the climb and correct it. A long dead time makes a loop slow and difficult, because no controller can correct a disturbance in less time than the dead time.

A second trap: the time constant is the time to 63.2%, not the time to finish. The lesson on first order systems and dead time reads all three numbers from a real record.

Check yourself

Question 1

Water leaves a tank at 0.3 m/s. The temperature sensor is on the pipe, 12 m from the tank. What dead time does the position of the sensor add?

Question 2

A tank has a time constant of 300 s. Once its temperature has started to move, about how long does it need to settle after a change?

Question 3

A temperature loop on a tank is hard to keep steady. The sensor is on the outlet pipe, some metres from the tank. Which change makes the loop easier to control for the rest of its life?

Where you meet it

  • A hot water tank with its sensor on the outlet pipeThe mass of water gives the time constant, and the length of pipe gives the dead time.
  • A booster pump under pressure controlThe pressure answers in seconds with almost no wait, so the loop is easy.
  • A dryer or an oven with a conveyorThe product is measured after it leaves, so every correction is seen late.
Key points
  • Dead time θ is the wait before the measured value first moves.
  • The time constant τ is the time from the first movement to 63.2% of the change. Settling takes about 4τ.
  • A long τ makes a loop slow. A long θ makes it difficult.
  • The ratio θ ÷ τ tells you how hard a loop will be before you tune it.