Transformer losses and efficiency
Transformers, Generators and Voltage Drop
On this page
A transformer hums all night for a site that is closed, and nobody counts the energy it turns into heat. A motor at the end of a long cable starts slowly and the lights dim, because the cable keeps some of the volts. During a power cut, a 100 kVA generator runs for hours to feed a few lights and a cold room, and each kWh costs five or six times the mains price. These three losses lie between the supply and the machine, and each one can be calculated from a few figures on a nameplate or a data sheet. This lesson shows the calculations and their limits. #Transformers #VoltageDrop #DieselGenerator
Learning Objectives
By the end of this lesson, you will be able to:
- Calculate the iron loss, copper loss and efficiency of a transformer at any load, and the load at which its efficiency is highest
- Estimate the energy that a transformer loses in a year and what it costs
- Calculate the voltage drop on a three-phase cable from its resistance, its reactance and the power factor of the load
- Distinguish the kW rating of a generator from its kVA rating and say which one limits a given load
- Work out the fuel cost of each kWh from a generator at different loads
Real-World System Problem: The path from the 11 kV line to the motor
Site E is a cold store. Its supply arrives at 11 kV and a 200 kVA transformer reduces it to 415 V. From the main board, an 85 m copper cable feeds the 22 kW compressor motor. When the mains supply fails, a changeover switch connects the board to a 100 kVA diesel generator.
Each of these three items takes something for itself. The transformer loses a fixed amount of power in its iron core for every hour that it is energised, and a further amount in its windings that grows with the load. The cable loses voltage, so the motor never receives the full 415 V, and it receives least during starting, when it needs torque most. The generator burns fuel only to keep turning, before it delivers any power at all.
None of these effects appears as a separate line on a bill. They are inside the kWh and the fuel account. The figures needed to find them are on the nameplates and in the length and size of the cable.
Fundamental Theory: What the supply path keeps for itself
The supply in this course is three-phase, four-wire, 50 Hz, with a line voltage
What a transformer rating says
A transformer nameplate gives a rating in kVA, not in kW, because the heating of the windings depends on the current and the maker cannot know the power factor of the load.
Transformer D is rated 200 kVA, 11 kV to 415 V. Its rated current on the 415 V side is
This lesson uses one more quantity, the load fraction
where
Two losses that behave differently
The iron loss
The copper loss is the
The load of best efficiency
At very light load the efficiency is poor, because the iron loss is shared by few kW. At heavy load the copper loss grows faster than the output. The loss for each kVA delivered is proportional to
For transformer D,
The curve is flat near its top. Transformer D at a power factor of 0.78 has an efficiency of 98.52 percent at 30 percent load, 98.58 percent at 40 percent and 98.55 percent at 50 percent.
Percent impedance and fault level
The nameplate figure “impedance 4.5 percent” means that 4.5 percent of the rated voltage is lost inside the transformer at rated current. Reverse the idea: if the 415 V terminals are short-circuited, the only thing that limits the current is this impedance, so the current is
Voltage drop in a cable
A cable has resistance
What matters to the motor is how much smaller the voltage at its end,
Voltage drop of a balanced three-phase cable
Three points about this formula.
- In a balanced three-phase circuit the neutral carries no current, so only one conductor length counts and the factor is
. A single-phase circuit has current in two conductors and the factor is 2. - For small cables
is much larger than , and the resistance part decides the result. For large cables (240 mm² and above) is about as large as , and a low power factor then makes the drop worse. - The formula is an approximation. It ignores the part of the cable voltage that is at right angles to the supply voltage. The error grows when the drop is several percent, as Application 2 shows.
- The resistance of copper rises by about 0.4 percent for each degree. A data sheet often gives it at 20 °C, while a loaded cable with PVC insulation may run at up to 70 °C, where its resistance is about 1.2 times larger. Tables for wiring rules usually give the drop at the working temperature, in mV per ampere per metre, and their figures are higher for that reason.
Voltage drop is one of three checks that choose a cable size, and it is not the first. The cable must carry the load current without overheating, using the rating from the tables of the local wiring rules for its installation method, reduced by factors for a hot ambient, for cables grouped together and for burial. It must also survive a fault until the protection opens it, and the fault current at its far end must be large enough to make that protection open quickly. A cable that passes the voltage drop check can still fail either of the others.
The limit on voltage drop
Wiring rules limit the voltage drop between the origin of an installation and the equipment. Many rules use figures of a few percent of the nominal voltage for normal running, and values from 3 to 5 percent are common. The figure, and the point from which it is measured, differ from one country to another, so check the rule that applies where the installation is.
The reason for the limit is physical. The torque of an induction motor at a given speed varies with the square of its voltage, so a motor at 95 percent voltage has only 90 percent of its torque. During starting the drop is several times larger, because the starting current is several times the full-load current. A larger drop is accepted for those few seconds, provided the motor still accelerates its load.
A generator has two ratings
A generating set is two machines on one shaft. The engine produces mechanical power, which limits the kW. The alternator carries current, which limits the kVA. Generator C is rated 100 kVA and 80 kW, and a load must respect both limits.
- At a power factor above 0.8, the engine limit is reached first. A load of 90 kW at unity power factor is only 90 kVA, but it overloads the engine.
- At a power factor below 0.8, the alternator limit is reached first. Site E has a power factor of 0.78, so 100 kVA carries only
.
The maximum demand of site E is 150 kVA, so generator C cannot carry the whole site. It is a standby set for selected loads. A motor that starts on the generator needs a third check, because its starting kVA reduces the voltage of a generator far more than it reduces the voltage of the mains.
Fuel for each kWh
A diesel engine uses fuel in two parts. One part only keeps the engine turning against its own friction, its fan, its pumps and the alternator losses. This part is almost the same at every load. The other part is proportional to the electrical output.
Divide the fuel for one hour by the kWh delivered in that hour, and the fixed part is shared by fewer kWh at light load. This is the reason that the fuel for each kWh rises as the load falls. A typical maker’s curve for a set of this size gives about 0.28 litres per kWh at 75 percent load and about 0.40 litres per kWh at 25 percent load. These are typical figures. The data sheet of the real set gives its own curve.
Light load has a second cost. Many makers advise against long running below about 30 percent of rated load, because the engine runs too cool to burn its fuel cleanly. The limit comes from the maker of the set.
Application 1: Transformer D at the load of site E
Step 1: The two load fractions
Click to reveal the load fractions
-
At the maximum demand.
The output is
. ✅ -
Average real power.
The site takes 58.33 kW on average, half of its peak. ✅
-
Average load fraction. Convert to kVA first, because the copper loss follows the kVA.
On average the transformer carries 37.4 percent of its rating. ✅
Step 2: Losses and efficiency
Click to reveal the losses
-
Copper loss at the peak.
✅
-
Total loss and efficiency at the peak.
The efficiency at the maximum demand is 98.30 percent. ✅
-
Copper loss at the average load.
At this load the copper loss is smaller than the iron loss of 0.45 kW. ✅
-
Total loss and efficiency at the average load.
The efficiency at the average load is 98.58 percent. ✅
Step 3: The load of best efficiency
Click to reveal the best point
-
Load fraction. The efficiency is highest where the copper loss equals the iron loss.
The best point is at 80.2 kVA, where the total loss is
. ✅ -
Compare. The average load of 74.8 kVA is close to the best point, and the efficiency there (98.58 percent) is the same as the best value to two decimal places. The transformer is well matched to this site. ✅
Step 4: Energy lost in a year
Click to reveal the annual loss
-
Iron loss energy. The iron loss is present for every hour of the year.
This energy is lost even if the site is closed all year. ✅
-
Copper loss energy. Use the average load fraction for the whole year.
This is a low estimate, for the reason given in the insight below. ✅
-
Total and cost.
(The cost uses the unrounded energy.) The loss is 1.46 percent of the
that the site buys in a year. ✅ -
Check a second way. The mean loss over the year is
, and , which agrees with item 3 within rounding. The Python script prints 7,372 kWh and efficiencies of 98.30 and 98.58 percent. ✅
Application 2: Voltage drop on the feeder to the compressor
Step 1: Resistance and reactance of the cable
Click to reveal the cable values
-
Resistance of one conductor.
✅
-
Reactance of one conductor.
The resistance is 14 times the reactance, so this cable is almost purely resistive. ✅
Step 2: Drop at full-load current
Click to reveal the running drop
-
Angle.
, so . ✅ -
Drop in each phase.
The reactance gives only 0.148 V of this. ✅
-
Drop between lines.
The motor receives about 409 V. ✅
-
Compare with a limit. A drop of 1.43 percent is inside the limits of a few percent that wiring rules commonly use. The same current over 178 m of this cable would give 3 percent. ✅
Step 3: Drop during starting
Click to reveal the starting drop
-
Angle.
, so . ✅ -
Drop in each phase.
The current is 6.5 times larger, but the drop is only 2.7 times larger, because the starting current is mostly reactive and this cable has little reactance. ✅
-
Drop between lines.
The approximate formula gives 3.89 percent during starting. ✅
Step 4: Check with exact phasors
Click to reveal the check
-
Method. Take the motor voltage
as the reference. The supply voltage is the phasor sum , and the size of is fixed at . The cable voltage has a part along , which is the already found, and a part at right angles to it, . ✅ -
Running. The part at right angles is
. The exact drop is 5.96 V between lines, or 1.44 percent. The approximation gave 5.94 V. ✅
-
Starting. The part at right angles is
. The exact drop is 18.16 V between lines, or 4.38 percent, and the motor terminals receive 396.8 V. The approximation gave 16.13 V, which is 11 percent too low. ✅
-
Check with the script. The Python script prints 5.94 V and 5.96 V for running, and 16.13 V and 18.16 V for starting. ✅
Application 3: Fuel cost of each kWh from generator C
Step 1: Fuel and cost at the two loads
Click to reveal the fuel cost
-
At 75 percent load. The output is
. Each kWh costs 4.2 times the mains price in fuel alone. ✅
-
At 25 percent load. The output is
. Each kWh costs 6.0 times the mains price. ✅
-
Compare. The output fell to one third, and the fuel for an hour fell only to 48 percent. ✅
Step 2: The fuel burned at no load
Click to reveal the straight line
-
Slope. Between the two points the fuel rises by
for 40 kW more output. ✅
-
Fuel at no load.
The line says that the set burns about 3.6 litres an hour before it delivers anything, which is 648 currency units an hour. ✅
-
Check. The line must return the second point:
, which is correct. At 10 kW it gives , or 0.58 litres and 104.4 currency units for each kWh. The script prints the same values. ✅
Verify It in Python
The script repeats the three applications and saves one figure: the efficiency curve of transformer D, the two voltage drops of feeder F and the fuel cost of generator C against load.
"""Transformer D losses, voltage drop on feeder F, and the fuel cost of generator C."""import cmathimport mathimport numpy as npimport matplotlib.pyplot as plt
V_L = 415.0ROOT3 = math.sqrt(3.0)
# ---------- Part 1: transformer D ----------S_TX, Z_TX = 200.0, 0.045 # kVA, impedance per unitP_FE, P_CU = 0.45, 2.8 # iron loss and full-load copper loss, kWPF = 0.78 # power factor of site ERATE_KWH = 12.00 # tariff G, currency units per kWh
def tx_losses(x): """Total loss in kW at the load fraction x = S / S_rated.""" return P_FE + P_CU * x ** 2
def tx_efficiency(x, pf): p_out = x * S_TX * pf return p_out / (p_out + tx_losses(x))
x_best = math.sqrt(P_FE / P_CU)x_peak = 150.0 / S_TXp_avg = 42000.0 / 720.0 # average kW of a 30-day monthx_avg = p_avg / PF / S_TXprint("Transformer D")print(f" best efficiency at x = {x_best:.3f} = {x_best * S_TX:.1f} kVA, " f"efficiency {100.0 * tx_efficiency(x_best, PF):.2f} % at pf {PF}")for name, x in (("peak (150 kVA)", x_peak), ("average load", x_avg)): print(f" {name}: x = {x:.3f}, copper {P_CU * x ** 2:.3f} kW, " f"total loss {tx_losses(x):.3f} kW, output {x * S_TX * PF:.1f} kW, " f"efficiency {100.0 * tx_efficiency(x, PF):.2f} %")e_fe = P_FE * 8760.0e_cu = P_CU * x_avg ** 2 * 8760.0print(f" average demand {p_avg:.2f} kW = {p_avg / PF:.1f} kVA")print(f" annual iron loss {e_fe:.0f} kWh, copper loss {e_cu:.0f} kWh, " f"total {e_fe + e_cu:.0f} kWh")print(f" cost {RATE_KWH * (e_fe + e_cu):,.0f} currency units a year, " f"{100.0 * (e_fe + e_cu) / (12.0 * 42000.0):.2f} % of the energy bought")s_fault = S_TX / Z_TXprint(f" fault level {s_fault:.0f} kVA, fault current " f"{s_fault / (ROOT3 * V_L):.2f} kA")
# ---------- Part 2: feeder F ----------LENGTH, R_M, X_M = 85.0, 1.15e-3, 0.08e-3 # m, ohm per metreR, X = LENGTH * R_M, LENGTH * X_Mprint("Feeder F")print(f" R = {R:.5f} ohm, X = {X:.4f} ohm per conductor")drops = {}for name, amp, pf in (("running", 40.0, 0.84), ("starting", 260.0, 0.30)): sin_phi = math.sqrt(1.0 - pf ** 2) dv_r, dv_x = amp * R * pf, amp * X * sin_phi dv = dv_r + dv_x # exact: supply end held at 415/sqrt(3) V, motor voltage at angle zero v_send = V_L / ROOT3 dz = cmath.rect(amp, -math.acos(pf)) * complex(R, X) v_rec = math.sqrt(v_send ** 2 - dz.imag ** 2) - dz.real exact = ROOT3 * (v_send - v_rec) drops[name] = exact print(f" {name}: {amp:.0f} A at pf {pf:.2f}: R part {dv_r:.3f} V, " f"X part {dv_x:.3f} V, per phase {dv:.3f} V") print(f" line to line {ROOT3 * dv:.2f} V = {100.0 * ROOT3 * dv / V_L:.2f} % " f"of 415 V, cable loss {3.0 * amp ** 2 * R / 1000.0:.2f} kW") print(f" exact phasor result {exact:.2f} V = {100.0 * exact / V_L:.2f} %, " f"voltage at the motor {V_L - exact:.1f} V")print(f" length for 3 % at 40 A: " f"{0.03 * V_L / (ROOT3 * 40.0 * (R_M * 0.84 + X_M * 0.5426)):.0f} m")
# ---------- Part 3: generator C ----------S_GEN, P_GEN = 100.0, 80.0 # kVA and kW ratingsFUEL_PRICE = 180.0 # currency units per litre (an example)points = {0.25: 0.40, 0.75: 0.28} # typical litres per kWh at two loadsprint("Generator C")print(f" at pf {PF} the 100 kVA limit allows {S_GEN * PF:.0f} kW; " f"the engine allows {P_GEN:.0f} kW")rate = {}for frac, sfc in points.items(): p = frac * P_GEN rate[frac] = p * sfc print(f" {100 * frac:.0f} % load = {p:.0f} kW: {sfc:.2f} L/kWh, " f"{p * sfc:.1f} L/h, {sfc * FUEL_PRICE:.1f} currency units per kWh " f"({sfc * FUEL_PRICE / RATE_KWH:.1f} times the mains price)")slope = (rate[0.75] - rate[0.25]) / (0.5 * P_GEN)idle = rate[0.25] - slope * 0.25 * P_GENprint(f" straight line through the two points: " f"{idle:.1f} L/h at no load + {slope:.2f} L per kWh")for p in (10.0, 40.0, 80.0): sfc = idle / p + slope print(f" {p:.0f} kW: {idle + slope * p:.1f} L/h, {sfc:.3f} L/kWh, " f"{sfc * FUEL_PRICE:.1f} per kWh")
# ---------- Plot ----------fig, ax = plt.subplots(1, 3, figsize=(13, 4))xs = np.linspace(0.02, 1.2, 300)ax[0].plot(100 * xs, [100 * tx_efficiency(x, PF) for x in xs])ax[0].axvline(100 * x_best, linestyle="--", color="gray")ax[0].set_ylim(96.0, 99.0)ax[0].set_xlabel("load (% of 200 kVA)")ax[0].set_ylabel("efficiency (%)")ax[0].set_title("Transformer D at pf 0.78")ax[1].bar(list(drops.keys()), [100 * d / V_L for d in drops.values()])ax[1].set_ylabel("voltage drop (% of 415 V)")ax[1].set_title("Feeder F, 85 m of 16 mm2 copper")ps = np.linspace(5.0, 80.0, 200)ax[2].plot(ps, (idle / ps + slope) * FUEL_PRICE)ax[2].axhline(RATE_KWH, linestyle="--", color="gray")ax[2].set_xlabel("generator load (kW)")ax[2].set_ylabel("fuel cost (currency units per kWh)")ax[2].set_title("Generator C (dashed: mains energy price)")fig.tight_layout()fig.savefig("transformer_cable_generator.png", dpi=120)print("Saved transformer_cable_generator.png")Expected output
Transformer D best efficiency at x = 0.401 = 80.2 kVA, efficiency 98.58 % at pf 0.78 peak (150 kVA): x = 0.750, copper 1.575 kW, total loss 2.025 kW, output 117.0 kW, efficiency 98.30 % average load: x = 0.374, copper 0.392 kW, total loss 0.842 kW, output 58.3 kW, efficiency 98.58 % average demand 58.33 kW = 74.8 kVA annual iron loss 3942 kWh, copper loss 3430 kWh, total 7372 kWh cost 88,459 currency units a year, 1.46 % of the energy bought fault level 4444 kVA, fault current 6.18 kAFeeder F R = 0.09775 ohm, X = 0.0068 ohm per conductor running: 40 A at pf 0.84: R part 3.284 V, X part 0.148 V, per phase 3.432 V line to line 5.94 V = 1.43 % of 415 V, cable loss 0.47 kW exact phasor result 5.96 V = 1.44 %, voltage at the motor 409.0 V starting: 260 A at pf 0.30: R part 7.624 V, X part 1.687 V, per phase 9.311 V line to line 16.13 V = 3.89 % of 415 V, cable loss 19.82 kW exact phasor result 18.16 V = 4.38 %, voltage at the motor 396.8 V length for 3 % at 40 A: 178 mGenerator C at pf 0.78 the 100 kVA limit allows 78 kW; the engine allows 80 kW 25 % load = 20 kW: 0.40 L/kWh, 8.0 L/h, 72.0 currency units per kWh (6.0 times the mains price) 75 % load = 60 kW: 0.28 L/kWh, 16.8 L/h, 50.4 currency units per kWh (4.2 times the mains price) straight line through the two points: 3.6 L/h at no load + 0.22 L per kWh 10 kW: 5.8 L/h, 0.580 L/kWh, 104.4 per kWh 40 kW: 12.4 L/h, 0.310 L/kWh, 55.8 per kWh 80 kW: 21.2 L/h, 0.265 L/kWh, 47.7 per kWhSaved transformer_cable_generator.pngCommon Mistakes
- Calculating copper loss from kW. The copper loss follows the square of the kVA, so divide the kW by the power factor first.
- Forgetting the iron loss when the site is idle. It is present for all 8,760 hours of the year, with or without load.
- Checking the voltage drop only at full-load current. The largest drop occurs during starting, and that is when the motor needs its torque.
- Sizing a generator from the kW of the loads alone. The alternator is limited in kVA, and motor starting needs a separate check.
- Costing generator energy from the fuel figure at full load. The cost for each kWh depends strongly on how lightly the set is loaded.
Summary
- A transformer has an iron loss that is constant while it is energised and a copper loss that follows the square of the load fraction:
. Its efficiency is highest where the two are equal. - Transformer D loses 2.025 kW at the 150 kVA peak of site E (98.30 percent efficiency) and 0.842 kW at the average load (98.58 percent). Over a year it loses at least 7,372 kWh.
- The percent impedance gives the fault level:
, or 6.18 kA at 415 V, counting the transformer only. - The voltage drop of a three-phase cable is
. Feeder F drops 1.43 percent at full-load current and about 4.4 percent during a direct-on-line start, where the simple formula reads 3.89 percent. - A generator has a kW limit from its engine and a kVA limit from its alternator. Its fuel for each kWh rises steeply at light load: for generator C, 50.4 currency units per kWh at 75 percent load and 72.0 at 25 percent, at the example fuel price.
Exercises
1. A 500 kVA transformer has an iron loss of 0.90 kW and a copper loss of 5.5 kW at rated load. Find the load of best efficiency, and the efficiency at 60 percent load and a power factor of 0.85.
Answer
2. A transformer of 315 kVA has an impedance of 5 percent. Estimate the fault level and the fault current at its 415 V terminals, counting the transformer only.
Answer
3. A 35 mm² copper cable, 120 m long, has a typical resistance of 0.63 mΩ per metre and a reactance of 0.08 mΩ per metre. It carries 75 A at a power factor of 0.85 lagging on a 415 V three-phase supply. Find the voltage drop between lines in volts and in percent.
Answer
4. During power cuts, generator C carries 30 kW for 3 hours a day on 30 days of a month. Use the straight line of Application 3 (3.6 L/h at no load and 0.22 L for each kWh) and a fuel price of 180 currency units per litre. Find the fuel for each kWh, the fuel cost for the month, and the cost of the same energy from the mains at 12.00 currency units per kWh.
Answer
The set burns
References
- S. J. Chapman, Electric Machinery Fundamentals, 5th edition, McGraw-Hill, 2012.
- J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and Design, 6th edition, Cengage Learning, 2017.
- A. Hughes and B. Drury, Electric Motors and Drives: Fundamentals, Types and Applications, 5th edition, Newnes, 2019.
A 200 kVA transformer can run a site at 150 kVA or at 80 kVA. At which load does it lose the smallest share of the power it passes?
Transformer D of the lesson: 200 kVA, iron loss 0.45 kW at any load, copper loss 2.8 kW at rated load, growing with the square of the load. Power factor 0.78, as at site E. The marker shows the chosen load; the dotted line is the load where the two losses are equal.
Check yourself
Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.
1. A 100 kVA transformer has an iron loss of 0.30 kW and a copper loss of 1.9 kW at rated load. At what load is its efficiency highest?
2. A 60 m run of the lesson's 16 mm² cable (1.15 mΩ and 0.08 mΩ per metre) carries 50 A at power factor 0.84. What is the voltage drop between lines, as a share of 415 V?
3. A spare 200 kVA transformer (iron loss 0.45 kW) is left energised all year with no load on it. About how much energy does it lose in a year?
- The current lags the motor voltage. Its IR drop is in step with it; its IX drop is 90° ahead.
- Only the parts along the voltage shorten it: IR cos φ + IX sin φ.
- Feeder F at 40.0 A, pf 0.84: 3.28 V + 0.15 V = 3.43 V in each phase.
- Between lines the drop is √3 × 3.43 = 5.94 V, 1.43%: the motor gets about 409 V.
- In this 16 mm² cable R is 14 times X, so the resistance gives almost all the drop.
Discussion
No comments yet. Questions, results from your own build, a better way to explain it: all welcome.