Transformers, Generators and Voltage Drop

Lesson 9 of 10 27 min read
Found this useful?

A transformer hums all night for a site that is closed, and nobody counts the energy it turns into heat. A motor at the end of a long cable starts slowly and the lights dim, because the cable keeps some of the volts. During a power cut, a 100 kVA generator runs for hours to feed a few lights and a cold room, and each kWh costs five or six times the mains price. These three losses lie between the supply and the machine, and each one can be calculated from a few figures on a nameplate or a data sheet. This lesson shows the calculations and their limits. #Transformers #VoltageDrop #DieselGenerator

Learning Objectives

By the end of this lesson, you will be able to:

  1. Calculate the iron loss, copper loss and efficiency of a transformer at any load, and the load at which its efficiency is highest
  2. Estimate the energy that a transformer loses in a year and what it costs
  3. Calculate the voltage drop on a three-phase cable from its resistance, its reactance and the power factor of the load
  4. Distinguish the kW rating of a generator from its kVA rating and say which one limits a given load
  5. Work out the fuel cost of each kWh from a generator at different loads

Real-World System Problem: The path from the 11 kV line to the motor



Site E is a cold store. Its supply arrives at 11 kV and a 200 kVA transformer reduces it to 415 V. From the main board, an 85 m copper cable feeds the 22 kW compressor motor. When the mains supply fails, a changeover switch connects the board to a 100 kVA diesel generator.

Each of these three items takes something for itself. The transformer loses a fixed amount of power in its iron core for every hour that it is energised, and a further amount in its windings that grows with the load. The cable loses voltage, so the motor never receives the full 415 V, and it receives least during starting, when it needs torque most. The generator burns fuel only to keep turning, before it delivers any power at all.

None of these effects appears as a separate line on a bill. They are inside the kWh and the fuel account. The figures needed to find them are on the nameplates and in the length and size of the cable.

Motor A22 kWGenerator C100 kVATransformer D200 kVA 4.5%changeover switch11 kV415 V main boardother loadsfeeder F, 85 mother loads16 mm² copper
Site E from the 11 kV line to the compressor

Fundamental Theory: What the supply path keeps for itself



The supply in this course is three-phase, four-wire, 50 Hz, with a line voltage of 415 V and 240 V from line to neutral. These are the nominal figures in Kenya and much of East Africa, and many countries use the IEC nominal of 400/230 V. All values are RMS. is real power in kW, is apparent power in kVA, and is the power factor.

What a transformer rating says

A transformer nameplate gives a rating in kVA, not in kW, because the heating of the windings depends on the current and the maker cannot know the power factor of the load.

Transformer D is rated 200 kVA, 11 kV to 415 V. Its rated current on the 415 V side is

This lesson uses one more quantity, the load fraction :

where is the kVA that the transformer carries at that moment. At the maximum demand of site E, .

Two losses that behave differently

The iron loss (also called the no-load loss) is the heating of the steel core by the alternating magnetic field. The field depends on the voltage, not on the load, so the iron loss is almost constant for every hour that the transformer is energised.

The copper loss is the heating of the windings. It depends on the square of the current. The nameplate or the test certificate gives its value at rated current, . At any other load the copper loss is .

Transformer losses and efficiency

is the efficiency. For transformer D, and .

loss (kW)3.25●total loss2.03●copper loss growswith the square0.90●oftheload0.45iron loss, the same at every load0load040 %75 %100 %
Losses of transformer D against load

The load of best efficiency

At very light load the efficiency is poor, because the iron loss is shared by few kW. At heavy load the copper loss grows faster than the output. The loss for each kVA delivered is proportional to . The first term falls as rises and the second rises, and their sum is smallest when they are equal, which means that the copper loss equals the iron loss:

For transformer D, , which is 80.2 kVA. Distribution transformers are designed this way on purpose, because most of them spend most of their life well below rated load.

The curve is flat near its top. Transformer D at a power factor of 0.78 has an efficiency of 98.52 percent at 30 percent load, 98.58 percent at 40 percent and 98.55 percent at 50 percent.

Percent impedance and fault level

The nameplate figure “impedance 4.5 percent” means that 4.5 percent of the rated voltage is lost inside the transformer at rated current. Reverse the idea: if the 415 V terminals are short-circuited, the only thing that limits the current is this impedance, so the current is times the rated current. Expressed as apparent power, this is the fault level, , and the fault current is , or 6.18 kA. Every breaker and fuse at the main board must be able to interrupt this current safely. The calculation counts the transformer only. The supplier’s network adds some impedance, so the real fault current is a little lower, and at the end of a long cable it is much lower.

Voltage drop in a cable

A cable has resistance , and also a small inductive reactance , because each conductor lies in the magnetic field of the others. A current produces a voltage across that is in phase with the current, and a voltage across that leads the current by .

RX●●supply endImotor endV_s (phase)V_r (phase)●●neutral: no current when balanced
One phase of the feeder to the motor

What matters to the motor is how much smaller the voltage at its end, , is than the voltage at the supply end, . That depends on the angle of the current. The part of the voltage that lies along the supply voltage is , and the part of the voltage that lies along it is .

Voltage drop of a balanced three-phase cable

is the line current, and belong to one conductor over the length of the cable, and is the angle of the load. is the drop in each phase and is the drop between lines.

Three points about this formula.

  • In a balanced three-phase circuit the neutral carries no current, so only one conductor length counts and the factor is . A single-phase circuit has current in two conductors and the factor is 2.
  • For small cables is much larger than , and the resistance part decides the result. For large cables (240 mm² and above) is about as large as , and a low power factor then makes the drop worse.
  • The formula is an approximation. It ignores the part of the cable voltage that is at right angles to the supply voltage. The error grows when the drop is several percent, as Application 2 shows.
  • The resistance of copper rises by about 0.4 percent for each degree. A data sheet often gives it at 20 °C, while a loaded cable with PVC insulation may run at up to 70 °C, where its resistance is about 1.2 times larger. Tables for wiring rules usually give the drop at the working temperature, in mV per ampere per metre, and their figures are higher for that reason.

Voltage drop is one of three checks that choose a cable size, and it is not the first. The cable must carry the load current without overheating, using the rating from the tables of the local wiring rules for its installation method, reduced by factors for a hot ambient, for cables grouped together and for burial. It must also survive a fault until the protection opens it, and the fault current at its far end must be large enough to make that protection open quickly. A cable that passes the voltage drop check can still fail either of the others.

The limit on voltage drop

Wiring rules limit the voltage drop between the origin of an installation and the equipment. Many rules use figures of a few percent of the nominal voltage for normal running, and values from 3 to 5 percent are common. The figure, and the point from which it is measured, differ from one country to another, so check the rule that applies where the installation is.

The reason for the limit is physical. The torque of an induction motor at a given speed varies with the square of its voltage, so a motor at 95 percent voltage has only 90 percent of its torque. During starting the drop is several times larger, because the starting current is several times the full-load current. A larger drop is accepted for those few seconds, provided the motor still accelerates its load.

A generator has two ratings

A generating set is two machines on one shaft. The engine produces mechanical power, which limits the kW. The alternator carries current, which limits the kVA. Generator C is rated 100 kVA and 80 kW, and a load must respect both limits.

  • At a power factor above 0.8, the engine limit is reached first. A load of 90 kW at unity power factor is only 90 kVA, but it overloads the engine.
  • At a power factor below 0.8, the alternator limit is reached first. Site E has a power factor of 0.78, so 100 kVA carries only .

The maximum demand of site E is 150 kVA, so generator C cannot carry the whole site. It is a standby set for selected loads. A motor that starts on the generator needs a third check, because its starting kVA reduces the voltage of a generator far more than it reduces the voltage of the mains.

Fuel for each kWh

A diesel engine uses fuel in two parts. One part only keeps the engine turning against its own friction, its fan, its pumps and the alternator losses. This part is almost the same at every load. The other part is proportional to the electrical output.

fuel (L/h)21.2●16.8●slope: 0.22 L8.0●foreachkWh3.6●fuel burned at no load0kW0206080
Fuel use of generator C against load

Divide the fuel for one hour by the kWh delivered in that hour, and the fixed part is shared by fewer kWh at light load. This is the reason that the fuel for each kWh rises as the load falls. A typical maker’s curve for a set of this size gives about 0.28 litres per kWh at 75 percent load and about 0.40 litres per kWh at 25 percent load. These are typical figures. The data sheet of the real set gives its own curve.

Light load has a second cost. Many makers advise against long running below about 30 percent of rated load, because the engine runs too cool to burn its fuel cleanly. The limit comes from the maker of the set.

Application 1: Transformer D at the load of site E



Step 1: The two load fractions

Click to reveal the load fractions
  1. At the maximum demand.

    The output is . ✅

  2. Average real power.

    The site takes 58.33 kW on average, half of its peak. ✅

  3. Average load fraction. Convert to kVA first, because the copper loss follows the kVA.

    On average the transformer carries 37.4 percent of its rating. ✅

Step 2: Losses and efficiency

Click to reveal the losses
  1. Copper loss at the peak.

    ✅

  2. Total loss and efficiency at the peak.

    The efficiency at the maximum demand is 98.30 percent. ✅

  3. Copper loss at the average load.

    At this load the copper loss is smaller than the iron loss of 0.45 kW. ✅

  4. Total loss and efficiency at the average load.

    The efficiency at the average load is 98.58 percent. ✅

Step 3: The load of best efficiency

Click to reveal the best point
  1. Load fraction. The efficiency is highest where the copper loss equals the iron loss.

    The best point is at 80.2 kVA, where the total loss is . ✅

  2. Compare. The average load of 74.8 kVA is close to the best point, and the efficiency there (98.58 percent) is the same as the best value to two decimal places. The transformer is well matched to this site. ✅

Step 4: Energy lost in a year

Click to reveal the annual loss
  1. Iron loss energy. The iron loss is present for every hour of the year.

    This energy is lost even if the site is closed all year. ✅

  2. Copper loss energy. Use the average load fraction for the whole year.

    This is a low estimate, for the reason given in the insight below. ✅

  3. Total and cost.

    (The cost uses the unrounded energy.) The loss is 1.46 percent of the that the site buys in a year. ✅

  4. Check a second way. The mean loss over the year is , and , which agrees with item 3 within rounding. The Python script prints 7,372 kWh and efficiencies of 98.30 and 98.58 percent. ✅

Application 2: Voltage drop on the feeder to the compressor



Step 1: Resistance and reactance of the cable

Click to reveal the cable values
  1. Resistance of one conductor.

    ✅

  2. Reactance of one conductor.

    The resistance is 14 times the reactance, so this cable is almost purely resistive. ✅

Step 2: Drop at full-load current

Click to reveal the running drop
  1. Angle. , so . ✅

  2. Drop in each phase.

    The reactance gives only 0.148 V of this. ✅

  3. Drop between lines.

    The motor receives about 409 V. ✅

  4. Compare with a limit. A drop of 1.43 percent is inside the limits of a few percent that wiring rules commonly use. The same current over 178 m of this cable would give 3 percent. ✅

Step 3: Drop during starting

Click to reveal the starting drop
  1. Angle. , so . ✅

  2. Drop in each phase.

    The current is 6.5 times larger, but the drop is only 2.7 times larger, because the starting current is mostly reactive and this cable has little reactance. ✅

  3. Drop between lines.

    The approximate formula gives 3.89 percent during starting. ✅

Step 4: Check with exact phasors

Click to reveal the check
  1. Method. Take the motor voltage as the reference. The supply voltage is the phasor sum , and the size of is fixed at . The cable voltage has a part along , which is the already found, and a part at right angles to it, . ✅

  2. Running. The part at right angles is .

    The exact drop is 5.96 V between lines, or 1.44 percent. The approximation gave 5.94 V. ✅

  3. Starting. The part at right angles is .

    The exact drop is 18.16 V between lines, or 4.38 percent, and the motor terminals receive 396.8 V. The approximation gave 16.13 V, which is 11 percent too low. ✅

  4. Check with the script. The Python script prints 5.94 V and 5.96 V for running, and 16.13 V and 18.16 V for starting. ✅

Application 3: Fuel cost of each kWh from generator C



Step 1: Fuel and cost at the two loads

Click to reveal the fuel cost
  1. At 75 percent load. The output is .

    Each kWh costs 4.2 times the mains price in fuel alone. ✅

  2. At 25 percent load. The output is .

    Each kWh costs 6.0 times the mains price. ✅

  3. Compare. The output fell to one third, and the fuel for an hour fell only to 48 percent. ✅

Step 2: The fuel burned at no load

Click to reveal the straight line
  1. Slope. Between the two points the fuel rises by for 40 kW more output.

    ✅

  2. Fuel at no load.

    The line says that the set burns about 3.6 litres an hour before it delivers anything, which is 648 currency units an hour. ✅

  3. Check. The line must return the second point: , which is correct. At 10 kW it gives , or 0.58 litres and 104.4 currency units for each kWh. The script prints the same values. ✅

Verify It in Python



The script repeats the three applications and saves one figure: the efficiency curve of transformer D, the two voltage drops of feeder F and the fuel cost of generator C against load.

transformer_cable_generator.py
"""Transformer D losses, voltage drop on feeder F, and the fuel cost of generator C."""
import cmath
import math
import numpy as np
import matplotlib.pyplot as plt
V_L = 415.0
ROOT3 = math.sqrt(3.0)
# ---------- Part 1: transformer D ----------
S_TX, Z_TX = 200.0, 0.045 # kVA, impedance per unit
P_FE, P_CU = 0.45, 2.8 # iron loss and full-load copper loss, kW
PF = 0.78 # power factor of site E
RATE_KWH = 12.00 # tariff G, currency units per kWh
def tx_losses(x):
"""Total loss in kW at the load fraction x = S / S_rated."""
return P_FE + P_CU * x ** 2
def tx_efficiency(x, pf):
p_out = x * S_TX * pf
return p_out / (p_out + tx_losses(x))
x_best = math.sqrt(P_FE / P_CU)
x_peak = 150.0 / S_TX
p_avg = 42000.0 / 720.0 # average kW of a 30-day month
x_avg = p_avg / PF / S_TX
print("Transformer D")
print(f" best efficiency at x = {x_best:.3f} = {x_best * S_TX:.1f} kVA, "
f"efficiency {100.0 * tx_efficiency(x_best, PF):.2f} % at pf {PF}")
for name, x in (("peak (150 kVA)", x_peak), ("average load", x_avg)):
print(f" {name}: x = {x:.3f}, copper {P_CU * x ** 2:.3f} kW, "
f"total loss {tx_losses(x):.3f} kW, output {x * S_TX * PF:.1f} kW, "
f"efficiency {100.0 * tx_efficiency(x, PF):.2f} %")
e_fe = P_FE * 8760.0
e_cu = P_CU * x_avg ** 2 * 8760.0
print(f" average demand {p_avg:.2f} kW = {p_avg / PF:.1f} kVA")
print(f" annual iron loss {e_fe:.0f} kWh, copper loss {e_cu:.0f} kWh, "
f"total {e_fe + e_cu:.0f} kWh")
print(f" cost {RATE_KWH * (e_fe + e_cu):,.0f} currency units a year, "
f"{100.0 * (e_fe + e_cu) / (12.0 * 42000.0):.2f} % of the energy bought")
s_fault = S_TX / Z_TX
print(f" fault level {s_fault:.0f} kVA, fault current "
f"{s_fault / (ROOT3 * V_L):.2f} kA")
# ---------- Part 2: feeder F ----------
LENGTH, R_M, X_M = 85.0, 1.15e-3, 0.08e-3 # m, ohm per metre
R, X = LENGTH * R_M, LENGTH * X_M
print("Feeder F")
print(f" R = {R:.5f} ohm, X = {X:.4f} ohm per conductor")
drops = {}
for name, amp, pf in (("running", 40.0, 0.84), ("starting", 260.0, 0.30)):
sin_phi = math.sqrt(1.0 - pf ** 2)
dv_r, dv_x = amp * R * pf, amp * X * sin_phi
dv = dv_r + dv_x
# exact: supply end held at 415/sqrt(3) V, motor voltage at angle zero
v_send = V_L / ROOT3
dz = cmath.rect(amp, -math.acos(pf)) * complex(R, X)
v_rec = math.sqrt(v_send ** 2 - dz.imag ** 2) - dz.real
exact = ROOT3 * (v_send - v_rec)
drops[name] = exact
print(f" {name}: {amp:.0f} A at pf {pf:.2f}: R part {dv_r:.3f} V, "
f"X part {dv_x:.3f} V, per phase {dv:.3f} V")
print(f" line to line {ROOT3 * dv:.2f} V = {100.0 * ROOT3 * dv / V_L:.2f} % "
f"of 415 V, cable loss {3.0 * amp ** 2 * R / 1000.0:.2f} kW")
print(f" exact phasor result {exact:.2f} V = {100.0 * exact / V_L:.2f} %, "
f"voltage at the motor {V_L - exact:.1f} V")
print(f" length for 3 % at 40 A: "
f"{0.03 * V_L / (ROOT3 * 40.0 * (R_M * 0.84 + X_M * 0.5426)):.0f} m")
# ---------- Part 3: generator C ----------
S_GEN, P_GEN = 100.0, 80.0 # kVA and kW ratings
FUEL_PRICE = 180.0 # currency units per litre (an example)
points = {0.25: 0.40, 0.75: 0.28} # typical litres per kWh at two loads
print("Generator C")
print(f" at pf {PF} the 100 kVA limit allows {S_GEN * PF:.0f} kW; "
f"the engine allows {P_GEN:.0f} kW")
rate = {}
for frac, sfc in points.items():
p = frac * P_GEN
rate[frac] = p * sfc
print(f" {100 * frac:.0f} % load = {p:.0f} kW: {sfc:.2f} L/kWh, "
f"{p * sfc:.1f} L/h, {sfc * FUEL_PRICE:.1f} currency units per kWh "
f"({sfc * FUEL_PRICE / RATE_KWH:.1f} times the mains price)")
slope = (rate[0.75] - rate[0.25]) / (0.5 * P_GEN)
idle = rate[0.25] - slope * 0.25 * P_GEN
print(f" straight line through the two points: "
f"{idle:.1f} L/h at no load + {slope:.2f} L per kWh")
for p in (10.0, 40.0, 80.0):
sfc = idle / p + slope
print(f" {p:.0f} kW: {idle + slope * p:.1f} L/h, {sfc:.3f} L/kWh, "
f"{sfc * FUEL_PRICE:.1f} per kWh")
# ---------- Plot ----------
fig, ax = plt.subplots(1, 3, figsize=(13, 4))
xs = np.linspace(0.02, 1.2, 300)
ax[0].plot(100 * xs, [100 * tx_efficiency(x, PF) for x in xs])
ax[0].axvline(100 * x_best, linestyle="--", color="gray")
ax[0].set_ylim(96.0, 99.0)
ax[0].set_xlabel("load (% of 200 kVA)")
ax[0].set_ylabel("efficiency (%)")
ax[0].set_title("Transformer D at pf 0.78")
ax[1].bar(list(drops.keys()), [100 * d / V_L for d in drops.values()])
ax[1].set_ylabel("voltage drop (% of 415 V)")
ax[1].set_title("Feeder F, 85 m of 16 mm2 copper")
ps = np.linspace(5.0, 80.0, 200)
ax[2].plot(ps, (idle / ps + slope) * FUEL_PRICE)
ax[2].axhline(RATE_KWH, linestyle="--", color="gray")
ax[2].set_xlabel("generator load (kW)")
ax[2].set_ylabel("fuel cost (currency units per kWh)")
ax[2].set_title("Generator C (dashed: mains energy price)")
fig.tight_layout()
fig.savefig("transformer_cable_generator.png", dpi=120)
print("Saved transformer_cable_generator.png")

Expected output

Transformer D
best efficiency at x = 0.401 = 80.2 kVA, efficiency 98.58 % at pf 0.78
peak (150 kVA): x = 0.750, copper 1.575 kW, total loss 2.025 kW, output 117.0 kW, efficiency 98.30 %
average load: x = 0.374, copper 0.392 kW, total loss 0.842 kW, output 58.3 kW, efficiency 98.58 %
average demand 58.33 kW = 74.8 kVA
annual iron loss 3942 kWh, copper loss 3430 kWh, total 7372 kWh
cost 88,459 currency units a year, 1.46 % of the energy bought
fault level 4444 kVA, fault current 6.18 kA
Feeder F
R = 0.09775 ohm, X = 0.0068 ohm per conductor
running: 40 A at pf 0.84: R part 3.284 V, X part 0.148 V, per phase 3.432 V
line to line 5.94 V = 1.43 % of 415 V, cable loss 0.47 kW
exact phasor result 5.96 V = 1.44 %, voltage at the motor 409.0 V
starting: 260 A at pf 0.30: R part 7.624 V, X part 1.687 V, per phase 9.311 V
line to line 16.13 V = 3.89 % of 415 V, cable loss 19.82 kW
exact phasor result 18.16 V = 4.38 %, voltage at the motor 396.8 V
length for 3 % at 40 A: 178 m
Generator C
at pf 0.78 the 100 kVA limit allows 78 kW; the engine allows 80 kW
25 % load = 20 kW: 0.40 L/kWh, 8.0 L/h, 72.0 currency units per kWh (6.0 times the mains price)
75 % load = 60 kW: 0.28 L/kWh, 16.8 L/h, 50.4 currency units per kWh (4.2 times the mains price)
straight line through the two points: 3.6 L/h at no load + 0.22 L per kWh
10 kW: 5.8 L/h, 0.580 L/kWh, 104.4 per kWh
40 kW: 12.4 L/h, 0.310 L/kWh, 55.8 per kWh
80 kW: 21.2 L/h, 0.265 L/kWh, 47.7 per kWh
Saved transformer_cable_generator.png

Common Mistakes



  • Calculating copper loss from kW. The copper loss follows the square of the kVA, so divide the kW by the power factor first.
  • Forgetting the iron loss when the site is idle. It is present for all 8,760 hours of the year, with or without load.
  • Checking the voltage drop only at full-load current. The largest drop occurs during starting, and that is when the motor needs its torque.
  • Sizing a generator from the kW of the loads alone. The alternator is limited in kVA, and motor starting needs a separate check.
  • Costing generator energy from the fuel figure at full load. The cost for each kWh depends strongly on how lightly the set is loaded.

Summary



  • A transformer has an iron loss that is constant while it is energised and a copper loss that follows the square of the load fraction: . Its efficiency is highest where the two are equal.
  • Transformer D loses 2.025 kW at the 150 kVA peak of site E (98.30 percent efficiency) and 0.842 kW at the average load (98.58 percent). Over a year it loses at least 7,372 kWh.
  • The percent impedance gives the fault level: , or 6.18 kA at 415 V, counting the transformer only.
  • The voltage drop of a three-phase cable is . Feeder F drops 1.43 percent at full-load current and about 4.4 percent during a direct-on-line start, where the simple formula reads 3.89 percent.
  • A generator has a kW limit from its engine and a kVA limit from its alternator. Its fuel for each kWh rises steeply at light load: for generator C, 50.4 currency units per kWh at 75 percent load and 72.0 at 25 percent, at the example fuel price.

Exercises



1. A 500 kVA transformer has an iron loss of 0.90 kW and a copper loss of 5.5 kW at rated load. Find the load of best efficiency, and the efficiency at 60 percent load and a power factor of 0.85.

Answer

, which is 202 kVA. At the output is and the loss is . The efficiency is percent.

2. A transformer of 315 kVA has an impedance of 5 percent. Estimate the fault level and the fault current at its 415 V terminals, counting the transformer only.

Answer

. The fault current is , or 8.76 kA.

3. A 35 mm² copper cable, 120 m long, has a typical resistance of 0.63 mΩ per metre and a reactance of 0.08 mΩ per metre. It carries 75 A at a power factor of 0.85 lagging on a 415 V three-phase supply. Find the voltage drop between lines in volts and in percent.

Answer

and , with . . Between lines this is , or 2.17 percent.

4. During power cuts, generator C carries 30 kW for 3 hours a day on 30 days of a month. Use the straight line of Application 3 (3.6 L/h at no load and 0.22 L for each kWh) and a fuel price of 180 currency units per litre. Find the fuel for each kWh, the fuel cost for the month, and the cost of the same energy from the mains at 12.00 currency units per kWh.

Answer

The set burns , which is 0.34 L and 61.2 currency units for each kWh. In 90 hours it burns 918 litres, which cost 165,240 currency units, and it delivers 2,700 kWh. The same energy from the mains costs 32,400 currency units.

References



  • S. J. Chapman, Electric Machinery Fundamentals, 5th edition, McGraw-Hill, 2012.
  • J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and Design, 6th edition, Cengage Learning, 2017.
  • A. Hughes and B. Drury, Electric Motors and Drives: Fundamentals, Types and Applications, 5th edition, Newnes, 2019.


© 2021-2026 SiliconWit®. All rights reserved.
Predict first

A 200 kVA transformer can run a site at 150 kVA or at 80 kVA. At which load does it lose the smallest share of the power it passes?

11 kV, small current415 V, large current same power, less a little loss
See it: two losses, and where the efficiency peaks

Efficiency
Total loss
Iron loss
Copper loss

Transformer D of the lesson: 200 kVA, iron loss 0.45 kW at any load, copper loss 2.8 kW at rated load, growing with the square of the load. Power factor 0.78, as at site E. The marker shows the chosen load; the dotted line is the load where the two losses are equal.

11 kV Transformer D 200 kVA, 4.5 % G ~ Generator C 100 kVA changeover switch 415 V main board other loads other loads feeder F, 85 m 16 mm² copper M 3~ Motor A 22 kW
The path from the 11 kV line to the motor
0 0.45 0.90 2.03 3.25 loss (kW) load 40 % 75 % 100 % 0 iron loss, the same at every load total loss copper loss grows with the square of the load
Two losses that behave differently
R X I supply end V_s (phase) motor end V_r (phase) neutral: no current when balanced
Voltage drop in a cable
3.6 8.0 16.8 21.2 0 fuel (L/h) kW 0 20 60 80 fuel burned at no load slope: 0.22 L for each kWh
Fuel for each kWh

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. A 100 kVA transformer has an iron loss of 0.30 kW and a copper loss of 1.9 kW at rated load. At what load is its efficiency highest?

2. A 60 m run of the lesson's 16 mm² cable (1.15 mΩ and 0.08 mΩ per metre) carries 50 A at power factor 0.84. What is the voltage drop between lines, as a share of 415 V?

3. A spare 200 kVA transformer (iron loss 0.45 kW) is left energised all year with no load on it. About how much energy does it lose in a year?

Watch it build: the drop along one cable
Vr motor end I φ not to scale IRIX Vs IR: in step with IIX: 90° ahead of I the drop is the partalong V: IR cos φ + IX sin φ IR cos φ = 3.28 VIX sin φ = 0.15 V3.43 V per phase × √3 = 5.94 V, 1.43%motor gets 409 V R is 14 × X here:IR gives 3.28 of 3.43 V
  1. The current lags the motor voltage. Its IR drop is in step with it; its IX drop is 90° ahead.
  2. Only the parts along the voltage shorten it: IR cos φ + IX sin φ.
  3. Feeder F at 40.0 A, pf 0.84: 3.28 V + 0.15 V = 3.43 V in each phase.
  4. Between lines the drop is √3 × 3.43 = 5.94 V, 1.43%: the motor gets about 409 V.
  5. In this 16 mm² cable R is 14 times X, so the resistance gives almost all the drop.