Estimate of the voltage dip at starting
Motor Starting and Protection
On this page
The mains supply fails, the standby generator takes the load, and the cold store compressor tries to start. The lights dim, a contactor in another panel opens, a computer restarts, and the compressor stops before it reaches speed. On the mains the same motor started every day and nobody noticed. Nothing is broken: for a few seconds the motor asks for 260 A from a source that was sized for its 40.0 A running current. This lesson shows how to calculate the starting current, estimate the voltage dip it causes, compare the ways to reduce it, and understand what the protective devices in a starter do when they trip. #MotorStarting #VoltageDip #MotorProtection
Learning Objectives
By the end of this lesson, you will be able to:
- Calculate the starting current and the starting kVA of an induction motor from its nameplate
- Estimate the voltage dip that a motor start causes on a transformer and on a generator
- Compare direct on line, star-delta, soft starter and drive starting by current and by torque
- Explain what an overload relay, its trip class, and short-circuit and phase-loss protection each respond to
- Explain why every start heats a motor and why the number of starts per hour is limited
Real-World System Problem: One compressor, two sources
The cold store compressor motor is rated 22 kW, 415 V, 50 Hz, with a full-load current of 40.0 A. The supply of 415 V between lines is the nominal figure in Kenya and much of East Africa (the IEC nominal figure is 400 V, and the method is the same). Normally it comes from a 200 kVA distribution transformer. When the mains fails, a 100 kVA standby diesel generator takes its place.
At the moment of starting the motor draws 6.5 times its full-load current, and it continues to draw several times full-load current until it is close to full speed. That current flows through the impedance of the source, and the voltage at every load on the same busbar falls while it flows. The transformer is a stiff source and its voltage falls by a few percent. The generator is a weak source and its voltage falls much further. Whether a start is acceptable depends on the source as much as on the motor.
Fundamental Theory: Starting current, voltage dip and protection
Why a motor at standstill takes so much current
An induction motor behaves as a transformer whose secondary winding is the rotor. At full speed the slip is small and only a small voltage is induced in the rotor. At standstill the slip is 1. The field passes the rotor bars at its full speed, the induced rotor voltage is at its largest, and the rotor behaves as a short-circuited secondary. The stator must supply a matching current.
This is the locked-rotor current
The apparent power that the motor asks for at that moment is the starting kVA:
The power factor during starting is low, typically about 0.2 to 0.3, because the current is limited mainly by the leakage reactance of the windings. Most of the starting kVA is reactive. The current also does not fall steadily as the motor gains speed. It stays near the locked-rotor value for most of the run and falls quickly only near full speed.
Starting torque
A current of 6.5 times full load does not give 6.5 times the torque. The power factor of the rotor circuit is poor at standstill, and the starting torque of a standard motor is typically 1.5 to 2.5 times the full-load torque. The maker’s data gives the real figure.
At any given speed, the motor behaves as a fixed impedance. Its current is then proportional to the voltage at its terminals, and its torque is proportional to the square of that voltage:
These two relations explain every reduced-voltage starting method: half the current means one quarter of the torque. The motor accelerates only while its torque is greater than the torque of the load, so a method that reduces the current too far leaves the machine unable to reach speed.
Voltage dip on the source
Every source has an internal impedance
A source impedance is usually quoted as a short-circuit capacity
Since an impedance is
This is an estimate, and it has four assumptions.
- It adds the two impedances as plain numbers, as if they had the same angle. A source impedance is almost pure reactance and a starting motor has a power factor of only 0.2 to 0.3, so the angles are close and the estimate is slightly high.
- It treats the motor as a fixed impedance, which is correct for the first instant.
- For a transformer,
ignores the network behind the transformer. The real is a little lower and the real dip a little higher. - For a generator, the subtransient reactance describes the first cycles only. After that the reactance rises, and then the voltage regulator restores the voltage. Generator makers publish motor starting curves that include both effects.
What a dip does
A dip cuts the torque of the starting motor by the square of the voltage, so the start takes longer. Every other load on the busbar feels it: lamps flicker, electronics may reset, running motors draw more current. A contactor is held closed by a coil fed from the same supply, and if the voltage falls far enough the coil releases the contacts in the middle of the start.
Limits differ between supply authorities and sites. A dip of about 10 to 15 percent at the motor terminals during starting is a commonly used limit, and contactors may drop out when the voltage falls by about 20 to 30 percent. Both are typical values. Real work uses the local rules and the maker’s data.
Four ways to start
Direct on line. A contactor connects the motor to the full supply voltage. The motor takes its full locked-rotor current and gives its full starting torque. It is the simplest method, and on a stiff supply it is often the correct one.
Star-delta. A motor that runs in delta, with all six winding ends brought to the terminal box, is first connected in star. Each winding then receives
After a set time the starter opens the star connection and closes the delta connection. Two things can go wrong. If the load needs more than one third of the starting torque, the motor stops accelerating well below full speed, and the change to delta then draws almost the full direct on line current. Also, the common open-transition starter disconnects the motor briefly during the change. The motor keeps a voltage of its own, which may be out of step with the supply when the delta contactor closes, giving a short spike that can exceed the direct on line current. Star-delta starting suits loads that are light during starting, such as an unloaded compressor or a fan.
Soft starter. A soft starter uses thyristors in each line to raise the motor voltage smoothly, and usually to hold the current at a set limit, for example 3 times full-load current. There is no step and no transition spike. The law
A soft starter controls the voltage and not the frequency. It cannot give full torque at low current.
Variable speed drive. A drive raises the frequency and the voltage together from near zero. The motor always runs at a small slip, so it can give full-load torque while it draws about full-load current. This is the gentlest start for the supply and the most expensive.
What each protective device is watching
A starter contains several devices, and each one answers a different question.
Thermal overload relay. An overloaded motor does not fail at once. Its windings become too hot, and heat shortens the life of the insulation. The overload relay is a model of that heating. A bimetal strip or an electronic circuit follows the line current and trips when the modelled temperature is too high: slowly for a small overload and quickly for a large one. The relay is set to the full-load current on the nameplate for the supply voltage in use, 40.0 A for the compressor, and not to a current measured on a lightly loaded day. In a star-delta starter the relay usually sits in the motor leads after the main contactor, where it carries the winding current, and it is then set to
Trip class. The relay must not trip during a normal start, when the current is several times the setting for some seconds. The trip class states how much time it allows. In the IEC standard for motor starters (IEC 60947-4-1), the class number is the longest time, in seconds, that the relay takes to trip from cold at 7.2 times its current setting.
| Trip class | Trip time from cold at 7.2 times the setting |
|---|---|
| 10 | more than 4 s, not more than 10 s |
| 20 | more than 6 s, not more than 20 s |
| 30 | more than 9 s, not more than 30 s |
Class 10 suits most motors with a short start. Classes 20 and 30 are for loads of high inertia that need a long start, and the motor must be able to survive that start. A current only a little above the setting gives no trip for a long time.
Short-circuit protection. A fault between phases or to earth drives thousands of amperes, and it must be cleared in milliseconds by fuses or by a circuit breaker with a magnetic trip. This protection must ignore the starting current, including its first peak, which is higher than the steady locked-rotor value. An overload relay is too slow for a short circuit, and a fuse that passes the starting current is too large to protect against an overload.
A miniature circuit breaker (MCB) shows the same problem in its curve letter, which gives the band of current, as a multiple of its rating
Earth fault. A fault from a winding to the frame must make the protection act before the frame voltage harms a person. That needs a sound earth connection, and an earth fault current is often too small to trip a large breaker quickly. A residual current device (RCD) trips on a difference between the outgoing and returning currents: typically 30 mA on circuits people touch, such as sockets, and more on fixed motor circuits. A drive fed from three phases can give a smooth DC fault current, which blinds the common type AC and type A devices, so a circuit that feeds a drive needs the RCD type that the drive maker states, usually type B.
Phase loss and unbalance. If one supply conductor is lost (a blown fuse, a failed contact), a running motor continues on the two phases that remain. It draws a much higher current in those two lines, about 1.7 times at the same load, and the windings heat unequally. A stopped motor with one phase missing cannot start: it hums and draws a heavy current. Many overload relays trip faster when the three currents are unequal, and separate relays watch the voltage for phase loss and unbalance. A voltage unbalance of a few percent causes a much larger current unbalance.
Why starts per hour are limited
The copper loss in the stator is proportional to the square of the current, so at 6.5 times full-load current the stator windings are heated at
The rotor is heated too. When a motor accelerates an inertia
A load torque during the start makes it larger. A reduced-voltage start does not make it smaller: it spreads the same heat over a longer time. Only a drive, which keeps the slip small, avoids it.
During a start the fan on the shaft turns slowly and removes little heat. If the next start comes before the motor has cooled, the temperature rises from start to start. For this reason a maker states a permitted number of starts per hour, often only a few for a motor of this size. A thermostat that uses on-off control with a narrow band can ask a compressor to start far more often. The answer is a wider band or a minimum time between starts, not a higher overload setting.
Application 1: Direct on line start on the transformer
Step 1: Starting current and starting kVA
Click to reveal the starting current and kVA
-
Starting current.
The motor takes 260 A at the first instant. ✅
-
Starting kVA.
The motor asks for 186.9 kVA at standstill. Its running apparent power is
. With a typical starting power factor of 0.2 to 0.3, only 37 to 56 kW of the 186.9 kVA is real power. ✅
Step 2: Short-circuit capacity and dip
Click to reveal the dip on the transformer
-
Short-circuit capacity of the transformer.
This ignores the network behind the transformer, so the real value is a little lower. ✅
-
Dip.
The busbar voltage falls from 415 V to about
while the motor is near standstill. ✅ -
Compare with the limit. A dip of 4.0 percent is well inside a limit of 10 to 15 percent. Direct on line starting is acceptable on this transformer by this estimate. ✅
Step 3: Check by impedances
Click to reveal the check
-
Motor impedance at standstill, per phase.
✅
-
Source impedance, per phase.
✅
-
Voltage divider.
The same 4.0 percent. ✅
Application 2: The same start on the standby generator
Step 1: Direct on line on the generator
Click to reveal the dip on the generator
-
Short-circuit capacity of the generator. Use the subtransient reactance, which describes the first cycles.
The generator is more than five times weaker than the transformer as a source. ✅
-
Dip.
The voltage falls to about
. ✅ -
Compare with the limit. 18.3 percent is above the commonly used limit of 10 to 15 percent and close to the range where contactors may drop out. The motor takes
, about 1.5 times the 139 A rated current of the generator, and its torque falls to of the full-voltage starting value. ✅
Step 2: Star-delta
Click to reveal the star-delta result
-
Current and kVA in star. One third of the direct on line values.
✅
-
Dip. The motor in star is still a fixed impedance, three times larger, so the same formula applies.
The dip is inside the limit. ✅
-
Torque. One third of the full-voltage starting torque, reduced again by the square of the remaining voltage:
The compressor must accelerate on 29 percent of the direct on line starting torque. ✅
Step 3: Soft starter limited to 3 times full-load current
Click to reveal the soft starter result
-
Current and kVA.
✅
-
Dip. The soft starter holds the current at 120 A whatever the voltage does. The motor is then a fixed current and not a fixed impedance, and the dip is the drop of that current in the source impedance:
The dip is at the lower edge of the commonly used limit. ✅
-
Torque. The torque follows the square of the current.
The motor has 21 percent of its direct on line starting torque. ✅
Step 4: Check and compare
Click to reveal the check and the comparison
-
Check the soft starter dip in volts. The source impedance of the generator is
per phase. The same 10.4 percent. ✅
-
The comparison.
Method Line current Dip Torque, fraction of Direct on line 212 A (260 A at full voltage) 18.3 percent 0.67 Star-delta, in star 86.7 A 7.0 percent 0.29 Soft starter, 3 times full load 120 A 10.4 percent 0.21 The script reproduces every figure in this table. ✅
Verify It in Python
The script calculates the starting kVA, the short-circuit capacity of each source and the dip for each starting method, and it plots the dip against the starting kVA for both sources.
"""Starting kVA of a motor and the voltage dip on a transformer and on a generator."""import mathimport numpy as npimport matplotlib.pyplot as plt
V_L = 415.0 # V, line to lineI_FL = 40.0 # A, full-load current of the motorK_LR = 6.5 # locked-rotor current as a multiple of full-load currentP_SHAFT = 22.0e3 # WN_FL = 1465.0 # rev/min at full loadROOT3 = math.sqrt(3.0)
def kva(amps): """Apparent power in kVA of a balanced current at the nominal voltage.""" return ROOT3 * V_L * amps / 1000.0
def dip_impedance(s_start, s_sc): """Dip for a load of fixed impedance (starting kVA quoted at full voltage).""" return s_start / (s_start + s_sc)
def dip_current(s_drawn, s_sc): """Dip for a load that holds its current whatever the voltage does.""" return s_drawn / s_sc
# ---------- The motor ----------I_LR = K_LR * I_FLS_FL = kva(I_FL)S_START = kva(I_LR)T_FL = P_SHAFT / (2.0 * math.pi * N_FL / 60.0)print("Motor")print(f" full load: {I_FL:.1f} A, {S_FL:.2f} kVA, shaft torque {T_FL:.1f} N m")print(f" locked rotor: {I_LR:.0f} A, starting kVA {S_START:.1f}")for pf in (0.2, 0.3): print(f" at starting power factor {pf}: {S_START * pf:.1f} kW, " f"{S_START * math.sqrt(1.0 - pf * pf):.1f} kvar")
# ---------- The two sources ----------S_TX, Z_TX = 200.0, 0.045S_GEN, X_GEN = 100.0, 0.12SSC_TX = S_TX / Z_TXSSC_GEN = S_GEN / X_GENprint("Sources")for name, s_rated, s_sc in (("transformer", S_TX, SSC_TX), ("generator", S_GEN, SSC_GEN)): i_rated = 1000.0 * s_rated / (ROOT3 * V_L) i_sc = 1000.0 * s_sc / (ROOT3 * V_L) z = V_L ** 2 / (1000.0 * s_sc) print(f" {name}: rated current {i_rated:.1f} A, S_sc {s_sc:.1f} kVA, " f"fault current {i_sc:.0f} A, source impedance {1000.0 * z:.1f} milliohm") print(f" starting current / rated current = {I_LR / i_rated:.2f}")
# ---------- Application 1: direct on line on the transformer ----------d_tx = dip_impedance(S_START, SSC_TX)print("Application 1: direct on line on the transformer")print(f" dip {100.0 * d_tx:.2f} %, terminal voltage {V_L * (1.0 - d_tx):.1f} V, " f"actual current {I_LR * (1.0 - d_tx):.1f} A")z_m = V_L / (ROOT3 * I_LR)z_s = V_L ** 2 / (1000.0 * SSC_TX)print(f" check by impedances: motor {1000.0 * z_m:.1f} milliohm, " f"source {1000.0 * z_s:.2f} milliohm, dip {100.0 * z_s / (z_s + z_m):.2f} %")
# ---------- Application 2: the same start on the generator ----------print("Application 2: on the generator")d_gen = dip_impedance(S_START, SSC_GEN)print(f" direct on line: dip {100.0 * d_gen:.1f} %, terminal voltage " f"{V_L * (1.0 - d_gen):.0f} V, actual current {I_LR * (1.0 - d_gen):.0f} A, " f"torque {100.0 * (1.0 - d_gen) ** 2:.1f} % of the full-voltage starting torque")I_STAR = I_LR / 3.0S_STAR = kva(I_STAR)d_star = dip_impedance(S_STAR, SSC_GEN)print(f" star-delta, in star: {I_STAR:.1f} A, {S_STAR:.1f} kVA, dip {100.0 * d_star:.2f} %, " f"torque {100.0 / 3.0:.1f} % (before the dip), " f"{100.0 * (1.0 - d_star) ** 2 / 3.0:.1f} % (with the dip)")I_SOFT = 3.0 * I_FLS_SOFT = kva(I_SOFT)d_soft = dip_current(S_SOFT, SSC_GEN)print(f" soft starter at 3 x full load: {I_SOFT:.0f} A, {S_SOFT:.1f} kVA, " f"dip {100.0 * d_soft:.2f} %, torque {100.0 * (I_SOFT / I_LR) ** 2:.1f} %")z_g = V_L ** 2 / (1000.0 * SSC_GEN)print(f" check: root 3 x {I_SOFT:.0f} A x {1000.0 * z_g:.1f} milliohm = " f"{ROOT3 * I_SOFT * z_g:.1f} V = {100.0 * ROOT3 * I_SOFT * z_g / V_L:.2f} %")d_lim = 0.15s_max = d_lim * SSC_GEN / (1.0 - d_lim)print(f" largest fixed-impedance start for a {100.0 * d_lim:.0f} % dip: {s_max:.0f} kVA, " f"{1000.0 * s_max / (ROOT3 * V_L):.0f} A")
# ---------- Plot: dip against starting kVA for the two sources ----------s = np.linspace(0.0, 250.0, 200)fig, ax = plt.subplots(figsize=(8, 5))ax.plot(s, 100.0 * s / (s + SSC_TX), label="transformer, 200 kVA, 4.5 %")ax.plot(s, 100.0 * s / (s + SSC_GEN), label="generator, 100 kVA, 12 %")ax.axhspan(10.0, 15.0, alpha=0.2, label="commonly used limit, 10 to 15 %")for s_pt, name in ((S_START, "direct on line"), (S_STAR, "star")): ax.axvline(s_pt, color="gray", linestyle=":", linewidth=1.0) ax.text(s_pt + 2.0, 21.0, name, rotation=90, va="top")ax.set_xlabel("starting kVA of the motor at full voltage")ax.set_ylabel("voltage dip (%)")ax.set_title("Voltage dip when a motor starts on a stiff and on a weak source")ax.set_ylim(0.0, 25.0)ax.legend(loc="upper left")fig.tight_layout()fig.savefig("motor_starting_dip.png", dpi=120)print("Saved motor_starting_dip.png")Expected output
Motor full load: 40.0 A, 28.75 kVA, shaft torque 143.4 N m locked rotor: 260 A, starting kVA 186.9 at starting power factor 0.2: 37.4 kW, 183.1 kvar at starting power factor 0.3: 56.1 kW, 178.3 kvarSources transformer: rated current 278.2 A, S_sc 4444.4 kVA, fault current 6183 A, source impedance 38.8 milliohm starting current / rated current = 0.93 generator: rated current 139.1 A, S_sc 833.3 kVA, fault current 1159 A, source impedance 206.7 milliohm starting current / rated current = 1.87Application 1: direct on line on the transformer dip 4.04 %, terminal voltage 398.3 V, actual current 249.5 A check by impedances: motor 921.5 milliohm, source 38.75 milliohm, dip 4.04 %Application 2: on the generator direct on line: dip 18.3 %, terminal voltage 339 V, actual current 212 A, torque 66.7 % of the full-voltage starting torque star-delta, in star: 86.7 A, 62.3 kVA, dip 6.96 %, torque 33.3 % (before the dip), 28.9 % (with the dip) soft starter at 3 x full load: 120 A, 86.3 kVA, dip 10.35 %, torque 21.3 % check: root 3 x 120 A x 206.7 milliohm = 43.0 V = 10.35 % largest fixed-impedance start for a 15 % dip: 147 kVA, 205 ASaved motor_starting_dip.pngThe last line of Application 2 shows that a fixed-impedance start on this generator must stay below 147 kVA (205 A) for a dip of 15 percent. The direct on line start needs 260 A.
Common Mistakes
- Sizing a generator from the running load of its motors. The compressor runs at 28.8 kVA and its start asks for 186.9 kVA.
- Expecting 6.5 times the torque because the current is 6.5 times. The starting torque is typically 1.5 to 2.5 times full load.
- Forgetting the torque when the current is reduced. Star-delta gives one third of the torque, and a soft starter at 3 times full-load current gives about one fifth for this motor.
- Raising an overload relay setting, or choosing a slower trip class, to stop trips during starting. The trips show that the start is too long or too frequent, and the cause is still present.
- Expecting the overload relay to protect against a short circuit, or the fuses to protect against an overload. Each device covers a different range of current and of time.
Summary
- At standstill an induction motor takes its locked-rotor current, typically 6 to 8 times full-load current, at a low power factor. The compressor motor takes 260 A, which is 186.9 kVA.
- The dip is estimated as the starting kVA divided by the sum of the starting kVA and the short-circuit capacity of the source: about 4.0 percent on the 200 kVA transformer and 18.3 percent on the 100 kVA generator.
- Current is proportional to voltage and torque to the square of voltage. On the generator, star-delta gives a dip of about 7.0 percent with one third of the torque, and a soft starter at 3 times full-load current gives about 10.4 percent with 21 percent of the torque.
- The overload relay models the heating of the windings, and its trip class is the longest trip time in seconds from cold at 7.2 times the setting. Fuses or a breaker clear short circuits.
- Every start heats the stator and the rotor, so the number of starts per hour is limited.
- The choice and the setting of protective devices belong to a qualified person.
Exercises
1. A motor has a full-load current of 21.0 A on a 415 V supply, and its locked-rotor current is 7.0 times full-load current. It starts direct on line from a 500 kVA transformer with an impedance of 5.0 percent. Ignore the network behind the transformer. Find the starting current, the starting kVA and the estimated voltage dip.
Answer
2. The same motor starts from a 60 kVA generator with a subtransient reactance of 15 percent. Estimate the dip for a direct on line start and for the star stage of a star-delta start.
Answer
3. The cold store compressor motor (40.0 A at full load, 260 A locked rotor) starts on the 100 kVA generator with a subtransient reactance of 12 percent, through a soft starter with a current limit. Find the current limit that gives a dip of 10 percent, as a multiple of full-load current, and the torque available as a fraction of the direct on line starting torque.
Answer
With a current limit the dip is
4. A 4-pole, 50 Hz motor and its load have a total inertia of 0.60 kg m². The motor starts with no load torque. Find the heat released in the rotor during one start. State what a star-delta start does to this figure.
Answer
The synchronous speed is 1500 rev/min, so
References
- S. J. Chapman, Electric Machinery Fundamentals, 5th edition, McGraw-Hill, 2012.
- A. Hughes and B. Drury, Electric Motors and Drives: Fundamentals, Types and Applications, 5th edition, Newnes, 2019.
- J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and Design, 6th edition, Cengage Learning, 2017.
- IEC 60947-4-1, Low-voltage switchgear and controlgear, Part 4-1: Contactors and motor-starters, Electromechanical contactors and motor-starters, International Electrotechnical Commission.
The compressor motor takes 40 A when it runs at full load. It is switched straight onto 415 V from standstill. About what current does it take in the first instant?
The compressor motor: 40 A at full load, 260 A locked rotor, so 186.9 kVA at standstill on 415 V. Direct on line and star-delta treat the motor as a fixed impedance; the soft starter holds the current at its limit. Torque is shown as a share of the direct on line starting torque at full voltage.
Check yourself
Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.
1. The same motor (186.9 kVA at standstill) starts direct on line from a 315 kVA transformer with 5 percent impedance. About what voltage dip results?
2. A loaded conveyor needs 40 percent of the motor's direct on line starting torque to begin to move. It is on a strong supply, so the dip is small. Can a star-delta starter start it?
3. On the standby generator, the soft starter is set to limit the current to 2.5 times full-load current. What share of the direct on line starting torque is left?
- Running at 1465 rev/min the slip is 2.3% and the motor takes 40 A. At standstill the slip is 1.
- The rotor acts as a short-circuited secondary: 6.5 × 40 A = 260 A at the first instant.
- That current at 415 V is a demand of √3 × 415 × 260 = 186.9 kVA, against 28.8 kVA running.
- The current stays near 260 A for most of the run and falls only near full speed. Most of it is reactive.
Discussion
No comments yet. Questions, results from your own build, a better way to explain it: all welcome.
My notes on this page
Kept on this device only. Nothing is sent anywhere.
Tip: select words in the lesson, or tap a figure or an equation, to put a note right there.
Notes on earlier wording
The lesson has changed and these words are no longer in it. Your notes are kept, with the words you chose.