Lesson 8 of 10 26 min read
Found this useful?

A farm buys a variable speed drive for its borehole pump because the proposal promised to cut the energy almost in half. A year later the electricity bill has fallen by less than half of what was promised, and nobody can say why. In another case an operator lowers the speed to save more, and the pump runs for hours and delivers no water at all. The drive worked correctly both times. The promise came from a law that is true for one kind of pipe system and was applied to a different kind. This lesson shows what a drive does, where the affinity laws hold, and how to calculate the saving that a real system will give. #VariableSpeedDrive #AffinityLaws #PumpEnergy

Learning Objectives

By the end of this lesson, you will be able to:

  1. Explain how a variable speed drive produces a supply of variable frequency and voltage
  2. Apply the affinity laws to the flow, the head and the power of a pump
  3. Calculate the speed and the power of a pump on a system that has static head
  4. Compare throttling with speed control in kW, in kWh per year and in money
  5. Judge when a drive does not pay, and find the minimum useful speed of a pump

Real-World System Problem: A borehole pump that does not need full flow



A borehole pump is driven by a 7.5 kW, 2-pole motor on a 415 V, 50 Hz three-phase supply (415 V is the nominal line voltage in Kenya and much of East Africa, and the IEC nominal figure is 400 V). At 50 Hz the pump delivers 18 m³/h and takes 6.8 kW at its shaft. For much of the year the site needs only about 80 percent of that flow.

A pump that runs continuously can give less flow in two ways. Close a valve partly: the pump still turns at full speed, and the valve destroys the pressure that is not needed, like driving with the brake on. Or turn the pump more slowly with a variable speed drive, so that it produces only the pressure that is needed.

The pump does two jobs: it lifts the water from the level in the borehole to the tank, a height that does not change with the flow, and it pushes the water through the pipe against friction, which grows with the square of the flow. A slower pump saves much of the friction part and none of the lifting part. On this borehole the lift is 60 percent of the total head at full flow.

tankmotor and pump18 m3/h, 6.8 kW415 Vdrivegroundcablepipefrictionstaticheadheadwater level
The borehole pump and its two kinds of head

Fundamental Theory: Variable frequency, pump curves and the affinity laws



How a drive makes a variable frequency

The speed of an induction motor follows the frequency of its supply. The synchronous speed is

with in rev/min, the frequency in Hz and the number of poles. A 2-pole motor has at 50 Hz and at 40 Hz. The motor runs a little below , by its slip. To change the speed, change the frequency.

A variable speed drive does this in three stages.

AC to DC6 diodescapacitor560 V DCDC to AC6 fastswitchessupplyrectifierDC linkinverter415 V50 Hzmotorfixed frequency0to50Hz,0to415V
The three stages of a variable speed drive
  • The rectifier turns the three-phase supply into DC. A six-diode rectifier gives a mean voltage of about .
  • The DC link is a capacitor bank that smooths this voltage and stores energy for the next stage.
  • The inverter has six fast electronic switches. It connects each motor terminal to the positive or the negative side of the DC link thousands of times each second. By changing the width of these pulses (pulse-width modulation) it produces a voltage whose average follows a sine wave of any chosen frequency and size.

Volts per hertz

The magnetic flux in a motor is proportional to the voltage divided by the frequency. If the frequency falls and the voltage stays at 415 V, the flux rises, the iron saturates, and the magnetising current becomes very large. So the drive lowers the voltage with the frequency and keeps their ratio constant:

At 45 Hz the motor receives about . With constant flux the motor can give its rated torque at any speed below its rated speed. Above 50 Hz the drive has no more voltage to give, the flux falls, and the available torque falls with it.

volts415●no more voltage374●45 Hzconstant volts per hertz,constant flux0frequency4550 Hz
Voltage against frequency in a drive

The pump curve and the system curve

Two curves decide what a pump delivers. Both are drawn as head (the pressure, expressed as a height of water) against flow .

The pump curve shows the head that the pump can produce at each flow, at one speed. It is highest at zero flow, where it is called the shut-off head, and it falls as the flow rises.

The system curve shows the head that the pipework needs at each flow. It has two parts:

is the static head: the height through which the water must be lifted, plus any pressure held at the outlet. It does not depend on the flow. The term is the friction head, and is a constant of the pipework.

The pump runs at the point where the two curves cross, because only there does it produce exactly the head that the system needs.

The affinity laws

Take one pump and change its speed from to . Write the speed ratio as . Every water velocity inside the pump changes in proportion to the speed, and from this three relations follow.

The affinity laws for one pump at two speeds

is the flow, the head and the shaft power. The laws connect one point on the pump curve at the first speed to the matching point on the curve at the second speed. The pump efficiency is taken as equal at the two matching points.

The third law is the one quoted in proposals for drives. At 80 percent speed, : about half the power for four fifths of the flow.

If and , then the matching points lie on a curve , a parabola through the origin. The laws describe the pump. They say nothing about where the system lets the pump run.

The effect of static head

In this lesson, heads and flows are written as fractions of their values at full speed and full flow:

So and at full flow. The system curve, with a static part , becomes

For the pump curve, this lesson assumes a simple shape: a shut-off head at full speed of 1.25 times the full-flow head, falling with the square of the flow. Scaled to another speed by the affinity laws, it is

This is an assumed curve. A real pump curve comes from the maker’s data and must be used for real work.

Set the two heads equal and solve for the speed ratio that gives a wanted flow :

With no static head () this gives , which is the affinity law. With static head, is greater than , because the pump must still produce the lift.

The shaft power is proportional to flow multiplied by head, divided by the pump efficiency . With the simplification that stays the same, the power as a fraction of the full-flow power is

On a real pump the efficiency falls when the operating point moves away from the best point, so treat results from this simplification as a first estimate.

Throttling against speed control

A throttling valve adds friction. The operating point moves back along the full-speed pump curve to a lower flow and a higher head, and the valve turns the extra head into heat and noise. The shaft power falls only a little, because the flow falls while the head rises.

Speed control lowers the pump curve until it crosses the unchanged system curve at the wanted flow.

1.25shut-off head of the pump at full speed1.09● pump at full speedlostinthevalve: 0.2340.856● system with 60 percentstatic head0.64● system with friction only0.60static head0
Heads at 80 percent flow, as fractions of the full-flow head

Minimum speed

A pump delivers water only if it can produce more than the static head. Its shut-off head falls with the square of the speed, for the assumed curve. At the speed where the shut-off head equals the static head, the flow is zero:

Below this speed the pump turns, takes power and lifts nothing. The water inside it becomes hot, and a pump that depends on the flow for cooling can be damaged. Just above this speed, a change of one or two hertz changes the flow greatly. Makers of pumps and of submersible motors also state a minimum frequency for cooling and for bearing life, and that figure must be respected.

Drive losses and harmonics

A drive has losses of its own, typically about 3 percent of the power that passes through it, so its efficiency is about 97 percent. At full speed, a motor on a drive therefore takes more from the supply than the same motor connected directly.

The rectifier draws its current in short pulses and not as a sine wave. With no line choke, a total harmonic distortion of the input current of about 40 percent is typical, and about 30 percent with a 3 percent line choke. With 40 percent distortion the RMS input current is times its fundamental part.

The output side has a problem of its own, which matters most in a borehole. Each fast switching edge of the inverter travels down the motor cable and is reflected at the motor, and on a long cable the voltage at the motor terminals can reach about twice the DC link voltage, near 1,100 V on a 415 V supply. Over months this breaks down the insulation of a motor that was not made for it. Submersible motor makers therefore state the longest cable allowed with a drive and usually require an output filter (a dV/dt or sine-wave filter) between the drive and the cable.

When a drive does not pay

A drive does not pay, or pays slowly, in these cases.

  • The pump runs at or near full flow all the time. There is nothing to save, and the drive adds its 3 percent loss.
  • The static head is a large part of the total head. The speed can be reduced only a little, and the saving is small.
  • The running hours are few. A saving in kW becomes money only through hours.
  • The pump fills a tank and can simply stop. A pump at full speed that runs fewer hours may use almost as little energy for each cubic metre as a slowed pump.

A drive can still be justified by a gentle start on a weak supply, less pressure shock in the pipes, or steady pressure control. Those are real benefits, but they are not energy savings.

Application 1: The borehole pump at 80 percent flow



Step 1: Throttling at full speed

Click to reveal the throttled case
  1. Head of the pump at 80 percent flow, full speed.

    The pump produces 9 percent more head than at full flow. ✅

  2. Head that the system needs at 80 percent flow.

    The valve must destroy of the full-flow head. ✅

  3. Shaft power. Flow multiplied by head, at constant pump efficiency.

    The flow fell by 20 percent, and the shaft power fell by only 12.8 percent. ✅

Step 2: Speed control with the pure affinity law

Click to reveal the friction-only case
  1. Speed. With no static head, the flow follows the speed, so , which is 40 Hz. ✅

  2. Head. , which is also what a friction-only system needs: . ✅

  3. Shaft power.

    This is the figure that a proposal based on the cube law will quote. ✅

Step 3: Speed control with 60 percent static head

Click to reveal the real system
  1. Head needed. From Step 1, the system needs at . This does not depend on how the flow is reduced. ✅

  2. Speed. Set the pump head equal to the system head.

    The drive runs at , not at 40 Hz. A reduction of 20 percent in flow needs a reduction of only 10 percent in speed. ✅

  3. Shaft power.

    The power is 0.685 of the full-flow power, not 0.512. ✅

Step 4: Electrical input and annual energy

Click to reveal the energy
  1. Throttled, no drive. Only the motor efficiency applies.

    ✅

  2. Speed control, friction only. The motor and the drive are in series.

    ✅

  3. Speed control, real system.

    ✅

  4. Annual energy for 3,000 hours. Multiply each input power (carried to four decimal places: 6.7382, 4.0787 and 5.4553 kW) by 3,000 h.

    CaseInput powerAnnual energy
    (a) Throttled at full speed6.738 kW20,215 kWh
    (b) Speed control, friction only4.079 kW12,236 kWh
    (c) Speed control, 60 percent static head5.455 kW16,366 kWh

    ✅

  5. Saving against throttling.

    The cube law promises 2.07 times the saving that this system can give. ✅

Step 5: Check a second way

Click to reveal the check
  1. Find the matching point at full speed. The affinity laws connect the real operating point (, , ) to a point on the full-speed curve:

    ✅

  2. Is that point on the full-speed pump curve?

    It is. The speed found in Step 3 is correct. ✅

  3. Power by the cube law from the matching point.

    The same 0.6848 as in Step 3. The cube law is not wrong. It must be applied from the correct point with the correct speed ratio, 0.9016 and not 0.80. ✅

Application 2: Simple payback of the drive



Step 1: Payback against throttling

Click to reveal the payback
  1. Annual saving on the real system.

    ✅

  2. Simple payback. The cost divided by the annual saving.

    ✅

  3. What the cube law would have promised.

    The promised payback is less than half of the real one. ✅

Step 2: Against a pump that simply runs fewer hours

Click to reveal the on-off comparison
  1. Volume delivered in the year.

    ✅

  2. Hours and energy at full speed. At 18 m³/h the same volume needs .

    This is possible only if the water goes to a tank, so that the pump can stop when the tank is full. ✅

  3. Saving and payback against this alternative.

    ✅

Step 3: Full flow all the time, and a check

Click to reveal the full-flow case and the check
  1. Drive loss at full flow. With the drive the input is .

    At full flow the drive costs about 8,600 currency units a year in energy and saves nothing. ✅

  2. Check by energy for each cubic metre. Divide each input power by its flow.

    For 43,200 m³ the difference between throttling and speed control is , which agrees with 3,849 kWh within the rounding of the two figures. ✅

Verify It in Python



The script solves the three cases at 80 percent flow from the assumed pump curve and the system curve, calculates the annual energy and the three paybacks, finds the minimum speed, and plots the curves with the three operating points.

pump_speed_control.py
"""Pump at 80 percent flow: throttling against speed control, with and without static head."""
import math
import numpy as np
import matplotlib.pyplot as plt
# Heads are fractions of the head at full flow, flows are fractions of full flow.
P_FULL = 6.8 # kW at the shaft, full speed and full flow
Q_FULL = 18.0 # m3/h
ETA_MOTOR = 0.88
ETA_DRIVE = 0.97
HOURS = 3000.0
PRICE = 12.00 # currency units per kWh
DRIVE_COST = 120000.0 # currency units, an example figure
H0 = 1.25 # shut-off head at full speed
A = H0 - 1.0 # so that the pump gives head 1 at flow 1
F_SUPPLY = 50.0
def pump_head(q, r):
"""Head of the pump at flow q and speed ratio r (assumed curve)."""
return H0 * r ** 2 - A * q ** 2
def system_head(q, static):
"""Head the pipework needs at flow q, with a static part."""
return static + (1.0 - static) * q ** 2
def speed_for(q, static):
"""Speed ratio at which the pump curve meets the system curve at flow q."""
return math.sqrt((system_head(q, static) + A * q ** 2) / H0)
def shaft_kw(q, h):
"""Shaft power, proportional to flow times head at constant pump efficiency."""
return P_FULL * q * h
Q = 0.80
print("Full flow, no drive")
e_full = P_FULL / ETA_MOTOR
print(f" shaft {P_FULL:.2f} kW, input {e_full:.3f} kW, "
f"{e_full / Q_FULL:.3f} kWh per m3")
rows = []
# (a) throttling at full speed
h_a = pump_head(Q, 1.0)
p_a = shaft_kw(Q, h_a)
e_a = p_a / ETA_MOTOR
print("(a) Throttling at full speed")
print(f" pump head {h_a:.3f}, system needs {system_head(Q, 0.6):.3f}, "
f"valve wastes {h_a - system_head(Q, 0.6):.3f}")
print(f" shaft {p_a:.3f} kW ({p_a / P_FULL:.3f} of full), input {e_a:.3f} kW")
rows.append(("throttled", e_a))
# (b) speed control, no static head (pure affinity law)
r_b = speed_for(Q, 0.0)
h_b = system_head(Q, 0.0)
p_b = shaft_kw(Q, h_b)
e_b = p_b / (ETA_MOTOR * ETA_DRIVE)
print("(b) Speed control, friction only")
print(f" speed ratio {r_b:.4f}, head {h_b:.3f}, shaft {p_b:.3f} kW "
f"({p_b / P_FULL:.3f} of full, cube law {Q ** 3:.3f}), input {e_b:.3f} kW")
rows.append(("speed, friction only", e_b))
# (c) speed control with 60 percent static head
r_c = speed_for(Q, 0.6)
h_c = system_head(Q, 0.6)
p_c = shaft_kw(Q, h_c)
e_c = p_c / (ETA_MOTOR * ETA_DRIVE)
print("(c) Speed control, 60 percent static head")
print(f" speed ratio {r_c:.4f} ({F_SUPPLY * r_c:.1f} Hz), head {h_c:.3f}, "
f"shaft {p_c:.3f} kW ({p_c / P_FULL:.3f} of full), input {e_c:.3f} kW")
q_eq = Q / r_c
print(f" check by the affinity parabola: full-speed point flow {q_eq:.4f}, "
f"head {pump_head(q_eq, 1.0):.4f}, power {q_eq * pump_head(q_eq, 1.0):.4f} "
f"x r^3 {r_c ** 3:.4f} = {q_eq * pump_head(q_eq, 1.0) * r_c ** 3:.4f}")
rows.append(("speed, 60 % static", e_c))
print(f"Annual energy over {HOURS:.0f} h (whole kWh)")
kwh = {}
for name, e in rows:
kwh[name] = round(e * HOURS)
print(f" {name}: {e:.4f} kW, {kwh[name]:,} kWh, {e / (Q * Q_FULL):.3f} kWh per m3")
save_c = kwh["throttled"] - kwh["speed, 60 % static"]
save_b = kwh["throttled"] - kwh["speed, friction only"]
print(f" saving against throttling: real system {save_c:,} kWh, "
f"cube law alone {save_b:,} kWh (ratio {save_b / save_c:.2f})")
print("Payback")
print(f" real system: {save_c * PRICE:,.0f} per year, "
f"payback {DRIVE_COST / (save_c * PRICE):.2f} years")
print(f" cube law alone: {save_b * PRICE:,.0f} per year, "
f"payback {DRIVE_COST / (save_b * PRICE):.2f} years")
vol = Q * Q_FULL * HOURS
h_onoff = vol / Q_FULL
e_onoff = round(h_onoff * e_full)
save_onoff = e_onoff - kwh["speed, 60 % static"]
print(f" against full speed, on and off: {vol:,.0f} m3 in {h_onoff:.0f} h, "
f"{e_onoff:,} kWh, saving {save_onoff:,} kWh, "
f"{save_onoff * PRICE:,.0f} per year, payback "
f"{DRIVE_COST / (save_onoff * PRICE):.2f} years")
loss_full = e_full / ETA_DRIVE - e_full
print(f" drive loss at full flow: {loss_full:.3f} kW, "
f"{loss_full * HOURS:,.0f} kWh per {HOURS:.0f} h")
r_min = math.sqrt(0.6 / H0)
print("Minimum speed")
print(f" shut-off head equals the static head at speed ratio {r_min:.4f}, "
f"{F_SUPPLY * r_min:.1f} Hz")
print(" flow against frequency on the real system:")
for hz in (35.0, 40.0, 45.0, 50.0):
r = hz / F_SUPPLY
q_hz = math.sqrt(max(H0 * r ** 2 - 0.6, 0.0) / (1.0 - 0.6 + A))
print(f" {hz:.0f} Hz: flow {q_hz:.3f}, flow by the affinity law {r:.3f}")
# ---------- Plot ----------
q = np.linspace(0.0, 1.15, 200)
fig, ax = plt.subplots(figsize=(8, 5.5))
ax.plot(q, pump_head(q, 1.0), label="pump, full speed")
ax.plot(q, pump_head(q, r_c), label=f"pump, speed ratio {r_c:.3f}")
ax.plot(q, pump_head(q, r_b), "--", label=f"pump, speed ratio {r_b:.3f}")
ax.plot(q, system_head(q, 0.6), label="system, 60 % static head")
ax.plot(q, system_head(q, 0.0), "--", label="system, friction only")
ax.plot([Q, Q, Q], [h_a, h_c, h_b], "ko")
ax.annotate("throttled", (Q, h_a), textcoords="offset points", xytext=(8, 4))
ax.annotate("speed, real system", (Q, h_c), textcoords="offset points", xytext=(8, -12))
ax.annotate("speed, friction only", (Q, h_b), textcoords="offset points", xytext=(8, -12))
ax.set_xlabel("flow (fraction of full flow)")
ax.set_ylabel("head (fraction of head at full flow)")
ax.set_ylim(0.0, 1.4)
ax.set_title("Pump and system curves at 80 percent flow")
ax.legend(loc="lower left")
fig.tight_layout()
fig.savefig("pump_speed_control.png", dpi=120)
print("Saved pump_speed_control.png")

Expected output

Full flow, no drive
shaft 6.80 kW, input 7.727 kW, 0.429 kWh per m3
(a) Throttling at full speed
pump head 1.090, system needs 0.856, valve wastes 0.234
shaft 5.930 kW (0.872 of full), input 6.738 kW
(b) Speed control, friction only
speed ratio 0.8000, head 0.640, shaft 3.482 kW (0.512 of full, cube law 0.512), input 4.079 kW
(c) Speed control, 60 percent static head
speed ratio 0.9016 (45.1 Hz), head 0.856, shaft 4.657 kW (0.685 of full), input 5.455 kW
check by the affinity parabola: full-speed point flow 0.8874, head 1.0531, power 0.9345 x r^3 0.7328 = 0.6848
Annual energy over 3000 h (whole kWh)
throttled: 6.7382 kW, 20,215 kWh, 0.468 kWh per m3
speed, friction only: 4.0787 kW, 12,236 kWh, 0.283 kWh per m3
speed, 60 % static: 5.4553 kW, 16,366 kWh, 0.379 kWh per m3
saving against throttling: real system 3,849 kWh, cube law alone 7,979 kWh (ratio 2.07)
Payback
real system: 46,188 per year, payback 2.60 years
cube law alone: 95,748 per year, payback 1.25 years
against full speed, on and off: 43,200 m3 in 2400 h, 18,545 kWh, saving 2,179 kWh, 26,148 per year, payback 4.59 years
drive loss at full flow: 0.239 kW, 717 kWh per 3000 h
Minimum speed
shut-off head equals the static head at speed ratio 0.6928, 34.6 Hz
flow against frequency on the real system:
35 Hz: flow 0.139, flow by the affinity law 0.700
40 Hz: flow 0.555, flow by the affinity law 0.800
45 Hz: flow 0.797, flow by the affinity law 0.900
50 Hz: flow 1.000, flow by the affinity law 1.000
Saved pump_speed_control.png

The last lines show the minimum speed. The shut-off head of the pump equals the static head at a speed ratio of 0.693, which is 34.6 Hz, and below that frequency this pump lifts no water. At 40 Hz the flow is 0.555 of full flow, where the affinity law alone would predict 0.800. Between 35 Hz and 45 Hz the flow changes from almost nothing to 80 percent, so the useful speed range of this pump is narrow.

Common Mistakes



  • Applying the cube law to a system with static head. The power follows the cube of the speed, and on such a system the speed falls much less than the flow.
  • Reading the speed ratio as the flow ratio. On this borehole, 90 percent speed gives 80 percent flow, and 80 percent speed gives about 56 percent flow.
  • Lowering the frequency below the speed at which the shut-off head equals the static head. The pump then turns and delivers nothing.
  • Comparing the drive with throttling when the pump could simply run fewer hours. The saving must be measured against what the pump really does today.
  • Counting a gentle start or a steadier pressure as an energy saving. These are benefits of a drive, and they do not reduce the kWh.

Summary



  • A drive rectifies the supply to DC and uses an inverter to produce a new three-phase voltage of variable frequency, with a constant ratio of volts to hertz so that the flux stays constant.
  • For one pump the flow changes with the speed, the head with the square of the speed and the shaft power with the cube. These affinity laws give the real operating point only on a system with friction and no static head.
  • With static head, solve for the speed at which the pump curve meets the system curve. The borehole pump needs 90.2 percent speed (45.1 Hz) for 80 percent flow, and 0.685 of its full-flow shaft power, not 0.512.
  • At 80 percent flow for 3,000 hours, throttling uses 20,215 kWh and speed control uses 16,366 kWh. The saving is 3,849 kWh, less than half of the 7,979 kWh that the cube law alone suggests.
  • With a drive cost of 120,000 currency units and energy at 12.00 per kWh, the simple payback is 2.60 years against throttling and 4.59 years against a pump that runs fewer hours at full speed.
  • Below 34.6 Hz this pump lifts no water. A drive does not pay where the pump runs near full flow all the time or where the static head dominates.

Exercises



1. A fan on a duct system (friction only) takes 15.0 kW at its shaft at full speed. Find the flow, the pressure and the shaft power at 70 percent speed, as fractions of full speed, and the shaft power in kW.

Answer

Flow 0.70, pressure , power . The shaft power is .

2. A pump with the assumed curve works on a system whose static head is 80 percent of the total head at full flow. Find the minimum speed ratio and the frequency below which it delivers no water.

Answer

, which is 40 Hz. This pump has a useful speed range of only 40 Hz to 50 Hz.

3. The borehole pump of this lesson (6.8 kW at the shaft at full flow, motor efficiency 0.88, drive efficiency 0.97, the same assumed pump curve) is moved to a system whose static head is only 30 percent of the total head at full flow. Find the speed ratio, the shaft power and the electrical input power at 80 percent flow with speed control.

Answer

. , which is 42.6 Hz. Shaft power: . Input: . With less static head the result moves towards the cube-law value of 4.079 kW.

4. The borehole pump of this lesson, on its real system with 60 percent static head, must deliver 60 percent flow for 3,000 hours each year. Find the speed ratio, and the electrical input power with speed control and with throttling. Find the annual saving in kWh.

Answer

. , which is 40.8 Hz. Speed control: shaft , input . Throttling: , shaft , input . Saving: (5,467 kWh with unrounded values).

5. For the case of exercise 4, energy costs 12.00 currency units per kWh and the drive costs 150,000 currency units. Find the simple payback against throttling. State one condition under which this figure would be too optimistic.

Answer

Annual saving: currency units. Payback: . It is too optimistic if the pump does not really run throttled for 3,000 hours today, for example if it fills a tank and could simply stop, or if the real pump efficiency falls at the reduced speed.

References



  • A. Hughes and B. Drury, Electric Motors and Drives: Fundamentals, Types and Applications, 5th edition, Newnes, 2019.
  • S. J. Chapman, Electric Machinery Fundamentals, 5th edition, McGraw-Hill, 2012.
  • I. J. Karassik, J. P. Messina, P. Cooper and C. C. Heald, Pump Handbook, 4th edition, McGraw-Hill, 2008.
  • F. M. White, Fluid Mechanics, 8th edition, McGraw-Hill, 2016.


© 2021-2026 SiliconWit®. All rights reserved.
Predict first

A borehole pump must deliver 80 percent of its full flow. A proposal for a drive says: "power follows the cube of the speed, and 0.8³ = 0.51, so the pump will need about half the power". Of the head at full flow, 60 percent is the height of the lift. What share of the full-flow shaft power does the slowed pump really need?

See it: two ways to reduce the flow

Speed needed
Head needed, and lost in the valve
Pump lifts no water below
Input, throttled
Input, speed control
Saving in 3,000 hours

Heads are fractions of the head at full flow and flows are fractions of the full flow of 18 m³/h, as in the lesson. The pump curve is the lesson's assumed shape, 1.25 r² − 0.25 q², not a maker's curve. The dashed curve is the system, and the dotted line is its static head. A valve moves the operating point up the full-speed curve to the upper dot, and the head between the two dots is destroyed in the valve. A drive lowers the pump curve until it meets the system curve at the lower dot. The bars show the electrical input: the motor (88 percent) for the throttled pump, the motor and the drive (97 percent) for the other two. The dashed bar is the cube law applied to the flow ratio, which is correct only when the static head is zero. Energy is for the lesson's 3,000 hours a year. The pump and motor efficiencies are taken as constant, so read the results as a first estimate.

ground water level motor and pump motor and pump 18 m³/h, 6.8 kW 415 V drive cable tank pipe: friction head static head
A borehole pump that does not need full flow (not to scale)
supply 415 V, 50 Hz rectifier AC to DC 6 diodes + − DC link 560 V DC capacitor inverter DC to AC 6 fast switches M 3~ fixed frequency 0 to 50 Hz, 0 to 415 V
How a drive makes a variable frequency
374 415 0 volts frequency 0 45 Hz 50 Hz no more voltage constant volts per hertz, constant flux: 8.3 V per Hz
Volts per hertz
0 0.60 0.856 1.09 1.25 shut-off head of the pump at full speed pump at full speed lost in the valve: 0.234 system with 60 percent static head: 0.856 static head throttled 0.64 system with friction only
Heads at 80 percent flow, as fractions of the full-flow head

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. The borehole pump of the lesson (static head 60 percent of the full-flow head) is slowed from 50 Hz to 40 Hz. What flow does it deliver?

2. On another borehole the static head is 80 percent of the head at full flow. The pump has the same assumed curve, with a shut-off head of 1.25 at full speed. Below which frequency does it deliver no water?

3. A pump must run at full flow for all of its 3,000 hours a year. A drive is fitted and set to 50 Hz. What happens to the energy taken from the supply?

full flowvalve, 80 %drive, 80 % 6.8 kW5.93 kW4.66 kW A valve is driving with the brake on
Watch it build: slow the pump to 80 percent
flowheadpower 18 m³/hfull head6.8 kW 50 Hz, full speed × 0.8 = 14.4 m³/h× 0.8² = 0.64 r = 0.8, 40 Hz power: ? × 0.8³ = 0.512, 3.48 kW lift: 4.66 kW 60% lift: needs r = 0.90
  1. At 50 Hz the borehole pump gives 18 m³/h and takes 6.8 kW at its shaft.
  2. At 80% speed the flow falls with the speed, to 14.4 m³/h, and the head with its square, 0.64.
  3. The power falls with the cube: 0.8³ = 0.512, 3.48 kW. About half the power for four fifths of the flow.
  4. Only with no lift. With 60% static head the same flow needs 90% speed and 4.66 kW.