Skip to content
You Start with one site
Amounts in Start with one site
Electrical Power · Concept

Affinity laws

One idea Intermediate 5 min read
Found this useful?

Ride a bicycle twice as fast and the wind does not ask for twice the power. It asks for about eight times as much. Pumps and fans follow the same kind of rule. The affinity laws say that when the speed of a pump or fan changes, the flow follows the speed, the head follows its square, and the shaft power follows its cube.

80%?That is the flow. The air moves at 80% of its speed.First power
64%?That is the pressure the fan makes: 0.8 × 0.8.Second power
51%?Power is flow times pressure: 0.8 × 0.8 × 0.8.Third power

See it

Predict first

A pump takes 2.5 kW at its shaft at full speed. A drive slows it to 80% of that speed. About how much shaft power does it take now, as a share of full?

See it: one pump at a lower speed

Flow
Head
Shaft power

Each bar is a share of the value at full speed: 2,900 rev/min, 20 m³/h, 30 m and 2.5 kW. The bars show what the pump itself does at a lower speed. Whether real pipes let it work there is a separate question, answered below.

The idea

Inside a pump or fan, every speed of the water or air is tied to the speed of the wheel that throws it. Slow the wheel to 80% and every speed inside becomes 80%.

The flow is a speed times an area, so it follows the speed. The head comes from speed squared, so it follows the square. Shaft power is flow times head, so it follows the cube. Write r for the speed ratio: the new speed divided by the full speed.

Q2 = Q1 × r    H2 = H1 × r²    P2 = P1 × r³

Q is flow, H is head, P is shaft power. 1 is full speed, 2 is the new speed

The laws hold for the same machine and the same fluid, and they take the efficiency as unchanged. At much reduced speed a small pump is a little less efficient than they say.

One worked number

The question

At 2,900 rev/min a pump delivers 20 m³/h at 30 m of head and takes 2.5 kW at its shaft. A drive slows it to 2,320 rev/min. What are the flow, the head and the shaft power now?

Show the worked solution, 4 steps
  1. Find the speed ratio

    r = 2,320 ÷ 2,900 = 0.8.

  2. Flow follows r

    20 × 0.8 = 16 m³/h.

  3. Head follows r²

    0.8 × 0.8 = 0.64, so 30 × 0.64 = 19.2 m.

  4. Power follows r³

    0.8 × 0.8 × 0.8 = 0.512, so 2.5 × 0.512 = 1.28 kW. Check it in the figure: set the slider to 80%.

The mistake to avoid

"80% speed, half the power" is not true for every system. The laws describe the pump. They do not say where the pipes let it work. If the pipes lift water up a height, the slower pump must still reach that height. A booster pump that makes 42 m at zero flow, against 22 m of lift, makes less than 22 m below about 72% speed. It then turns, heats the water and delivers nothing.

The cube law is close for fans, and for water that only circulates in a closed loop, where nothing is lifted. Where most of the head is lift, find the new duty point first. The lesson on the affinity laws and speed control does this for two real pumps.

Check yourself

Question 1

A fan takes 4.0 kW at its shaft at full speed. It is slowed to 90% of full speed. What shaft power does it take?

Question 2

A fan pushes air round a closed duct loop, with nothing to lift. At about what speed does it take half of its full shaft power?

Question 3

A borehole pump makes 110 m of head at zero flow at full speed. It must lift water 60 m before any reaches the tank. Someone sets its drive to 70% speed "to cut the power by two thirds". What happens?

Where you meet it

  • Fans in buildings and cold roomsA fan slowed a little for a cool night takes much less power, which is the main reason drives are fitted to fans.
  • Circulation pumpsChilled water and heating loops lift nothing, so their pumps follow the cube law closely.
  • Borehole pumpsMost of the head is lift, so slowing the pump saves little energy for each cubic metre.
Key points
  • Flow follows the speed, head follows its square, shaft power follows its cube.
  • At 80% speed: 80% of the flow, 64% of the head, 51% of the power.
  • The laws describe the machine, not the pipes. With lift in the system, find the duty point first.
Practice

Found this useful?

Discussion