Three-Phase Systems: Star and Delta

Lesson 2 of 10 24 min read
Found this useful?

A motor that is connected in star when its nameplate asks for delta gives one third of its torque, fails to reach speed and overheats. A supply whose three voltages differ by only 2 percent can make the three currents of a motor differ by 12 to 20 percent, and the hottest winding decides the life of the whole machine. A neutral conductor that was expected to carry nothing carries 17 A. All three problems come from one subject: how three phases are connected, and what happens when they are not equal. This lesson derives the relations for star and delta, calculates what the neutral carries, and shows how to put a number on unbalance. #ThreePhase #StarDelta #VoltageUnbalance

Learning Objectives

By the end of this lesson, you will be able to:

  1. Explain why power is generated and distributed in three phases
  2. Derive the line and phase relations of star and delta connections by phasor subtraction
  3. Calculate the voltage and the current of a motor winding in star and in delta
  4. Calculate the neutral current of an unbalanced load by phasor sum
  5. Measure voltage unbalance and estimate what it does to the currents of a motor

Real-World System Problem: One supply, two kinds of load



A cold store takes a three-phase, four-wire supply at 50 Hz from its transformer: 415 V between any two phases and 240 V from any phase to the neutral. These are the nominal figures in Kenya and much of East Africa. The IEC nominal figures are 400 V and 230 V, and many countries use them. The supply feeds two kinds of load.

The 22 kW compressor motor is a three-phase load. It uses the three phase conductors and no neutral, and it draws 40.0 A in each. Its three windings are equal, so it is a balanced load. The lighting and the sockets are single-phase loads. Each circuit is connected between one phase and the neutral, and the designer shares the circuits among the three phases. People switch them at different times, so the three phases are never loaded equally.

The unequal single-phase loads cause unequal voltage drops, and the three voltages at the motor terminals are then no longer equal. The motor did nothing wrong, yet it pays for the unbalance with heat. To follow this chain you need the relations between line and phase quantities, the current in the neutral, and a measure of unbalance.

cb3-phasebalancedno NTransformersecondary (star)Compressor motoraNlighting circuits,one phase each(30A,20A,10A)
The supply, the motor and the single-phase loads

Fundamental Theory: Three phases and their two connections



Why three phases

A three-phase generator has three windings placed 120° apart around the machine. They produce three voltages of equal size, each 120° behind the one before. With phase a as the reference and the sequence a, b, c:

is the RMS voltage from one phase to the neutral point n. There are three reasons for the extra conductors.

Constant power. The power of one phase pulses. It falls to zero twice in every period, because and both pass through zero. In a balanced three-phase system the three pulsing powers are 120° apart and their sum does not change with time:

A three-phase motor therefore gives a steady torque, and a single-phase motor of the same size vibrates more.

Less copper. To carry the same power at the same voltage between conductors, with the same loss, a three-phase line with three conductors needs only 75 percent of the copper of a single-phase line with two.

A rotating field. Three windings 120° apart in space, fed by three currents 120° apart in time, make a magnetic field of constant size that rotates. This field turns the rotor of an induction motor with no brushes and no starting device. It is described in induction motors, slip and the nameplate.

Line and phase quantities

Two pairs of words must be kept apart.

  • A line quantity is measured on the supply conductors. The line voltage is between two line conductors. The line current is in one line conductor.
  • A phase quantity belongs to one element of the load or the source: one winding, one heater element. is the voltage across that element and is the current through it.

A nameplate gives line quantities, because those can be measured from outside the machine. The winding lives on phase quantities. The connection, star or delta, decides how one is converted to the other.

The star connection

In a star connection (also called wye, with the symbol Y) one end of each element is joined at a common point, the star point. The other three ends go to the lines. The star point may be connected to the neutral.

I_L=I_phaZbZ●star pointcZNacross each Z: V_ph = 240 Vatob:V_L=415V
Star connection

The current has only one path from a line into its element, so the line current equals the phase current. The line voltage is the difference of two phase voltages. Use the phasors above:

The size of is , and its angle is . So

The line voltage is times the phase voltage and leads it by 30°. With this gives 415.7 V, the nominal 415 V. The same subtraction gives and , each 120° behind the one before.

The delta connection

In a delta connection (symbol Δ) the three elements are joined in a ring, and each corner of the ring goes to one line. There is no star point and no place for a neutral.

ZcaZabZbcI_La●I_phb●●cacross each Z: V_ph = V_L = 415 V
Delta connection

Each element is connected directly between two lines, so the phase voltage equals the line voltage. The line current divides at the corner. At corner a, the current that arrives on the line leaves through element ab and returns through element ca (Kirchhoff’s current law):

For a balanced load the three phase currents are equal in size and 120° apart. Take as the reference for this step, so that is at :

The line current is times the phase current and lags it by 30°.

Line and phase relations (balanced)

is the angle between the voltage across one element and the current through that element. It is not the angle between a line voltage and a line current.

The same load in star and in delta

Take three equal elements, each of impedance , on the same supply. In delta each element has the full line voltage across it. In star each has only . The element current falls by the factor , and in star the line current is that same current, while in delta the line current was times larger than the element current. The result:

A set of heater elements moved from delta to star gives one third of the heat. This ratio needs the impedance to stay the same in both connections, which is true for a heater and true for a motor only at one given speed.

A motor nameplate says which connection to use by giving two voltages, for example “Δ 415 V / Y 720 V” or “Δ 230 V / Y 400 V”. The first figure is the line voltage for delta and the second, times larger, is the line voltage for star. Each pair means the same winding voltage, the smaller figure. On a 415 V supply the first motor is connected in delta. The second, a small motor, is connected in star: in delta its windings would receive 415 V instead of about 240 V, draw a very large magnetising current and burn out unless the protection trips. Read the pair before you judge a connection, and never judge it from the size of the motor alone.

The neutral and what it carries

In a four-wire system the neutral carries whatever the three line currents do not cancel among themselves. Kirchhoff’s current law at the star point gives

as a phasor sum. If the three currents are equal in size and 120° apart, the three arrows close into a triangle and the sum is zero. A balanced load needs no neutral, which is why a motor has only three supply conductors.

If the loads are unequal, the neutral carries the part that does not cancel. For three loads with the same power factor, the size has a compact form:

When the power factors differ, use the phasor sum with the real angle of each current.

Balanced against unbalanced

A system is balanced when the three voltages are equal and 120° apart and the three load impedances are equal. Then one phase tells the whole story: solve one phase and multiply the power by three. All the formulas with belong to this case.

When the loads are unequal, each phase must be solved separately with its own voltage, current and angle, and the results added as phasors (for currents) or as plain numbers (for real power).

Voltage unbalance and what it does to a motor

Unequal single-phase loads, one weak connection, or one failed capacitor make the three line voltages unequal. A simple measure, defined by NEMA, needs only a voltmeter.

Voltage unbalance (NEMA definition)

Suppose the three line voltages at a motor are 415 V, 410 V and 398 V. The average is

The deviations from the average are 7.3 V, 2.3 V and 9.7 V. The largest is 9.7 V, so

A figure of 2.37 percent looks harmless. For a motor it is not. An unbalanced set of voltages behaves as a normal set with a small second set added that rotates in the opposite direction. The motor turns with the first set and against the second. Against a field that rotates backward the motor has a very low impedance, close to its impedance at standstill, so a small backward voltage drives a large current.

A common rule of thumb, used with the NEMA motor standard, is that the current unbalance at full load is roughly six to ten times the voltage unbalance. For 2.37 percent this is roughly 14 to 24 percent. It is a rule of thumb and not a calculation: the true figure depends on the motor design and on its load. The extra current heats one winding more than the others, and it produces no useful torque.

Application 1: Motor winding voltage and current in star and in delta



Step 1: The windings in delta

Click to reveal the delta values
  1. Winding voltage. In delta each winding is connected between two lines.

    Each winding has the full 415 V across it. ✅

  2. Winding current. The line current is a difference of two winding currents, so it is times larger.

    Each winding carries 23.1 A, not 40.0 A. ✅

  3. Winding impedance at full load.

    Each winding behaves as 18.0 Ω at an angle of . ✅

Step 2: The same windings in star

Click to reveal the star values
  1. Winding voltage. In star the line voltage is shared between two windings as a phasor difference.

    Each winding receives 240 V, which is 58 percent of the voltage it was designed for. ✅

  2. Winding current with the same impedance.

    ✅

  3. Line current. In star the line current equals the winding current, so .

    The line current in star is one third of the line current in delta. ✅

  4. What this does to torque and current. At a given speed the torque of an induction motor is proportional to the square of the winding voltage, so in star the motor gives of its torque and takes one third of the line current. This is why star-delta starting works: the motor starts in star to limit the current, and is switched to delta near full speed to recover its full torque. ✅

Step 3: Check the delta result

Click to reveal the check
  1. Angles of the winding currents. The line voltage leads by 30°, and each winding current lags its own voltage by 32.9°. So is at , and is 120° ahead of it, at . ✅

  2. Phasor subtraction.

    The line current is 40.0 A, and it lags the phase-a voltage by 32.9°, whose cosine is 0.84. The nameplate current and power factor are recovered. ✅

  3. Power from phase quantities.

    ✅

  4. Power from line quantities.

    The two forms agree, and both agree with the nameplate: 22 kW at the shaft divided by an efficiency of 0.910 is 24.2 kW. ✅

Application 2: Neutral current of an unbalanced lighting load



Step 1: Write the three currents

Click to reveal the three phasors
  1. Angles. At unity power factor each current is in phase with its own phase voltage. The currents are therefore at 0°, −120° and +120°. ✅

  2. Rectangular form.

    ✅

Step 2: Add them

Click to reveal the neutral current
  1. Sum of the parts.

    ✅

  2. Size.

    The neutral carries 17.3 A. ✅

  3. Angle.

    The neutral current lags the phase-a voltage by 30°. ✅

Step 3: Check, and the balanced case

Click to reveal the check
  1. Check by the formula. All three loads have the same power factor, so the compact form applies.

    The formula agrees with the phasor sum. ✅

  2. Check by removing a balanced part. Take 10 A from every phase. Those three equal currents cancel, so the neutral current does not change. What remains is 20 A at 0° and 10 A at −120°, and their sum is , which is 17.3 A again. ✅

  3. Equal loads. With 20 A on each phase:

    The neutral carries nothing. ✅

  4. Compare with the wrong answers. The plain sum of the three currents is 60 A, and the neutral carries less than a third of that. The other wrong answer is zero, which is true only for equal loads. ✅

Verify It in Python



The script derives the star line voltages by complex subtraction, calculates the motor windings in delta and in star, sums the neutral current for the unequal and the equal loads, calculates the voltage unbalance, and shows that the total power of three balanced phases is constant.

three_phase_star_delta.py
"""Star and delta relations, motor windings, neutral current and voltage unbalance."""
import cmath
import math
import numpy as np
import matplotlib.pyplot as plt
V_PH = 240.0 # V RMS, line to neutral
F = 50.0 # Hz
def phasor(mag, deg):
return cmath.rect(mag, math.radians(deg))
def show(z, unit):
return f"{abs(z):.1f} {unit} at {math.degrees(cmath.phase(z)):.1f} deg"
# ---------- Line and phase relations by phasor subtraction ----------
Van, Vbn, Vcn = phasor(V_PH, 0.0), phasor(V_PH, -120.0), phasor(V_PH, 120.0)
Vab, Vbc, Vca = Van - Vbn, Vbn - Vcn, Vcn - Van
print("Star: line voltages from phase voltages")
for name, v in (("Vab", Vab), ("Vbc", Vbc), ("Vca", Vca)):
print(f" {name} = {show(v, 'V')}")
print(f" ratio {abs(Vab) / V_PH:.4f}, sum of line voltages {abs(Vab + Vbc + Vca):.1f} V")
# ---------- Application 1: motor A windings in delta and in star ----------
V_L = 415.0
I_L = 40.0
PF = 0.84
phi = math.degrees(math.acos(PF))
print("Application 1: motor windings")
I_w = I_L / math.sqrt(3.0)
Z_w = V_L / I_w
print(f" delta: winding voltage {V_L:.0f} V, winding current {I_w:.1f} A, "
f"winding impedance {Z_w:.2f} ohm")
# check by phasor subtraction of two winding currents
Iab = phasor(I_w, 30.0 - phi) # Vab leads Van by 30 deg
Ica = phasor(I_w, 150.0 - phi)
Ia = Iab - Ica
print(f" check: Ia = Iab - Ica = {show(Ia, 'A')} "
f"(behind Van by {-math.degrees(cmath.phase(Ia)):.1f} deg)")
print(f" power: 3 x {V_L:.0f} x {I_w:.1f} x {PF} = "
f"{3.0 * V_L * I_w * PF / 1000.0:.2f} kW, "
f"root 3 form {math.sqrt(3.0) * V_L * I_L * PF / 1000.0:.2f} kW")
V_star = V_L / math.sqrt(3.0)
I_star = V_star / Z_w
print(f" star, same winding impedance: winding voltage {V_star:.1f} V, "
f"winding and line current {I_star:.1f} A")
print(f" line current ratio star/delta {I_star / I_L:.3f}, "
f"torque ratio {(V_star / V_L) ** 2:.3f}")
# ---------- Application 2: neutral current ----------
print("Application 2: neutral current")
for amps in ((30.0, 20.0, 10.0), (20.0, 20.0, 20.0)):
Ia_, Ib_, Ic_ = phasor(amps[0], 0.0), phasor(amps[1], -120.0), phasor(amps[2], 120.0)
In = Ia_ + Ib_ + Ic_
print(f" {amps[0]:.0f} A, {amps[1]:.0f} A, {amps[2]:.0f} A: "
f"In = {In.real:.2f} {In.imag:+.2f}j A = {abs(In):.1f} A"
+ (f" at {math.degrees(cmath.phase(In)):.1f} deg" if abs(In) > 1e-6 else ""))
a, b, c = 30.0, 20.0, 10.0
print(f" formula check: {math.sqrt(a*a + b*b + c*c - a*b - b*c - c*a):.1f} A, "
f"arithmetic sum {a + b + c:.0f} A")
# ---------- Voltage unbalance (NEMA definition) ----------
volts = np.array([415.0, 410.0, 398.0])
avg = volts.mean()
dev = np.abs(volts - avg)
unb = 100.0 * dev.max() / avg
print("Voltage unbalance")
print(f" average {avg:.1f} V, deviations {dev[0]:.1f}, {dev[1]:.1f}, {dev[2]:.1f} V")
print(f" unbalance {unb:.2f} %")
print(f" rule of thumb, current unbalance: {6.0 * unb:.0f} to {10.0 * unb:.0f} %")
# ---------- Constant power, and the plot ----------
t = np.linspace(0.0, 0.04, 4000, endpoint=False)
w = 2.0 * math.pi * F
shifts = (0.0, -120.0, 120.0)
p_one = 2.0 * np.sin(w * t) ** 2 # one phase, mean value 1
p_three = sum(2.0 * np.sin(w * t + math.radians(s)) ** 2 for s in shifts)
print("Power into a balanced resistive load (one phase mean = 1)")
print(f" one phase: from {p_one.min():.2f} to {p_one.max():.2f}")
print(f" three phases: from {p_three.min():.2f} to {p_three.max():.2f}")
fig, ax = plt.subplots(2, 1, figsize=(8, 7))
for s, name in zip(shifts, ("a", "b", "c")):
ax[0].plot(1000.0 * t, V_PH * math.sqrt(2.0) * np.sin(w * t + math.radians(s)),
label=f"phase {name}")
ax[0].set_xlabel("time (ms)")
ax[0].set_ylabel("phase voltage (V)")
ax[0].set_title("Three phase voltages, 120 degrees apart")
ax[0].legend()
ax[1].plot(1000.0 * t, p_one, label="one phase")
ax[1].plot(1000.0 * t, p_three, label="three phases together")
ax[1].set_xlabel("time (ms)")
ax[1].set_ylabel("power (one phase mean = 1)")
ax[1].set_title("One phase pulses, three phases give constant power")
ax[1].legend()
fig.tight_layout()
fig.savefig("three_phase_star_delta.png", dpi=120)
print("Saved three_phase_star_delta.png")

Expected output

Star: line voltages from phase voltages
Vab = 415.7 V at 30.0 deg
Vbc = 415.7 V at -90.0 deg
Vca = 415.7 V at 150.0 deg
ratio 1.7321, sum of line voltages 0.0 V
Application 1: motor windings
delta: winding voltage 415 V, winding current 23.1 A, winding impedance 17.97 ohm
check: Ia = Iab - Ica = 40.0 A at -32.9 deg (behind Van by 32.9 deg)
power: 3 x 415 x 23.1 x 0.84 = 24.15 kW, root 3 form 24.15 kW
star, same winding impedance: winding voltage 239.6 V, winding and line current 13.3 A
line current ratio star/delta 0.333, torque ratio 0.333
Application 2: neutral current
30 A, 20 A, 10 A: In = 15.00 -8.66j A = 17.3 A at -30.0 deg
20 A, 20 A, 20 A: In = 0.00 +0.00j A = 0.0 A
formula check: 17.3 A, arithmetic sum 60 A
Voltage unbalance
average 407.7 V, deviations 7.3, 2.3, 9.7 V
unbalance 2.37 %
rule of thumb, current unbalance: 14 to 24 %
Power into a balanced resistive load (one phase mean = 1)
one phase: from 0.00 to 2.00
three phases: from 3.00 to 3.00
Saved three_phase_star_delta.png

The script prints the winding impedance as 17.97 Ω and the power as 24.15 kW, which the hand calculation rounds to 18.0 Ω and 24.2 kW. The last two lines show the first reason for three phases: the power of one phase moves between zero and twice its mean, and the sum of three phases does not move.

Common Mistakes



  • Applying to both voltage and current. In star it belongs to the voltage only, and in delta to the current only.
  • Using on an unbalanced load. The formula is for balanced loads. For unequal phases, calculate each phase and add the powers.
  • Adding the three line currents as plain numbers to find the neutral current, or assuming that the neutral current is always zero. It is a phasor sum, and it is zero only for equal loads.
  • Reading a nameplate current of 40.0 A as the current in each winding. In a delta-connected motor the winding carries 23.1 A.
  • Connecting a motor without reading which connection its nameplate requires for the supply voltage. A motor marked for delta at 415 V receives only 240 V per winding in star.
  • Calling a voltage unbalance of 2 percent small. For a motor the current unbalance can be roughly six to ten times larger.

Summary



  • Three phases give constant total power, use less copper for the same power, and make the rotating field that turns an induction motor.
  • In star, the line voltage is times the phase voltage and the line current equals the phase current. In delta, the line voltage equals the phase voltage and the line current is times the phase current. Both results come from the difference of two phasors 120° apart.
  • The compressor motor in delta has 415 V and 23.1 A in each winding at full load. The same windings in star would receive 240 V, and at the same speed would give one third of the torque and take one third of the line current.
  • The neutral current is the phasor sum of the three line currents. For 30 A, 20 A and 10 A at unity power factor it is 17.3 A, and for equal loads it is zero.
  • Voltage unbalance is the largest deviation from the average line voltage divided by the average. Line voltages of 415 V, 410 V and 398 V give 2.37 percent, and as a rule of thumb the current unbalance of a motor is roughly six to ten times that.

Exercises



1. A country uses the IEC nominal line voltage of 400 V. Find the voltage from phase to neutral.

Answer

, which is given the nominal name 230 V.

2. Three heater elements of 30 Ω each are connected in delta to a 415 V supply. Find the current in each element, the line current and the total power. Then find the total power if the same elements are connected in star.

Answer

Delta: , , and . Star: each element has 239.6 V and carries 8.0 A, so , one third of the delta value.

3. Single-phase loads at unity power factor draw 25 A on phase a, 25 A on phase b and 10 A on phase c. Find the neutral current.

Answer

Remove a balanced 10 A from every phase. What remains is 15 A at 0° and 15 A at −120°, whose sum is 15 A at −60°. The neutral carries 15.0 A. The formula gives .

4. The line voltages at a motor are 402 V, 396 V and 390 V. Find the voltage unbalance by the NEMA definition, and estimate the range of the current unbalance at full load with the rule of thumb.

Answer

The average is 396 V and the largest deviation is 6 V, so the unbalance is percent. The rule of thumb gives a current unbalance of roughly 9 to 15 percent. This motor is above the 1 percent level at which derating is advised.

5. Phase a carries 30 A at unity power factor. Phase b carries 20 A at a power factor of 0.80 lagging. Phase c carries 10 A at unity power factor. Find the neutral current. Explain why the compact formula cannot be used.

Answer

The current of phase b lags its own voltage by , so it is at : . With and , the sum is , which is 6.7 A. The compact formula assumes the same power factor in every phase, and here the angles between the currents are no longer 120°.

References



  • S. J. Chapman, Electric Machinery Fundamentals, 5th edition, McGraw-Hill, 2012.
  • A. Hughes and B. Drury, Electric Motors and Drives: Fundamentals, Types and Applications, 5th edition, Newnes, 2019.
  • J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and Design, 6th edition, Cengage Learning, 2017.
  • NEMA MG 1, Motors and Generators, National Electrical Manufacturers Association.


© 2021-2026 SiliconWit®. All rights reserved.
Predict first

Three groups of lights are connected from phase to neutral. They draw 30 A, 20 A and 10 A on the three phases. About what current flows in the shared neutral?

240 V240 V120° 415 V phase: 240 Vline: 240 × √3 = 415 Vnot 480 V
See it: three currents, one neutral

Neutral current
Its angle
Simple sum, wrong

Lighting at unity power factor on a 415/240 V supply, so each current is in step with its own phase voltage: phase a at 0°, b at −120°, c at +120°. On the right the three arrows are placed tip to tail. If they close the triangle, the neutral carries nothing. The gold arrow is what is left over, and it returns through the neutral.

Transformer secondary (star) a b c N Compressor motor M 3~ balanced, no N 30 A 20 A 10 A lighting circuits, one phase each
One supply, two kinds of load
a Z b Z c Z N star point I_L = I_ph a to b: V_L = 415 V V_L V_ph across each Z: V_ph = 240 V
The star connection

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. A pump motor connected in delta draws 30 A in each line. What current flows in each winding?

2. The compressor motor draws 40 A in each line when its windings are in delta on 415 V. The same windings are reconnected in star on the same supply. What line current flows now, if the winding impedance is unchanged?

3. Lighting on a four-wire supply draws 25 A, 25 A and 10 A on phases a, b and c, all at unity power factor. What current flows in the neutral?

Watch it build: the current at one corner of a delta
abc 415 V on each winding Ia = Iab − Ica Iab Ica each 23.1 A,120° apart −Ica reverse one,add tip to tail 30° Ia = 40.0 A 1.732 × 23.1 A
  1. In delta each winding sits between two lines, so it has the full 415 V across it.
  2. At corner a, the line current arrives, Iab leaves and Ica comes back: Ia = Iab − Ica.
  3. Balanced: the winding currents are equal, 23.1 A for the compressor, and 120° apart.
  4. To subtract Ica, reverse it and place it at the tip of Iab. The line current closes the triangle.
  5. Ia is √3 × 23.1 = 40.0 A, the nameplate current, and lags the winding current by 30°.