Induction Motors: Slip, Torque and the Nameplate

Lesson 6 of 10 26 min read
Found this useful?

A motor draws 25 A against a nameplate current of 40 A, and the technician reports that it is “62 percent loaded”. The true figure is close to 50 percent, and the same error across a factory hides many motors that are far too large for their work. Those motors do their work, so nobody looks at them, yet together they pull the power factor of the site down and the demand charge up. The nameplate and one speed reading are enough to find them. This lesson explains how an induction motor makes torque, what each line of its nameplate means, and how to estimate the load on a running motor. #InductionMotor #Slip #MotorLoad

Learning Objectives

By the end of this lesson, you will be able to:

  1. Calculate the synchronous speed, the slip and the shaft torque of an induction motor from its nameplate
  2. Explain why the rotor must turn slower than the field, and how the torque changes with speed
  3. Read every line of a motor nameplate and find the input power and the losses
  4. Estimate the load on a running motor from its measured speed, and state how rough the estimate is
  5. Explain why a lightly loaded motor has a poor power factor and why its current is a poor guide to its load

Real-World System Problem: The cold store compressor motor



A cold store has a 22 kW compressor motor on a 415 V, three-phase, 50 Hz supply. (The IEC nominal voltage is 400 V, and many countries use it.) The motor runs about 14 hours a day. Its nameplate gives 1465 rev/min, 40.0 A, a power factor of 0.84 and an efficiency of 91.0 percent.

The nameplate describes full load only, and the compressor does not always ask for it: in cool weather, or when the store is half empty, it needs much less torque. The owner wants to know how hard the motor really works, because a motor that is too large for its load lowers the power factor of the whole site.

Without a torque sensor the shaft power cannot be measured directly, but three quantities can be measured from outside: the speed, the current and the input power. Each gives an estimate of the load, they are not equally good, and judging them needs an idea of how the motor makes its torque.

fieldcage22 kWoutputwindingand core24.2 kWinputsupplystatorairrotorshaft415V,40.0Agapstator copperrotor copper loss,andironlossfriction, fantotal losses 2.2 kW, all of it heat
Power through the motor at full load

Fundamental Theory: How an induction motor makes torque



The rotating field and synchronous speed

The stator of a three-phase motor has three windings placed around the machine. Three currents, 120° apart in time, flow in three windings that are apart in space. Together they make a magnetic field of constant size that rotates.

The speed of the field is the synchronous speed . It depends on the supply frequency and on the number of poles that the winding makes:

The field moves past one pair of poles in each period of the supply. A winding with more poles therefore gives a slower field.

Poles at 50 Hz at 60 Hz
23000 rev/min3600 rev/min
41500 rev/min1800 rev/min
61000 rev/min1200 rev/min
8750 rev/min900 rev/min

The synchronous speed changes only with the number of poles or the frequency, which is why a variable speed drive changes the frequency.

Why the rotor must slip

The rotor of a cage motor is a set of aluminium or copper bars joined by a ring at each end. It has no electrical connection to the supply. The rotating field passes across the bars and induces a voltage in them, as in the secondary winding of a transformer. The voltage drives a current in the bars, and a current in a magnetic field feels a force. The forces on the bars make the torque.

If the rotor turned at exactly the speed of the field, the field would not pass across the bars: no induced voltage, no current, no torque. So the rotor always turns a little slower than the field. The difference, as a fraction of the synchronous speed, is the slip :

Slip

is the speed of the rotor. At standstill . At synchronous speed . At full load the slip of an industrial motor is small, usually between 1 and 5 percent.

The rotor bars see the field pass at the slip speed only, so the frequency of the rotor current is . At a slip of 2 percent on a 50 Hz supply, the rotor current alternates once per second.

A larger load torque slows the rotor slightly. The slip rises, the induced voltage and the rotor current rise, and the torque rises until it equals the load again.

Where the power goes

Follow the power from the supply to the shaft. The stator takes the input power . Part of it heats the stator winding (copper loss) and the steel core (iron loss). The rest crosses the air gap to the rotor, carried by the field. In the rotor, a fraction equal to the slip becomes heat in the bars. A rotor that slips by 2 percent turns 2 percent of the power that crosses the air gap into heat. The remainder becomes mechanical power, and after friction and the cooling fan take their share, what is left is the shaft power .

Low slip and high efficiency go together.

Torque and the torque-speed curve

Shaft power is torque multiplied by angular speed:

is in newton metres when is in watts and is in radians per second. The common mistake is to use the synchronous speed here. The shaft turns at , not at .

The torque that a motor can give depends on its speed. The curve has three points with names.

torquebreakdown torquestartingtorqueworking region(nearly a- - - - - - - - - - - - - - ● straight line)rated torque●speed01465 1500 rev/mins=1s=0
Torque against speed for a cage motor
  • The starting torque (locked-rotor torque) is what the motor gives at standstill. The current at this point is several times the full-load current: for the compressor motor it is 6.5 times, which is 260 A.
  • The breakdown torque is the highest torque the motor can give, typically two to three times the rated torque. A load above it stalls the motor.
  • The working region is the steep part between the breakdown point and synchronous speed. Here the torque is very nearly proportional to the slip. Twice the torque needs twice the slip.

The motor runs where its curve crosses the torque that the load demands. In the working region the speed changes very little, from 1500 rev/min with no load to 1465 rev/min at full load. That small change of speed tells you the load.

Reading the nameplate

Every line of the plate has a meaning. Here is the plate of the compressor motor, with the lines that a plate of this kind usually carries.

3~ MOTOR IEC 60034-122 kW S1 50 HzΔ 415 V 40.0 A cos φ 0.841465 r/min η 91.0 % 4 poleIns. cl. F IP55 40 °C
Nameplate of the compressor motor
LineMeaning
22 kWRated power at the shaft, not the electrical input
S1Duty type: continuous running at constant load
50 HzSupply frequency the ratings refer to
Δ 415 VLine voltage and the winding connection for that voltage
40.0 ALine current at rated load and rated voltage
cos φ 0.84Power factor at rated load
1465 r/minSpeed at rated load, from which the slip follows
η 91.0 %Efficiency at rated load, sometimes with the efficiency class
Ins. cl. FInsulation class, the temperature the winding insulation withstands (class F is 155 °C)
IP55Protection of the enclosure against dust and water
40 °CHighest ambient temperature for the full rating

If a plate does not state the number of poles, find it from the speed: the synchronous speed is the value in the table just above the rated speed. A rated speed of 1465 rev/min at 50 Hz can only belong to 1500 rev/min, so the motor has 4 poles.

The plate gives the output power and three electrical quantities. The input power can therefore be found in two ways, and the two should agree:

Efficiency classes

IEC 60034-30-1 sorts motors into efficiency classes by their efficiency at rated load: IE1 (standard), IE2 (high), IE3 (premium) and IE4 (super premium). The efficiency required for each class depends on the rated power and on the number of poles. A higher class means lower losses at the same shaft power. It usually also means a lower slip, so a replacement motor of a higher class runs slightly faster, and a pump or fan on it takes slightly more power.

The lowest full-load efficiency of each class, for 4-pole motors at 50 Hz, as given in the 2014 edition of the standard:

Rated powerIE1 (%)IE2 (%)IE3 (%)IE4 (%)
7.5 kW86.088.790.492.6
22 kW89.991.693.094.5

To find the class of a motor whose plate does not print it, compare its efficiency with the row for its power and poles. The compressor motor, 22 kW and 4 poles at 91.0 percent, is above the IE1 figure and below IE2, so it is an IE1 motor. Many countries now require IE2 or IE3 for new motors of this size.

Estimating the load from slip

In the working region the torque is nearly proportional to the slip, and the speed is nearly constant, so the shaft power is nearly proportional to the slip as well. The nameplate gives the slip at full load. A measured speed gives the slip now.

The slip method

is the measured speed and is the nameplate speed. The shaft power is the load fraction multiplied by the rated power.

The method costs almost nothing, and it is rough.

  • The nameplate speed is rounded, and standards allow the real full-load slip to differ from the nameplate value (by up to 20 percent for a motor of this size). The estimate carries the same uncertainty.
  • The full-load slip is 35 rev/min. An error of 2 rev/min in the measured speed is an error of 6 percent of full load. The speed must be measured to 1 rev/min, and the supply frequency must be close to 50 Hz.
  • The slip at a given torque varies inversely with the square of the voltage. If the voltage at the terminals differs from the rated voltage , correct the estimate:
  • The synchronous speed follows the frequency. On this motor 0.1 Hz moves by 3 rev/min, which is 9 percent of full load: at 49.9 Hz the same 1482 rev/min means 43 percent load, not 51 percent. Measure the frequency at the same moment and use with the measured . On a site running on its own generator this correction is essential.
  • The slip rises as the rotor warms, so measure when the motor has reached its working temperature.

Where a power meter is available, a better estimate comes from the measured input power: the shaft power is the input power multiplied by the efficiency, and the efficiency changes little between half load and full load.

Why current is a poor guide below half load

Many people divide the measured current by the nameplate current and call the result the load. This fails at low load.

The motor current has two parts. One part carries the real power and rises and falls with the load. The other part is the magnetising current, which builds the rotating field. The field is at full strength whenever the motor is connected, loaded or not, so the magnetising current is nearly constant, and it lags the voltage by nearly 90°.

A motor with nothing on its shaft still draws a no-load current of about 30 to 40 percent of its full-load current. This is a typical range: small motors and motors with many poles are higher. The two parts are nearly 90° apart, so they add as phasors and not as plain numbers. A rough model for the compressor motor, with a no-load current of 35 percent (14.0 A), gives the following.

LoadCurrentCurrent as a share of 40.0 A
0 percent14.0 A35 percent
25 percent16.8 A42 percent
50 percent23.4 A58 percent
75 percent31.4 A78 percent
100 percent40.0 A100 percent

Between no load and 25 percent load the current rises by only 2.8 A. Below half load the current says very little about the load. Above about 75 percent it is a fair guide.

Efficiency and power factor at part load

The efficiency of a motor stays close to its full-load value down to about half load, and then falls quickly, because the iron loss, the friction and the fan take the same power at any load.

The power factor behaves differently. It falls steadily as the load falls, because the real part of the current shrinks and the magnetising part does not. A motor with a power factor of 0.84 at full load typically has about 0.70 at half load and much less at a quarter load. An oversized motor therefore costs little in kWh and a great deal in kvar.

Application 1: The nameplate of the compressor motor



Step 1: Synchronous speed and slip

Click to reveal the speed and slip
  1. Synchronous speed.

    The field turns at 1500 rev/min. ✅

  2. Slip at full load.

    The slip is 2.33 percent. The rotor falls 35 rev/min behind the field. ✅

  3. Rotor frequency.

    The current in the rotor bars alternates about once each second. ✅

Step 2: Shaft torque

Click to reveal the torque
  1. Angular speed of the shaft. Use the rotor speed, not the synchronous speed.

    ✅

  2. Torque.

    The rated torque is 143.4 N·m. ✅

Step 3: Input power and losses

Click to reveal the input power and losses
  1. Input power from the efficiency.

    The motor takes 24.2 kW from the supply. ✅

  2. Total losses.

    The motor turns 2.18 kW into heat, which is 9.0 percent of its input. ✅

  3. Loss energy for one day.

    The losses use 30.5 kWh each day. ✅

  4. Where the losses arise. The slip of 2.33 percent says that 2.33 percent of the power that crosses the air gap becomes heat in the rotor bars. The rest of the 2.18 kW is stator copper loss, iron loss, friction and the fan. The nameplate cannot separate these: that needs the maker’s test data. ✅

Step 4: Check a second way

Click to reveal the check
  1. Input power from the electrical quantities.

    The two routes give 24.18 kW and 24.15 kW. They differ by 0.1 percent, which is the rounding of the nameplate figures. The plate is consistent. ✅

  2. Torque check. Multiply the torque by the angular speed.

    The shaft power of 22 kW is recovered. ✅

Application 2: The load on the motor at 1482 rev/min



Step 1: Load from the slip

Click to reveal the load estimate
  1. Load fraction.

    The motor carries about 51 percent of its rated load. ✅

  2. Shaft power.

    The compressor takes about 11.3 kW from the shaft. The voltage is at its rated value, so no voltage correction is needed. ✅

Step 2: Input power, current and reactive power

Click to reveal the electrical quantities
  1. Input power, with the typical efficiency of 0.90.

    ✅

  2. Apparent power, with the typical power factor of 0.70.

    ✅

  3. Line current.

    The motor draws about 25.0 A. ✅

  4. Reactive power. With , .

    The motor takes 12.83 kvar: more kvar than kW. ✅

Step 3: What the oversized motor costs

Click to reveal the comparison
  1. The same motor at full load. With , .

    From full load to 51 percent load the real power fell from 24.18 kW to 12.57 kW, a fall of 48 percent. The reactive power fell from 15.62 kvar to 12.83 kvar, a fall of only 18 percent. ✅

  2. A 15 kW motor on the same load. The load is percent of its rating. With an efficiency of 0.90 the input power is the same, 12.57 kW. With , .

    ✅

  3. The difference.

    For the same work and the same kWh, the 22 kW motor takes 3.40 kvar and 3.1 A more than a motor of the right size. ✅

Step 4: Check, and the estimate from current

Click to reveal the check
  1. Check the power triangle.

    The three quantities agree. ✅

  2. The estimate from current. The current ratio is

    A person who uses current alone reports 62 percent load. The slip method gives 51 percent. The current overstates the load because of the magnetising current. ✅

  3. Effect of a low voltage. If the terminal voltage had been 400 V and not 415 V, the corrected estimate would be

    The load would be 48 percent, not 51 percent. Always record the voltage with the speed. ✅

Verify It in Python



The script reproduces both applications, applies the voltage correction, prints the rough current model (which gives 23.8 A at the measured load, against 25.0 A from the typical values), and plots a simplified torque-speed curve with the two operating points.

induction_motor_slip_load.py
"""Induction motor: slip, torque, losses, load from slip, and the cost of oversizing."""
import math
import numpy as np
import matplotlib.pyplot as plt
F = 50.0 # Hz
POLES = 4
V_L = 415.0 # V
P_RATED = 22.0 # kW at the shaft
N_RATED = 1465.0 # rev/min at full load
I_FL = 40.0 # A
PF_FL = 0.84
ETA_FL = 0.910
ROOT3 = math.sqrt(3.0)
def kvar(p_kw, pf):
return p_kw * math.tan(math.acos(pf))
# ---------- Application 1: the nameplate ----------
n_s = 120.0 * F / POLES
s_fl = (n_s - N_RATED) / n_s
omega = 2.0 * math.pi * N_RATED / 60.0
torque = 1000.0 * P_RATED / omega
p_in = P_RATED / ETA_FL
p_in_elec = ROOT3 * V_L * I_FL * PF_FL / 1000.0
print("Application 1: nameplate")
print(f" synchronous speed {n_s:.0f} rev/min, slip {100.0 * s_fl:.2f} %, "
f"rotor frequency {s_fl * F:.2f} Hz")
print(f" shaft speed {omega:.1f} rad/s, shaft torque {torque:.1f} N.m")
print(f" input power {p_in:.2f} kW from efficiency, "
f"{p_in_elec:.2f} kW from V, I and power factor")
print(f" losses {p_in - P_RATED:.2f} kW, "
f"which is {100.0 * (p_in - P_RATED) / p_in:.1f} % of the input")
print(f" S {ROOT3 * V_L * I_FL / 1000.0:.2f} kVA, Q {kvar(p_in, PF_FL):.2f} kvar")
print(f" loss energy at 14 h per day: {(p_in - P_RATED) * 14.0:.1f} kWh per day")
# ---------- Application 2: load from the measured speed ----------
N_MEAS = 1482.0
ETA_PART = 0.90 # typical at half load
PF_PART = 0.70 # typical at half load
load = (n_s - N_MEAS) / (n_s - N_RATED)
p_shaft = load * P_RATED
p_in2 = p_shaft / ETA_PART
s2 = p_in2 / PF_PART
i2 = 1000.0 * s2 / (ROOT3 * V_L)
q2 = kvar(p_in2, PF_PART)
print("Application 2: measured at 1482 rev/min")
print(f" slip {100.0 * (n_s - N_MEAS) / n_s:.2f} %, load fraction {load:.3f}")
print(f" shaft power {p_shaft:.2f} kW, torque "
f"{1000.0 * p_shaft / (2.0 * math.pi * N_MEAS / 60.0):.1f} N.m")
print(f" input {p_in2:.2f} kW, {s2:.2f} kVA, {i2:.1f} A, {q2:.2f} kvar")
print(f" current is {100.0 * i2 / I_FL:.0f} % of full-load current "
f"at {100.0 * load:.0f} % load")
print(f" kvar per kW: full load {kvar(1.0, PF_FL):.2f}, measured {kvar(1.0, PF_PART):.2f}")
# a motor of the right size: 15 kW at about 75 % load, typical values
ETA_SMALL = 0.90
PF_SMALL = 0.80
p_in3 = p_shaft / ETA_SMALL
q3 = kvar(p_in3, PF_SMALL)
i3 = 1000.0 * p_in3 / (ROOT3 * V_L * PF_SMALL)
print(f" 15 kW motor at {100.0 * p_shaft / 15.0:.0f} % load: "
f"{p_in3:.2f} kW, {q3:.2f} kvar, {i3:.1f} A")
print(f" extra reactive power of the oversized motor: {q2 - q3:.2f} kvar, "
f"extra current {i2 - i3:.1f} A")
# voltage correction of the slip method
for v_meas in (415.0, 400.0):
corrected = (n_s - N_MEAS) / ((n_s - N_RATED) * (V_L / v_meas) ** 2)
print(f" slip method at {v_meas:.0f} V: load fraction {corrected:.3f}")
# ---------- Why current is a poor guide at low load ----------
I_0 = 0.35 * I_FL # typical no-load current, 30 to 40 % of full-load current
print("Rough current model (no-load current 35 % of full-load current)")
for x in (0.0, 0.25, 0.50, 0.75, 1.00):
i_x = math.sqrt(I_0 ** 2 + x ** 2 * (I_FL ** 2 - I_0 ** 2))
print(f" load {100.0 * x:3.0f} %: current {i_x:4.1f} A "
f"= {100.0 * i_x / I_FL:3.0f} % of full-load current")
i_model = math.sqrt(I_0 ** 2 + load ** 2 * (I_FL ** 2 - I_0 ** 2))
print(f" at the measured load of {100.0 * load:.0f} %: model {i_model:.1f} A, "
f"typical-value calculation {i2:.1f} A")
# ---------- Plot ----------
fig, ax = plt.subplots(2, 1, figsize=(8, 7))
# simplified torque-speed curve, breakdown torque 2.5 times rated (typical)
ratio = 2.5
s_m = s_fl * (ratio + math.sqrt(ratio ** 2 - 1.0))
s = np.linspace(1e-4, 1.0, 2000)
t_curve = torque * ratio * 2.0 / (s / s_m + s_m / s)
ax[0].plot(n_s * (1.0 - s), t_curve)
ax[0].plot([N_RATED], [torque], "o", label="full load, 1465 rev/min")
ax[0].plot([N_MEAS], [load * torque], "s", label="measured, 1482 rev/min")
ax[0].set_xlabel("speed (rev/min)")
ax[0].set_ylabel("torque (N.m)")
ax[0].set_title("Simplified torque-speed curve (breakdown at 2.5 times rated)")
ax[0].legend()
x = np.linspace(0.0, 1.0, 101)
ax[1].plot(100.0 * x, 100.0 * np.sqrt(I_0 ** 2 + x ** 2 * (I_FL ** 2 - I_0 ** 2)) / I_FL,
label="current (rough model)")
ax[1].plot(100.0 * x, 100.0 * x, "--", label="if current were proportional to load")
ax[1].set_xlabel("load (% of rated shaft power)")
ax[1].set_ylabel("current (% of full-load current)")
ax[1].set_title("Current is a poor guide to load below half load")
ax[1].legend()
fig.tight_layout()
fig.savefig("induction_motor_slip_load.png", dpi=120)
print(f"Simplified curve: slip at breakdown {100.0 * s_m:.1f} %, "
f"speed {n_s * (1.0 - s_m):.0f} rev/min")
print("Saved induction_motor_slip_load.png")

Expected output

Application 1: nameplate
synchronous speed 1500 rev/min, slip 2.33 %, rotor frequency 1.17 Hz
shaft speed 153.4 rad/s, shaft torque 143.4 N.m
input power 24.18 kW from efficiency, 24.15 kW from V, I and power factor
losses 2.18 kW, which is 9.0 % of the input
S 28.75 kVA, Q 15.62 kvar
loss energy at 14 h per day: 30.5 kWh per day
Application 2: measured at 1482 rev/min
slip 1.20 %, load fraction 0.514
shaft power 11.31 kW, torque 72.9 N.m
input 12.57 kW, 17.96 kVA, 25.0 A, 12.83 kvar
current is 62 % of full-load current at 51 % load
kvar per kW: full load 0.65, measured 1.02
15 kW motor at 75 % load: 12.57 kW, 9.43 kvar, 21.9 A
extra reactive power of the oversized motor: 3.40 kvar, extra current 3.1 A
slip method at 415 V: load fraction 0.514
slip method at 400 V: load fraction 0.478
Rough current model (no-load current 35 % of full-load current)
load 0 %: current 14.0 A = 35 % of full-load current
load 25 %: current 16.8 A = 42 % of full-load current
load 50 %: current 23.4 A = 58 % of full-load current
load 75 %: current 31.4 A = 78 % of full-load current
load 100 %: current 40.0 A = 100 % of full-load current
at the measured load of 51 %: model 23.8 A, typical-value calculation 25.0 A
Simplified curve: slip at breakdown 11.2 %, speed 1332 rev/min
Saved induction_motor_slip_load.png

The torque-speed curve in the plot comes from a standard simplified formula that neglects the stator resistance, fixed by two values: the rated point and a breakdown torque of 2.5 times the rated torque, which is a typical assumption and not a nameplate figure. It shows the working region well and gives a starting torque that is too low, because the bars of a real cage rotor are shaped to raise the torque at standstill.

Common Mistakes



  • Reading the kW on the nameplate as the electrical input. It is the shaft output. The input is the output divided by the efficiency.
  • Calculating torque with the synchronous speed. The shaft turns at the rotor speed, 1465 rev/min here, not 1500 rev/min.
  • Estimating load as measured current divided by nameplate current. Below half load the magnetising current makes this far too high: a motor with nothing on its shaft still draws about a third of its full-load current.
  • Using the slip method with a speed reading that is only good to 5 or 10 rev/min. The whole range from no load to full load is 35 rev/min for this motor.
  • Choosing a motor “one size larger to be safe”. The extra size is paid for in reactive power for the whole life of the motor.

Summary



  • The stator makes a field that rotates at the synchronous speed , which is 1500 rev/min for 4 poles at 50 Hz. The rotor must turn slower than the field, and the slip is the difference as a fraction of .
  • The compressor motor has a slip of 2.33 percent, a rated torque of 143.4 N·m, an input power of 24.2 kW and losses of 2.18 kW at full load.
  • In the working region the torque is nearly proportional to the slip. The load fraction is therefore about . The method is rough: it depends on a rounded nameplate speed and on the square of the voltage.
  • At 1482 rev/min the motor carries about 51 percent of its load, 11.3 kW at the shaft. With typical part-load values it takes 12.57 kW, 12.83 kvar and 25.0 A.
  • The magnetising current is nearly constant, so the power factor falls at part load and the current is a poor guide to load below half load.
  • Efficiency classes IE1 to IE4 rank motors by their efficiency at rated load.

Exercises



1. A borehole pump motor is rated 7.5 kW at 2900 rev/min on a 50 Hz supply. Find the number of poles, the slip and the rated shaft torque.

Answer

The synchronous speed just above 2900 rev/min is 3000 rev/min, so the motor has 2 poles. percent. and .

2. A 4-pole motor on a 60 Hz supply has a nameplate speed of 1760 rev/min. It is measured at 1775 rev/min at rated voltage. Estimate its load fraction.

Answer

. Load fraction: , about 63 percent.

3. The 22 kW compressor motor (1465 rev/min at 415 V) is measured at 1490 rev/min with 400 V at its terminals. Estimate its load fraction and shaft power without and with the voltage correction.

Answer

Without correction: , which is 6.29 kW. With correction: , which is 5.84 kW. At such a low load the estimate is very sensitive to the speed reading: 1 rev/min is 3 percent of full load.

4. The same 22 kW motor runs at 30 percent of its rated load. Typical values at this load are an efficiency of 0.86 and a power factor of 0.55. Find the input power, the apparent power, the line current at 415 V and the reactive power. State the current as a share of the full-load current of 40.0 A.

Answer

Shaft power: . . . . . The current is 49 percent of the full-load current while the load is 30 percent.

References



  • S. J. Chapman, Electric Machinery Fundamentals, 5th edition, McGraw-Hill, 2012.
  • A. Hughes and B. Drury, Electric Motors and Drives: Fundamentals, Types and Applications, 5th edition, Newnes, 2019.
  • IEC 60034-1, Rotating electrical machines, Part 1: Rating and performance, International Electrotechnical Commission.
  • IEC 60034-30-1, Rotating electrical machines, Part 30-1: Efficiency classes of line operated AC motors (IE code), International Electrotechnical Commission.


© 2021-2026 SiliconWit®. All rights reserved.
Predict first

A 22 kW motor has 40.0 A on its nameplate. The coupling is removed and the motor runs with nothing on its shaft. About what current does it draw?

See it: the load chooses the speed

Speed
Slip
Shaft power
Current (typical)
Power factor (typical)
Shaft torque
Three answers to "how loaded is this motor?"
The real load
The slip method says
Current alone says

The curve is the simplified formula that the lesson's script uses, fixed by the rated point and a breakdown torque of 2.5 times the rated torque. It is a typical shape, not data for this motor, and its starting torque is lower than that of a real cage motor. The load is drawn as a level line: a torque that does not change with speed. The motor runs where the line crosses the steep side of the curve. The current comes from the lesson's rough model with a no-load current of 14.0 A, and the power factor from the lesson's typical values at no load, quarter, half, three quarter and full load, held at 0.84 above full load. Both are typical, not measured. The slip method treats the working region as a straight line. This curve bends a little, so at 1482 rev/min the load on the curve is 53 percent and the slip method says 51 percent. "Current alone" is the measured current divided by the 40.0 A of the nameplate.

supply stator air gap rotor shaft 24.2 kW input winding and core field cage 22 kW output 415 V, 40.0 A stator copper and iron loss rotor copper loss, friction, fan Total losses 2.2 kW, all of it heat.
Power through the motor at full load
100 % 200 % 0 torque, % of rated speed starting torque 55 % breakdown torque 250 % rated torque, 143.4 N·m working region (nearly a straight line) 0 500 1000 1465 1500 rev/min s = 1 s = 0 Example curve: breakdown assumed 2.5 times rated; T / T rated = 5 / (s / 0.112 + 0.112 / s).
Torque against speed for a cage motor (example curve). The simple formula understates the start: real cage motors start at 1.5 to 2.5 times rated torque.
3~ MOTOR IEC 60034-1 22 kW S1 50 Hz Δ 415 V 40.0 A cos φ 0.84 1465 r/min η 91.0 % 4 pole Ins. cl. F IP55 40 °C
The nameplate of the compressor motor

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. A 4-pole, 50 Hz motor has 1465 rev/min on its nameplate. It is measured at 1490 rev/min at rated voltage. About what share of its rated load does it carry?

2. The compressor motor (40.0 A on the nameplate, no-load current about 14 A) draws 16.8 A. A technician reports "42 percent loaded". What is the load, by the lesson's rough model?

3. The same motor falls from full load to about half load. With the lesson's typical values, what happens to its real power and its reactive power?

field: 1500 rev/minrotor: 1465 rev/min slip 2.3 % no slip, no torque
Watch it build: what the clamp reading hides
clamp 40.0 A 40.0 Afull load field 14.0 A work part 37.5 A 14.0 Ano load work 9.4 A 16.8 Aat 25% load +2.8 Afor 0 to 25% loadreading 100%100% 0%35% 25%42%
  1. At full load the clamp reads 40.0 A. Is the load simply the reading divided by 40.0 A?
  2. The current has two parts 90° apart: 37.5 A that does the work, 14.0 A that builds the field.
  3. With nothing on the shaft, the field part stays: the clamp reads 14.0 A, 35%, at 0% load.
  4. At 25% load the work part is 9.4 A. The two add as arrows: 16.8 A, 42%.
  5. From no load to 25% load the reading rises by only 2.8 A. Below half load it says little.