Skip to content
You Start with one site
Amounts in Start with one site
Electrical Power · Concept

Three phase power

One idea Intermediate 5 min read
Found this useful?

On a bicycle your push on the pedals falls to almost nothing twice in every turn. Put three riders on one machine, with their pedals one third of a turn apart, and the total push never falls. Three phase power is the same arrangement for electricity: three alternating voltages of equal size, each one third of a cycle after the one before, that together deliver steady power.

A heavy flywheel?It smooths the motion and does not remove the pulsing push.Helps a small motor
A higher frequency?The power still falls to zero, only more often.Still pulsing
Three supplies in turn?When one is at zero, the other two are working.This is three phase

See it

Predict first

A heater element on one phase takes a power that pulses between 0 and 16 kW, 100 times a second. Two more equal elements are added, one on each of the other two phases. What does the total power of the three do?

See it: three phases through one cycle

Phase a at this instant
Total at this instant
Total through the cycle

Above: the three voltages on a 240 V, 50 Hz supply. Below: the power of an equal heater element on each phase, and the thick line that is their total. Each element pulses between 0 and 16 kW. With all three switched on, the total is a level line.

The idea

A three phase supply has three live conductors, called phases a, b and c. Each carries a sine wave voltage of the same size. Phase b reaches its peak one third of a cycle after phase a, and phase c one third of a cycle after b.

The power of one phase pulses: it falls to zero twice in every cycle. With equal loads on the three phases, each pulsing power fills the gaps of the others, and the total does not change with time. That is why a three phase motor gives a steady turning force.

The supply gives two voltages. The phase voltage is from one phase to the neutral conductor. The line voltage is between two phases.

Vline = √3 × Vphase

√3 is about 1.732. Both are RMS values: 240 V to neutral gives 415 V between phases.

The total is steady only when the three loads are equal.

One worked number

The question

Three equal heater elements are connected one to each phase. The power of each pulses between 0 and 16 kW. When phase a is at its peak, b and c are each at one quarter of their peak power. When a is at zero, b and c are each at three quarters. What is the total at each of these two instants?

Show the worked solution, 3 steps
  1. Phase a at its peak

    a gives 16 kW. b and c each give 16 ÷ 4 = 4 kW. Total = 16 + 4 + 4 = 24 kW.

  2. Phase a at zero

    a gives 0 kW. b and c each give 16 × 3 ÷ 4 = 12 kW. Total = 0 + 12 + 12 = 24 kW.

  3. Check it in the figure

    The figure opens with phase a at its peak. Move the slider to 10.0 ms, where phase a is at zero. The total reads 24.0 kW at every position.

The mistake to avoid

Two phases of 240 V do not give 480 V between them. Sizes add directly only for voltages that rise and fall together. Two phases are one third of a cycle apart, so they never reach their peaks at the same instant, and a meter between them reads 1.732 × 240 V = 415 V.

A second trap: the neutral carries no current only when the three loads are equal. Circuits that take 30 A, 20 A and 10 A on the three phases put 17.3 A in the neutral.

Check yourself

Question 1

A country has a supply of 230 V from each phase to neutral. What does a meter read between two phases?

Question 2

One of the three equal heater elements in the worked number fails and takes no power. The other two still work. What is the total power now?

Question 3

A technician measures 240 V from phase a to neutral and 240 V from phase b to neutral, then reads 415 V between a and b and suspects a fault. What should you tell the technician?

Where you meet it

  • Factory and pump motorsA compressor or borehole pump motor uses the three phases and no neutral.
  • Distribution boardsEach lighting or socket circuit uses one phase and the neutral, and the circuits are shared among the three phases.
  • NameplatesA motor marked 415 V or 400 V states the line voltage.
Key points
  • Three equal voltages, each one third of a cycle after the one before.
  • One phase delivers pulsing power. Three equal loads together take steady power.
  • Line voltage = 1.732 × phase voltage: 415 V from 240 V, or 400 V from 230 V.
  • Unequal loads put current in the neutral.
Practice

Found this useful?

Discussion

    Comments show your name. Be kind, stay on the topic.