Electrical Power · Concept

RMS

One idea Beginner 5 min read
Found this useful?

Rub your hands together. They move forward and back, so their average movement is zero, and still they become warm. An alternating voltage does the same to a heater: it reverses again and again, its average is zero, and the heater becomes hot. The RMS value (root mean square) of an alternating voltage is the steady voltage that would produce the same heat.

The average?Over a full cycle the average of the wave is zero.Of no use
The peak?339 V lasts for an instant. Most of the time the voltage is lower.Too high
The heating value?The steady voltage that makes a heater equally hot.This is RMS

See it

Predict first

One heater is connected to a steady 240 V from a battery bank. An equal heater is connected to a 240 V alternating supply, which swings between +339 V and −339 V. Which heater becomes hotter?

See it: a wave and the heat it makes

Peak voltage
RMS voltage
Mean heating power

The upper line is the voltage across a 28.8 Ω heater. The lower line is the heating power at each instant: it is never negative, because both halves of the wave heat. Its mean is the power that a steady voltage equal to the RMS value would give. Change the shape and the same peak gives a different RMS value.

The idea

The heating power in a resistance depends on the square of the voltage, and a square is never negative. So the negative half of the wave heats as much as the positive half.

Read the name from the inside to the outside. Take the square of the voltage at every instant, take the mean of the squares over one cycle, then take the root. The result is the steady voltage that puts the same mean power into the same resistance. For a sine wave the three steps give one short rule.

Vrms = Vpeak ÷ √2

for a sine wave only: √2 is about 1.414, so the peak is 1.414 times the RMS value

Meters, nameplates and tariffs give RMS values unless they say otherwise. The idea is the same for current: a cable is heated by the RMS current that it carries.

One worked number

The question

A heater with a resistance of 28.8 Ω is on a sine wave supply that peaks at 339 V. What is the RMS voltage, and what power does the heater take?

Show the worked solution, 3 steps
  1. Divide the peak by √2

    Vrms = 339 V ÷ 1.414 = 240 V.

  2. Use the RMS value as if it were a steady voltage

    Power = V² ÷ R = 240 × 240 ÷ 28.8 = 2,000 W, which is 2.00 kW. A steady 240 V gives exactly the same.

  3. Check it in the figure

    The figure opens on this case: peak 339 V, RMS 240 V, mean power 2.00 kW. Now press the square wave button. The peak is the same and the power doubles.

The mistake to avoid

The peak is not always 1.414 times the RMS value. That factor belongs to the sine wave. A square wave has an RMS value equal to its peak, and the current of an LED lamp driver can have a peak of three times its RMS value. For any other shape, return to the three steps: square, mean, root. A low-cost meter that is not marked True RMS assumes a sine wave, and on a distorted current it can read more than 10% low.

A second trap: a part must withstand the peak, not the RMS value. A capacitor rated for 250 V fails on a 240 V supply, because the supply reaches 339 V.

Check yourself

Question 1

A country has a 230 V sine wave supply. What peak voltage must the insulation of an appliance withstand?

Question 2

A square wave switches between +12 V and −12 V and spends equal time at each. What is its RMS value?

Question 3

A clamp meter that is not marked True RMS shows 9.0 A on a cable that feeds LED lighting. The cable is warmer than 9.0 A can explain. What is the most likely reason?

Where you meet it

  • Meters and nameplatesThe 240 V of a supply and the 40 A on a compressor motor nameplate are RMS values.
  • Cable sizesA cable is heated by the RMS current, so that is the value used to choose its size.
  • Insulation and capacitorsThese must withstand the peak, which is 339 V on a 240 V supply.
  • Drives and LED lightingTheir current is not a sine wave, so only a true RMS meter reads it correctly.
Key points
  • The RMS value is the steady voltage or current that gives the same heating.
  • Square, mean, root: this definition is true for a wave of any shape.
  • For a sine wave, RMS = peak ÷ 1.414. A 240 V supply peaks at 339 V.
  • Heating follows the RMS value. Insulation must withstand the peak.
Practice

Found this useful?

Discussion

    Comments show your name. Be kind, stay on the topic.