Electrical Power · Concept

Power factor

One idea Intermediate 5 min read
Found this useful?

Pull a loaded cart with a rope that is at an angle to the road. Only the part of your pull that points along the road moves the cart, and the rope still carries your whole pull. A motor does the same with current: part of it does work, and the cable carries all of it. The power factor is the share of the supplied power that does work, a number between 0 and 1.

The meter is wrong?It is correct. It counts the power that does work, in kW.Not the reason
Energy is lost?Very little. The extra current carries energy out and back.Not the reason
More current flows?Motors need current for their magnetic field as well as for work.This is power factor

See it

Predict first

A site takes 72 kW at a power factor of 0.80. Capacitors are fitted and the power factor becomes 1.00. The machines do the same work and the meter still shows 72 kW. What happens to the current in the main cable?

See it: the same work at a different power factor

Apparent power S
Reactive power Q
Current in each line

The base of the triangle is the real power, and it does not change: the site does the same work at every setting. A lower power factor makes the triangle taller, so the sloping side, which the cable and the transformer must carry, becomes longer. The site is on a 415 V three phase supply.

The idea

An alternating supply carries three kinds of power. Real power P, in kW, becomes work, heat or light. Reactive power Q, in kvar, is energy that enters the magnetic field of a motor and returns to the supply in every cycle. It does no work, and a motor cannot run without it. Apparent power S, in kVA, is the voltage multiplied by the current: the total that the cable carries.

The three are the sides of a right-angled triangle, so S is never smaller than P.

power factor = P ÷ S

P in kW, S in kVA. The current in the cable follows S, so for the same work it is 1 ÷ power factor times larger.

A heater has a power factor of 1. A motor at full load has about 0.85, and less when its load is light, because its field needs almost the same kvar while it does less work.

The triangle is true for sine waves. A drive or an LED lamp driver distorts the current, and the power factor is then lower than the triangle says.

One worked number

The question

A site takes 72 kW at a power factor of 0.80. What apparent power must its cable carry? How much more current and how much more cable heat is that than at a power factor of 1.00?

Show the worked solution, 3 steps
  1. Find the apparent power

    S = P ÷ power factor = 72 kW ÷ 0.80 = 90 kVA.

  2. Compare the currents

    At 1.00 the cable would carry 72 kVA. The current follows the kVA: 90 ÷ 72 = 1.25, so the current is 25% more.

  3. Compare the heat

    Heat in a cable follows the square of the current: 1.25 × 1.25 = 1.56 times. Check it in the figure: at 0.80 it shows 125 A, and at 1.00 it shows 100 A.

The mistake to avoid

A power factor of 0.80 does not mean that 20% of the energy is wasted. The machines receive all 72 kW, and the kWh meter does not count reactive power. The cost is the extra current: hotter cables, a transformer that is full sooner, and on many tariffs a surcharge. Capacitors can supply the reactive power locally, which is the subject of power factor correction.

Check yourself

Question 1

A compressor motor takes 24.2 kW from the supply at a power factor of 0.84. What apparent power does it place on its cable?

Question 2

The bill of a factory shows an average power factor of 0.78 and a surcharge. The owner says: 22% of my electricity is being lost in my machines. Is that correct?

Question 3

A transformer is rated 200 kVA. The loads on it have a power factor of 0.80. How much real power can it supply when it is full?

Where you meet it

  • The electricity billMany industrial tariffs charge for kVA, or add a surcharge when the average power factor of the month is low.
  • Capacitor banksCapacitors at the main board supply reactive power locally, so less current flows from the supplier.
  • Transformers and generatorsThey are rated in kVA, because the current heats their windings whatever it is used for.
  • Lightly loaded motorsA large motor that drives a small load has a low power factor.
Key points
  • Power factor = real power (kW) ÷ apparent power (kVA).
  • The meter counts kW. The cable and the transformer carry kVA.
  • For the same work, the current is 1 ÷ power factor times larger.
  • Reactive power is not wasted energy. Its cost is the current that carries it.