Skip to content
You Start with one site
Amounts in Start with one site
Control, Measurement & Energy · Course

Refrigerants and the Pressure-Enthalpy Diagram

Lesson 2 of 10 26 min read
Found this useful?

A suction gauge on a cold room reads 1.5 bar. One person says the evaporator is at −6 °C and the system is healthy. Another reads the temperature scale printed on the same gauge, gets −4 °C, and decides something is wrong. They disagree by 2 K because the site is 1,600 m above sea level and the printed scale assumes the coast. An error of that size can hide a real fault or invent one that does not exist. This lesson shows how pressure and boiling temperature are tied together for a refrigerant, how to read a gauge correctly at any altitude, and how one diagram holds every state the refrigerant passes through. #Refrigerants #PressureEnthalpy #R134a

Learning Objectives

By the end of this lesson, you will be able to:

  1. Find the saturation pressure of a refrigerant at a given temperature, and the saturation temperature at a given pressure
  2. Convert between gauge and absolute pressure for the atmospheric pressure of a site
  3. Identify a state as subcooled liquid, saturated mixture or superheated vapour from its pressure and temperature
  4. Calculate the enthalpy of a mixture from its quality, and work with enthalpy differences
  5. Locate a state on the pressure-enthalpy diagram and name the lines that pass through it

Real-World System Problem: Reading a circuit you cannot see into



The refrigerant of a cold room is sealed inside copper pipe. Nobody can see whether it is liquid or vapour at a point, or how much heat each kilogram carries. From outside you can measure only a pressure on the low side, a pressure on the high side, and the pipe surface temperature at a few points.

That is enough, because a refrigerant’s properties are tied together. A pressure fixes a boiling temperature. A pressure and a temperature together fix whether it is liquid or vapour and how much energy it carries. The pressure-enthalpy diagram is the map of those ties.

The cold room of this course uses R134a, which boils in the evaporator at −6 °C and condenses in the condenser at 42 °C at the design point. This lesson finds the two pressures that go with those temperatures and places four states of the circuit on the map.

Condenser42 °Cgaugep_egaugep_cExpansionvalveCompressorhigh sidelow sideEvaporator−6 °C
What can be measured on the circuit from outside

Fundamental Theory: Saturation, the three regions and the diagram



One pressure for each boiling temperature

Water boils at 100 °C at sea level (101.3 kPa), at 94.6 °C in a town 1,600 m up (83.5 kPa), and at 120.2 °C in a pressure cooker (200 kPa). The boiling temperature of a pure liquid is set by the pressure on it, and by nothing else.

The pressure at which a liquid boils at a given temperature is its saturation pressure; the temperature at which it boils at a given pressure is its saturation temperature. They are one pair: know one, and you know the other.

R134a boils at −26.1 °C at 101.3 kPa. To make it boil at −6 °C, hold it at 2.343 bar; to make it condense at 42 °C, hold it at 10.722 bar. The compressor and the expansion valve keep those two pressures in the two halves of the circuit.

Saturation temperature (°C)−20−60420304250
R134a saturation pressure (bar absolute)1.3272.3432.9283.3775.7177.70210.72213.179

Three regions

At one pressure, a refrigerant is in one of three conditions. Compare its temperature with the saturation temperature at that pressure.

  • Subcooled liquid: is below . All of it is liquid. The difference is the subcooling.
  • Saturated mixture: equals . Liquid and vapour are present together, and the refrigerant is boiling or condensing.
  • Superheated vapour: is above . All of it is vapour. The difference is the superheat.

In the subcooled and superheated regions, pressure and temperature are independent, and together they fix the state. Inside the mixture they are tied: at 2.343 bar the temperature is −6 °C whether the refrigerant is nearly all liquid or nearly all vapour, as a pot of boiling water stays at 100 °C until the last drop. A third quantity must say how much has boiled.

Quality

The quality is the fraction of the mass that is vapour: for saturated liquid about to boil, for saturated vapour that has just finished. Quality has no meaning outside the mixture.

Enthalpy

The specific enthalpy , in kJ/kg, is the energy that each kilogram of a flowing fluid carries past a point. When refrigerant flows steadily through a component, the first law for that component is

where is the heat flow into the refrigerant in kW and is the mass flow in kg/s.

At one saturation temperature, is the enthalpy of saturated liquid and that of saturated vapour. Their difference, the enthalpy of evaporation , is the latent heat at that temperature.

Enthalpy of a saturated mixture

is the quality, between 0 and 1. All values are taken at the same saturation temperature.

The reference state

A value of enthalpy is counted from a zero that somebody chose, as a height is counted from the floor or from sea level. CoolProp’s default for R134a gives saturated liquid at 0 °C the value 200.00 kJ/kg; many printed tables give saturated liquid at −40 °C the value zero. The two sets differ by a constant, 148.14 kJ/kg for R134a.

At −6 °C, CoolProp gives and kJ/kg, and a table with the other zero gives 43.84 and 246.92 kJ/kg. Neither is wrong: the difference is 203.08 kJ/kg in both, and every calculation in refrigeration uses differences.

The pressure-enthalpy diagram

Plot absolute pressure upward and specific enthalpy across. Join all the saturated liquid states into one line and all the saturated vapour states into another. The two lines meet at the top, at the critical point, and form a dome.

p (log scale)critical point●SUBCOOLEDSUPERHEATEDLIQUIDVAPOURA ●MIXTUREliquid + vapourB ●C●●Dhsaturated liquidsaturated vapourline, x = 0line, x = 1
Regions and lines of the pressure-enthalpy diagram
  • Left of the dome: subcooled liquid. Right of it: superheated vapour. Under it: a mixture.
  • A horizontal line is constant pressure, and under the dome also constant temperature, because boiling at one pressure happens at one temperature. Evaporators and condensers work along horizontal lines, if the small pressure loss in their tubes is ignored.
  • The width of the dome at one pressure is , and quality divides it evenly: a point 30 percent of the way across has .
  • A vertical line is constant enthalpy. An expansion valve works along one, because no heat and no work cross it.
  • An isotherm (a line of constant temperature) is nearly vertical in the liquid, horizontal under the dome, and falls steeply in the vapour. In the liquid, enthalpy depends almost only on temperature.

The pressure axis is logarithmic: the low side is near 2 bar, the high side near 11 bar, and the dome reaches 40.6 bar at the critical point of R134a (101.1 °C). On a linear axis the evaporator would be pressed against the bottom of the page. Above the critical temperature no pressure can make the vapour condense.

Gauge pressure and absolute pressure

The pressures in property data are absolute, counted from a perfect vacuum. A service gauge measures how far the refrigerant is above the atmosphere round the gauge, and reads zero when open to the air.

Gauge and absolute pressure

is the atmospheric pressure where the gauge is: 101.3 kPa at sea level, 83.5 kPa at about 1,600 m. One bar is 100 kPa.

The boiling temperature follows the absolute pressure, so the same refrigerant state gives a higher gauge reading at altitude, where the atmosphere takes less away.

absolute pressure (kPa)234.3R134a boiling at −6 °Cgauge readsgauge reads133.0 kPa150.8 kPa101.3sea level83.5site at 1,600 m0.0perfect vacuum
One refrigerant state, two gauge readings

Many refrigeration gauges carry a temperature scale for each refrigerant, printed for sea level. At altitude it reads too warm, most of all on the low side, where the atmosphere is a large part of the absolute pressure.

Why refrigerants differ

Any liquid that boils and condenses could carry heat. The useful ones boil at the evaporator temperature a little above atmospheric pressure, so that a leak pushes refrigerant out and does not pull air and moisture in, and condense at the condenser temperature at a pressure ordinary pipe and compressors can hold. CoolProp values at the cold room’s two temperatures:

Refrigerant at −6 °C (bar abs) at 42 °C (bar abs)Ratio at −6 °C (kJ/kg)Note
R134a2.3410.724.58203Not flammable
R1234yf2.5610.714.18167Mildly flammable
R290 (propane)3.9314.343.65383Highly flammable
R600a (isobutane)1.265.604.43360Highly flammable
R717 (ammonia)3.4116.434.821,283Toxic
R404A (blend)4.9319.043.86171Not flammable, very high GWP
R326.6826.013.90324Mildly flammable
R744 (carbon dioxide)29.63nonenone248Not flammable, very high pressure

The last three rows use the same CoolProp calls (R404A as one pseudo-pure fluid). Each refrigerant has its own pressures, so a gauge reading means nothing until you know the refrigerant: read the label on the condensing unit before you read the gauge. Ammonia carries six times as much heat per kilogram as R134a, but its vapour is much less dense and a compressor moves volume, not mass, so the gain in compressor size is far smaller than six. No refrigerant is best on pressure, heat carried, safety, cost and environmental effect together.

R744 cannot condense at 42 °C: its critical temperature is 31.0 °C. On a hot day a carbon dioxide system cools a dense gas in a “gas cooler” at around 90 bar instead, and even standing still at 30 °C it holds 72 bar.

Blends and glide

Many cold rooms run on blends: R404A, R407C, R448A, R449A. A blend boils over a range of temperature at one pressure, because the parts that boil most easily leave the liquid first. The temperature where the first bubble forms is the bubble point; the temperature where the last drop of liquid has boiled is the dew point. The difference is the glide. CoolProp’s mixture model gives, at the pressures of the cold room’s duty:

  • R404A: glide 0.5 K on the low side. It behaves almost like a pure refrigerant.
  • R449A: dew point −6.0 °C and bubble point −11.4 °C at 4.17 bar, a glide of 5.4 K; on the high side about 4.3 K.

So for a blend with a large glide, take superheat from the dew point and subcooling from the bubble point. Gauge scales and apps for these blends show both; the wrong one moves the answer by the whole glide. The rest of this lesson uses R134a, a pure refrigerant.

Refrigerants and the environment

Two measures describe the harm a refrigerant does when it escapes to the air.

The ozone depletion potential (ODP) compares the damage one kilogram does to the ozone layer with the damage done by one kilogram of the old refrigerant R11. Refrigerants that contain chlorine, such as R12 and R22, have an ODP above zero, and an international agreement, the Montreal Protocol, is removing them from use. R134a contains no chlorine and its ODP is zero.

The global warming potential (GWP) compares the heat trapped in the atmosphere by one kilogram of the gas, over a stated period that is usually 100 years, with the heat trapped by one kilogram of carbon dioxide. R134a has a GWP of about 1,430 on the 100-year basis used in the IPCC Fourth Assessment Report. Other assessment reports give somewhat different figures, so always state the basis. One kilogram of R134a that leaks warms the climate about as much as 1.4 tonnes of carbon dioxide.

The Kigali Amendment to the Montreal Protocol commits countries to reduce refrigerants with a high GWP, and national limits and dates differ and grow stricter: check the rules where you work before you specify a refrigerant. This course uses R134a because it is widely installed and typical, not because it is the right choice for a new system.

Application 1: Saturation pressures and gauge readings



Step 1: Absolute pressures

Click to reveal the absolute pressures
  1. Evaporating pressure. bar absolute. ✅

  2. Condensing pressure. bar absolute. ✅

  3. Pressure ratio. A ratio must use absolute pressures.

    The compressor raises the absolute pressure 4.58 times. ✅

Step 2: Gauge readings

Click to reveal the gauge readings
  1. Low side at the site.

    The suction gauge reads 1.508 bar. ✅

  2. Low side at sea level.

    The same state reads 1.330 bar at the coast. ✅

  3. High side. At the site, kPa, which is 9.887 bar. At sea level, kPa, which is 9.709 bar. ✅

  4. Difference. On both sides the site reading is higher by kPa, which is 0.178 bar. That is about 12 percent of the low-side reading and less than 2 percent of the high-side reading. ✅

Step 3: The error of a sea-level scale

Click to reveal the temperature error
  1. What the printed scale assumes. It adds 101.3 kPa to the reading. For the site’s reading of 150.8 kPa it assumes

    This is 17.8 kPa above the true absolute pressure. ✅

  2. Temperature shown. The saturation temperature of R134a at 252.1 kPa is −4.1 °C. The printed scale shows −4.1 °C when the evaporator is really at −6.0 °C, an error of 1.9 K. ✅

  3. High side. By the same method the high-side scale shows 42.6 °C in place of 42.0 °C, an error of 0.6 K. ✅

  4. Check a second way. Near −6 °C the table in the theory section gives a slope of bar per kelvin. An excess of 0.178 bar is then K, which agrees with the 1.9 K from CoolProp. The script prints the same pressures and errors. ✅

Application 2: Enthalpy of evaporation and four states



Step 1: Enthalpy of evaporation

Click to reveal the enthalpy of evaporation
  1. Subtract.

    The subtraction of the rounded values gives 203.07. CoolProp’s unrounded values give 203.08, and that figure is used below. ✅

  2. Meaning. Each kilogram of R134a that boils completely at −6 °C absorbs 203.08 kJ. ✅

Step 2: Name each state

Click to reveal the four regions
  1. State A. At 10.722 bar the saturation temperature is 42 °C. The refrigerant is at 38 °C, which is lower, so it is subcooled liquid with a subcooling of K. ✅

  2. State B. It is given as a mixture, so its temperature is the saturation temperature at 2.343 bar, which is −6 °C. Its quality is 0.30. ✅

  3. State C. Saturated vapour at 2.343 bar is at −6 °C, with . ✅

  4. State D. At 2.343 bar the saturation temperature is −6 °C. The refrigerant is at 0 °C, which is higher, so it is superheated vapour with a superheat of K. ✅

Step 3: Enthalpy of each state

Click to reveal the enthalpies
  1. State B, from the quality.

    The mixture carries 252.91 kJ/kg. ✅

  2. State C. kJ/kg. ✅

  3. States A and D. These are single-phase states, so pressure and temperature fix them, and the values come from the property data: kJ/kg and kJ/kg. ✅

  4. Check A a second way. The enthalpy of a liquid depends almost only on its temperature. Saturated liquid at 38 °C has kJ/kg, against 253.42 kJ/kg for the subcooled liquid at 38 °C and 10.722 bar. The difference is 0.01 kJ/kg. ✅

Step 4: Place the states on the diagram

StateRegion (°C) (bar abs) (kJ/kg)Position on the diagram
ASubcooled liquid38.010.722253.42On the upper pressure line, just left of the dome
BMixture, −6.02.343252.91On the lower pressure line, 30 percent of the way across the dome
CSaturated vapour−6.02.343395.06On the lower pressure line, on the right edge of the dome
DSuperheated vapour0.02.343400.27On the lower pressure line, just right of the dome
Click to reveal what the positions show
  1. A and B. They have almost the same enthalpy, 253.42 and 252.91 kJ/kg, at very different pressures. B is almost directly below A on the diagram. ✅

  2. Quality directly below A. A point at 2.343 bar with exactly the enthalpy of A has

    Liquid at A that falls to the low pressure with no change of enthalpy becomes a mixture that is already 30.2 percent vapour. ✅

  3. Differences. From B to C the refrigerant gains kJ/kg. From A to D it gains kJ/kg. These differences are the same in any table, whatever its reference state. ✅

  4. Check with the script. The script prints the same four enthalpies, the quality 0.302 and the two differences, and it draws the diagram with A, B, C and D marked. ✅

Verify It in Python



The script calculates both applications with CoolProp, prints the reference-state comparison and the table of other refrigerants, and draws the pressure-enthalpy diagram of R134a: the saturation dome, five isotherms and the four states, with a logarithmic pressure axis. It needs numpy, matplotlib and CoolProp.

r134a_ph_diagram.py
"""R134a: saturation pressures, gauge readings, four states and the p-h diagram."""
import numpy as np
import matplotlib.pyplot as plt
from CoolProp.CoolProp import PropsSI
FLUID = "R134a"
T_E, T_C = -6.0, 42.0 # degC, evaporating and condensing
P_SITE, P_SEA = 83.5, 101.3 # kPa, atmospheric pressure
def kelvin(t_c):
return t_c + 273.15
def p_sat(t_c):
"""Saturation pressure in kPa absolute at a temperature in degC."""
return PropsSI("P", "T", kelvin(t_c), "Q", 0, FLUID) / 1000.0
def t_sat(p_kpa):
"""Saturation temperature in degC at a pressure in kPa absolute."""
return PropsSI("T", "P", p_kpa * 1000.0, "Q", 0, FLUID) - 273.15
def h_sat(t_c, quality):
"""Enthalpy in kJ/kg on the saturation line (quality 0 or 1) or inside."""
return PropsSI("H", "T", kelvin(t_c), "Q", quality, FLUID) / 1000.0
def h_tp(t_c, p_kpa):
"""Enthalpy in kJ/kg of a single-phase state."""
return PropsSI("H", "T", kelvin(t_c), "P", p_kpa * 1000.0, FLUID) / 1000.0
# ---------- Application 1: saturation and gauge pressures ----------
p_e, p_c = p_sat(T_E), p_sat(T_C)
print("Application 1: saturation pressures of R134a")
for name, t, p in (("evaporating", T_E, p_e), ("condensing", T_C, p_c)):
print(f" {name} {t:.0f} degC: {p:.1f} kPa = {p / 100.0:.3f} bar absolute")
print(f" gauge at the site: {(p - P_SITE) / 100.0:.3f} bar, "
f"gauge at sea level: {(p - P_SEA) / 100.0:.3f} bar")
print(f" pressure ratio p_c / p_e: {p_c / p_e:.2f}")
print(f" difference between the two gauge readings: "
f"{(P_SEA - P_SITE) / 100.0:.3f} bar")
for name, t, p in (("low side", T_E, p_e), ("high side", T_C, p_c)):
wrong = t_sat(p - P_SITE + P_SEA)
print(f" {name}: site gauge read on a sea-level scale gives {wrong:.1f} degC "
f"(error {wrong - t:.1f} K)")
print(f" boiling point at 101.3 kPa: {t_sat(P_SEA):.1f} degC, "
f"at 83.5 kPa: {t_sat(P_SITE):.1f} degC")
# ---------- Application 2: enthalpy of evaporation and four states ----------
h_f, h_g = h_sat(T_E, 0), h_sat(T_E, 1)
h_fg = h_g - h_f
print("Application 2: enthalpy at -6 degC")
print(f" h_f = {h_f:.2f}, h_g = {h_g:.2f}, h_fg = {h_fg:.2f} kJ/kg")
X_B = 0.30
states = {
"A": ("subcooled liquid", 38.0, p_c, h_tp(38.0, p_c)),
"B": (f"mixture, x = {X_B:.2f}", T_E, p_e, h_sat(T_E, X_B)),
"C": ("saturated vapour", T_E, p_e, h_g),
"D": ("superheated vapour", 0.0, p_e, h_tp(0.0, p_e)),
}
for key, (kind, t, p, h) in states.items():
print(f" {key}: {kind:<20} T = {t:5.1f} degC, "
f"p = {p / 100.0:6.3f} bar, h = {h:6.2f} kJ/kg")
print(f" B by hand: {h_f:.2f} + {X_B:.2f} x {h_fg:.2f} = {h_f + X_B * h_fg:.2f} kJ/kg")
print(f" A by the saturated-liquid estimate at 38 degC: {h_sat(38.0, 0):.2f} kJ/kg")
h_a, h_d = states["A"][3], states["D"][3]
print(f" quality at -6 degC with the enthalpy of A: {(h_a - h_f) / h_fg:.3f}")
print(f" h_C - h_B = {h_g - states['B'][3]:.2f}, h_D - h_C = {h_d - h_g:.2f}, "
f"h_D - h_A = {h_d - h_a:.2f} kJ/kg")
# ---------- Reference state: values move, differences do not ----------
shift = h_sat(-40.0, 0) # a table that sets h_f = 0 at -40 degC
print("Reference state")
print(f" CoolProp default: h_f = {h_sat(0.0, 0):.2f} kJ/kg at 0 degC")
print(f" table with h_f = 0 at -40 degC: every value lower by {shift:.2f} kJ/kg")
print(f" at -6 degC that table gives h_f = {h_f - shift:.2f}, "
f"h_g = {h_g - shift:.2f}, h_fg = {(h_g - shift) - (h_f - shift):.2f} kJ/kg")
# ---------- Other refrigerants at the same two temperatures ----------
print("Other refrigerants at -6 and 42 degC (bar absolute, kJ/kg)")
for name in ("R134a", "R1234yf", "R290", "R600a", "R717"):
pe = PropsSI("P", "T", kelvin(T_E), "Q", 1, name) / 1e5
pc = PropsSI("P", "T", kelvin(T_C), "Q", 1, name) / 1e5
hfg = (PropsSI("H", "T", kelvin(T_E), "Q", 1, name)
- PropsSI("H", "T", kelvin(T_E), "Q", 0, name)) / 1000.0
print(f" {name:<8} p_e = {pe:5.2f}, p_c = {pc:5.2f}, "
f"ratio = {pc / pe:4.2f}, h_fg = {hfg:6.0f}")
# ---------- Plot: the p-h diagram ----------
t_crit = PropsSI("Tcrit", FLUID) - 273.15
p_crit = PropsSI("Pcrit", FLUID) / 1000.0
print(f"Critical point: {t_crit:.1f} degC, {p_crit / 100.0:.1f} bar")
t_dome = np.linspace(-40.0, t_crit - 0.05, 300)
h_liq = np.array([h_sat(t, 0) for t in t_dome])
h_vap = np.array([h_sat(t, 1) for t in t_dome])
p_dome = np.array([p_sat(t) for t in t_dome])
fig, ax = plt.subplots(figsize=(8, 6))
ax.plot(h_liq, p_dome / 100.0, color="black", label="saturated liquid")
ax.plot(h_vap, p_dome / 100.0, color="black", linestyle="--",
label="saturated vapour")
ax.plot([h_liq[-1], h_vap[-1]], [p_dome[-1] / 100.0] * 2, color="black")
for t in (-20.0, -6.0, 20.0, 42.0, 70.0):
ps = p_sat(t)
p_low = np.geomspace(60.0, ps * 0.999, 60) # vapour side
p_high = np.geomspace(ps * 1.001, 4000.0, 40) # liquid side
h_line = ([h_tp(t, p) for p in p_low] + [h_sat(t, 1), h_sat(t, 0)]
+ [h_tp(t, p) for p in p_high])
p_line = list(p_low) + [ps, ps] + list(p_high)
ax.plot(h_line, np.array(p_line) / 100.0, color="gray", linewidth=0.8)
ax.annotate(f"{t:.0f} degC", (h_tp(t, 60.0), 0.6), fontsize=8,
textcoords="offset points", xytext=(2, 4), rotation=80)
for key, (kind, t, p, h) in states.items():
ax.plot(h, p / 100.0, "o", color="tab:red")
ax.annotate(key, (h, p / 100.0), textcoords="offset points",
xytext=(-14 if key == "C" else 6, 6), fontsize=11,
fontweight="bold")
ax.set_yscale("log")
ax.set_xlim(120.0, 500.0)
ax.set_ylim(0.5, 50.0)
ax.set_xlabel("specific enthalpy h (kJ/kg)")
ax.set_ylabel("absolute pressure p (bar)")
ax.set_title("Pressure-enthalpy diagram of R134a (CoolProp)")
ax.legend(loc="upper left")
ax.grid(True, which="both", linewidth=0.3)
fig.tight_layout()
fig.savefig("r134a_ph_diagram.png", dpi=120)
print("Saved r134a_ph_diagram.png")

Expected output

Application 1: saturation pressures of R134a
evaporating -6 degC: 234.3 kPa = 2.343 bar absolute
gauge at the site: 1.508 bar, gauge at sea level: 1.330 bar
condensing 42 degC: 1072.2 kPa = 10.722 bar absolute
gauge at the site: 9.887 bar, gauge at sea level: 9.709 bar
pressure ratio p_c / p_e: 4.58
difference between the two gauge readings: 0.178 bar
low side: site gauge read on a sea-level scale gives -4.1 degC (error 1.9 K)
high side: site gauge read on a sea-level scale gives 42.6 degC (error 0.6 K)
boiling point at 101.3 kPa: -26.1 degC, at 83.5 kPa: -30.2 degC
Application 2: enthalpy at -6 degC
h_f = 191.99, h_g = 395.06, h_fg = 203.08 kJ/kg
A: subcooled liquid T = 38.0 degC, p = 10.722 bar, h = 253.42 kJ/kg
B: mixture, x = 0.30 T = -6.0 degC, p = 2.343 bar, h = 252.91 kJ/kg
C: saturated vapour T = -6.0 degC, p = 2.343 bar, h = 395.06 kJ/kg
D: superheated vapour T = 0.0 degC, p = 2.343 bar, h = 400.27 kJ/kg
B by hand: 191.99 + 0.30 x 203.08 = 252.91 kJ/kg
A by the saturated-liquid estimate at 38 degC: 253.43 kJ/kg
quality at -6 degC with the enthalpy of A: 0.302
h_C - h_B = 142.15, h_D - h_C = 5.21, h_D - h_A = 146.85 kJ/kg
Reference state
CoolProp default: h_f = 200.00 kJ/kg at 0 degC
table with h_f = 0 at -40 degC: every value lower by 148.14 kJ/kg
at -6 degC that table gives h_f = 43.84, h_g = 246.92, h_fg = 203.08 kJ/kg
Other refrigerants at -6 and 42 degC (bar absolute, kJ/kg)
R134a p_e = 2.34, p_c = 10.72, ratio = 4.58, h_fg = 203
R1234yf p_e = 2.56, p_c = 10.71, ratio = 4.18, h_fg = 167
R290 p_e = 3.93, p_c = 14.34, ratio = 3.65, h_fg = 383
R600a p_e = 1.26, p_c = 5.60, ratio = 4.43, h_fg = 360
R717 p_e = 3.41, p_c = 16.43, ratio = 4.82, h_fg = 1283
Critical point: 101.1 degC, 40.6 bar
Saved r134a_ph_diagram.png

In the plot, A lies very close to the saturated liquid line, because 4 K of subcooling is a small step in enthalpy. C and D are close together for the same reason on the vapour side.

Common Mistakes



  • Using a gauge reading where the property data needs an absolute pressure. Add the atmospheric pressure first, and use the site’s value, not 101.3 kPa, when the site is high.
  • Forming a pressure ratio from gauge readings. At the site, , which is wrong. The ratio of absolute pressures is 4.58.
  • Reading the saturation temperature from a chart or gauge scale for a different refrigerant. Each refrigerant has its own pressure for each temperature.
  • Expecting a temperature reading to show how much liquid is in a mixture. Under the dome the temperature is the same at every quality.
  • Taking from one table and from another program. The reference states may differ, and the difference is then meaningless.

Summary



  • A pure refrigerant has one saturation pressure for each temperature. R134a boils at −6 °C at 2.343 bar absolute and condenses at 42 °C at 10.722 bar absolute.
  • Compare the measured temperature with the saturation temperature at the measured absolute pressure: lower means subcooled liquid, equal means saturated, higher means superheated vapour.
  • A gauge reads the absolute pressure minus the local atmosphere. The same state reads 0.178 bar higher at a site with 83.5 kPa than at sea level, and a sea-level temperature scale is 1.9 K wrong on the low side.
  • In a mixture, . For R134a at −6 °C, kJ/kg.
  • Enthalpy values depend on the reference state of the source. Enthalpy differences do not.

Exercises



Use CoolProp or an R134a table where a saturation value is needed. The answers use CoolProp.

1. A suction gauge on an R134a system at sea level (101.3 kPa) reads 3.00 bar. Find the absolute pressure and the evaporating temperature.

Answer

kPa, which is 4.013 bar. The saturation temperature of R134a at 401.3 kPa is 9.0 °C.

2. The same reading of 3.00 bar is taken at the site where the atmospheric pressure is 83.5 kPa. Find the evaporating temperature, and the error made by a person who uses the sea-level answer.

Answer

kPa. The saturation temperature is 7.7 °C. The sea-level answer of 9.0 °C is 1.3 K too high.

3. R134a in a liquid line is at 8.00 bar absolute and 25 °C. The saturation temperature at 8.00 bar is 31.3 °C. Name the state, and give the subcooling or the superheat.

Answer

The temperature is below the saturation temperature, so the refrigerant is subcooled liquid. The subcooling is K.

4. R134a at −6 °C is a mixture with an enthalpy of 300.00 kJ/kg on the CoolProp reference (, kJ/kg). Find the quality.

Answer

. The mixture is 53.2 percent vapour by mass.

5. Refrigerant enters an evaporator at −6 °C with quality 0.30 and leaves as saturated vapour. The evaporator must absorb 3.0 kW. Find the heat absorbed by each kilogram and the mass flow.

Answer

Each kilogram absorbs kJ. From , kg/s, which is about 76 kg per hour.

6. A printed table sets at −40 °C and gives, at −6 °C, and kJ/kg. A colleague takes kJ/kg from CoolProp and kJ/kg from the table and reports an enthalpy of evaporation of 351.22 kJ/kg. Find the correct value from each source and explain the error.

Answer

From the table: kJ/kg. From CoolProp: kJ/kg (203.08 unrounded). The two sources agree. The colleague mixed two reference states, which differ by a constant 148.14 kJ/kg, so the reported value is too high by that amount.

References



  • Y. A. Çengel and M. A. Boles, Thermodynamics: An Engineering Approach, 8th edition, McGraw-Hill, 2015.
  • W. F. Stoecker and J. W. Jones, Refrigeration and Air Conditioning, 2nd edition, McGraw-Hill, 1982.
  • I. H. Bell, J. Wronski, S. Quoilin and V. Lemort, “Pure and Pseudo-pure Fluid Thermophysical Property Evaluation and the Open-Source Thermophysical Property Library CoolProp”, Industrial and Engineering Chemistry Research, volume 53, 2014.
  • R. Tillner-Roth and H. D. Baehr, “An International Standard Formulation for the Thermodynamic Properties of 1,1,1,2-Tetrafluoroethane (HFC-134a)”, Journal of Physical and Chemical Reference Data, volume 23, 1994.


© 2021-2026 SiliconWit®. All rights reserved.
Predict first

Halfway along an evaporator, a probe on the pipe reads −6 °C and the gauge shows 2.343 bar absolute, the R134a boiling pressure at −6 °C. What fraction of the refrigerant at that point has already boiled to vapour?

83.5 kPa, 1,600 m101.3 kPa, coast200 kPa, cooker 94.6 °C100 °C120.2 °C R134a: −6 °C at 2.343 bar, 42 °C at 10.722 bar
Try it: the same gauge reading, two temperatures

True evaporating temperature
Sea-level scale shows
Error of the scale

R134a saturation pressures from CoolProp, for each kelvin from −40 °C to 20 °C. The atmosphere comes from the standard formula for altitude: 101.3 kPa at sea level, 83.5 kPa at 1,600 m. The boiling temperature follows the absolute pressure, the left column. A temperature scale printed on a gauge always adds the sea-level atmosphere, the right column, so above sea level it reads too warm.

ABCD liquidliquid + vapourvapour 10.7 bar, 42 °C2.3 bar, −6 °C energy per kilogram, h →pressure, log scale →
Watch it build: the pressure-enthalpy diagram
p, logh, kJ/kg 110 liquid mixture vapour 10.72 bar, 42 °C 2.34 bar, −6 °C width 203.08 kJ/kg x = 0.30 valve 40.6 bar, 101.1 °C
  1. Pressure up on a log scale, enthalpy across. The saturated liquid and vapour lines form a dome.
  2. Left of the dome is liquid, right of it vapour, and under it a boiling mixture.
  3. Horizontal lines keep one pressure: the evaporator at 2.34 bar, the condenser at 10.72 bar.
  4. At 2.34 bar the dome is 203.08 kJ/kg wide; 30 percent across is x = 0.30.
  5. The valve is a vertical line: same enthalpy, from 10.72 bar down to 2.34 bar.
  6. The dome closes at the critical point, 40.6 bar and 101.1 °C. The log axis keeps 2 bar readable.
HIGH SIDE LOW SIDE Condenser 42 °C Evaporator −6 °C Compressor Expansion valve high side gauge reads pc low side gauge reads pe
What can be measured on the circuit from outside
absolute pressure (kPa) 234.3 101.3 83.5 0.0 R134a boiling at −6 °C perfect vacuum gauge reads 133.0 kPa sea level atmosphere 101.3 gauge reads 150.8 kPa site at 1,600 m atmosphere 83.5 at sea level at the site
One refrigerant state, two gauge readings

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. A cold room with R134a stands at 2,400 m, where the atmospheric pressure is 75.6 kPa. The suction gauge reads 1.60 bar. What is the evaporating temperature?

2. On a cool night the liquid R134a reaches the expansion valve at 30 °C, not 38 °C. Its enthalpy is 241.72 kJ/kg. At −6 °C, hf = 191.99 and hfg = 203.08 kJ/kg. What fraction is vapour just after the valve?

3. Liquid at 38 °C (h = 253.43 kJ/kg in CoolProp) passes the valve and leaves the evaporator as saturated vapour at −6 °C (h = 395.06 kJ/kg in CoolProp). A printed table with its zero at −40 °C gives 105.29 kJ/kg for the liquid. How much heat does each kilogram take from the room?

Found this useful?

Discussion

    Comments show your name. Be kind, stay on the topic.