Skip to content
You Start with one site
Amounts in Start with one site
Control, Measurement & Energy · Course

A Cold Room Energy Balance

Lesson 10 of 10 26 min read
Found this useful?

The compressor of a cold room runs seventeen hours a day. One person says that is normal for a busy store, another wants a larger unit, and a third suspects the door. Nobody can prove anything, because nobody has written down how many hours the room should need. Without that number, every hour of running looks the same, and a loss worth a third of the bill stays for years. This lesson puts every load of the room on one page, predicts the run hours and the daily energy, and then uses a month of records to find what the extra hours are made of. #Refrigeration #EnergyBalance #ColdRoom

Learning Objectives

By the end of this lesson, you will be able to:

  1. Add the daily loads of a cold room into one balance and state each load’s share
  2. Calculate the expected run-time fraction, compressor hours, electricity and cost for a day, a month and a year
  3. Predict how a door, a strip curtain, wet insulation, a dirty condenser, an electric defrost and a colder setting change the run hours and the energy
  4. Separate two causes of extra running in a monthly record and put a yearly cost on each
  5. State the limits of the balance and how closely it can be expected to agree with a measurement

Real-World System Problem: One room, one page



The cold room of this course is 30 m³ inside, holds fresh produce at 4 °C and stands in a store at 30 °C. Its R134a system gives 3.0 kW of cooling at the design point for 1.156 kW of electricity at the compressor. Each earlier part of the course calculated one flow of heat into this room or one property of the machine that removes it.

One at a time, those results do not answer the owner’s question: how many hours should the compressor run, and how many kilowatt-hours should the meter count? That needs all the loads in one unit, added, and divided by what the machine can do. The result is a reference, like a household budget: a measured room is compared with it, and each difference has a size and a cause.

evaporatorenvelope 9.45lights 0.12, person 0.27doorCOLD ROOM, 4 °C10.99produceevaporator fans 2.88respiration 2.1611.0836.95 kWh a day leaves with the refrigerant
Every flow of heat into the room on the design day (kWh)

Fundamental Theory: From loads to hours to kilowatt-hours



The balance

The first law, with a boundary round the room, says that over a day in which the room temperature ends where it began, the heat removed by the evaporator equals the heat that entered. The balance has four lines.

The daily balance

is each daily load of heat in kWh and their total. is the cooling capacity in kW, the compressor hours a day, the electrical input of the compressor, the condenser fan power, the daily energy of the evaporator fans and that of a defrost heater, if one is used.

Two properties of the machine enter and do different work: the capacity decides how many hours the compressor runs, and the system COP, , how many kilowatt-hours those hours cost. A fault can move one without the other, which makes diagnosis possible.

× priceperkWh÷ coolingcapacity= hours× inputpower,plus fansloads ofheat,kWh a day36.95 kWh12.32 h18.23 kWh218.7 units
The chain from heat to money

Loads that the meter counts twice

The evaporator fans, the lights, a person and an electric defrost heater release their heat inside the insulated room. Their electricity is counted once at the meter, and the compressor then uses more to carry the same heat out. Off-cycle defrost is the exception: it melts frost with room air, uses no heater and adds nothing. The electric defrost of this course, when used, adds its whole 1.20 kWh a day to the room load.

How each fault moves the record

A fault either adds heat to the room or weakens the machine. The table gives the direction of each change against the reference.

CauseRun hoursCompressor power while runningClue in the record
Door open longerUpSameDoor minutes up, extra running in working hours
Wet insulationUpSameExtra running at night as well, with the door shut
Frost on the coilUpSlightly downRecovers after each defrost
Dirty condenserUp a littleUpCondensing temperature further above the air
Too little refrigerantUpDownHigh superheat and low subcooling, read by a technician

The night test

Between late evening and early morning the door is shut, the lights are off and the day’s produce has reached the room temperature. Only three loads remain: transmission, respiration and the evaporator fans.

A sound room at the design condition runs its compressor about 20 percent of the night hours. The figure does not depend on the door model, so it tests the envelope and the machine apart from the weakest term of the balance.

Use the store air of those night hours, not the 30 °C of the design day. If the store cools to 22 °C at night, a sound envelope passes only 291 W, and with a capacity of 2.817 kW the night fraction is 17.8 percent; wet insulation would give 24.8 percent. A record of 21 percent then lies between the two and proves neither. So log the store air beside the room air.

Application 1: The balance for the design day



Step 1: The load table

Click to reveal the loads and their shares
  1. The two small loads. Lighting: . Person: . ✅

  2. All loads on one page. The last column is the compressor running that each load explains, its kWh divided by 3.000 kW.

    LoadkWh a dayAverage (W)Share (%)Hours
    Transmission9.4539425.63.15
    Infiltration at the door10.9945829.73.66
    Product11.0846230.03.69
    Respiration2.16905.80.72
    Evaporator fans2.881207.80.96
    Lighting0.1250.30.04
    Person0.27110.70.09
    Defrost (off-cycle)0.0000.00.00
    Total36.951,54010012.32

    The room gains 36.95 kWh of heat on the design day. ✅

  3. Average load.

    The average load is 1,540 W, about half of the capacity. ✅

Step 2: Run time

Click to reveal the hours
  1. Run-time fraction.

    ✅

  2. Compressor hours.

    The reference for this room is 12.3 hours of running on the design day. ✅

Step 3: Electricity and cost

Click to reveal the energy and the cost
  1. Compressor. . ✅

  2. Condenser fan. . ✅

  3. Evaporator fans. . ✅

  4. Total.

    ✅

  5. Cost. With unrounded values, 218.7 currency units a day, 6,562 a month and 79,840 a year (6,653 kWh). ✅

  6. Electricity for each kWh of cooling.

    The overall COP with all fans is , against 2.595 for the compressor alone. ✅

  7. Check a second way. The compressor energy is the load divided by the system COP: . The watts of the table add to . Both agree, and the script prints the same figures. ✅

Step 4: Six changes to the same balance

Click to reveal the sensitivity table
  1. New load or new machine for each case. (a) The simple door model doubles the infiltration: . (b) The curtain leaves 1.65 kWh of infiltration: . (c) Transmission becomes : total 43.37 kWh. (d) and (f) keep 36.95 kWh and change the machine. (e) The heater adds 1.20 kWh of load and 1.20 kWh at the meter: load 38.15 kWh. ✅

  2. One case in full, the dirty condenser.

    ✅

  3. All cases.

    CaseHeat (kWh)Run hoursElectricity (kWh a day)ChangeUnits a year
    Design day36.9512.3218.23
    (a) Door-open time doubled47.9415.9822.79+4.56+19,993
    (b) Strip curtain27.619.2014.35−3.88−16,994
    (c) Wet insulation43.3714.4620.90+2.67+11,682
    (d) Dirty condenser, 48 °C36.9513.1220.80+2.57+11,273
    (e) Electric defrost38.1512.7219.93+1.70+7,439
    (f) Room at 2 °C36.9513.3719.17+0.95+4,140

    ✅

  4. The colder room with its own loads. Case (f) uses the machine figures of the COP calculation and holds the load. A room at 2 °C also gains more heat: transmission 10.22 kWh, infiltration 11.74 kWh (CoolProp, room air at 2 °C and 85 percent) and product 12.14 kWh, a total of 39.53 kWh. The balance then gives 14.30 h and 20.31 kWh a day, which is 2.08 kWh above the design day and 9,128 units a year. ✅

Application 2: A month of records



Step 1: The gap

Click to reveal the size of the gap
  1. Run hours. a day above the reference, which is 38 percent. ✅

  2. Energy. a day above the reference, which is 43 percent. ✅

  3. First reading. The energy has risen by a larger share than the hours. Extra heat alone does the opposite, because the evaporator fans do not change: case (a) has 30 percent more hours and 25 percent more energy. So the compressor also draws more power for each hour. The room temperature of 4.1 °C shows that the system still meets the load on average, so the first-law balance of a steady room applies. An average says nothing about how long the product was too warm: for that, the record needs its highest reading and the minutes above the limit. ✅

Step 2: The door

Click to reveal what the door explains
  1. Door minutes. The switch counted the design number of openings, 40, but 40 minutes open against 20. Each opening lasts twice as long. ✅

  2. New load. In the simple door model the exchange follows the open time, so the infiltration doubles to 21.98 kWh.

    ✅

  3. Hours with a healthy machine.

    The door explains of the 4.68 extra hours. About one hour is still missing. ✅

Step 3: The condenser

Click to reveal what the condenser explains
  1. Condensing temperature. absolute, so . ✅

  2. Condenser temperature difference. , against 12 K at design. The condenser rejects heat badly. ✅

  3. Hours with the real capacity.

    The lower capacity explains the missing . The record shows 17.0 h. ✅

  4. Energy.

    The record shows 26.1 kWh. ✅

  5. Check with the compressor power. From the record alone, the power of the compressor is

    This is the input at 48 °C, not the 1.156 kW of the design point. Two independent readings, the head pressure and the meter, give the same answer. ✅

Step 4: The causes that do not fit

Click to reveal the night test
  1. Night load. . ✅

  2. Expected night run fraction with the capacity of 2.817 kW.

    The record shows 21 percent. The envelope is sound. ✅

  3. If the insulation were wet. The night load would be and the fraction . The record excludes this. ✅

  4. Frost and refrigerant. Both would lower the capacity at night as well and raise the night fraction above 21.4 percent. Nothing in this record points to them. ✅

Step 5: The yearly cost of each cause

Click to reveal the costs
  1. Door alone, clean condenser. Case (a) of Application 1: 22.79 kWh a day, which is 4.56 kWh above the reference. In a year: 1,666 kWh, 19,993 currency units. ✅

  2. Condenser alone, careful door. Case (d): 20.80 kWh a day, 2.57 kWh above the reference. In a year: 939 kWh, 11,273 currency units. ✅

  3. Both together. a day. In a year: 2,885 kWh, 34,619 currency units. ✅

  4. The part that belongs to both. a day, 3,353 units a year. The two faults multiply: the dirty condenser makes each kilowatt-hour of door heat more expensive to remove. Correcting the door first saves a day, and cleaning the condenser first saves a day. ✅

Where the 17 hours a day come from
reference, design day 12.32 h ############
door, 20 minutes more +3.66 h ####
condenser, 6 K warmer +1.04 h #
───────
predicted 17.02 h
recorded 17.0 h

The limits of the balance



The balance is a model, and its terms are not equally good.

The infiltration is the weakest. The fraction of the room exchanged at each opening, 0.5, was chosen, not measured: with 0.3 the design day has 32.55 kWh of heat and 10.85 hours of running, with 0.7 it has 41.34 kWh and 13.78 hours. One assumed number moves the result by 12 percent each way. Doubling the infiltration with the open time in Application 2 has the same weakness, because a real exchange does not grow in a straight line with time.

The other terms have smaller errors. The transmission uses inside dimensions and ignores joints and the door frame, so it is low by several percent. The product mass changes from day to day, and its specific heat and heat of respiration are typical values. The machine figures come from a cycle with constant efficiencies, which makes hot conditions look milder than they are. And the balance assumes the room ends each day as warm as it began, true of a month but not of every single day.

As a judgement from these errors: a balance that agrees with a careful measurement within 15 to 20 percent is a good result, and a larger gap is a finding. The balance is most reliable for differences in one room against its own earlier months, because most of the fixed errors then cancel.

Verify It in Python



The script builds every load from the room data with CoolProp, prints the design balance, the sensitivity table and the diagnosis of the month, and plots the daily electricity of each case. It needs CoolProp as well as matplotlib: pip install CoolProp.

cold_room_energy_balance.py
"""Energy balance of the cold room: loads, run hours, kWh a day, and a month diagnosed."""
import matplotlib.pyplot as plt
from CoolProp.CoolProp import PropsSI, HAPropsSI
FLUID, K0, P_ATM = "R134a", 273.15, 83.5e3
ETA_IS, ETA_MOTOR = 0.68, 0.85
COND_FAN, EVAP_FANS = 0.090, 0.120 # kW
PRICE = 12.00 # currency units per kWh
T_STORE, RH_STORE, T_GROUND = 30.0, 0.60, 22.0
def cycle(t_e, t_c):
"""Refrigerating effect, work (kJ/kg) and suction density of the R134a cycle."""
p_e = PropsSI("P", "T", t_e + K0, "Q", 1, FLUID)
p_c = PropsSI("P", "T", t_c + K0, "Q", 0, FLUID)
t1 = t_e + 6.0 + K0
h1 = PropsSI("H", "T", t1, "P", p_e, FLUID)
s1 = PropsSI("S", "T", t1, "P", p_e, FLUID)
h2s = PropsSI("H", "P", p_c, "S", s1, FLUID)
h3 = PropsSI("H", "T", t_c - 4.0 + K0, "P", p_c, FLUID)
rho1 = PropsSI("D", "T", t1, "P", p_e, FLUID)
return (h1 - h3) / 1e3, (h2s - h1) / ETA_IS / 1e3, rho1
Q0, W0, RHO0 = cycle(-6.0, 42.0)
VOLUME_FLOW = 3.0 / Q0 / RHO0 # m3/s, constant displacement
def machine(t_e=-6.0, t_c=42.0):
"""Capacity and compressor electrical input in kW."""
q_e, w, rho1 = cycle(t_e, t_c)
m = VOLUME_FLOW * rho1
return m * q_e, m * w / ETA_MOTOR
def loads(t_room=4.0, door=1.0, curtain=0.0, k=0.023, heater=0.0):
"""Daily loads of heat in kWh. door multiplies the door-open time."""
u = 1.0 / (1 / 8.0 + 0.080 / k + 1 / 20.0)
trans = u * (47.0 * (T_STORE - t_room) + 12.0 * (T_GROUND - t_room)) * 0.024
room = ("T", t_room + K0, "P", P_ATM, "R", 0.85)
dh = (HAPropsSI("H", "T", T_STORE + K0, "P", P_ATM, "R", RH_STORE)
- HAPropsSI("H", *room)) / 1e3
m_da = 40 * 0.5 * door * 30.0 / HAPropsSI("V", *room)
return {"transmission": trans,
"infiltration": m_da * dh / 3600.0 * (1.0 - curtain),
"product": 500.0 * 3.8 * (25.0 - t_room) / 3600.0,
"respiration": 3000.0 * 0.03 * 0.024,
"evaporator fans": EVAP_FANS * 24.0,
"lighting": 0.060 * 2.0,
"person": 0.270 * 1.0,
"defrost heater": heater}
def balance(load, cap, elec, heater=0.0):
"""Run hours and electricity (kWh a day) for a daily load in kWh."""
hours = load / cap
comp, cfan, efan = hours * elec, hours * COND_FAN, EVAP_FANS * 24.0
return hours, comp, cfan, comp + cfan + efan + heater
# ---------- Application 1: the design day ----------
CAP, ELEC = machine()
base = loads()
total = sum(base.values())
print("Design day: loads of heat")
for name, kwh in base.items():
print(f" {name:16s} {kwh:6.2f} kWh {kwh * 1000 / 24:5.0f} W "
f"{100 * kwh / total:5.1f} %")
print(f" {'total':16s} {total:6.2f} kWh {total * 1000 / 24:5.0f} W")
hours, comp, cfan, elec_day = balance(total, CAP, ELEC)
print(f" capacity {CAP:.3f} kW, input {ELEC:.3f} kW, run-time fraction "
f"{hours / 24:.3f}, {hours:.2f} h a day")
print(f" compressor {comp:.2f}, condenser fan {cfan:.2f}, evaporator fans "
f"{EVAP_FANS * 24:.2f}, total {elec_day:.2f} kWh a day")
print(f" cost {elec_day * PRICE:.1f} a day, {elec_day * PRICE * 30:,.0f} a month "
f"(30 days), {elec_day * PRICE * 365:,.0f} a year ({elec_day * 365:,.0f} kWh)")
print(f" {elec_day / total:.3f} kWh of electricity per kWh of cooling "
f"(overall COP {total / elec_day:.2f}; check: load / system COP "
f"{total / (CAP / ELEC):.2f} kWh for the compressor)")
# ---------- Sensitivity ----------
CAP_D, ELEC_D = machine(t_c=48.0) # dirty condenser
CAP_2, ELEC_2 = machine(t_e=-8.0) # room at 2 degC
cases = [
("design day", base, CAP, ELEC, 0.0),
("a door time doubled", loads(door=2.0), CAP, ELEC, 0.0),
("b strip curtain", loads(curtain=0.85), CAP, ELEC, 0.0),
("c wet insulation", loads(k=0.040), CAP, ELEC, 0.0),
("d dirty condenser", base, CAP_D, ELEC_D, 0.0),
("e electric defrost", loads(heater=1.2), CAP, ELEC, 1.2),
("f room at 2 degC", base, CAP_2, ELEC_2, 0.0),
(" f with its loads", loads(t_room=2.0), CAP_2, ELEC_2, 0.0),
]
print("Sensitivity (heat kWh, run h, electricity kWh a day, change, per year)")
results = []
for name, ld, cap, elec, heater in cases:
q = sum(ld.values())
h, _, _, e = balance(q, cap, elec, heater)
results.append((name, e))
print(f" {name:20s} {q:6.2f} {h:6.2f} {e:6.2f} {e - elec_day:+6.2f} "
f"{(e - elec_day) * 365 * PRICE:+8,.0f}")
for f in (0.3, 0.7):
q = total + base["infiltration"] * (f / 0.5 - 1.0)
h, _, _, e = balance(q, CAP, ELEC)
print(f" door fraction {f}: {q:.2f} kWh of heat, {h:.2f} h, {e:.2f} kWh "
f"({100 * (h / hours - 1):+.0f} % run hours)")
# ---------- Application 2: a month of records ----------
RUN_H, KWH, DOOR_MIN, T_AIR, HEAD_GAUGE, NIGHT = 17.0, 26.1, 40.0, 30.0, 11.7, 0.21
print("Month of records")
print(f" run hours {RUN_H - hours:+.2f} h ({100 * (RUN_H / hours - 1):+.0f} %), "
f"energy {KWH - elec_day:+.2f} kWh ({100 * (KWH / elec_day - 1):+.0f} %)")
t_c = PropsSI("T", "P", HEAD_GAUGE * 1e5 + P_ATM, "Q", 0, FLUID) - K0
print(f" head pressure {HEAD_GAUGE} bar gauge = {HEAD_GAUGE + P_ATM / 1e5:.3f} bar abs, "
f"condensing {t_c:.1f} degC, difference {t_c - T_AIR:.1f} K")
power = (KWH - EVAP_FANS * 24) / RUN_H - COND_FAN
print(f" compressor power from the record {power:.3f} kW "
f"(design {ELEC:.3f}, at 48 degC {ELEC_D:.3f})")
door_load = sum(loads(door=DOOR_MIN / 20.0).values())
h_door, _, _, e_door = balance(door_load, CAP, ELEC)
h_both, _, _, e_both = balance(door_load, CAP_D, ELEC_D)
h_cond, _, _, e_cond = balance(total, CAP_D, ELEC_D)
print(f" door alone: load {door_load:.2f} kWh, {h_door:.2f} h "
f"({h_door - hours:+.2f}), {e_door:.2f} kWh")
print(f" door and condenser: {h_both:.2f} h ({h_both - h_door:+.2f} more), "
f"{e_both:.2f} kWh; measured {RUN_H} h and {KWH} kWh")
night = (base["transmission"] + base["respiration"]) / 24 + EVAP_FANS
wet = (loads(k=0.040)["transmission"] + base["respiration"]) / 24 + EVAP_FANS
print(f" night load {night * 1000:.0f} W: run fraction {night / CAP:.3f} at design, "
f"{night / CAP_D:.3f} at 48 degC, {wet / CAP_D:.3f} with wet insulation "
f"(measured {NIGHT})")
print(" cost per year (kWh a day, kWh a year, units a year)")
for name, e in (("door alone", e_door), ("condenser alone", e_cond),
("both together", e_both)):
d = e - elec_day
print(f" {name:16s} {d:+.2f} {d * 365:+7,.0f} {d * 365 * PRICE:+8,.0f}")
inter = e_both - e_door - e_cond + elec_day
print(f" interaction {inter:+.2f} {inter * 365:+7,.0f} "
f"{inter * 365 * PRICE:+8,.0f}")
# ---------- Plot ----------
results.append(("month: door + condenser", e_both))
names = [n.strip() for n, _ in results]
fig, ax = plt.subplots(figsize=(8, 4.8))
ax.barh(names[::-1], [e for _, e in results][::-1], color="tab:blue")
ax.axvline(elec_day, color="gray", linestyle="--", linewidth=0.8)
ax.set_xlabel("electricity (kWh a day)")
ax.set_title("Cold room at 4 degC: design day and what each change does")
fig.tight_layout()
fig.savefig("cold_room_energy_balance.png", dpi=120)
print("Saved cold_room_energy_balance.png")

Expected output

Design day: loads of heat
transmission 9.45 kWh 394 W 25.6 %
infiltration 10.99 kWh 458 W 29.7 %
product 11.08 kWh 462 W 30.0 %
respiration 2.16 kWh 90 W 5.8 %
evaporator fans 2.88 kWh 120 W 7.8 %
lighting 0.12 kWh 5 W 0.3 %
person 0.27 kWh 11 W 0.7 %
defrost heater 0.00 kWh 0 W 0.0 %
total 36.95 kWh 1540 W
capacity 3.000 kW, input 1.156 kW, run-time fraction 0.513, 12.32 h a day
compressor 14.24, condenser fan 1.11, evaporator fans 2.88, total 18.23 kWh a day
cost 218.7 a day, 6,562 a month (30 days), 79,840 a year (6,653 kWh)
0.493 kWh of electricity per kWh of cooling (overall COP 2.03; check: load / system COP 14.24 kWh for the compressor)
Sensitivity (heat kWh, run h, electricity kWh a day, change, per year)
design day 36.95 12.32 18.23 +0.00 +0
a door time doubled 47.94 15.98 22.79 +4.56 +19,993
b strip curtain 27.61 9.20 14.35 -3.88 -16,994
c wet insulation 43.37 14.46 20.90 +2.67 +11,682
d dirty condenser 36.95 13.12 20.80 +2.57 +11,273
e electric defrost 38.15 12.72 19.93 +1.70 +7,439
f room at 2 degC 36.95 13.37 19.17 +0.95 +4,140
f with its loads 39.53 14.30 20.31 +2.08 +9,128
door fraction 0.3: 32.55 kWh of heat, 10.85 h, 16.40 kWh (-12 % run hours)
door fraction 0.7: 41.34 kWh of heat, 13.78 h, 20.05 kWh (+12 % run hours)
Month of records
run hours +4.68 h (+38 %), energy +7.87 kWh (+43 %)
head pressure 11.7 bar gauge = 12.535 bar abs, condensing 48.0 degC, difference 18.0 K
compressor power from the record 1.276 kW (design 1.156, at 48 degC 1.276)
door alone: load 47.94 kWh, 15.98 h (+3.66), 22.79 kWh
door and condenser: 17.02 h (+1.04 more), 26.13 kWh; measured 17.0 h and 26.1 kWh
night load 604 W: run fraction 0.201 at design, 0.214 at 48 degC, 0.309 with wet insulation (measured 0.21)
cost per year (kWh a day, kWh a year, units a year)
door alone +4.56 +1,666 +19,993
condenser alone +2.57 +939 +11,273
both together +7.90 +2,885 +34,619
interaction +0.77 +279 +3,353
Saved cold_room_energy_balance.png

In the plot the strip curtain is the only bar to the left of the dashed design line, and the month with two faults is the longest bar.

Common Mistakes



  • Judging a room by its temperature. A room at 4 °C can cost 43 percent more than it should. Compare run hours and kWh a day with a calculated reference.
  • Adding watts and kilowatt-hours in one column. Convert every load to kWh a day first: a steady load in kW times 24 h, an intermittent load in kW times its own hours.
  • Forgetting that the fans, the lights and a defrost heater are loads as well as consumers. Their heat is released inside the room and must be removed.
  • Blaming one cause for the whole gap. Find what the door minutes explain first, then test the machine with the compressor power and the condenser difference.
  • Trusting the infiltration figure as if it were measured. It rests on a chosen fraction, so use the night hours to test the envelope and the machine apart from the door.
  • Dividing the daily load by the design capacity when the condensing or evaporating temperature has moved. The capacity moves with them.

Summary



  • On the design day the room gains 36.95 kWh of heat: product 30.0 percent, infiltration 29.7, transmission 25.6, evaporator fans 7.8, respiration 5.8, and lighting and one person 1.0 together.
  • At a capacity of 3.000 kW the run-time fraction is 0.513, which is 12.32 compressor hours a day.
  • The electricity is 18.23 kWh a day (compressor 14.24, condenser fan 1.11, evaporator fans 2.88), 0.493 kWh for each kWh of heat removed, and 79,840 currency units a year at the example price.
  • Capacity decides the hours and COP decides the kilowatt-hours. A larger load raises the hours at the same power. A weaker machine raises the power, the hours or both.
  • In the recorded month, 40 door minutes a day explained 3.66 of 4.68 extra hours, and a condenser difference of 18 K explained the remaining hour and the higher power. Together they cost 34,619 units a year.
  • The infiltration term is the weakest, so agreement within 15 to 20 percent of a careful measurement is a good result.

Exercises



Use the design-day figures of this lesson where a problem does not give its own: capacity 3.000 kW, compressor input 1.156 kW, condenser fan 0.090 kW, evaporator fans 2.88 kWh a day.

1. On a busy day the loads of a room add to 42.0 kWh of heat. Find the run-time fraction, the compressor hours and the total electricity for the day.

Answer

Fraction and . Electricity .

2. The store starts to receive 800 kg of produce a day in place of 500 kg, at the same 25 °C, with . All other loads stay at their design values. Find the new product load, the daily total, the compressor hours and the electricity.

Answer

Product: . Total: . Hours: . Electricity: a day.

3. On a hot day the store air is at 36 °C. The transmission load is 470.8 W, the infiltration is 15.74 kWh and the unit condenses at 48 °C (capacity 2.817 kW, input 1.276 kW). The other loads are unchanged. Find the daily heat, the compressor hours and the electricity. Compare the hours with the design day.

Answer

Transmission: . Total: . Hours: , which is 3.14 h more than the design day. Electricity: . The load rose and the capacity fell on the same day.

4. Another room of the same design shows, as monthly averages: 14.5 run hours and 20.9 kWh a day, door open 20 minutes a day, condenser difference 12 K, and a night run fraction of 29 percent. Find the night load and the transmission load that it implies, name the cause that fits, and find its yearly cost against the reference of 18.23 kWh a day.

Answer

Night load: . Without respiration and fans, of transmission, against 393.6 W for dry panels. This fits wet insulation (661.1 W, case (c): 14.46 h and 20.90 kWh). The door and the condenser are at their design values. Cost: units a year.

5. In the room of Application 2 a strip curtain of effectiveness 0.85 is fitted, but the doors still stay open 40 minutes a day and the condenser is not cleaned. Predict the daily heat, the compressor hours and the electricity. How much of the 26.13 kWh a day does the curtain remove?

Answer

Infiltration: . Total: . Hours: . Electricity: a day. The curtain removes 9.06 kWh a day, more than a third of the bill, while the condenser fault remains.

References



  • ASHRAE, ASHRAE Handbook: Refrigeration, American Society of Heating, Refrigerating and Air-Conditioning Engineers, 2022 (chapter on refrigeration load).
  • W. F. Stoecker and J. W. Jones, Refrigeration and Air Conditioning, 2nd edition, McGraw-Hill, 1982.
  • R. J. Dossat and T. J. Horan, Principles of Refrigeration, 5th edition, Prentice Hall, 2001.
  • I. H. Bell, J. Wronski, S. Quoilin and V. Lemort, “Pure and Pseudo-pure Fluid Thermophysical Property Evaluation and the Open-Source Thermophysical Property Library CoolProp”, Industrial and Engineering Chemistry Research, vol. 53, no. 6, 2014.


© 2021-2026 SiliconWit®. All rights reserved.
Predict first

A cold room at 4 °C runs its compressor 12.3 hours on a normal day. The door is open for 20 minutes of that day in total. The staff start to leave it open twice as long, 40 minutes. The room still holds 4 °C. How much longer does the compressor run?

See it: the heat of one day, and the electricity that removes it
Heat into the room in a day
Compressor run time in a day
Electricity in a day
Cost in a month of 30 days
Electricity for each kWh of cooling
Capacity · compressor input

Both bars use one scale, so the lower bar shows how much electricity removes the heat of the upper bar. The two marks on the upper bar are the heat the machine can remove in 20 and in 24 hours of running. The loads follow the lesson's models. The door load follows the open time. At 20 minutes it is the lesson's 40 openings, each exchanging half of the room's air. A strip curtain stops 85 percent of it. The product is cooled from 25 °C to 4 °C. Respiration is for the 3,000 kg in store. Wet insulation means k = 0.040 W/(m·K) and dry means 0.023. Electric defrost is a 1.2 kW heater for one hour a day in total, and its heat stays in the room. The surrounding air changes three things: the transmission through the walls and ceiling, the heat in the door air (taken at 60 percent humidity), and the condensing temperature, which is the air temperature plus 12 K for a clean condenser or 18 K for a dirty one. Capacity and compressor input are CoolProp values of the lesson's cycle at each kelvin of condensing temperature, stored as a table. The room stays at 4 °C and the evaporating temperature at −6 °C. Cost is at 12.00 currency units per kWh. The door model is the weakest term, as the lesson explains.

produce cooleddoor airwalls, ceiling, floorevaporator fansproduce breathinglights, a person 11.0810.999.452.882.160.39 36.95 kWh of heat on the design day
4.5 °C3.5 °Ccompressorrunning 00:0006:0012:0018:0024:00 night 20 %day 62 %
Watch it build: from heat to hours to kilowatt-hours
36.95 kWh produce 11.08door 10.99panels 9.45fans and rest 5.43 ÷ 3.0 kW capacity 12.32 h of 24 × 1.246 kW: 15.35+ room fans 2.88 18.23 kWh
  1. The day's heat, load by load, adds to 36.95 kWh: this is what the evaporator must carry out.
  2. Divided by the 3.0 kW capacity: 12.32 hours of running in the 24.
  3. At the meter: 12.32 h × 1.246 kW = 15.35 kWh, plus 2.88 for the fans, which are also a load: 18.23 kWh.
envelope 9.45 lights 0.12, person 0.27 door 10.99 produce 11.08 Cold room, 4 °C evaporator fans 2.88 respiration 2.16 evaporator 36.95 kWh a day leaves with the refrigerant arrow widths to scale
Every flow of heat into the room on the design day (kWh)
reference, design day 12.32 h door, 20 minutes more +3.66 h condenser, 6 K warmer +1.04 h predicted 17.02 h recorded 17.0 h 0 h 6 h 12 h 18 h
Where the 17 hours a day come from

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. Dust on the condenser raises the condensing temperature from 42 °C to 48 °C. The capacity falls to 2.817 kW and the compressor input rises to 1.276 kW. No heat is added to the room: the load stays at 36.95 kWh a day. The design day uses 18.23 kWh of electricity. What does the dirty day use?

2. The room is changed to electric defrost. The heater uses 1.20 kWh a day, and its heat stays inside the room. By how much does the daily reading of the meter rise?

3. The system COP of the machine is 2.595, so the 36.95 kWh of the design day should need 36.95 / 2.595 = 14.24 kWh. The meter on a healthy room shows 18.23 kWh. What explains the difference of 3.99 kWh?

Found this useful?

Discussion

    Comments show your name. Be kind, stay on the topic.