Heat to remove frost
Evaporators, Frost and Defrost
On this page
The evaporator of a cold room becomes a white block of ice, the air from its fans weakens, and the room climbs from 4 °C to 7 °C on a busy afternoon. Someone answers by adding more defrosts, each with a 1.2 kW heater inside the cold room, and the electricity bill rises while the produce dries and loses weight. Both problems start at the same place: the temperature of the coil surface and the water that the door brings in. This lesson shows how to estimate the frost, what a defrost really costs, and what the fans and the coil temperature difference add to the bill. #Refrigeration #Defrost #Evaporator
Learning Objectives
By the end of this lesson, you will be able to:
- Explain when a coil stays dry, when it runs wet and when it collects frost
- Estimate the daily frost mass and the energy needed to melt it
- Calculate how much of an electric defrost melts frost and how much becomes room load
- Calculate the energy of the evaporator fans and the electricity needed to remove their heat
- Describe how a larger evaporator temperature difference changes room humidity and COP, and how frost shows in a record
Real-World System Problem: The evaporator of the produce cold room
The evaporator of this course’s cold room is a finned coil under the ceiling with two fans of 60 W each. Refrigerant R134a boils inside its tubes at
The coil surface is close to the evaporating temperature, below 0 °C. The door brings in about 9 kg of water a day with the store air; that water cannot stay in the room air, and the coldest surface in the room, this coil, collects it as frost.
Frost must be removed, and every way of removing it has a cost. The fans have a cost that is easy to forget: they stand inside the insulated room, so every watt they take is a watt of heat the system must remove again.
Fundamental Theory: The coil surface, frost and the heat that removes it
The evaporator temperature difference
Heat passes from the room air to the refrigerant because the refrigerant is colder. The evaporator temperature difference is
For this room it is
The same 3.0 kW can come from a small coil with a large difference or a large coil with a small one. The small coil is cheaper to buy; the rest of this lesson shows what it costs to run.
Dry, wet or frosted
The coil surface is a little warmer than the boiling refrigerant and much colder than the air; for estimates, take it at the evaporating temperature. Two temperatures then decide what happens to the water vapour in the air. The first is the dew point of the room air, 1.7 °C at 4 °C and 85 percent at this site’s 83.5 kPa: a colder surface takes water out of the air. The second is 0 °C: a colder surface freezes the water.
At −6 °C this coil is in the last case. A room at 4 °C is in an awkward position: the air is above freezing, and the coil is below it.
The coil difference sets the humidity
Air that touches the coil leaves almost saturated at the surface temperature, and cold saturated air holds little water: 2.768 g per kilogram of dry air at −6 °C, against 5.212 g/kg in the room air at 4 °C and 85 percent. So the coil is a dryer, and a colder coil a stronger one.
One number shows the trend. If the coil were the only influence and all the air left it saturated at the surface temperature, the room air at 4 °C would settle at a relative humidity this lesson calls the humidity floor:
| Saturated humidity ratio at the coil (g/kg) | Humidity floor at 4 °C | ||
|---|---|---|---|
| 10 | −6 | 2.768 | 45.3 % |
| 12 | −8 | 2.326 | 38.1 % |
The real room stays far above the floor, because the door brings water in, the produce gives off water, and part of the air passes between the fins without touching them. The direction is what matters: a larger difference pulls the room toward a lower humidity, and the produce supplies the missing water. It dries, loses weight and wilts, and it is sold by weight. For this reason rooms for fresh produce are designed with a small difference and a large coil, commonly a difference of a few kelvin, where a room for packaged goods may use 10 K or more.
A larger difference also means a lower evaporating temperature, and that lowers the COP. For this system the COP falls by 2.94 percent for each kelvin of lower evaporating temperature near the design point.
What frost does to the coil
Frost is a porous layer of ice crystals with air between them, like a blanket over the fins. It harms the coil in two ways: it insulates the metal from the air, and it narrows the passages between the fins, so the fans move less air. Both lower
The system then responds in a fixed order. To move heat through a poorer coil the refrigerant must be colder, so the evaporating temperature and the suction pressure fall. Thinner vapour at the compressor inlet lowers the capacity, and the COP falls too. The compressor runs longer to remove the same daily heat, and once it runs all the time, the room temperature rises.
A record shows frost by the sign of each change between one defrost and the next:
| Quantity in the record | Change as frost builds |
|---|---|
| Air flow through the coil | Falls |
| Suction pressure and evaporating temperature | Fall |
| Difference between room air and coil | Rises |
| Cooling capacity | Falls |
| Compressor run time for the same day’s load | Rises |
| Room temperature, once the compressor runs all the time | Rises |
The size of each change depends on the coil and the frost, and this lesson puts no numbers on them. One reference point helps: in the COP tables of this course, 2 K of lower evaporating temperature, from −6 °C to −8 °C, lowers the suction pressure from 2.343 to 2.169 bar absolute and the capacity from 3.000 to 2.764 kW.
The energy in frost
To remove 1 kg of frost from a coil at temperature
The refrigerant first removed this same heat when the water froze on the coil. The door calculation counted 2,501 kJ/kg for water that leaves the air as liquid; water that leaves as frost at −6 °C gives up
Three ways to defrost
The compressor stops and the fans keep running. Room air above 0 °C passes through the coil and melts the frost. The melting heat comes from the room air, which is cooled by it, so the room gets back the heat that freezing cost. No heater is used, and nothing is added to the room.
The limit is the small difference between the air and the ice. At 4 °C the air is only 4 K above the melting point, so melting is slow. With heavy door traffic the frost may not clear in the time the compressor is off, and ice then builds from day to day. The method does not work in a room held at or below about 0 °C.
The compressor and the fans stop, and electric heaters in the coil melt the frost. It is simple and works at any room temperature.
All the heater energy is released inside the cold room. The part that melts frost leaves as water down the drain. The remainder warms the coil metal, the casing and the air, and is a load on the room.
Hot vapour from the compressor discharge is sent through the evaporator tubes, so the coil is heated from the inside. It is fast and uses no heater, but it needs extra valves and piping, and it is common on larger systems.
At this room temperature, off-cycle defrost is the normal choice and is enough in normal use. The example of this lesson assumes that heavy door traffic has led to an electric defrost: a 1.2 kW heater used four times a day for 15 minutes.
When a defrost ends
A defrost that stops too early leaves ice, which grows from one cycle to the next; one that continues after the coil is clear turns all its heat into room load. Three methods end it: a timer, after a fixed time whatever the frost; a temperature sensor on the coil, when the coil reaches a set temperature a few kelvin above 0 °C, which shows the ice is gone; or, in many controllers, the sensor with the timer kept as a safety limit. After an electric defrost, a short drain time and a fan delay let the water leave and the coil cool before the fans start, so that drops and warm air are not blown onto the produce.
Fan energy is a load inside the room
The fan motors stand inside the room, and all the electricity they take ends as heat in the room air: the motor losses directly, the moving air by friction. So a fan is paid for twice, as if one porter carried a bag in and a second carried it out again. The meter counts the fan’s own energy and the compressor energy that removes its heat:
Application 1: Frost mass and the cost of electric defrost
Step 1: Frost mass and the heat to melt it
Click to reveal the frost energy
-
Frost mass. In a steady state the water that enters must leave, and it leaves at the coil:
a day. This counts the door water only. Water given off by the produce would add to it. ✅ -
Heat for each kilogram.
Warming the ice takes 12.6 kJ/kg and melting takes 334 kJ/kg. ✅
-
Heat for the day’s frost.
Melting the day’s frost needs 0.869 kWh. ✅
Step 2: The heater energy and where it goes
Click to reveal the split
-
Heater energy.
The heaters use 1.20 kWh a day. ✅
-
Share that melts frost.
At most 72.4 percent of the heater energy melts frost and leaves as water. ✅
-
Surplus.
The other 27.6 percent warms the coil metal, the casing and the air round it. It stays in the room as heat. ✅
-
Electricity to remove the surplus.
The compressor uses 0.128 kWh a day to remove the surplus heat. ✅
Step 3: The full cost, with a boundary round the room
Step 2 follows the heater energy. A first-law boundary round the room gives the full comparison with off-cycle defrost, and it checks the split.
Click to reveal the room balance
-
Off-cycle defrost. The frost melts with heat from the room air. The room air loses 0.869 kWh, which is the same heat that the refrigerant removed when the water froze. The two cancel, no electricity crosses the boundary for defrost, and the water leaves as liquid. The net addition to the room’s load is zero. ✅
-
Electric defrost. The water leaves as the same liquid, but 1.20 kWh of electricity now crosses the boundary inward. In a steady state the evaporator must carry all of it out.
Electric defrost adds 1.20 kWh a day to the room’s load. ✅
-
Check against Step 2. The frost heat that the room air no longer supplies, plus the surplus:
. The two methods agree. ✅ -
Electricity.
In a year of 365 days this is 607 kWh, about 7,280 currency units. ✅
-
A cleaner door. With the strip curtain of the door calculation the water falls to 1.35 kg a day, and melting it needs
. A timer that still gives 1.20 kWh then spends only 10.9 percent of it on frost. ✅ -
Python. The script prints 346.6 kJ/kg, 0.869 kWh, 72.4 percent, 0.331 kWh, 0.128 kWh, 1.662 kWh a day and 10.9 percent. ✅
Defrost in the temperature record
During each 15 minute electric defrost the compressor is off, the heater is on, and the room’s other loads continue: about 1.40 kW for the door, product, respiration and envelope of this course. An air probe near the coil shows a rise of several kelvin four times a day, a regular sawtooth. The stock barely notices: even if the whole 1,560 kJ of one defrost (the loads for 15 minutes plus the heater’s surplus) went into the 3,000 kg of produce, it would warm by 0.14 K.
Many controllers therefore hold back the temperature alarm during defrost and for a recovery time after it. That is reasonable, with one condition: the hold must end. A defrost that does not stop, because a contact has welded shut or the termination sensor has failed, keeps the heater on and the compressor off. The room then gains about
Application 2: Fan energy and a larger coil difference
Step 1: The fans
Click to reveal the fan energy
-
Fan energy.
The fans take 2.88 kWh a day, and all of it becomes heat in the room: a steady load of 120 W. ✅
-
Electricity to remove the fan heat.
The compressor uses 1.110 kWh a day for the fans’ heat. ✅
-
Total electricity caused by the fans.
The fans cost 3.99 kWh a day at the meter, 1.39 times their own consumption. ✅
-
Share of the load. The four loads are
a day, and the fans are percent of them. At 3.0 kW the fans alone explain hours of compressor running a day. ✅
Step 2: A 2 K larger difference
Click to reveal the COP change
-
New evaporating temperature.
The coil runs 2 K colder. ✅
-
Cycle COP by the rule.
The COP falls by 5.88 percent. ✅
-
System COP.
The system COP falls from 2.595 to 2.442. ✅
-
Electricity for the same cooling.
The compressor uses 6.25 percent more electricity for the same heat. For each 10 kWh of cooling it uses
kWh in place of kWh. ✅ -
Check with the full cycle. The script recomputes the cycle at −8 °C with CoolProp and gives a COP of 2.881 and a rise of 5.97 percent. The rule gives 2.873 and 6.25 percent. The rule is a slope at the design point, so it is slightly pessimistic over 2 K. ✅
-
Humidity. The saturated humidity ratio at the coil falls from 2.768 to 2.326 g/kg, and the humidity floor from 45.3 to 38.1 percent. The colder coil takes more water from the same air. ✅
Verify It in Python
The script computes the door water again from CoolProp by the same method as the door calculation, then repeats both applications. It needs CoolProp as well as numpy and matplotlib. The plot shows the cycle COP and the humidity floor against the evaporator temperature difference for a room at 4 °C.
"""Evaporator of a cold room: frost mass, defrost energy, fan energy, coil difference."""import numpy as npimport matplotlib.pyplot as pltfrom CoolProp.CoolProp import PropsSI, HAPropsSI
P_SITE = 83.5e3 # Pa, atmospheric pressure at the siteKJ_PER_KWH = 3600.0FLUID = "R134a"T_ROOM, RH_ROOM = 4.0, 0.85T_STORE, RH_STORE = 30.0, 0.60SYSTEM_COP_DESIGN = 2.595 # with the compressor motor, from the cycle lesson
def humidity_ratio(t_c, rh): return HAPropsSI("W", "T", t_c + 273.15, "P", P_SITE, "R", rh)
def cycle_cop(t_e, t_c=42.0, superheat=6.0, subcool=4.0, eta_is=0.68): """Cycle COP of the course's R134a system (temperatures in degC).""" p_e = PropsSI("P", "T", t_e + 273.15, "Q", 1, FLUID) p_c = PropsSI("P", "T", t_c + 273.15, "Q", 0, FLUID) h1 = PropsSI("H", "T", t_e + superheat + 273.15, "P", p_e, FLUID) s1 = PropsSI("S", "T", t_e + superheat + 273.15, "P", p_e, FLUID) h2s = PropsSI("H", "P", p_c, "S", s1, FLUID) h3 = PropsSI("H", "T", t_c - subcool + 273.15, "P", p_c, FLUID) return (h1 - h3) / ((h2s - h1) / eta_is)
# ---------- Water brought in at the door (same method as the door lesson) ----------w_room = humidity_ratio(T_ROOM, RH_ROOM)w_store = humidity_ratio(T_STORE, RH_STORE)v_room = HAPropsSI("V", "T", T_ROOM + 273.15, "P", P_SITE, "R", RH_ROOM)m_da = 40 * 0.5 * 30.0 / v_room # kg of dry air a daywater = m_da * (w_store - w_room) # kg a dayprint("Water from the door")print(f" dry air exchanged: {m_da:.1f} kg a day, water: {water:.2f} kg a day")
# ---------- Application 1: frost and defrost ----------T_COIL = -6.0 # degC, coil surface taken at the evaporating temperatureH_FUSION, CP_ICE, H_VAP_0 = 334.0, 2.1, 2501.0 # kJ/kg, kJ/(kg.K), kJ/kgHEATER_KW, DEFROSTS, MINUTES = 1.2, 4, 15.0PRICE = 12.00
per_kg = H_FUSION + CP_ICE * (0.0 - T_COIL)melt = water * per_kg / KJ_PER_KWH # kWh a dayheater = HEATER_KW * DEFROSTS * MINUTES / 60.0 # kWh a daysurplus = heater - meltprint("Application 1: frost and electric defrost")print(f" heat to warm and melt 1 kg of frost: {per_kg:.1f} kJ")print(f" frost {water:.2f} kg a day needs {water * per_kg:,.0f} kJ = {melt:.3f} kWh")print(f" heater energy: {heater:.2f} kWh a day")print(f" share that melts frost: {100 * melt / heater:.1f} %, " f"surplus {surplus:.3f} kWh ({100 * surplus / heater:.1f} %)")print(f" electricity to remove the surplus: {surplus / SYSTEM_COP_DESIGN:.3f} kWh")print(f" room boundary: heater adds {heater:.2f} kWh = " f"{heater * 1000 / 24:.0f} W average of load")extra = heater / SYSTEM_COP_DESIGNprint(f" electricity to remove it: {extra:.3f} kWh, " f"total for electric defrost {heater + extra:.3f} kWh a day, " f"{(heater + extra) * 365 * PRICE:,.0f} units a year")print(f" frost made from vapour: {H_VAP_0 + per_kg:.1f} kJ/kg, " f"{100 * per_kg / H_VAP_0:.1f} % more than condensing")water_curtain = water * 0.15melt_curtain = water_curtain * per_kg / KJ_PER_KWHprint(f" with a strip curtain: frost {water_curtain:.2f} kg, " f"melting {melt_curtain:.3f} kWh, " f"{100 * melt_curtain / heater:.1f} % of the same heater energy")
# ---------- Application 2: fans and the coil temperature difference ----------FANS, FAN_W = 2, 60.0fan_kwh = FANS * FAN_W * 24.0 / 1000.0fan_removal = fan_kwh / SYSTEM_COP_DESIGNdoor_product = 10.99 + 11.08 + 2.16 # kWh a day, from the door lessonprint("Application 2: fans")print(f" fan energy: {fan_kwh:.2f} kWh a day = {FANS * FAN_W:.0f} W of room load")print(f" electricity to remove the fan heat: {fan_removal:.3f} kWh")print(f" total electricity caused by the fans: {fan_kwh + fan_removal:.2f} kWh a day")print(f" share of door, product, respiration and fan load: " f"{100 * fan_kwh / (door_product + fan_kwh):.1f} % of " f"{door_product + fan_kwh:.2f} kWh")print(f" compressor hours for the fans at 3.0 kW: {fan_kwh / 3.0:.2f} h")
print("Coil temperature difference")SLOPE = 0.0294 # per K, from the COP lessoncop_design = cycle_cop(-6.0)for diff in (10.0, 12.0): t_e = T_ROOM - diff w_coil = humidity_ratio(t_e, 1.0) floor = HAPropsSI("R", "T", T_ROOM + 273.15, "P", P_SITE, "W", w_coil) print(f" difference {diff:.0f} K: T_e = {t_e:.0f} degC, cycle COP " f"{cycle_cop(t_e):.3f}, saturated W at the coil " f"{w_coil * 1000:.3f} g/kg, humidity floor {100 * floor:.1f} %")cop_rule = cop_design * (1.0 - SLOPE * 2.0)print(f" rule of 2.94 % per K: COP {cop_design:.3f} x (1 - {SLOPE * 2:.4f}) " f"= {cop_rule:.3f}, system COP " f"{SYSTEM_COP_DESIGN * (1.0 - SLOPE * 2.0):.3f}")print(f" electricity for the same cooling rises by " f"{100 * (1.0 / (1.0 - SLOPE * 2.0) - 1.0):.2f} % (rule), " f"{100 * (cop_design / cycle_cop(-8.0) - 1.0):.2f} % (CoolProp)")print(f" room air holds {w_room * 1000:.3f} g/kg at {T_ROOM:.0f} degC " f"and {100 * RH_ROOM:.0f} %")
# ---------- Plot ----------diffs = np.linspace(4.5, 14.0, 39)cops = [cycle_cop(T_ROOM - d) for d in diffs]floors = [100 * HAPropsSI("R", "T", T_ROOM + 273.15, "P", P_SITE, "W", humidity_ratio(T_ROOM - d, 1.0)) for d in diffs]fig, ax1 = plt.subplots(figsize=(8, 4.5))ax1.plot(diffs, cops, color="tab:blue")ax1.set_xlabel("room temperature minus evaporating temperature (K)")ax1.set_ylabel("cycle COP", color="tab:blue")ax2 = ax1.twinx()ax2.plot(diffs, floors, color="tab:red", linestyle="--")ax2.set_ylabel("humidity floor of the room air (%)", color="tab:red")ax1.axvline(10.0, color="gray", linewidth=0.8)ax1.set_title("A larger coil difference: lower COP and drier air (room at 4 degC)")fig.tight_layout()fig.savefig("frost_defrost_fans.png", dpi=120)print("Saved frost_defrost_fans.png")Expected output
Water from the door dry air exchanged: 624.8 kg a day, water: 9.02 kg a dayApplication 1: frost and electric defrost heat to warm and melt 1 kg of frost: 346.6 kJ frost 9.02 kg a day needs 3,128 kJ = 0.869 kWh heater energy: 1.20 kWh a day share that melts frost: 72.4 %, surplus 0.331 kWh (27.6 %) electricity to remove the surplus: 0.128 kWh room boundary: heater adds 1.20 kWh = 50 W average of load electricity to remove it: 0.462 kWh, total for electric defrost 1.662 kWh a day, 7,281 units a year frost made from vapour: 2847.6 kJ/kg, 13.9 % more than condensing with a strip curtain: frost 1.35 kg, melting 0.130 kWh, 10.9 % of the same heater energyApplication 2: fans fan energy: 2.88 kWh a day = 120 W of room load electricity to remove the fan heat: 1.110 kWh total electricity caused by the fans: 3.99 kWh a day share of door, product, respiration and fan load: 10.6 % of 27.11 kWh compressor hours for the fans at 3.0 kW: 0.96 hCoil temperature difference difference 10 K: T_e = -6 degC, cycle COP 3.053, saturated W at the coil 2.768 g/kg, humidity floor 45.3 % difference 12 K: T_e = -8 degC, cycle COP 2.881, saturated W at the coil 2.326 g/kg, humidity floor 38.1 % rule of 2.94 % per K: COP 3.053 x (1 - 0.0588) = 2.873, system COP 2.442 electricity for the same cooling rises by 6.25 % (rule), 5.97 % (CoolProp) room air holds 5.212 g/kg at 4 degC and 85 %Saved frost_defrost_fans.pngThe script carries the unrounded water mass, so it prints 3,128 kJ where the hand calculation with 9.02 kg gives 3,130 kJ after rounding. In the plot both curves fall as the coil difference grows.
Common Mistakes
- Counting only the heater’s own energy as the cost of an electric defrost. The heat is released inside the room and must be removed again: 1.20 kWh at the heater becomes 1.662 kWh at the meter.
- Adding defrosts to a timer because the coil once iced. When the frost is light, almost all the heater energy becomes room load. Reduce the water at the door first.
- Forgetting that the fans are a load. Two fans of 60 W add 2.88 kWh of heat a day and cost 3.99 kWh of electricity.
- Choosing a small coil with a large temperature difference for fresh produce. It lowers the COP and dries the product.
- Reading a low suction pressure as proof of low refrigerant charge. A frosted coil and a failed fan give the same reading. Check whether the reading recovers after a defrost.
Summary
- A coil surface below the dew point of the room air takes water out of the air, and a surface below 0 °C freezes it. This coil at −6 °C, in a room at 4 °C with a dew point of 1.7 °C, collects frost.
- The door water of 9.02 kg a day needs 346.6 kJ/kg, or 0.869 kWh a day, to be warmed and melted.
- An electric defrost of 1.20 kWh a day spends at most 72.4 percent on frost. The surplus of 0.331 kWh is room load. Against off-cycle defrost, the whole 1.20 kWh (50 W average) is added to the room, and the meter sees 1.662 kWh a day.
- Off-cycle defrost uses room air above 0 °C and adds nothing to the load. It is the normal choice at 4 °C, and its limit is slow melting under heavy frost.
- The two fans add 2.88 kWh a day (120 W) to the room and cost 3.99 kWh a day in total.
- A 2 K larger coil difference lowers the COP by about 6 percent, lowers the capacity and dries the room. Frost shows in a record as a lower suction pressure, a longer run time and then a rising room temperature, all of which recover after a defrost.
Exercises
1. A coil at −10 °C collects 5.0 kg of frost a day. Find the heat needed to warm and melt it, in kJ and kWh. Use
Answer
For each kilogram:
2. The coil of exercise 1 has a 1.5 kW defrost heater that runs 3 times a day for 20 minutes. Find the heater energy, the share that melts frost, the surplus, and the electricity needed to remove the surplus at a system COP of 2.595.
Answer
3. A larger cold room has three evaporator fans of 45 W each that run 24 hours a day. The system COP is 2.595 and electricity costs 12.00 currency units per kWh. Find the fan energy a day, the total electricity the fans cause, and the cost for a year of 365 days.
Answer
4. The fans of this lesson are rewired by an electrician to run only with the compressor, which runs 60 percent of the time. Find the new fan energy a day and the total electricity saved a day at a system COP of 2.595. Give one disadvantage of this control.
Answer
Run time:
5. The coil of this lesson has
Answer
References
- ASHRAE, ASHRAE Handbook: Refrigeration, 2022 (chapters on refrigeration load and on forced-circulation air coolers and defrost).
- W. F. Stoecker and J. W. Jones, Refrigeration and Air Conditioning, 2nd edition, McGraw-Hill, 1982.
- R. J. Dossat and T. J. Horan, Principles of Refrigeration, 5th edition, Prentice Hall, 2001.
- ASHRAE, ASHRAE Handbook: Fundamentals, 2021 (chapter on psychrometrics).
To save money, a smaller evaporator coil is fitted. It gives the same 3.0 kW, but its refrigerant must boil 12 K below the room air in place of 10 K. What happens to the fresh produce in the room?
The water the door brings in a day, taken as frost on the coil at −6 °C and spread evenly over the day. Each kilogram needs 346.6 kJ to warm to 0 °C and melt. The heater gives 1.2 kW for 15 minutes, four times a day, whatever the frost. In an off-cycle defrost the fans blow room air through the coil and no heater runs; it is slower than drawn here. The weakening air is drawn without numbers: how much it falls depends on the coil and the frost.
- Room air at 4 °C, coil at −6 °C: a 10 K difference carries the 3.0 kW.
- This coil passes 3,000 W ÷ 10 K = 300 W for each kelvin.
- Below the dew point, 1.7 °C, a surface gets wet; below 0 °C it frosts.
- At −6 °C this coil is in the frost band: frost builds on the fins.
- Room air holds 5.212 g of water per kg; air leaving the coil only 2.768 g. The coil dries the room.
- Alone, the coil would pull the room to 45.3 percent; a 12 K difference, to 38.1 percent.
Check yourself
Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.
1. A freezer room's coil runs at −28 °C and collects 5 kg of frost between defrosts. With cice = 2.1 kJ/(kg·K) and hsf = 334 kJ/kg, how much heat does it take to clear it?
2. A larger room has three evaporator fans of 45 W each, running all day. The system COP is 2.595. How much electricity do the fans cost in a day, counting everything?
3. A record shows the suction pressure falling and the compressor run time rising through the day. After each defrost the coil is clear, but the suction pressure and the run time do not recover. What does this point to?
Discussion
No comments yet. Questions, results from your own build, a better way to explain it: all welcome.
My notes on this page
Kept on this device only. Nothing is sent anywhere.
Tip: select words in the lesson, or tap a figure or an equation, to put a note right there.
Notes on earlier wording
The lesson has changed and these words are no longer in it. Your notes are kept, with the words you chose.