Door Openings, Infiltration and Product Load

Lesson 7 of 10 26 min read
Found this useful?

A cold room with good panels still runs its compressor for long hours, the evaporator is white with frost every morning, and the floor near the door is wet. The panels are not the cause. The door is opened forty times a day, and each time warm, humid air enters and cold air leaves. That air carries heat in two forms, and the larger form is hidden in its water vapour. This lesson shows how to calculate the heat and the water that the door brings in, and then adds the heat of the produce itself. #Refrigeration #Infiltration #MoistAir

Learning Objectives

By the end of this lesson, you will be able to:

  1. Describe moist air by its temperature, relative humidity, humidity ratio and enthalpy, and find these with CoolProp
  2. Estimate the mass of air that door openings exchange in a day, with a simple model whose limit you can state
  3. Calculate the infiltration load, its sensible and latent parts, and the water brought into the room
  4. Calculate the product load and the respiration load of stored produce
  5. Compare the effect of a strip curtain and of a shorter door-open time on the daily load

Real-World System Problem: The door of a produce cold room



The cold room of this course is 4.0 m × 3.0 m × 2.5 m inside, which is 30 m³, and it is held at 4 °C and about 85 percent relative humidity. It stands in a store building where the air is at 30 °C and 60 percent relative humidity. Its hinged door is 1.0 m wide and 2.0 m high. Workers open it about 40 times a day for about 30 s each time, which is 20 minutes a day in total.

When the door is open, the cold room air, heavier than the warm air outside, flows out along the floor, and warm air flows in at the top of the doorway to replace it. Nobody feels a strong wind, but in 30 s a large part of the room’s air is exchanged. This air exchange through openings is called infiltration.

The air that enters must be cooled from 30 °C to 4 °C, and it holds almost four times as much water vapour as the room air. That water leaves the air as condensate or frost on the evaporator, giving its latent heat to the room’s load. So the door decides two things: a large part of the daily load, and how fast the evaporator collects frost.

STORE, 30 °C, 60 %COLD ROOM, 4 °C, 85 %warm, humid airmixes,enters at the topcools,doorwaylosescold, dry airwaterleaves at floor
Air exchange at an open door (side view)

Fundamental Theory: Moist air and the loads it carries



Air is a mixture of dry air and water vapour

The air around us is dry air with a small amount of water vapour mixed in. The vapour is a small share of the mass, about 2 percent in the store building, but it carries a large share of the energy, because 1 kg of vapour holds about 2,500 kJ of latent heat.

When air is cooled or dried, the mass of water vapour changes and the mass of dry air does not, so every property of moist air is written for each kilogram of dry air: the one convention that keeps the calculations simple.

Four quantities describe a state of moist air.

  • The dry-bulb temperature is the temperature an ordinary thermometer reads.
  • The relative humidity is the vapour pressure in the air divided by the highest vapour pressure possible at that temperature (the saturation pressure). Air at 100 percent can hold no more vapour.
  • The humidity ratio is the mass of water vapour for each kilogram of dry air, in kg/kg or g/kg. Some books write it as .
  • The specific enthalpy is the energy that the mixture carries, in kJ for each kilogram of dry air. It includes the latent heat of the vapour.

Two more are useful. The specific volume is the volume of mixture that holds 1 kg of dry air, in m³/kg. The dew point is the temperature at which the air, when cooled, reaches 100 percent relative humidity and water starts to leave it.

Relative humidity is not the amount of water

Warm air can hold far more vapour than cold air. The room air at 85 percent sounds wetter than the store air at 60 percent, but the store air holds much more water, as a bucket 60 percent full holds more than a cup 85 percent full. Relative humidity says how near the air is to its limit; the humidity ratio says how much water is there.

The humidity ratio follows from the vapour pressure and the total pressure :

The number 0.622 is the ratio of the molar mass of water to that of dry air. The total pressure matters: at this site, about 1,600 m up where the atmosphere is at 83.5 kPa, air at 30 °C and 60 percent holds 19.7 g/kg, against 16.1 g/kg at sea level, because the same vapour is shared with less dry air.

Enthalpy of moist air

The enthalpy of moist air is the sum of the enthalpy of the dry air and the enthalpy of the vapour. A good approximation, with in °C and in kJ per kg of dry air, is

The first term is the sensible heat of the dry air; the second is the vapour, 2,501 kJ/kg of latent heat at 0 °C plus a small sensible part. This form sets for dry air and for liquid water at 0 °C. Another source may use another zero, so use only differences of enthalpy, with both values from one source.

For the two air states of this course, CoolProp gives:

PropertyRoom air, 4 °C, 85 %Store air, 30 °C, 60 %
Vapour pressure (kPa)0.6942.558
Humidity ratio (g/kg)5.21219.655
Enthalpy (kJ/kg)17.1480.45
Specific volume (m³/kg)0.96031.0747
Dew point (°C)1.721.4

All “per kg” values are for each kilogram of dry air. The store air holds 3.8 times as much water as the room air, and its dew point is 21.4 °C. Every surface in the room is colder than that, so the incoming air must lose water.

ω (g/kg)19.7dew point 21.4 °C ●● store aircools30°C,60%water leaves the air:14.4gforeachkgofdryair5.2●roomair,4°C,85%T (°C)421.430
Store air cooled to the room state

Sensible and latent parts of the load

Each kilogram of dry air that enters and is brought to the room state gives up

where is the enthalpy of the outside (store) air and that of the room air. Part of this is latent: the water that leaves the air, , multiplied by its latent heat.

Infiltration load

is the mass of dry air exchanged, in kg. The sensible part is . The water brought in is .

The common mistake is to calculate only for the air. For this room that finds less than half of the load, as Application 1 shows.

The value 2,501 kJ/kg takes the water from vapour to liquid. On a coil below 0 °C the water freezes as well, which adds 334 kJ/kg more. That extra heat, and what defrost does with it, is left for the frost calculation.

How much air a door opening exchanges

The flow through an open doorway is driven by the density difference between cold and warm air. It depends on the door’s height and width, the two air states, how long the door stays open and what stands in the doorway. For design, engineers use the doorway flow equation of Gosney and Olama, given in the ASHRAE Handbook, Refrigeration volume, with factors for the door-open time and for protective devices. This lesson uses a simpler model.

Simple air-change model of this lesson

Each door opening of about 30 s replaces half of the room’s air with store air.

is the number of openings a day, is the fraction exchanged at each opening and is the room volume.

With 40 openings this gives a day, which is 20 room volumes a day. That is a reasonable figure for a small room in busy use.

The limits are plain. The fraction 0.5 is chosen, not derived. A real exchange grows with the door’s size and the temperature difference, and not in a straight line with time, because the flow slows as the room fills with warm air: a door left open for ten minutes does not exchange twenty half-rooms. Use the model to see the size of the load and what changes it, and the handbook method to select equipment.

The mass of dry air follows from the volume. The air that leaves is room air, so the model divides by its specific volume:

Strip curtains and door discipline

A strip curtain is a row of overlapping clear plastic strips hanging in the doorway; people and trolleys push through and it closes behind them. Its effectiveness is the fraction of the infiltration it stops, typically 0.8 to 0.9 in good condition; this lesson uses 0.85.

Strips that are missing, tied back or stiff with age give a much lower value. The other measure costs nothing: open the door less, and for less time. In the simple model, halving the open time of each opening halves the fraction .

Product load and respiration

Warm produce that enters the room must be cooled. This is sensible heat, , and for the daily 500 kg from 25 °C to 4 °C the first-law calculation of this course gave 39,900 kJ, which is 11.08 kWh a day or 462 W on average.

Fresh fruit and vegetables are alive: they consume their own sugars and oxygen and release heat, the heat of respiration, for as long as they are stored. The rate depends strongly on the kind of produce and its temperature, and is given in watts for each kilogram:

This course takes , a typical figure for moderately respiring produce near 4 °C. Other produce releases several times more, and warm produce far more than cold, which is one reason to cool it quickly.

COLDROOM4 °Cdoor airsensible (air cooled 26 K)600 m³/daylatent (9 kg of water)producesensible (500 kg cooled 21 K)500 kg/daystoredrespiration (3,000 kg alive)3,000 kg
Where the daily heat of this lesson comes from

Application 1: The infiltration load of the door



Step 1: The differences between the two air states

Click to reveal the differences
  1. Enthalpy difference.

    Each kilogram of dry air that enters brings 63.31 kJ that the evaporator must remove. ✅

  2. Humidity ratio difference.

    The script, with unrounded values, gives 14.444 g/kg, and the next steps use that figure. Each kilogram of dry air brings 14.44 g of water that must leave the air. ✅

Step 2: The air exchanged in a day

Click to reveal the air mass
  1. Volume.

    The door exchanges 600 m³ a day, 20 times the room volume. ✅

  2. Mass of dry air.

    About 625 kg of dry air passes through the doorway each day. ✅

Step 3: The load and its two parts

Click to reveal the load
  1. Total infiltration load.

    The door adds 10.99 kWh of heat a day. ✅

  2. Average over the day.

    The average is 458 W. ✅

  3. Water brought in.

    The door brings 9.02 kg of water into the room each day. ✅

  4. Latent part.

    This is 57.1 percent of the infiltration load. ✅

  5. Sensible part, by difference.

    This is 42.9 percent of the load. ✅

Step 4: Check a second way

Click to reveal the checks
  1. Enthalpy from the approximate formula. For the store air, . For the room air, . The difference is 63.33 kJ/kg, against 63.31 from CoolProp. ✅

  2. Sensible part from the dry air alone. . The 4.72 kWh found by difference is a little larger, because the vapour itself is also cooled. The two agree within 4 percent. ✅

  3. Each opening. One opening exchanges 15 m³, which is 15.62 kg of dry air. It brings and 0.226 kg of water. Forty openings give 39,560 kJ and 9.02 kg. ✅

  4. Python. The script below prints 624.8 kg, 10.99 kWh, 458 W, 6.27 kWh latent, 4.72 kWh sensible and 9.02 kg of water. ✅

What the temperature record sees at a door opening

The air and the product react very differently. In the simple model the air just after an opening is half store air: about 17 °C if it were fully mixed, 13 K above the setting. The produce hardly moves: even if all 989 kJ of one opening went into the 3,000 kg of stock, it would warm by K.

So a bare probe in the air shows a spike at every opening, and an alarm set on it sounds every busy hour. People then learn to ignore the alarm, which is worse than having none. Two remedies are used, often together:

  • A buffered probe: the sensor sits in a small bottle of glycol or a block that behaves like product. With a time constant of 20 minutes, a 13 K air spike that fades in 3 to 5 minutes lifts it by only 1.4 to 2.1 K. It reports what the product feels, not what the doorway feels.
  • An alarm delay: the alarm sounds only if the reading stays above its limit for a set time, for example 15 to 30 minutes, long enough for the room to recover from a normal opening and short enough to catch a door left open.

Keep the raw air reading in the record as well, next to the door events. An auditor asks for the product’s temperature history; an engineer needs the air to see why it moved.

Application 2: Product, respiration and two door measures



Step 1: Product and respiration

Click to reveal the two loads
  1. Product load.

    Over 24 hours this is , or 462 W on average. ✅

  2. Respiration load.

    The stored produce releases 90 W at all hours. ✅

  3. Respiration energy in a day.

    Respiration adds 2.16 kWh a day. ✅

Step 2: The strip curtain and the shorter open time

Click to reveal the door measures
  1. Strip curtain.

    The load falls to 1.65 kWh a day (69 W), and the water to . The curtain saves of cooling. ✅

  2. Open time halved. The fraction exchanged falls from 0.5 to 0.25.

    The load falls to 5.49 kWh a day (229 W), and the water to 4.51 kg. The saving is 5.49 kWh of cooling. ✅

  3. Both measures.

    The load falls to 0.82 kWh a day (34 W), and the water to 0.68 kg. The saving is 10.16 kWh of cooling. ✅

  4. Electricity saved. Divide the cooling saved by the system COP.

    These are the daily savings for the curtain, the shorter open time and both. ✅

  5. Yearly value. Multiply by 365 days and by 12.00 units per kWh. The script, with unrounded values, gives 15,765 units a year for the curtain, 9,274 for the shorter open time and 17,156 for both. ✅

Step 3: The load table and a check

Click to reveal the table
  1. Table of the loads of this lesson, with the door as used.

    LoadkWh a dayW average
    Infiltration at the door10.99458
    Product, 500 kg a day11.08462
    Respiration, 3,000 kg stored2.1690
    Total of these three24.231,010

    The three loads give 24.23 kWh a day. ✅

  2. Check by the watts. , and , which agrees with the table within rounding. ✅

  3. Compressor hours. At 3.0 kW these loads need hours of running a day. With the curtain the total is , which is 4.96 hours. ✅

  4. Python. The script prints the same table, the four door cases and the yearly values. ✅

Verify It in Python



The script takes the two air states from CoolProp at 83.5 kPa and repeats both applications. It needs CoolProp as well as numpy and matplotlib. The plot shows how the infiltration load of the same 600 m³ a day changes with the temperature and humidity of the store air.

door_infiltration_load.py
"""Door openings on a cold room: moist air, infiltration load, product load."""
import numpy as np
import matplotlib.pyplot as plt
from CoolProp.CoolProp import HAPropsSI
P_SITE = 83.5e3 # Pa, atmospheric pressure at the site
KJ_PER_KWH = 3600.0
H_VAP_0 = 2501.0 # kJ/kg, latent heat of water vapour at 0 degC
def moist_air(t_c, rh):
"""Enthalpy (kJ/kg dry air), humidity ratio, volume (m3/kg dry air), dew point."""
args = ("T", t_c + 273.15, "P", P_SITE, "R", rh)
h = HAPropsSI("H", *args) / 1000.0
w = HAPropsSI("W", *args)
v = HAPropsSI("V", *args)
dew = HAPropsSI("D", *args) - 273.15
return h, w, v, dew
# ---------- Moist air states ----------
h_r, w_r, v_r, dew_r = moist_air(4.0, 0.85) # room air
h_o, w_o, v_o, dew_o = moist_air(30.0, 0.60) # surrounding air
dh, dw = h_o - h_r, w_o - w_r
print("Moist air at 83.5 kPa (CoolProp HAPropsSI)")
print(f" room, 4 degC 85 %: h = {h_r:.2f} kJ/kg, W = {w_r * 1000:.3f} g/kg, "
f"v = {v_r:.4f} m3/kg, dew point {dew_r:.1f} degC")
print(f" store, 30 degC 60 %: h = {h_o:.2f} kJ/kg, W = {w_o * 1000:.3f} g/kg, "
f"v = {v_o:.4f} m3/kg, dew point {dew_o:.1f} degC")
print(f" differences: {dh:.2f} kJ/kg, {dw * 1000:.3f} g/kg (per kg of dry air)")
# ---------- Application 1: infiltration at the door ----------
ROOM_VOLUME = 4.0 * 3.0 * 2.5 # m3
OPENINGS = 40 # door openings a day
FRACTION = 0.5 # share of the room air exchanged per opening
def infiltration(volume_m3):
"""Daily figures for a volume of room air replaced by store air."""
m_da = volume_m3 / v_r # kg of dry air
total = m_da * dh # kJ
latent = m_da * dw * H_VAP_0 # kJ
return m_da, total, latent, total - latent, m_da * dw
volume = OPENINGS * FRACTION * ROOM_VOLUME
m_da, q_inf, q_lat, q_sen, water = infiltration(volume)
print("Application 1: infiltration load")
print(f" air exchanged: {volume:.0f} m3 a day "
f"({volume / ROOM_VOLUME:.0f} room volumes)")
print(f" dry air exchanged: {m_da:.1f} kg a day")
print(f" total: {q_inf:,.0f} kJ = {q_inf / KJ_PER_KWH:.2f} kWh a day "
f"= {q_inf / 86.4:.0f} W average")
print(f" latent: {q_lat:,.0f} kJ = {q_lat / KJ_PER_KWH:.2f} kWh "
f"({100 * q_lat / q_inf:.1f} %)")
print(f" sensible: {q_sen:,.0f} kJ = {q_sen / KJ_PER_KWH:.2f} kWh "
f"({100 * q_sen / q_inf:.1f} %)")
print(f" water brought in: {water:.2f} kg a day")
print(f" check, dry-air sensible estimate: "
f"{m_da * 1.006 * 26.0 / KJ_PER_KWH:.2f} kWh")
print(f" rate while the door is open: {q_inf / (OPENINGS * 30.0):.1f} kW")
# ---------- Application 2: product, respiration, and two door measures ----------
q_prod = 500.0 * 3.8 * (25.0 - 4.0) / KJ_PER_KWH # kWh a day
q_resp = 3000.0 * 0.03 * 24.0 / 1000.0 # kWh a day
CURTAIN = 0.85 # strip curtain effectiveness
SYSTEM_COP, PRICE = 2.595, 12.00
base = q_inf / KJ_PER_KWH
cases = [("door as used", 1.0),
("strip curtain", 1.0 - CURTAIN),
("open time halved", 0.5),
("both", 0.5 * (1.0 - CURTAIN))]
print("Application 2: product and door measures")
print(f" product: {q_prod:.2f} kWh a day = {q_prod * 1000 / 24:.0f} W")
print(f" respiration: {q_resp:.2f} kWh a day = {q_resp * 1000 / 24:.0f} W")
for name, factor in cases:
load = base * factor
saved = base - load
print(f" {name:17s}: {load:5.2f} kWh, {load * 1000 / 24:3.0f} W, "
f"water {water * factor:4.2f} kg, saves "
f"{saved / SYSTEM_COP:4.2f} kWh electricity a day, "
f"{saved / SYSTEM_COP * 365 * PRICE:6,.0f} units a year")
print("Load table (kWh a day, W average)")
rows = [("infiltration", base), ("product", q_prod), ("respiration", q_resp)]
for name, kwh in rows:
print(f" {name:13s} {kwh:6.2f} {kwh * 1000 / 24:5.0f}")
total = sum(k for _, k in rows)
print(f" {'total':13s} {total:6.2f} {total * 1000 / 24:5.0f}")
print(f" compressor hours at 3.0 kW: {total / 3.0:.2f} h")
# ---------- Plot: the infiltration load against the store air ----------
temps = np.linspace(20.0, 38.0, 60)
fig, ax = plt.subplots(figsize=(8, 4.5))
for rh in (0.4, 0.6, 0.8):
load = []
for t in temps:
h, w, _, _ = moist_air(t, rh)
load.append(m_da * (h - h_r) / KJ_PER_KWH)
ax.plot(temps, load, label=f"store air at {100 * rh:.0f} % relative humidity")
ax.plot(30.0, base, "o", color="black")
ax.annotate(f"{base:.2f} kWh", (30.0, base), textcoords="offset points",
xytext=(8, -14))
ax.set_xlabel("store air temperature (degC)")
ax.set_ylabel("infiltration load (kWh a day)")
ax.set_title("600 m3 of room air exchanged a day, room at 4 degC and 85 %")
ax.legend()
fig.tight_layout()
fig.savefig("door_infiltration_load.png", dpi=120)
print("Saved door_infiltration_load.png")

Expected output

Moist air at 83.5 kPa (CoolProp HAPropsSI)
room, 4 degC 85 %: h = 17.14 kJ/kg, W = 5.212 g/kg, v = 0.9603 m3/kg, dew point 1.7 degC
store, 30 degC 60 %: h = 80.45 kJ/kg, W = 19.655 g/kg, v = 1.0747 m3/kg, dew point 21.4 degC
differences: 63.31 kJ/kg, 14.444 g/kg (per kg of dry air)
Application 1: infiltration load
air exchanged: 600 m3 a day (20 room volumes)
dry air exchanged: 624.8 kg a day
total: 39,559 kJ = 10.99 kWh a day = 458 W average
latent: 22,571 kJ = 6.27 kWh (57.1 %)
sensible: 16,988 kJ = 4.72 kWh (42.9 %)
water brought in: 9.02 kg a day
check, dry-air sensible estimate: 4.54 kWh
rate while the door is open: 33.0 kW
Application 2: product and door measures
product: 11.08 kWh a day = 462 W
respiration: 2.16 kWh a day = 90 W
door as used : 10.99 kWh, 458 W, water 9.02 kg, saves 0.00 kWh electricity a day, 0 units a year
strip curtain : 1.65 kWh, 69 W, water 1.35 kg, saves 3.60 kWh electricity a day, 15,765 units a year
open time halved : 5.49 kWh, 229 W, water 4.51 kg, saves 2.12 kWh electricity a day, 9,274 units a year
both : 0.82 kWh, 34 W, water 0.68 kg, saves 3.92 kWh electricity a day, 17,156 units a year
Load table (kWh a day, W average)
infiltration 10.99 458
product 11.08 462
respiration 2.16 90
total 24.23 1010
compressor hours at 3.0 kW: 8.08 h
Saved door_infiltration_load.png

The script works with unrounded values, so its kilojoule figures differ from the hand calculation by one or two in the last place (39,559 against 39,560). In the plot the three lines spread apart as the store warms, so the humidity of the store matters most on a hot day.

Common Mistakes



  • Calculating the door load from the temperature difference alone. For this room the dry-air sensible estimate is 4.54 kWh a day and the true load is 10.99 kWh, because 57 percent of it is latent.
  • Reading relative humidity as the amount of water. The room air at 85 percent holds 5.2 g/kg and the store air at 60 percent holds 19.7 g/kg.
  • Using a sea-level psychrometric chart at a high site. At 83.5 kPa the same temperature and relative humidity give a higher humidity ratio and a higher enthalpy for each kilogram of dry air.
  • Treating the simple air-change fraction as a measured fact. It is a chosen value. For equipment selection use the doorway flow method of the ASHRAE Handbook.

Summary



  • Moist air is dry air plus water vapour, and its properties are written for each kilogram of dry air. Enthalpy includes the latent heat of the vapour, about 2,501 kJ/kg.
  • At 83.5 kPa the store air (30 °C, 60 percent) has an enthalpy 63.31 kJ/kg above the room air (4 °C, 85 percent) and holds 14.44 g/kg more water.
  • With the simple model of half a room volume at each of 40 openings, the door exchanges 600 m³, or 624.8 kg of dry air, a day. The infiltration load is 10.99 kWh a day (458 W average), of which 6.27 kWh is latent and 4.72 kWh is sensible, and it brings 9.02 kg of water.
  • The product load is 11.08 kWh a day (462 W) and respiration is 2.16 kWh a day (90 W). The three loads together are 24.23 kWh a day.
  • A strip curtain at 0.85 reduces the infiltration to 1.65 kWh a day, and halving the door-open time reduces it to 5.49 kWh. The air-change fraction is a simplification, so these figures show sizes, not measurements.

Exercises



Use the values of this lesson where a problem does not give its own: room air , , , and 624.8 kg of dry air a day.

1. A cold store holds 5,000 kg of produce with a heat of respiration of 0.05 W/kg. Find the respiration load in watts and in kWh a day.

Answer

W. In a day, kWh.

2. On another day 800 kg of produce enters at 28 °C and is cooled to 4 °C, with . Find the product load in kJ, in kWh, and as an average over 24 hours.

Answer

kJ, which is kWh. The average is kW, or 844 W.

3. On a hot, humid day the store air is at 36 °C and 60 percent relative humidity. CoolProp gives and at 83.5 kPa. With the same 624.8 kg of dry air a day, find the infiltration load and the water brought in.

Answer

kJ/kg, so kJ, which is 15.74 kWh a day. Water: kg a day. A store that is 6 K warmer raises the door load by 43 percent.

4. On a cooler, more humid day the store air is at 28 °C and 70 percent, for which CoolProp gives and . Find the infiltration load, its latent part and the water brought in, and compare them with the design day.

Answer

kJ, which is 10.98 kWh, almost the same as the 10.99 kWh of the design day. Water: kg. Latent: kJ, which is 6.61 kWh. The air is 2 K cooler, but it carries more water, so the load is the same and the frost is greater.

5. The door is opened 60 times a day instead of 40, with the same fraction of 0.5 and the design air states. A strip curtain with an effectiveness of 0.80 is then fitted. Find the infiltration load before and after, and the yearly value of the saving at a system COP of 2.595 and 12.00 currency units per kWh.

Answer

Volume: m³, so kg. Load: kJ, which is 16.48 kWh a day. With the curtain: kWh. Cooling saved: 13.19 kWh a day. Electricity saved: kWh a day, which is units a year.

References



  • ASHRAE, ASHRAE Handbook: Refrigeration, 2022 (chapter on refrigeration load, which gives the doorway infiltration method of Gosney and Olama).
  • ASHRAE, ASHRAE Handbook: Fundamentals, 2021 (chapter on psychrometrics).
  • W. F. Stoecker and J. W. Jones, Refrigeration and Air Conditioning, 2nd edition, McGraw-Hill, 1982.
  • Y. A. Çengel and M. A. Boles, Thermodynamics: An Engineering Approach, 8th edition, McGraw-Hill, 2015 (chapter on gas-vapour mixtures).


© 2021-2026 SiliconWit®. All rights reserved.
Predict first

Each time the door opens, warm, humid store air (30 °C, 60 percent) replaces cold room air (4 °C). The machine must cool that air to 4 °C and also take out the water vapour it carries. Which part of the door's load is larger?

5.2 g/kg19.7 g/kg room air, 4 °C, 85 %store air, 30 °C, 60 % Almost four times the water
temperature onlythe whole load 4.54 kWhair 4.72water 6.27 10.99 kWh a day, 9 kg of water
Try it: what the door costs in a day

Door load, cooling a day
Water brought in a day
Electricity for it, a year

The lesson's simple model: each 30 s opening replaces half of the 30 m³ room with store air at 30 °C and 60 percent, and a shorter or longer opening exchanges in proportion. Each kilogram of dry air brings 63.31 kJ and 14.44 g of water (CoolProp at 83.5 kPa). Electricity uses the system COP of 2.595 and 12.00 currency units per kWh. Long openings are where the model is weakest: the real flow slows as the room fills with warm air.

Watch it build: store air cooled to the room
water, g/kg430air temperature, °C saturated room 5.2 g store 19.7 g dew point 21.4 °C 14.4 g leaves 63.3 kJ 36.127.2 waterair air alone, × 26 K:26.2 of 63.3 kJ
  1. Water in the air against temperature. Room air at 4 °C and 85 percent holds 5.2 g/kg.
  2. Store air at 30 °C and 60 percent holds 19.7 g/kg, 3.8 times as much.
  3. Cooled, it reaches its dew point at 21.4 °C; on the way to the room 14.4 g/kg leaves it.
  4. Each kilogram of dry air gives up 80.45 − 17.14 = 63.3 kJ: 36.1 kJ is the water's latent heat, 27.2 kJ the air's.
  5. Counting the air alone, 1.006 × 26 = 26.2 kJ, finds less than half.
Store, 30 °C, 60 % Cold room, 4 °C, 85 % doorway warm, humid air enters at the top cold, dry air leaves at the floor mixes, cools, loses water
Air exchange at an open door (side view)
Cold room 4 °C door air 600 m³ a day sensible: air cooled 26 K latent: 9 kg of water produce 500 kg a day sensible: 500 kg cooled 21 K stored 3,000 kg respiration: 3,000 kg alive
Where the daily heat of this lesson comes from

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. Without a curtain the door brings in 10.99 kWh a day. Workers tie half the strips of the new curtain back, and its effectiveness falls from 0.85 to 0.4. What does the door bring in now?

2. On a rainy day the store air is at 25 °C and 80 percent. On a hot day it is at 30 °C and 60 percent. The site is at 83.5 kPa. For each kilogram of dry air that enters, which day brings more water into the room?

3. A strip curtain saves 9.34 kWh of cooling a day. The system COP is 2.595 and electricity costs 12.00 currency units per kWh. What does the curtain save in a year of 365 days?