Carnot COP for refrigeration
Both temperatures are absolute, in kelvin. The denominator is the lift.
The electricity bill of a cold room rises by a sixth in the hot season, and nobody has changed anything. In another store, someone sets the thermostat 2 °C colder than the produce needs “to be safe”, and the owner pays for that every day of the year without knowing the amount. Both costs have the same cause: the refrigeration system must lift heat through a larger temperature difference, and each kelvin of lift has a price. This lesson calculates that price for one real system. You will compare the cycle with the best any machine could do, and you will turn a change of temperature into run hours, kilowatt-hours and money. #Refrigeration #COP #EnergyEfficiency
By the end of this lesson, you will be able to:
The cold room of this course is held at 4 °C inside a store building. Its R134a system evaporates at −6 °C and condenses at 42 °C when the building air is at 30 °C. At that design point the cycle has a COP of 3.05 and gives 3.0 kW of cooling for 1.16 kW of electricity at the compressor.
None of those numbers is fixed. On a hot day the building air reaches 36 °C, and the condenser, about 12 K warmer than the air, runs at 48 °C. With the thermostat at 2 °C, the evaporator, about 10 K colder than the room, runs at −8 °C. Either way the compressor works across a larger pressure difference.
The owner sees none of this: the room still holds its temperature. What changes is how long the compressor runs each day and how much power it draws while it runs. The task is to put numbers on both.
The COP (coefficient of performance) of a refrigeration cycle is the heat removed divided by the work supplied:
where
The temperature lift,
The second law of thermodynamics sets an upper limit, the Carnot COP, on any machine that moves heat from
Carnot COP for refrigeration
Both temperatures are absolute, in kelvin. The denominator is the lift.
For the design point,
The common mistake is a Celsius numerator:
Before any refrigerant is chosen, the formula shows two things: the COP falls when the lift rises, and for the same lift a colder evaporator gives a lower COP, because the numerator is smaller.
The real cycle reaches 3.05, which is 55 percent of the Carnot value. The gap has three sources.
Compression losses. The compressor has an isentropic efficiency of 0.68. With an ideal compressor the same cycle would reach 4.49. This is the largest single loss.
Throttling. The expansion valve lowers the pressure without recovering any work, and about 30 percent of the refrigerant becomes flash gas that does no cooling. A Carnot machine would expand the liquid in a device that returns work.
Discharge superheat. This is not the superheat at the evaporator outlet; it is how far the gas leaving the compressor is above the condensing temperature: 67.7 °C against 42 °C, 25.7 K. Part of the heat is therefore rejected across a large temperature difference, after work spent reaching a temperature the condenser did not need. The suction superheat (6 K at the compressor inlet) adds to this a little, because it makes the vapour less dense and the compression start warmer.
Throttling and superheat bring the COP from 5.57 to 4.49 even with a perfect compressor; the real compressor brings it to 3.05, and the motor brings the system COP to 2.59.
One more loss sits outside the cycle. The room only needs heat lifted from 4 °C to 30 °C, 26 K, for which a Carnot machine would reach
Carnot, 4 °C to 30 °C 10.66 ##################### Carnot, −6 °C to 42 °C 5.57 ########### Cycle, ideal compressor 4.49 ######### Cycle, real compressor 3.05 ###### System, with the motor 2.59 #####The table holds the evaporating temperature at −6 °C, the superheat at 6 K, the subcooling at 4 K and the isentropic efficiency at 0.68, and moves only the condensing temperature. Every value is computed with CoolProp’s reference equation of state for R134a. The capacity and input columns use the compressor model explained below.
| Carnot COP | Cycle COP | Capacity (kW) | Electrical input (kW) | |
|---|---|---|---|---|
| 36 | 6.36 | 3.629 | 3.180 | 1.031 |
| 38 | 6.07 | 3.420 | 3.120 | 1.073 |
| 40 | 5.81 | 3.229 | 3.060 | 1.115 |
| 42 | 5.57 | 3.053 | 3.000 | 1.156 |
| 44 | 5.34 | 2.889 | 2.939 | 1.197 |
| 46 | 5.14 | 2.738 | 2.878 | 1.237 |
| 48 | 4.95 | 2.596 | 2.817 | 1.276 |
| 50 | 4.77 | 2.464 | 2.755 | 1.315 |
| 52 | 4.61 | 2.340 | 2.692 | 1.353 |
| 54 | 4.45 | 2.223 | 2.629 | 1.391 |
A higher condensing temperature hurts in three ways at once: the COP falls, the capacity falls and the input power rises.
This table holds the condensing temperature at 42 °C and moves only the evaporating temperature.
| Carnot COP | Cycle COP | Capacity (kW) | Electrical input (kW) | |
|---|---|---|---|---|
| −14 | 4.63 | 2.440 | 2.146 | 1.035 |
| −12 | 4.84 | 2.576 | 2.338 | 1.068 |
| −10 | 5.06 | 2.722 | 2.544 | 1.099 |
| −8 | 5.30 | 2.881 | 2.764 | 1.129 |
| −6 | 5.57 | 3.053 | 3.000 | 1.156 |
| −4 | 5.85 | 3.240 | 3.252 | 1.181 |
| −2 | 6.16 | 3.445 | 3.521 | 1.202 |
| 0 | 6.50 | 3.670 | 3.807 | 1.221 |
| 2 | 6.88 | 3.917 | 4.113 | 1.235 |
A lower evaporating temperature lowers the COP and lowers the capacity strongly: at −14 °C the system gives only 72 percent of its design capacity. The input power falls a little, which misleads many people: the compressor draws less but runs much longer, so the energy used rises.
Take the slope of each table across the design point, from 2 K below to 2 K above.
Condensing side, from 40 °C to 44 °C:
Evaporating side, from −8 °C to −4 °C:
This system's figure
Near its design point, this R134a system loses about 2.8 percent of its COP for each kelvin of higher condensing temperature, and about 2.9 percent for each kelvin of lower evaporating temperature. A fair short form is 3 percent per kelvin of lift, on either side.
This is not a universal law: it comes from one refrigerant, one design point and one fixed compressor efficiency, and other systems commonly give 2 to 4 percent per kelvin. It is also a slope at one point, accurate for a change of a few kelvin. Over 6 K the simple multiplication predicts a loss of 16.7 percent, and the table gives 15.0 percent.
A kelvin on the evaporating side costs slightly more than a kelvin on the condensing side. The Carnot formula shows why: lowering
A piston or scroll compressor at fixed speed draws in the same volume of vapour every second, as a cup scoops the same volume whether it scoops thick or thin soup. So this lesson takes the inlet volume flow
Constant-displacement model
When the evaporating temperature falls, the suction pressure falls and the vapour is less dense, so each stroke carries less mass: that is why the capacity falls so quickly in the second table. When only the condensing temperature rises, the inlet state and the mass flow do not change, and the capacity falls only because each kilogram reaches the evaporator with more flash gas.
The room does not need a power. It needs a daily load, an amount of heat in kWh of cooling removed each day, and the compressor runs until that load is met.
The second form carries a useful message. For a fixed load, the capacity decides how many hours the compressor runs, and the COP alone decides how many kilowatt-hours it uses.
Carnot COP. The lift is now
The limit itself has fallen, from 5.57 to 4.95. ✅
Refrigerating effect. The warmer liquid carries more enthalpy into the expansion valve.
This is 6.1 percent less than the 146.85 kJ/kg of the design point. ✅
Specific work.
This is 10.4 percent more than the 48.11 kJ/kg of the design point. ✅
Cycle COP.
The COP has fallen from 3.05 to 2.60, a loss of 15 percent. ✅
Mass flow. The inlet state has not changed, so the density and the mass flow are the same as at design:
Capacity.
The system has lost 0.183 kW of cooling. ✅
Electrical input.
The compressor draws 0.120 kW more than at design. ✅
System COP.
At design it was
Design day.
✅
Hot day.
✅
Difference. The compressor runs 0.78 h longer (47 minutes) and uses
Check a second way. Daily energy is the load divided by the system COP.
Both agree with the hours method, and the Python script prints the same values. ✅
Refrigerating effect.
This is almost the same as at design, because state 3 has not moved. ✅
Specific work. The pressure ratio is now
(The values are carried unrounded, so the last digit can differ by one from a calculation with the rounded figures.) ✅
Cycle COP.
The COP falls from 3.053 to 2.881, a loss of 5.6 percent for 2 K. The slope from the table predicted
Mass flow. The suction vapour is less dense, and the volume flow is fixed.
The compressor moves 7.1 percent less refrigerant. ✅
Capacity.
✅
Electrical input.
The input is 0.027 kW lower than at design. On an ammeter the colder setting looks slightly better. ✅
Run hours and daily energy.
The compressor runs 1.02 h longer each day. ✅
Extra energy per day.
Energy per year.
The colder setting uses 303 kWh more in a year. (The products use the unrounded daily values.) ✅
Cost per year.
The extra cost is 3,630 currency units a year. ✅
Check a second way. For the same load, the energy ratio is the inverse of the COP ratio.
The energy rises by 6.0 percent, which agrees with step 1. The motor efficiency cancels, so the cycle COP ratio is enough. ✅
The script computes the Carnot and cycle COP, both sensitivity tables with capacity and input power, the slopes at the design point, and the daily and yearly figures for both applications. It plots the cycle COP and the Carnot COP against each temperature. It needs CoolProp as well as numpy and matplotlib: pip install CoolProp.
"""COP, capacity and input power of the cold room cycle as the two temperatures move."""import numpy as npimport matplotlib.pyplot as pltfrom CoolProp.CoolProp import PropsSI
FLUID = "R134a"SUPERHEAT, SUBCOOLING = 6.0, 4.0 # KETA_IS, ETA_MOTOR = 0.68, 0.85T_E0, T_C0 = -6.0, 42.0 # design point, degCCAPACITY0 = 3.0 # kW at the design pointDAILY_LOAD = 36.0 # kWh of cooling a day (given)PRICE = 12.00 # currency units per kWhK0 = 273.15
def cycle(t_e, t_c, eta_is=ETA_IS): """Return q_e (kJ/kg), w (kJ/kg) and suction density (kg/m3).""" p_e = PropsSI("P", "T", t_e + K0, "Q", 1, FLUID) p_c = PropsSI("P", "T", t_c + K0, "Q", 0, FLUID) t1 = t_e + SUPERHEAT + K0 h1 = PropsSI("H", "T", t1, "P", p_e, FLUID) s1 = PropsSI("S", "T", t1, "P", p_e, FLUID) rho1 = PropsSI("D", "T", t1, "P", p_e, FLUID) h2s = PropsSI("H", "P", p_c, "S", s1, FLUID) h2 = h1 + (h2s - h1) / eta_is h3 = PropsSI("H", "T", t_c - SUBCOOLING + K0, "P", p_c, FLUID) return (h1 - h3) / 1e3, (h2 - h1) / 1e3, rho1
Q_E0, W0, RHO0 = cycle(T_E0, T_C0)VOLUME_FLOW = CAPACITY0 / Q_E0 / RHO0 # m3/s, fixed by the compressor
def machine(t_e, t_c): """Constant displacement: mass flow follows the suction density.""" q_e, w, rho1 = cycle(t_e, t_c) m = VOLUME_FLOW * rho1 capacity = m * q_e elec = m * w / ETA_MOTOR return q_e / w, capacity, elec
def carnot(t_e, t_c): return (t_e + K0) / (t_c - t_e)
q_ideal, w_ideal, _ = cycle(T_E0, T_C0, eta_is=1.0)print(f"Carnot COP at design: {carnot(T_E0, T_C0):.3f}")print(f"Cycle COP, ideal compressor: {q_ideal / w_ideal:.3f}")print(f"Cycle COP, real compressor: {Q_E0 / W0:.3f} " f"({100 * Q_E0 / W0 / carnot(T_E0, T_C0):.1f} % of Carnot)")print(f"System COP with the motor: {Q_E0 / W0 * ETA_MOTOR:.3f}")
print("Condensing temperature sweep, evaporating -6 degC")print(" T_c Carnot COP capacity kW input kW")tc_list = np.arange(36, 55, 2)cop_tc = []for t_c in tc_list: cop, cap, elec = machine(T_E0, t_c) cop_tc.append(cop) print(f" {t_c:3d} {carnot(T_E0, t_c):5.2f} {cop:5.3f} {cap:7.3f} {elec:7.3f}")
print("Evaporating temperature sweep, condensing 42 degC")print(" T_e Carnot COP capacity kW input kW")te_list = np.arange(-14, 3, 2)cop_te = []for t_e in te_list: cop, cap, elec = machine(t_e, T_C0) cop_te.append(cop) print(f" {t_e:3d} {carnot(t_e, T_C0):5.2f} {cop:5.3f} {cap:7.3f} {elec:7.3f}")
cop0 = Q_E0 / W0slope_tc = (machine(T_E0, 44)[0] - machine(T_E0, 40)[0]) / 4slope_te = (machine(-4, T_C0)[0] - machine(-8, T_C0)[0]) / 4print(f"COP change per kelvin of condensing temperature: {slope_tc:+.4f} " f"({100 * slope_tc / cop0:+.2f} %)")print(f"COP change per kelvin of evaporating temperature: {slope_te:+.4f} " f"({100 * slope_te / cop0:+.2f} %)")
def day(name, t_e, t_c): cop, cap, elec = machine(t_e, t_c) hours = DAILY_LOAD / cap energy = hours * elec print(f"{name}: COP {cop:.3f}, capacity {cap:.3f} kW, input {elec:.3f} kW, " f"system COP {cap / elec:.3f}") print(f" run {hours:.2f} h/day, {energy:.2f} kWh/day, " f"{energy * 365:.0f} kWh/year, cost {energy * 365 * PRICE:.0f} per year") return energy
e_design = day("Design (-6, 42)", T_E0, T_C0)e_hot = day("Hot day (-6, 48)", T_E0, 48.0)e_cold = day("Room at 2 degC (-8, 42)", -8.0, T_C0)print(f"Hot day against design: {100 * (e_hot / e_design - 1):+.1f} % energy")print(f"Colder room against design: {e_cold - e_design:+.3f} kWh/day, " f"{(e_cold - e_design) * 365:+.1f} kWh/year, " f"{(e_cold - e_design) * 365 * PRICE:+.0f} per year " f"({100 * (e_cold / e_design - 1):+.1f} %)")
# ---------- Plot ----------fig, ax = plt.subplots(1, 2, figsize=(10, 4.5), sharey=True)ax[0].plot(tc_list, cop_tc, "o-", label="cycle")ax[0].plot(tc_list, [carnot(T_E0, t) for t in tc_list], "--", label="Carnot")ax[0].set_xlabel("condensing temperature (degC)")ax[0].set_ylabel("COP")ax[0].set_title("Evaporating at -6 degC")ax[0].legend()ax[1].plot(te_list, cop_te, "o-", label="cycle")ax[1].plot(te_list, [carnot(t, T_C0) for t in te_list], "--", label="Carnot")ax[1].set_xlabel("evaporating temperature (degC)")ax[1].set_title("Condensing at 42 degC")ax[1].legend()for a in ax: a.grid(True, linewidth=0.3)fig.tight_layout()fig.savefig("cop_sensitivity.png", dpi=120)print("Saved cop_sensitivity.png")Expected output
Carnot COP at design: 5.566Cycle COP, ideal compressor: 4.489Cycle COP, real compressor: 3.053 (54.8 % of Carnot)System COP with the motor: 2.595Condensing temperature sweep, evaporating -6 degC T_c Carnot COP capacity kW input kW 36 6.36 3.629 3.180 1.031 38 6.07 3.420 3.120 1.073 40 5.81 3.229 3.060 1.115 42 5.57 3.053 3.000 1.156 44 5.34 2.889 2.939 1.197 46 5.14 2.738 2.878 1.237 48 4.95 2.596 2.817 1.276 50 4.77 2.464 2.755 1.315 52 4.61 2.340 2.692 1.353 54 4.45 2.223 2.629 1.391Evaporating temperature sweep, condensing 42 degC T_e Carnot COP capacity kW input kW -14 4.63 2.440 2.146 1.035 -12 4.84 2.576 2.338 1.068 -10 5.06 2.722 2.544 1.099 -8 5.30 2.881 2.764 1.129 -6 5.57 3.053 3.000 1.156 -4 5.85 3.240 3.252 1.181 -2 6.16 3.445 3.521 1.202 0 6.50 3.670 3.807 1.221 2 6.88 3.917 4.113 1.235COP change per kelvin of condensing temperature: -0.0849 (-2.78 %)COP change per kelvin of evaporating temperature: +0.0899 (+2.94 %)Design (-6, 42): COP 3.053, capacity 3.000 kW, input 1.156 kW, system COP 2.595 run 12.00 h/day, 13.87 kWh/day, 5064 kWh/year, cost 60769 per yearHot day (-6, 48): COP 2.596, capacity 2.817 kW, input 1.276 kW, system COP 2.207 run 12.78 h/day, 16.31 kWh/day, 5954 kWh/year, cost 71445 per yearRoom at 2 degC (-8, 42): COP 2.881, capacity 2.764 kW, input 1.129 kW, system COP 2.448 run 13.02 h/day, 14.70 kWh/day, 5367 kWh/year, cost 64399 per yearHot day against design: +17.6 % energyColder room against design: +0.829 kWh/day, +302.5 kWh/year, +3630 per year (+6.0 %)Saved cop_sensitivity.pngThe yearly figure printed for the hot day is what a full year at 48 °C would cost, for comparison only: no site has 365 hot days. In the plot the cycle curve stays a little above half of the Carnot curve across the whole range, and both fall as the lift rises.
1. A freezer evaporates at −25 °C and condenses at 40 °C. Find the Carnot COP. Compare it with the 5.57 of the cold room at −6 °C and 42 °C.
2. Use the condensing temperature table. Find the percent loss of cycle COP when the condensing temperature rises from 42 °C to 46 °C. Compare it with the estimate from 2.8 percent per kelvin.
3. A blocked air path raises the condensing temperature of the design system from 42 °C to 45 °C. Estimate the new cycle COP from the slope of
Estimate:
4. On a cool night the condensing temperature is 36 °C. Use the table values (capacity 3.180 kW, electrical input 1.031 kW). If the whole 36 kWh daily load were met at this condition, find the run hours, the daily energy and the saving against the design day’s 13.87 kWh.
Run hours
5. The room is set to 2 °C and the day is hot, so
6. A larger evaporator coil would let the same room at 4 °C run with
Run hours
The cold room's R134a system evaporates at −6 °C and condenses at 42 °C. Its cycle COP is 3.05. On a hot day the condensing temperature rises by 6 K, to 48 °C. Nothing else changes. By about how much does the COP fall?
Fixed in this figure: isentropic efficiency 0.68 · motor and mechanical efficiency 0.85
The curve is the saturation dome of R134a: liquid on its left, vapour on its right, a boiling mixture inside. The cycle runs 1 to 2 in the compressor, 2 to 3 in the condenser, 3 to 4 through the expansion valve at constant enthalpy, and 4 to 1 in the evaporator. The open dot is 2s, where an ideal compressor would end. The line from 1 to 2 only joins the two states. The gold bar is the refrigerating effect and the coral bar is the specific work, on the same scale, so the cycle COP is the length of one divided by the length of the other. The thin dashed outline is the design cycle, kept for comparison. Capacity and input use the lesson's constant-displacement model: the compressor draws in the same volume every second, so the mass flow follows the density of the vapour at state 1. Real compressors lose more capacity at a high pressure ratio than this model shows. Properties are CoolProp values stored as tables. Enthalpy has an arbitrary zero, so only differences have meaning.
Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.
1. On the hot day the condensing temperature is 48 °C and the capacity falls from 3.000 kW to 2.817 kW. In the constant-displacement model, what happens to the mass flow of refrigerant?
2. The thermostat is set 2 K colder, so the system evaporates at −8 °C. An ammeter shows that the compressor input fell from 1.156 kW to 1.129 kW. The daily cooling load is the same. What happens to the electrical energy used in a day?
3. At the design temperatures the subcooling at the condenser outlet is raised from 4 K to 8 K. The states at the compressor do not change. What happens to the cycle COP?