COP and What Lowers It

Lesson 4 of 10 25 min read
Found this useful?

The electricity bill of a cold room rises by a sixth in the hot season, and nobody has changed anything. In another store, someone sets the thermostat 2 °C colder than the produce needs “to be safe”, and the owner pays for that every day of the year without knowing the amount. Both costs have the same cause: the refrigeration system must lift heat through a larger temperature difference, and each kelvin of lift has a price. This lesson calculates that price for one real system. You will compare the cycle with the best any machine could do, and you will turn a change of temperature into run hours, kilowatt-hours and money. #Refrigeration #COP #EnergyEfficiency

Learning Objectives

By the end of this lesson, you will be able to:

  1. Calculate the Carnot COP for a pair of temperatures and explain why a real cycle is below it
  2. Compute the cycle COP across a range of condensing and evaporating temperatures with CoolProp
  3. Derive the percent change in COP per kelvin for a given system from its own table
  4. Estimate the change in capacity and input power with a constant-displacement compressor model
  5. Convert a change in COP and capacity into compressor hours, daily energy and yearly cost

Real-World System Problem: One condensing unit, two seasons and two setpoints



The cold room of this course is held at 4 °C inside a store building. Its R134a system evaporates at −6 °C and condenses at 42 °C when the building air is at 30 °C. At that design point the cycle has a COP of 3.05 and gives 3.0 kW of cooling for 1.16 kW of electricity at the compressor.

None of those numbers is fixed. On a hot day the building air reaches 36 °C, and the condenser, about 12 K warmer than the air, runs at 48 °C. With the thermostat at 2 °C, the evaporator, about 10 K colder than the room, runs at −8 °C. Either way the compressor works across a larger pressure difference.

The owner sees none of this: the room still holds its temperature. What changes is how long the compressor runs each day and how much power it draws while it runs. The task is to put numbers on both.

42 °Ccondensing temperature12 Kcondenser difference30 °Cbuilding air26 Kwhat the room needs4 °Croom air10 Kevaporator difference−6 °Cevaporating temperatureLift the compressor supplies: 42 − (−6) = 48 K
The temperature lift at the design point

Fundamental Theory: The temperature lift and its price



COP and the lift

The COP (coefficient of performance) of a refrigeration cycle is the heat removed divided by the work supplied:

where is the refrigerating effect and the specific work of the compressor, both in kJ/kg. The system COP divides the cooling capacity by the electrical input, so it also includes the losses of the motor.

The temperature lift, (condensing minus evaporating temperature), is the height through which the machine raises the heat. As a pump needs more work for each litre it lifts higher, a refrigeration system needs more work for each kilojoule it lifts through more kelvin.

The Carnot limit

The second law of thermodynamics sets an upper limit, the Carnot COP, on any machine that moves heat from to : that of an ideal machine with no friction and no heat transfer across a finite temperature difference.

Carnot COP for refrigeration

Both temperatures are absolute, in kelvin. The denominator is the lift.

For the design point, and the lift is 48 K:

The common mistake is a Celsius numerator: , a negative COP with no meaning. The lift is the same in kelvin and in Celsius, but the numerator must be in kelvin.

Before any refrigerant is chosen, the formula shows two things: the COP falls when the lift rises, and for the same lift a colder evaporator gives a lower COP, because the numerator is smaller.

Why the real cycle is lower

The real cycle reaches 3.05, which is 55 percent of the Carnot value. The gap has three sources.

Compression losses. The compressor has an isentropic efficiency of 0.68. With an ideal compressor the same cycle would reach 4.49. This is the largest single loss.

Throttling. The expansion valve lowers the pressure without recovering any work, and about 30 percent of the refrigerant becomes flash gas that does no cooling. A Carnot machine would expand the liquid in a device that returns work.

Discharge superheat. This is not the superheat at the evaporator outlet; it is how far the gas leaving the compressor is above the condensing temperature: 67.7 °C against 42 °C, 25.7 K. Part of the heat is therefore rejected across a large temperature difference, after work spent reaching a temperature the condenser did not need. The suction superheat (6 K at the compressor inlet) adds to this a little, because it makes the vapour less dense and the compression start warmer.

Throttling and superheat bring the COP from 5.57 to 4.49 even with a perfect compressor; the real compressor brings it to 3.05, and the motor brings the system COP to 2.59.

One more loss sits outside the cycle. The room only needs heat lifted from 4 °C to 30 °C, 26 K, for which a Carnot machine would reach . The two coils need a temperature difference to transfer heat, and those differences raise the lift from 26 K to 48 K before the cycle begins.

Where the COP goes at the design point
Carnot, 4 °C to 30 °C 10.66 #####################
Carnot, −6 °C to 42 °C 5.57 ###########
Cycle, ideal compressor 4.49 #########
Cycle, real compressor 3.05 ######
System, with the motor 2.59 #####

COP against condensing temperature

The table holds the evaporating temperature at −6 °C, the superheat at 6 K, the subcooling at 4 K and the isentropic efficiency at 0.68, and moves only the condensing temperature. Every value is computed with CoolProp’s reference equation of state for R134a. The capacity and input columns use the compressor model explained below.

(°C)Carnot COPCycle COPCapacity (kW)Electrical input (kW)
366.363.6293.1801.031
386.073.4203.1201.073
405.813.2293.0601.115
425.573.0533.0001.156
445.342.8892.9391.197
465.142.7382.8781.237
484.952.5962.8171.276
504.772.4642.7551.315
524.612.3402.6921.353
544.452.2232.6291.391

A higher condensing temperature hurts in three ways at once: the COP falls, the capacity falls and the input power rises.

COP against evaporating temperature

This table holds the condensing temperature at 42 °C and moves only the evaporating temperature.

(°C)Carnot COPCycle COPCapacity (kW)Electrical input (kW)
−144.632.4402.1461.035
−124.842.5762.3381.068
−105.062.7222.5441.099
−85.302.8812.7641.129
−65.573.0533.0001.156
−45.853.2403.2521.181
−26.163.4453.5211.202
06.503.6703.8071.221
26.883.9174.1131.235

A lower evaporating temperature lowers the COP and lowers the capacity strongly: at −14 °C the system gives only 72 percent of its design capacity. The input power falls a little, which misleads many people: the compressor draws less but runs much longer, so the energy used rises.

Percent per kelvin, from this system’s own tables

Take the slope of each table across the design point, from 2 K below to 2 K above.

Condensing side, from 40 °C to 44 °C:

Evaporating side, from −8 °C to −4 °C:

This system's figure

Near its design point, this R134a system loses about 2.8 percent of its COP for each kelvin of higher condensing temperature, and about 2.9 percent for each kelvin of lower evaporating temperature. A fair short form is 3 percent per kelvin of lift, on either side.

This is not a universal law: it comes from one refrigerant, one design point and one fixed compressor efficiency, and other systems commonly give 2 to 4 percent per kelvin. It is also a slope at one point, accurate for a change of a few kelvin. Over 6 K the simple multiplication predicts a loss of 16.7 percent, and the table gives 15.0 percent.

A kelvin on the evaporating side costs slightly more than a kelvin on the condensing side. The Carnot formula shows why: lowering raises the lift and also lowers the numerator.

Capacity: the constant-displacement model

A piston or scroll compressor at fixed speed draws in the same volume of vapour every second, as a cup scoops the same volume whether it scoops thick or thin soup. So this lesson takes the inlet volume flow as constant, and the mass flow follows the inlet vapour density .

Constant-displacement model

is the mass flow in kg/s, the cooling capacity in kW, the electrical input in kW and the motor and mechanical efficiency. At the design point and , so .

When the evaporating temperature falls, the suction pressure falls and the vapour is less dense, so each stroke carries less mass: that is why the capacity falls so quickly in the second table. When only the condensing temperature rises, the inlet state and the mass flow do not change, and the capacity falls only because each kilogram reaches the evaporator with more flash gas.

From power to energy

The room does not need a power. It needs a daily load, an amount of heat in kWh of cooling removed each day, and the compressor runs until that load is met.

The second form carries a useful message. For a fixed load, the capacity decides how many hours the compressor runs, and the COP alone decides how many kilowatt-hours it uses.

more kWhhigherliftmore runhoursmore workper kilogramless coolingper kilogramlowercapacitylower COP
How a higher lift reaches the bill

Application 1: A hot day at the condensing unit



Step 1: The cycle on the hot day

Click to reveal the COP at 48 °C
  1. Carnot COP. The lift is now .

    The limit itself has fallen, from 5.57 to 4.95. ✅

  2. Refrigerating effect. The warmer liquid carries more enthalpy into the expansion valve.

    This is 6.1 percent less than the 146.85 kJ/kg of the design point. ✅

  3. Specific work.

    This is 10.4 percent more than the 48.11 kJ/kg of the design point. ✅

  4. Cycle COP.

    The COP has fallen from 3.05 to 2.60, a loss of 15 percent. ✅

Step 2: Capacity and input power

Click to reveal the capacity and the power
  1. Mass flow. The inlet state has not changed, so the density and the mass flow are the same as at design: . ✅

  2. Capacity.

    The system has lost 0.183 kW of cooling. ✅

  3. Electrical input.

    The compressor draws 0.120 kW more than at design. ✅

  4. System COP.

    At design it was . ✅

Step 3: Hours and energy for the same load

Click to reveal the daily figures
  1. Design day.

    ✅

  2. Hot day.

    ✅

  3. Difference. The compressor runs 0.78 h longer (47 minutes) and uses more, which is 17.6 percent more energy for the same cooling. ✅

  4. Check a second way. Daily energy is the load divided by the system COP.

    Both agree with the hours method, and the Python script prints the same values. ✅

Application 2: The room set 2 K colder than needed



Step 1: The cycle at the lower evaporating temperature

Click to reveal the COP at −8 °C
  1. Refrigerating effect.

    This is almost the same as at design, because state 3 has not moved. ✅

  2. Specific work. The pressure ratio is now , against 4.58 at design.

    (The values are carried unrounded, so the last digit can differ by one from a calculation with the rounded figures.) ✅

  3. Cycle COP.

    The COP falls from 3.053 to 2.881, a loss of 5.6 percent for 2 K. The slope from the table predicted percent. ✅

Step 2: Capacity, power and the daily energy

Click to reveal the daily figures
  1. Mass flow. The suction vapour is less dense, and the volume flow is fixed.

    The compressor moves 7.1 percent less refrigerant. ✅

  2. Capacity.

    ✅

  3. Electrical input.

    The input is 0.027 kW lower than at design. On an ammeter the colder setting looks slightly better. ✅

  4. Run hours and daily energy.

    The compressor runs 1.02 h longer each day. ✅

Step 3: The yearly cost

Click to reveal the cost
  1. Extra energy per day. , which is 6.0 percent more. ✅

  2. Energy per year.

    The colder setting uses 303 kWh more in a year. (The products use the unrounded daily values.) ✅

  3. Cost per year.

    The extra cost is 3,630 currency units a year. ✅

  4. Check a second way. For the same load, the energy ratio is the inverse of the COP ratio.

    The energy rises by 6.0 percent, which agrees with step 1. The motor efficiency cancels, so the cycle COP ratio is enough. ✅

Verify It in Python



The script computes the Carnot and cycle COP, both sensitivity tables with capacity and input power, the slopes at the design point, and the daily and yearly figures for both applications. It plots the cycle COP and the Carnot COP against each temperature. It needs CoolProp as well as numpy and matplotlib: pip install CoolProp.

cop_sensitivity.py
"""COP, capacity and input power of the cold room cycle as the two temperatures move."""
import numpy as np
import matplotlib.pyplot as plt
from CoolProp.CoolProp import PropsSI
FLUID = "R134a"
SUPERHEAT, SUBCOOLING = 6.0, 4.0 # K
ETA_IS, ETA_MOTOR = 0.68, 0.85
T_E0, T_C0 = -6.0, 42.0 # design point, degC
CAPACITY0 = 3.0 # kW at the design point
DAILY_LOAD = 36.0 # kWh of cooling a day (given)
PRICE = 12.00 # currency units per kWh
K0 = 273.15
def cycle(t_e, t_c, eta_is=ETA_IS):
"""Return q_e (kJ/kg), w (kJ/kg) and suction density (kg/m3)."""
p_e = PropsSI("P", "T", t_e + K0, "Q", 1, FLUID)
p_c = PropsSI("P", "T", t_c + K0, "Q", 0, FLUID)
t1 = t_e + SUPERHEAT + K0
h1 = PropsSI("H", "T", t1, "P", p_e, FLUID)
s1 = PropsSI("S", "T", t1, "P", p_e, FLUID)
rho1 = PropsSI("D", "T", t1, "P", p_e, FLUID)
h2s = PropsSI("H", "P", p_c, "S", s1, FLUID)
h2 = h1 + (h2s - h1) / eta_is
h3 = PropsSI("H", "T", t_c - SUBCOOLING + K0, "P", p_c, FLUID)
return (h1 - h3) / 1e3, (h2 - h1) / 1e3, rho1
Q_E0, W0, RHO0 = cycle(T_E0, T_C0)
VOLUME_FLOW = CAPACITY0 / Q_E0 / RHO0 # m3/s, fixed by the compressor
def machine(t_e, t_c):
"""Constant displacement: mass flow follows the suction density."""
q_e, w, rho1 = cycle(t_e, t_c)
m = VOLUME_FLOW * rho1
capacity = m * q_e
elec = m * w / ETA_MOTOR
return q_e / w, capacity, elec
def carnot(t_e, t_c):
return (t_e + K0) / (t_c - t_e)
q_ideal, w_ideal, _ = cycle(T_E0, T_C0, eta_is=1.0)
print(f"Carnot COP at design: {carnot(T_E0, T_C0):.3f}")
print(f"Cycle COP, ideal compressor: {q_ideal / w_ideal:.3f}")
print(f"Cycle COP, real compressor: {Q_E0 / W0:.3f} "
f"({100 * Q_E0 / W0 / carnot(T_E0, T_C0):.1f} % of Carnot)")
print(f"System COP with the motor: {Q_E0 / W0 * ETA_MOTOR:.3f}")
print("Condensing temperature sweep, evaporating -6 degC")
print(" T_c Carnot COP capacity kW input kW")
tc_list = np.arange(36, 55, 2)
cop_tc = []
for t_c in tc_list:
cop, cap, elec = machine(T_E0, t_c)
cop_tc.append(cop)
print(f" {t_c:3d} {carnot(T_E0, t_c):5.2f} {cop:5.3f} {cap:7.3f} {elec:7.3f}")
print("Evaporating temperature sweep, condensing 42 degC")
print(" T_e Carnot COP capacity kW input kW")
te_list = np.arange(-14, 3, 2)
cop_te = []
for t_e in te_list:
cop, cap, elec = machine(t_e, T_C0)
cop_te.append(cop)
print(f" {t_e:3d} {carnot(t_e, T_C0):5.2f} {cop:5.3f} {cap:7.3f} {elec:7.3f}")
cop0 = Q_E0 / W0
slope_tc = (machine(T_E0, 44)[0] - machine(T_E0, 40)[0]) / 4
slope_te = (machine(-4, T_C0)[0] - machine(-8, T_C0)[0]) / 4
print(f"COP change per kelvin of condensing temperature: {slope_tc:+.4f} "
f"({100 * slope_tc / cop0:+.2f} %)")
print(f"COP change per kelvin of evaporating temperature: {slope_te:+.4f} "
f"({100 * slope_te / cop0:+.2f} %)")
def day(name, t_e, t_c):
cop, cap, elec = machine(t_e, t_c)
hours = DAILY_LOAD / cap
energy = hours * elec
print(f"{name}: COP {cop:.3f}, capacity {cap:.3f} kW, input {elec:.3f} kW, "
f"system COP {cap / elec:.3f}")
print(f" run {hours:.2f} h/day, {energy:.2f} kWh/day, "
f"{energy * 365:.0f} kWh/year, cost {energy * 365 * PRICE:.0f} per year")
return energy
e_design = day("Design (-6, 42)", T_E0, T_C0)
e_hot = day("Hot day (-6, 48)", T_E0, 48.0)
e_cold = day("Room at 2 degC (-8, 42)", -8.0, T_C0)
print(f"Hot day against design: {100 * (e_hot / e_design - 1):+.1f} % energy")
print(f"Colder room against design: {e_cold - e_design:+.3f} kWh/day, "
f"{(e_cold - e_design) * 365:+.1f} kWh/year, "
f"{(e_cold - e_design) * 365 * PRICE:+.0f} per year "
f"({100 * (e_cold / e_design - 1):+.1f} %)")
# ---------- Plot ----------
fig, ax = plt.subplots(1, 2, figsize=(10, 4.5), sharey=True)
ax[0].plot(tc_list, cop_tc, "o-", label="cycle")
ax[0].plot(tc_list, [carnot(T_E0, t) for t in tc_list], "--", label="Carnot")
ax[0].set_xlabel("condensing temperature (degC)")
ax[0].set_ylabel("COP")
ax[0].set_title("Evaporating at -6 degC")
ax[0].legend()
ax[1].plot(te_list, cop_te, "o-", label="cycle")
ax[1].plot(te_list, [carnot(t, T_C0) for t in te_list], "--", label="Carnot")
ax[1].set_xlabel("evaporating temperature (degC)")
ax[1].set_title("Condensing at 42 degC")
ax[1].legend()
for a in ax:
a.grid(True, linewidth=0.3)
fig.tight_layout()
fig.savefig("cop_sensitivity.png", dpi=120)
print("Saved cop_sensitivity.png")

Expected output

Carnot COP at design: 5.566
Cycle COP, ideal compressor: 4.489
Cycle COP, real compressor: 3.053 (54.8 % of Carnot)
System COP with the motor: 2.595
Condensing temperature sweep, evaporating -6 degC
T_c Carnot COP capacity kW input kW
36 6.36 3.629 3.180 1.031
38 6.07 3.420 3.120 1.073
40 5.81 3.229 3.060 1.115
42 5.57 3.053 3.000 1.156
44 5.34 2.889 2.939 1.197
46 5.14 2.738 2.878 1.237
48 4.95 2.596 2.817 1.276
50 4.77 2.464 2.755 1.315
52 4.61 2.340 2.692 1.353
54 4.45 2.223 2.629 1.391
Evaporating temperature sweep, condensing 42 degC
T_e Carnot COP capacity kW input kW
-14 4.63 2.440 2.146 1.035
-12 4.84 2.576 2.338 1.068
-10 5.06 2.722 2.544 1.099
-8 5.30 2.881 2.764 1.129
-6 5.57 3.053 3.000 1.156
-4 5.85 3.240 3.252 1.181
-2 6.16 3.445 3.521 1.202
0 6.50 3.670 3.807 1.221
2 6.88 3.917 4.113 1.235
COP change per kelvin of condensing temperature: -0.0849 (-2.78 %)
COP change per kelvin of evaporating temperature: +0.0899 (+2.94 %)
Design (-6, 42): COP 3.053, capacity 3.000 kW, input 1.156 kW, system COP 2.595
run 12.00 h/day, 13.87 kWh/day, 5064 kWh/year, cost 60769 per year
Hot day (-6, 48): COP 2.596, capacity 2.817 kW, input 1.276 kW, system COP 2.207
run 12.78 h/day, 16.31 kWh/day, 5954 kWh/year, cost 71445 per year
Room at 2 degC (-8, 42): COP 2.881, capacity 2.764 kW, input 1.129 kW, system COP 2.448
run 13.02 h/day, 14.70 kWh/day, 5367 kWh/year, cost 64399 per year
Hot day against design: +17.6 % energy
Colder room against design: +0.829 kWh/day, +302.5 kWh/year, +3630 per year (+6.0 %)
Saved cop_sensitivity.png

The yearly figure printed for the hot day is what a full year at 48 °C would cost, for comparison only: no site has 365 hot days. In the plot the cycle curve stays a little above half of the Carnot curve across the whole range, and both fall as the lift rises.

Common Mistakes



  • Using Celsius in the Carnot formula. The numerator must be in kelvin: 267.15, not −6.
  • Comparing the cycle with a Carnot COP taken between the room and the outside air, and then blaming the compressor for the whole gap. The coil temperature differences set the lift before the compressor does anything.
  • Judging a setting by the compressor’s power or current. At the colder setting the power fell by 0.027 kW while the daily energy rose by 6 percent. Compare energy per day.
  • Quoting “3 percent per kelvin” as a law. It is the slope of this system’s table at its design point. Compute the table for the system in question.
  • Forgetting that capacity falls with COP. A system that is only just large enough on a design day may run without stopping on a hot day and then lose the room temperature.
  • Holding the load constant without saying so. A hotter day and a colder room both raise the load as well, so the real cost is above the figure from the COP alone.

Summary



  • The Carnot COP, with temperatures in kelvin, is the upper limit for any machine working between two temperatures. At −6 °C and 42 °C it is 5.57.
  • The real cycle reaches 3.05. Throttling and superheat bring 5.57 down to 4.49, the compressor’s isentropic efficiency of 0.68 brings it to 3.05, and the motor brings the system COP to 2.59.
  • For this system, each kelvin of higher condensing temperature costs about 2.8 percent of the COP and each kelvin of lower evaporating temperature costs about 2.9 percent. The figure is this system’s, not a law.
  • With a constant-displacement compressor, capacity follows the suction vapour density and the refrigerating effect. The model keeps volumetric efficiency constant, which makes the hot day look milder than it is.
  • A hot day with condensing at 48 °C gives a COP of 2.60, a capacity of 2.817 kW and 16.31 kWh a day against 13.87 kWh for the same 36 kWh load. A room held 2 K too cold costs 6 percent more energy, 3,630 currency units a year at the example price.

Exercises



1. A freezer evaporates at −25 °C and condenses at 40 °C. Find the Carnot COP. Compare it with the 5.57 of the cold room at −6 °C and 42 °C.

Answer

and the lift is 65 K, so the Carnot COP is . The larger lift and the colder evaporator together lower the limit by about a third.

2. Use the condensing temperature table. Find the percent loss of cycle COP when the condensing temperature rises from 42 °C to 46 °C. Compare it with the estimate from 2.8 percent per kelvin.

Answer

, a loss of 10.3 percent. The estimate is percent. The straight-line estimate is a little high because the curve flattens as the temperature rises.

3. A blocked air path raises the condensing temperature of the design system from 42 °C to 45 °C. Estimate the new cycle COP from the slope of per kelvin. Then compute it with CoolProp, given , and at 45 °C.

Answer

Estimate: . CoolProp: , , COP . The estimate is within half a percent.

4. On a cool night the condensing temperature is 36 °C. Use the table values (capacity 3.180 kW, electrical input 1.031 kW). If the whole 36 kWh daily load were met at this condition, find the run hours, the daily energy and the saving against the design day’s 13.87 kWh.

Answer

Run hours . Energy . The saving is a day, or 15.9 percent.

5. The room is set to 2 °C and the day is hot, so and . CoolProp gives , and , with . Use the constant-displacement model ( at ), and . Find the cycle COP, the capacity, the electrical input, and the run hours and daily energy for a 36 kWh load.

Answer

, , COP . . Capacity . Electrical input . Run hours and daily energy , which is 24 percent above the design day.

6. A larger evaporator coil would let the same room at 4 °C run with . Use the evaporating temperature table (capacity 3.252 kW, electrical input 1.181 kW). For the 36 kWh daily load, find the run hours, the daily energy, and the yearly saving in kWh and in currency units at 12.00 per kWh against the design day’s 13.87 kWh.

Answer

Run hours . Energy . The saving is 0.80 kWh a day, about 293 kWh a year, worth about 3,500 currency units a year. The compressor draws more power (1.181 against 1.156 kW) and still uses less energy, because it runs for a shorter time.

References



  • Y. A. Çengel and M. A. Boles, Thermodynamics: An Engineering Approach, 8th edition, McGraw-Hill, 2015.
  • W. F. Stoecker and J. W. Jones, Refrigeration and Air Conditioning, 2nd edition, McGraw-Hill, 1982.
  • I. H. Bell, J. Wronski, S. Quoilin and V. Lemort, “Pure and Pseudo-pure Fluid Thermophysical Property Evaluation and the Open-Source Thermophysical Property Library CoolProp”, Industrial and Engineering Chemistry Research, vol. 53, no. 6, 2014.


© 2021-2026 SiliconWit®. All rights reserved.
Predict first

The cold room's R134a system evaporates at −6 °C and condenses at 42 °C. Its cycle COP is 3.05. On a hot day the condensing temperature rises by 6 K, to 48 °C. Nothing else changes. By about how much does the COP fall?

See it: the R134a cycle on the pressure-enthalpy diagram

pe · pc (bar absolute)
Refrigerating effect qe
Specific work w
Cycle COP
Carnot COP
System COP, with the motor
Cooling capacity
Electrical input
Discharge temperature

Fixed in this figure: isentropic efficiency 0.68 · motor and mechanical efficiency 0.85

The curve is the saturation dome of R134a: liquid on its left, vapour on its right, a boiling mixture inside. The cycle runs 1 to 2 in the compressor, 2 to 3 in the condenser, 3 to 4 through the expansion valve at constant enthalpy, and 4 to 1 in the evaporator. The open dot is 2s, where an ideal compressor would end. The line from 1 to 2 only joins the two states. The gold bar is the refrigerating effect and the coral bar is the specific work, on the same scale, so the cycle COP is the length of one divided by the length of the other. The thin dashed outline is the design cycle, kept for comparison. Capacity and input use the lesson's constant-displacement model: the compressor draws in the same volume every second, so the mass flow follows the density of the vapour at state 1. Real compressors lose more capacity at a high pressure ratio than this model shows. Properties are CoolProp values stored as tables. Enthalpy has an arbitrary zero, so only differences have meaning.

42 °C condensing30 °C building air4 °C room air−6 °C evaporating 12 K10 K 26 K48 K neededlifted
limit, room to airlimit, coil to coilideal compressorreal compressorwith the motor 10.665.574.493.052.59 The coil differences alone cut the limit almost in half.
Watch it build: where the COP goes
coil to coil5.57real cycle3.05 55 % ideal compressor4.49compressor valve valve, hot gas with the motor2.59motor room to air10.66the coils
  1. The real cycle reaches 3.05, 55 percent of the Carnot 5.57 between the same coil temperatures.
  2. An ideal compressor would reach 4.49. The real compressor is the largest single loss.
  3. The valve recovers no work, and its 30 percent flash gas cools nothing.
  4. Hot discharge gas adds to it: valve and superheat take 5.57 down to 4.49.
  5. The motor brings the system COP from 3.05 to 2.59.
  6. The room needs only 26 K of lift: limit 10.66. The coil differences cut it to 5.57.
42 °C condensing temperature 30 °C building air 4 °C room air −6 °C evaporating temperature 12 K condenser difference 26 K what the room needs 10 K evaporator difference 48 K Lift the compressor supplies: 42 − (−6) = 48 K
The temperature lift at the design point
Higher lift Less cooling per kilogram More work per kilogram More run hours More kWh lower capacity lower COP
How a higher lift reaches the bill

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. On the hot day the condensing temperature is 48 °C and the capacity falls from 3.000 kW to 2.817 kW. In the constant-displacement model, what happens to the mass flow of refrigerant?

2. The thermostat is set 2 K colder, so the system evaporates at −8 °C. An ammeter shows that the compressor input fell from 1.156 kW to 1.129 kW. The daily cooling load is the same. What happens to the electrical energy used in a day?

3. At the design temperatures the subcooling at the condenser outlet is raised from 4 K to 8 K. The states at the compressor do not change. What happens to the cycle COP?