COP
On this page
A water pump does not make water. It moves water that is already there, and a small pump can move a great deal of it. A cooling plant does the same with heat, and its COP (coefficient of performance) is the number of units of heat it moves for each unit of electricity it uses.
See it
A cold room needs the same amount of cooling every day. On a hot day its condenser runs 6 K hotter than usual, at 48 °C in place of 42 °C. What happens to the electricity the compressor uses that day?
The condensing temperature is the temperature of the refrigerant in the outdoor coil. It must stay above the outside air, here by about 12 K, so it rises on a hot day and when the coil is dirty. The room is held at 4 °C throughout and needs 36 kWh of cooling a day. The values are for one small cold room system.
The idea
COP is a ratio of two energies, so it has no unit.
both in kW, or both in kWh over the same time
A COP of 2.59 means that 2.59 kWh of heat leaves the room for each 1 kWh at the meter. The number can be above 1 because the plant does not turn electricity into cold. It uses electricity to carry heat that is already there, as the refrigeration cycle shows.
The COP is not fixed. The plant lifts heat from a cold temperature to a warm one, as a pump lifts water from a low level to a high one. A higher lift needs more work for each unit moved. In the system of the figure, each kelvin of extra lift costs about 3% of the COP. Other systems lose between 2% and 4%.
One worked number
A cold room system gives 3.0 kW of cooling while its compressor takes 1.16 kW of electricity. The room needs 36 kWh of cooling a day. What is the COP, and how much electricity does the compressor use in a day?
Show the worked solution, 3 steps
- Divide the heat moved by the electricity
COP = 3.0 kW ÷ 1.16 kW = 2.59.
- Use it on the daily cooling
Electricity = cooling ÷ COP = 36 kWh ÷ 2.59 = 13.9 kWh a day.
- Check it in the figure
At 42 °C the figure shows a COP of 2.59 and 13.9 kWh for one day. Move the slider to 48 °C to see the same room cost 16.3 kWh.
The mistake to avoid
A second trap: do not judge a setting by the power the compressor draws. Set the room 2 °C colder and the compressor draws slightly less power, runs for more hours, and uses 6% more energy in a day. Compare kWh for each day. The lesson on COP and what lowers it shows the numbers.
Check yourself
A chiller gives 12 kW of cooling and takes 4.8 kW of electricity. What is its COP?
Dust on a condenser coil makes it run 5 K hotter. The cold room still holds 4 °C, and the stock needs the same cooling. What happens to the electricity used each day?
A seller says: "This unit has a COP of 3, so it is 300% efficient and makes more energy than it uses." Which statement is correct?
Where you meet it
- A cold roomIts COP falls every hot afternoon and every week the condenser coil is not cleaned.
- A building chillerThe COP is the first number of an energy audit: cooling delivered, divided by electricity at the meter.
- A heat pump water heaterHere the useful side is the warm one, so its COP counts the heat delivered to the water.
- COP = heat moved ÷ electricity used. It has no unit.
- It can be above 1 because the plant moves heat and does not make it.
- It falls when the condenser is hotter or the cold side is colder: about 3% for each kelvin in this system.
- Always ask at which temperatures, and with which electricity counted.
Discussion
No comments yet. Questions, results from your own build, a better way to explain it: all welcome.