Refrigeration cycle
On this page
Wet your hand and wave it in the air. It feels cold, because the water takes heat from your skin as it evaporates. A cold room uses the same effect in a closed loop of pipe. The refrigeration cycle makes a fluid boil at low pressure to take heat in from a cold place, then compresses it so that it gives the heat out in a warmer place.
See it
The unit outside a cold room blows warm air all day. Where does that heat come from?
The same refrigerant goes round and round. The upper pipes are the high pressure side and the lower pipes are the low pressure side. The numbers are for one small cold room system, with the room at 4 °C and the outside air at 30 °C. Pressures are absolute.
The idea
A liquid takes in a large amount of heat when it boils, and gives the same heat back when it condenses. The temperature at which it does either depends on its pressure. The refrigerant in the figure boils at −6 °C when its pressure is 2.34 bar, and condenses at 42 °C when its pressure is 10.72 bar.
So the machine keeps one coil at low pressure and one at high pressure. In the evaporator the refrigerant boils, colder than the room, and takes heat from it. The compressor raises the pressure of the vapour. In the condenser the vapour condenses, warmer than the outside air, and gives the heat away. The expansion valve lets the liquid return to low pressure.
Qin is the heat taken from the cold room, W is the work of the compressor, Qout is the heat given to the outside air
This is the simple cycle. A real system also loses a little pressure in its pipes and coils, so measured values differ by a few percent.
One worked number
A cold room system takes 3.0 kW of heat out of the room. Its compressor puts 0.98 kW of work into the refrigerant. How much heat must the condenser give to the outside air?
Show the worked solution, 2 steps
- Add what enters the loop
Heat enters at the evaporator and work enters at the compressor. Both must leave at the condenser: 3.0 + 0.98 = 3.98 kW.
- Read what it means
3.98 ÷ 3.0 = 1.33. The condenser must release a third more heat than the room gave up. Check it in the figure: step to the condenser.
The mistake to avoid
For the same reason the warm air from the condenser must be free to leave. A condenser covered in dust, or shut in a small hot space, makes the system use more electricity for less cooling. The COP measures that cost, and the lesson on the vapour-compression cycle works through every state.
Check yourself
A chiller takes 5.0 kW of heat from the water it cools. Its compressor puts 1.6 kW of work into the refrigerant. How much heat does its condenser release?
In the evaporator the refrigerant boils at −6 °C. In the condenser the same refrigerant condenses at 42 °C. What makes the difference?
On a hot day a shop owner leaves the lid of a chest freezer open "to cool the shop". The freezer stands inside the shop. What happens to the shop?
Where you meet it
- A cold roomThe evaporator hangs inside the room, and the compressor and condenser stand outside as one unit.
- An air conditionerIt is the same loop. The evaporator is the indoor unit and the condenser is the outdoor unit.
- A water chillerThe evaporator cools water, and pumps carry the cold water to a building or a process.
- A fluid boils at low pressure to take heat in, and condenses at high pressure to give it out.
- Four parts: evaporator, compressor, condenser, expansion valve.
- Heat out = heat in + work of the compressor.
- The system moves heat. It does not make cold.
Discussion
No comments yet. Questions, results from your own build, a better way to explain it: all welcome.
My notes on this page
Kept on this device only. Nothing is sent anywhere.
Tip: select words in the lesson, or tap a figure or an equation, to put a note right there.
Notes on earlier wording
The lesson has changed and these words are no longer in it. Your notes are kept, with the words you chose.