Condensers, Ambient Temperature and Head Pressure

Lesson 9 of 10 26 min read
Found this useful?

The condensing unit of a cold room stands in a corner behind the store, and its coil has turned grey with dust. The room still holds 4 °C, so nobody looks at the unit. The compressor works against a higher pressure for every minute that it runs, draws more power, cools less, and runs longer, and the bill has risen by a sixth with no visible cause. This lesson shows how the air at the condenser sets the condensing temperature and the head pressure, and how to put a yearly cost on a dirty coil and on a badly placed unit. #Refrigeration #Condenser #HeadPressure

Learning Objectives

By the end of this lesson, you will be able to:

  1. Calculate the condensing temperature and the head pressure from the entering air temperature and the condenser temperature difference
  2. Explain what raises the condenser temperature difference and what raises the temperature of the entering air
  3. Compute the COP, capacity, input power, run hours and daily energy at a higher condensing temperature
  4. Estimate the yearly cost of a dirty condenser and the yearly saving from a better position for the unit
  5. Recognise a condenser that rejects heat badly in a record of temperature, power and run time

Real-World System Problem: The condensing unit of the cold room



The cold room of this course has an R134a system with a cooling capacity of 3.0 kW at its design point. The condensing unit holds the compressor, the condenser coil and one fan of 90 W. The fan draws air at 30 °C through the finned coil. Inside the tubes the refrigerant arrives as hot gas, condenses at 42 °C, and leaves as liquid at 38 °C.

The condenser is the only place where heat leaves the system: everything the evaporator took from the room passes through it, with the work of the compressor. The refrigerant can give this heat to the air only if it is warmer than the air, by an amount that is not fixed. A clean coil with a free flow of air needs about 12 K; a dusty coil needs more, and each extra kelvin raises the pressure against which the compressor works.

fan90 Whot gas from the compressor, 67.7 °CairCONDENSER COILair outrefrigerant at 42 °Cinand 10.72 bar abs39.2 °C30 °Cliquid to the expansion valve, 38 °Cheat given to the air: 3.98 kW
The condensing unit and what crosses it

Fundamental Theory: The air, the coil and the pressure



What the condenser must reject

The first law for the refrigerant circuit says that the heat rejected equals the heat absorbed plus the work that the compressor gives to the refrigerant:

is the heat rejected at the condenser, the cooling capacity and the shaft power of the compressor, all in kW. is the mass flow of refrigerant in kg/s, and and are the specific enthalpies at the condenser inlet and outlet in kJ/kg. At the design point this is .

Condensing temperature follows the air

Heat flows from the refrigerant to the air because the refrigerant is warmer. The condenser temperature difference is the condensing temperature minus the temperature of the air that enters the coil.

Condensing temperature

is the condensing (saturation) temperature, the temperature of the air entering the coil and the condenser temperature difference. For this unit at design, .

The compressor does not choose the condensing temperature: the condenser pressure rises until the refrigerant is warm enough to give all its heat to the air, and settles there. A simple model shows the size of the difference:

is the conductance of the whole coil in W/K, counted on the entering air: for this coil. It grows with the clean fin area and the air flow. The model is rough, because the air warms as it passes through the coil, but the direction is right: more heat or less conductance means a larger difference.

48 °Ccondensing, dirty coil18 K42 °Ccondensing, clean coil12 K30 °Cair entering the coil4 °Croom air10 K−6 °Cevaporating
The same air, a clean coil and a dirty coil

The two terms of the formula fail in different ways, and the remedy differs, so keep them apart.

What raises the difference

Anything that lowers the conductance of the coil raises :

  • Dust, grease, leaves or insects on the fins. They insulate the metal and block the passages.
  • A blocked air path: boxes stacked against the coil, or a unit pushed against a wall.
  • A fan that has failed, turns slowly, or has a damaged blade.
  • Fins that are bent flat over part of the face.

Air inside the refrigerant circuit, or any other gas that cannot condense, has a similar effect from the inside. It is described below.

What raises the entering air temperature

The entering air is not always the surrounding air. The common mistake is to take the air temperature from a weather report or a thermometer across the yard, and then blame the coil for a difference that is not its fault.

At design the fan moves 0.45 m³/s, and the air leaves 9.2 K warmer, at 39.2 °C. If that warm air finds its way back to the inlet, the coil breathes its own exhaust, as a sleeper with a blanket over the head breathes warm breath. With a fraction of the leaving air returning and an air temperature rise through the coil:

is the temperature of the surrounding air. With the entering air is at , and the condensing temperature rises by the same 2.3 K with a perfectly clean coil. A closed room does the same on a larger scale, because all the leaving air returns in the end, and sun on a dark casing warms the air near the coil too.

OPEN, SHADEDRECIRCULATIONwallunit39°Cawayunit30 °C32°CormoreCLOSED PLANT ROOMwarm airthe room air risesunitstays inuntil the walls andthe roomthe leaks carry the38 °Cheat away
Where the entering air becomes too warm

Head pressure

Head pressure is the pressure on the high side. In the condenser it is the saturation pressure at , so a high-side gauge is a thermometer for the condensing temperature. The table holds the air at 30 °C and the evaporating temperature at −6 °C, with superheat 6 K, subcooling 4 K and an isentropic efficiency of 0.68, and moves only the condenser temperature difference. The gauge column is for this site’s 83.5 kPa atmosphere.

(K) (°C) (bar abs)Gauge (bar)Cycle COPCapacity (kW)Input (kW)
124210.7229.8873.0533.0001.156
144411.30110.4662.8892.9391.197
164611.90311.0682.7382.8781.237
184812.52911.6942.5962.8171.276
205013.17912.3442.4642.7551.315

The capacity and input columns use the constant-displacement compressor model of this course. Near 45 °C each kelvin adds about 0.3 bar to the head pressure.

The cost of each kelvin

Near its design point this system loses 2.78 percent of its COP for each kelvin of higher condensing temperature, so the compressor needs more electricity for the same cooling. For this room’s daily load of 36.95 kWh of heat, one kelvin adds 0.41 kWh a day to the condensing unit, about 1,800 currency units a year at 12.00 per kWh. The capacity also falls, by about 1 percent per kelvin, so the compressor runs longer.

Head-pressure control

If a low condensing temperature is good, a cold night should be the best time to run, and it is, up to a limit. The expansion valve needs a pressure difference to push enough liquid into the evaporator, and when the head pressure falls too far it cannot feed the coil. So many units hold a minimum head pressure, most often by stopping or slowing the condenser fan. The control is necessary, and it has a price: a minimum set higher than the valve needs discards the cheap running that cool hours offer. The setting belongs to the maker’s data and a qualified technician.

Non-condensable gas

Air or nitrogen that has entered the circuit cannot condense at these pressures. It collects in the condenser, adds its own pressure to the refrigerant’s, and covers tube surface that should condense vapour. The head pressure is then higher than the coil temperature explains, and the compressor pays for the excess as it pays for dirt. A record shows a condenser temperature difference that stays high after the coil is cleaned and the air flow checked. Confirming it and removing the gas are tasks for a qualified refrigeration technician, and this lesson gives no method for them.

Where a condensing unit should stand

The unit needs cool air that passes through the coil once and then leaves. So it belongs outside or in a space open to outside air, in the shade, with the clear distances that the maker states, with its warm air blown away from the inlet and from other units, and away from sources of dust, grease and lint. A unit inside a closed room heats that room with the heat from the cold room and with all of its own electricity.

What a dirty condenser looks like in a record

A dirty coil gives no alarm. It changes four readings, all in one direction, and the comparison must be made at the same entering air temperature:

Quantity in the recordClean coilDirty coil (Application 1)
Condensing temperature minus entering air (K)1218
Head pressure at 30 °C air (bar gauge)9.8911.69
Compressor input power (kW)1.1561.276
Discharge temperature (°C)67.775.0
Compressor hours for the same daily load12.3213.12

The suction pressure hardly moves. A high head pressure alone does not name the cause: a coil that rejects heat badly, too much refrigerant and gas that cannot condense all raise it.

Application 1: A dirty condenser coil



Step 1: Condensing temperature and head pressure

Click to reveal the temperature and the pressure
  1. Condensing temperature.

    The refrigerant condenses 6 K warmer than with the clean coil. ✅

  2. Head pressure. The saturation pressure of R134a at 48 °C is 12.529 bar absolute. A gauge at the site reads

    With the clean coil the gauge read . The dirt has added 1.81 bar. ✅

Step 2: The cycle with the dirty coil

Click to reveal the COP, the capacity and the power
  1. Refrigerating effect and work.

    Each kilogram cools less and needs more work. ✅

  2. Cycle COP.

    The COP falls from 3.053 to 2.596, a loss of 15.0 percent. ✅

  3. Capacity and input power.

    The unit gives 0.183 kW less cooling and takes 0.120 kW more power. ✅

  4. The same numbers as a hot day. These are exactly the figures of the hot-day case of the COP lesson, where air at 36 °C met a clean coil. The compressor cannot tell the two apart: it sees only 48 °C. The difference is that a hot day ends in the evening, and dirt stays. ✅

Step 3: Hours and energy for the same daily load

Click to reveal the daily figures
  1. Clean coil.

    The fan adds , so the condensing unit uses 15.35 kWh a day. ✅

  2. Dirty coil.

    The fan adds , so the condensing unit uses 17.92 kWh a day. ✅

  3. Difference. The compressor runs 0.80 h longer each day (48 minutes), and the unit uses more, which is 16.8 percent. ✅

Step 4: The yearly cost and a check

Click to reveal the cost
  1. Energy in a year of 365 days. With unrounded daily values, the clean unit uses 5,602 kWh and the dirty unit 6,542 kWh. The dirt costs 939 kWh a year. ✅

  2. Cost.

    The script, with unrounded values, gives 11,273. ✅

  3. Check with the COP ratio. For the same load, the compressor energy is the inverse of the COP.

    This agrees with the 16.74 kWh of the hours method. ✅

  4. What the dirt did to the coil. The dirty coil rejects across 18 K, where . Its conductance is , which is 65 percent of the clean 332 W/K. ✅

Application 2: A closed plant room against shaded outside air



Step 1: The cycle in the plant room

Click to reveal the cycle at 50 °C
  1. Condensing temperature and head pressure.

    The coil is clean, and the head pressure is still 2.46 bar above its design reading. ✅

  2. Refrigerating effect, work and COP.

    ✅

  3. Capacity and input power.

    ✅

Step 2: Why the plant room is hot

Click to reveal the room balance
  1. Boundary round the plant room. The cold room is outside this boundary. The refrigerant brings in the heat taken from the cold room, and the supply cable brings in the electricity of the compressor and the fan. All of it becomes heat in the plant-room air.

    ✅

  2. Outside air needed for a rise of 8 K.

    A room at 38 °C is one that receives about this much outside air and no more. A grille and a door gap rarely pass so much without a fan, so a real plant room can be hotter. ✅

Step 3: Daily energy and the yearly saving

Click to reveal the comparison
  1. Plant room.

    The fan adds , so the unit uses 18.85 kWh a day. (The products use unrounded values.) ✅

  2. Shaded outside air. The unit runs at the design point: 12.32 h and 15.35 kWh a day. ✅

  3. Saving.

    This is 18.6 percent of the unit’s electricity. In a year it is 1,277 kWh, worth 15,324 currency units. ✅

  4. Check with the percent-per-kelvin figure. Eight kelvin at 2.78 percent each predicts a COP loss of 22 percent. The cycle gives percent. The straight-line figure overstates a change as large as 8 K, as the COP tables showed, and it confirms the size of the answer. ✅

Verify It in Python



The script builds the cycle at any condensing temperature with CoolProp, prints the head-pressure table and both applications, and plots the yearly cost of the condensing unit against the condenser temperature difference for entering air at 30 °C and 38 °C. It needs CoolProp as well as numpy and matplotlib: pip install CoolProp.

condenser_head_pressure.py
"""Condenser of the cold room: air temperature, head pressure and the cost of each kelvin."""
import numpy as np
import matplotlib.pyplot as plt
from CoolProp.CoolProp import PropsSI
FLUID = "R134a"
K0 = 273.15
T_E, SUPERHEAT, SUBCOOLING = -6.0, 6.0, 4.0 # degC, K, K
ETA_IS, ETA_MOTOR = 0.68, 0.85
CAPACITY0, T_C0 = 3.0, 42.0 # kW and degC at the design point
P_ATM = 83.5e3 # Pa, atmosphere at the site
COND_FAN = 0.090 # kW, runs with the compressor
DAILY_LOAD = 36.95 # kWh of heat a day (energy balance)
PRICE = 12.00 # currency units per kWh
AIR_FLOW, RHO_AIR, CP_AIR = 0.45, 0.96, 1.005 # m3/s, kg/m3, kJ/(kg.K)
def cycle(t_c):
"""States of the cycle at a condensing temperature in degC (kJ/kg, Pa)."""
p_e = PropsSI("P", "T", T_E + K0, "Q", 1, FLUID)
p_c = PropsSI("P", "T", t_c + K0, "Q", 0, FLUID)
t1 = T_E + SUPERHEAT + K0
h1 = PropsSI("H", "T", t1, "P", p_e, FLUID)
s1 = PropsSI("S", "T", t1, "P", p_e, FLUID)
rho1 = PropsSI("D", "T", t1, "P", p_e, FLUID)
h2s = PropsSI("H", "P", p_c, "S", s1, FLUID)
h2 = h1 + (h2s - h1) / ETA_IS
h3 = PropsSI("H", "T", t_c - SUBCOOLING + K0, "P", p_c, FLUID)
t2 = PropsSI("T", "P", p_c, "H", h2, FLUID) - K0
return p_c, h1 / 1e3, h2s / 1e3, h2 / 1e3, h3 / 1e3, rho1, t2
_, H1, _, H2, H3, RHO1, _ = cycle(T_C0)
MASS_FLOW = CAPACITY0 / (H1 - H3) # kg/s, fixed: the suction state does not move
def machine(t_c):
"""Constant displacement: COP, capacity, input, heat rejected (kW), p_c, T2."""
p_c, h1, h2s, h2, h3, _, t2 = cycle(t_c)
cap = MASS_FLOW * (h1 - h3)
elec = MASS_FLOW * (h2 - h1) / ETA_MOTOR
return {"cop": (h1 - h3) / (h2 - h1), "cap": cap, "elec": elec,
"q_c": MASS_FLOW * (h2 - h3), "p_c": p_c, "t2": t2,
"h": (h1, h2s, h3)}
def day(t_c):
"""Run hours and daily kWh of the condensing unit for the design daily load."""
m = machine(t_c)
hours = DAILY_LOAD / m["cap"]
comp = hours * m["elec"]
fan = hours * COND_FAN
return hours, comp, fan, comp + fan
def show(name, t_air, diff):
t_c = t_air + diff
m = machine(t_c)
hours, comp, fan, unit = day(t_c)
print(f"{name}: air {t_air:.0f} degC + {diff:.0f} K = condensing {t_c:.0f} degC")
print(f" head pressure {m['p_c'] / 1e5:.3f} bar abs = "
f"{(m['p_c'] - P_ATM) / 1e5:.3f} bar gauge at the site")
print(f" h1 {m['h'][0]:.2f}, h2s {m['h'][1]:.2f}, h3 {m['h'][2]:.2f} kJ/kg, "
f"discharge {m['t2']:.1f} degC")
print(f" COP {m['cop']:.3f}, capacity {m['cap']:.3f} kW, input {m['elec']:.3f} kW, "
f"heat rejected {m['q_c']:.3f} kW")
print(f" run {hours:.2f} h/day, compressor {comp:.2f} kWh, fan {fan:.2f} kWh, "
f"unit {unit:.2f} kWh/day")
print(f" {unit * 365:.0f} kWh/year, cost {unit * 365 * PRICE:.0f} per year")
return unit, m
# ---------- Theory: what the condenser does at the design point ----------
m0 = machine(T_C0)
c_air = AIR_FLOW * RHO_AIR * CP_AIR # kW/K
rise = m0["q_c"] / c_air
print("Design condenser")
print(f" heat rejected {m0['q_c']:.3f} kW, conductance on entering air "
f"{m0['q_c'] * 1000 / 12:.0f} W/K")
print(f" air rise through the coil {rise:.1f} K, leaving air {30 + rise:.1f} degC")
r = 0.20
print(f" with {100 * r:.0f} % of the leaving air returning, entering air "
f"{30 + r * rise / (1 - r):.1f} degC")
# ---------- Head pressure against the condenser difference, air at 30 degC ----------
print("Condenser difference sweep, entering air 30 degC")
print(" diff T_c bar abs bar gauge COP capacity input")
for diff in (12, 14, 16, 18, 20):
m = machine(30.0 + diff)
print(f" {diff:3d} {30 + diff:3d} {m['p_c'] / 1e5:6.3f} "
f"{(m['p_c'] - P_ATM) / 1e5:6.3f} {m['cop']:5.3f} {m['cap']:5.3f} "
f"{m['elec']:5.3f}")
# ---------- Application 1: dirty coil ----------
clean, _ = show("Clean coil", 30.0, 12.0)
dirty, md = show("Dirty coil", 30.0, 18.0)
print(f" conductance of the dirty coil {md['q_c'] * 1000 / 18:.0f} W/K "
f"({100 * md['q_c'] / 18 / (m0['q_c'] / 12):.0f} % of clean)")
extra = dirty - clean
print(f" dirty against clean: {extra:+.3f} kWh/day ({100 * extra / clean:+.1f} %), "
f"{extra * 365:+.0f} kWh/year, {extra * 365 * PRICE:+.0f} per year")
one = day(43.0)[3]
print(f" one kelvin (42 to 43 degC): {one - clean:+.3f} kWh/day "
f"({100 * (one / clean - 1):+.1f} %), {(one - clean) * 365 * PRICE:+.0f} per year")
# ---------- Application 2: closed plant room against shaded outside air ----------
room, mr = show("Closed plant room", 38.0, 12.0)
heat_room = mr["cap"] + mr["elec"] + COND_FAN
print(f" heat released in the plant room {heat_room:.3f} kW; outside air for an "
f"8 K rise {heat_room / (RHO_AIR * CP_AIR * 8.0):.3f} m3/s")
outside, _ = show("Shaded outside air", 30.0, 12.0)
saving = room - outside
print(f" moving the unit saves {saving:.3f} kWh/day ({100 * saving / room:.1f} %), "
f"{saving * 365:.0f} kWh/year, {saving * 365 * PRICE:.0f} per year")
# ---------- Plot: yearly cost against the condenser temperature difference ----------
diffs = np.arange(8.0, 24.5, 0.5)
fig, ax = plt.subplots(figsize=(8, 4.5))
for t_air in (30.0, 38.0):
cost = [day(t_air + d)[3] * 365 * PRICE / 1000 for d in diffs]
ax.plot(diffs, cost, label=f"entering air at {t_air:.0f} degC")
ax.plot([12, 18], [clean * 365 * PRICE / 1000, dirty * 365 * PRICE / 1000], "o",
color="black")
ax.set_xlabel("condenser temperature difference (K)")
ax.set_ylabel("condensing unit electricity (thousand units a year)")
ax.set_title("Cost of the condenser temperature difference, load 36.95 kWh a day")
ax.grid(True, linewidth=0.3)
ax.legend()
fig.tight_layout()
fig.savefig("condenser_head_pressure.png", dpi=120)
print("Saved condenser_head_pressure.png")

Expected output

Design condenser
heat rejected 3.983 kW, conductance on entering air 332 W/K
air rise through the coil 9.2 K, leaving air 39.2 degC
with 20 % of the leaving air returning, entering air 32.3 degC
Condenser difference sweep, entering air 30 degC
diff T_c bar abs bar gauge COP capacity input
12 42 10.722 9.887 3.053 3.000 1.156
14 44 11.301 10.466 2.889 2.939 1.197
16 46 11.903 11.068 2.738 2.878 1.237
18 48 12.529 11.694 2.596 2.817 1.276
20 50 13.179 12.344 2.464 2.755 1.315
Clean coil: air 30 degC + 12 K = condensing 42 degC
head pressure 10.722 bar abs = 9.887 bar gauge at the site
h1 400.27, h2s 432.98, h3 253.42 kJ/kg, discharge 67.7 degC
COP 3.053, capacity 3.000 kW, input 1.156 kW, heat rejected 3.983 kW
run 12.32 h/day, compressor 14.24 kWh, fan 1.11 kWh, unit 15.35 kWh/day
5602 kWh/year, cost 67228 per year
Dirty coil: air 30 degC + 18 K = condensing 48 degC
head pressure 12.529 bar abs = 11.694 bar gauge at the site
h1 400.27, h2s 436.38, h3 262.39 kJ/kg, discharge 75.0 degC
COP 2.596, capacity 2.817 kW, input 1.276 kW, heat rejected 3.901 kW
run 13.12 h/day, compressor 16.74 kWh, fan 1.18 kWh, unit 17.92 kWh/day
6542 kWh/year, cost 78501 per year
conductance of the dirty coil 217 W/K (65 % of clean)
dirty against clean: +2.574 kWh/day (+16.8 %), +939 kWh/year, +11273 per year
one kelvin (42 to 43 degC): +0.410 kWh/day (+2.7 %), +1796 per year
Closed plant room: air 38 degC + 12 K = condensing 50 degC
head pressure 13.179 bar abs = 12.344 bar gauge at the site
h1 400.27, h2s 437.48, h3 265.43 kJ/kg, discharge 77.5 degC
COP 2.464, capacity 2.755 kW, input 1.315 kW, heat rejected 3.873 kW
run 13.41 h/day, compressor 17.64 kWh, fan 1.21 kWh, unit 18.85 kWh/day
6879 kWh/year, cost 82552 per year
heat released in the plant room 4.160 kW; outside air for an 8 K rise 0.539 m3/s
Shaded outside air: air 30 degC + 12 K = condensing 42 degC
head pressure 10.722 bar abs = 9.887 bar gauge at the site
h1 400.27, h2s 432.98, h3 253.42 kJ/kg, discharge 67.7 degC
COP 3.053, capacity 3.000 kW, input 1.156 kW, heat rejected 3.983 kW
run 12.32 h/day, compressor 14.24 kWh, fan 1.11 kWh, unit 15.35 kWh/day
5602 kWh/year, cost 67228 per year
moving the unit saves 3.499 kWh/day (18.6 %), 1277 kWh/year, 15324 per year
Saved condenser_head_pressure.png

In the plot the two lines rise almost in parallel, about 8 K of entering air apart. A point on the upper line with a clean coil costs as much as a point on the lower line with a very dirty one.

Common Mistakes



  • Taking the air temperature from a weather report. The condenser responds to the air that enters its coil, which may be several kelvin warmer because of recirculation, a closed room or the sun.
  • Judging the condenser by the head pressure alone. A head pressure of 11.7 bar gauge is normal for this unit in 36 °C air and a fault in 30 °C air. Compare the condensing temperature with the entering air temperature.
  • Treating a high head pressure as proof of a dirty coil. Too much refrigerant and gas that cannot condense give a similar reading, and separating them is a technician’s work.
  • Counting only the higher power. The capacity falls too, so the compressor also runs longer: its 17.6 percent more energy came from 10.4 percent more power and 6.5 percent more hours.

Summary



  • The condenser rejects the heat from the room plus the compressor’s work: 3.983 kW at the design point.
  • The condensing temperature is the entering air temperature plus the condenser temperature difference. For this unit, and 10.722 bar absolute, which is 9.887 bar gauge at this site.
  • Dirt, a blocked air path and a weak fan raise the difference. Recirculation, a closed room and sun raise the entering air temperature. Each kelvin costs this system about 2.8 percent of its COP.
  • A dirty coil at 18 K gives 48 °C and 11.694 bar gauge, a COP of 2.596, a capacity of 2.817 kW and an input of 1.276 kW. The unit uses 17.92 kWh a day against 15.35 kWh, which costs about 11,300 currency units a year.
  • A clean unit in a plant room at 38 °C condenses at 50 °C and uses 18.85 kWh a day. Moving it to shaded air at 30 °C saves 3.50 kWh a day, about 15,300 currency units a year.
  • In a record, a condenser that rejects heat badly shows a higher head pressure at the same air temperature, a higher input power and a longer run time.

Exercises



1. The entering air is at 34 °C and the coil is clean (difference 12 K). Use the head-pressure table. Find the condensing temperature, the gauge reading at this site, and the run hours and daily electricity of the condensing unit (compressor and 90 W fan) for the 36.95 kWh load.

Answer

, 11.903 bar absolute, 11.068 bar gauge. Capacity 2.878 kW and input 1.237 kW, so run hours and electricity a day.

2. A high-side gauge at this site (atmosphere 83.5 kPa) reads 12.0 bar while the air entering the coil is at 30 °C. CoolProp gives the saturation temperature of R134a at 12.835 bar absolute as 49.0 °C. Find the condenser temperature difference and say whether it is normal for this unit.

Answer

, so and the difference is . The design value is 12 K, so the condenser rejects heat badly or something else raises the head pressure. The reading alone does not show which.

3. On a cool night the entering air is at 18 °C, and the unit could condense at 30 °C. A head-pressure control holds 38 °C. CoolProp gives at 30 °C: and , with and . Find the cycle COP at 30 °C. The COP at 38 °C is 3.420. By what percentage does the control raise the compressor energy for the cooling done in those hours?

Answer

, , COP . Energy for the same cooling rises by percent. Whether the valve of a given system can work at 30 °C is a question for its maker’s data.

4. A coil is cleaned twice a year, and between cleanings its difference grows evenly from 12 K to 18 K, so the average is 15 K ( at 30 °C air). At 45 °C the capacity is 2.909 kW and the input 1.217 kW. Find the run hours, the daily electricity of the condensing unit for the 36.95 kWh load, and the yearly cost above the clean figure of 15.35 kWh a day at 12.00 per kWh.

Answer

Run hours . Electricity a day, which is 1.25 kWh above clean. In a year that is 457 kWh, about 5,480 currency units. This is about half of the 11,273 units of a coil that is never cleaned.

References



  • W. F. Stoecker and J. W. Jones, Refrigeration and Air Conditioning, 2nd edition, McGraw-Hill, 1982.
  • R. J. Dossat and T. J. Horan, Principles of Refrigeration, 5th edition, Prentice Hall, 2001.
  • ASHRAE, ASHRAE Handbook: HVAC Systems and Equipment, American Society of Heating, Refrigerating and Air-Conditioning Engineers, 2020 (chapter on condensers).
  • I. H. Bell, J. Wronski, S. Quoilin and V. Lemort, “Pure and Pseudo-pure Fluid Thermophysical Property Evaluation and the Open-Source Thermophysical Property Library CoolProp”, Industrial and Engineering Chemistry Research, vol. 53, no. 6, 2014.


© 2021-2026 SiliconWit®. All rights reserved.
Predict first

The condenser coil of the cold room is grey with dust, but the room still holds 4 °C all day. What does the dust cost?

air 36 °C+ 12 Kair 30 °C+ 18 K clean coil, hot daydirty coil, normal day 48 °C, 11.69 bar gauge
unit 30 °C fresh39.2 °Cone fifth turns back 32.3 °C in
Try it: the air, the coil, the gauge and the bill

Condensing, head pressure
Cycle COP, capacity
Extra cost a year

The cold room's unit with every refrigerant value from CoolProp: evaporating at −6 °C, superheat 6 K, subcooling 4 K, the constant-displacement compressor of this course, a 90 W fan that runs with the compressor, and a daily load of 36.95 kWh. The air that returns is warmed by 9.2 K, its rise at design. The gauge reads above the site's 83.5 kPa atmosphere. Costs are at 12.00 currency units per kWh against the design point.

Watch it build: what sets the condensing temperature
condensing unit 30 °C30 °C air 42 °C12 K 332 W per K dirt on the fins 48 °C18 K 39.2 °C 42 °C12 K 20 % comes back 32.3 °C 32.3 °C 44.3 °C12 K
  1. Air enters the coil at 30 °C. The refrigerant must be 12 K warmer: it condenses at 42 °C.
  2. The coil passes 3,983 W ÷ 12 K = 332 W per kelvin of difference.
  3. Dirt lowers that conductance, so the difference grows: 18 K, condensing at 48 °C.
  4. Clean again. The fan blows the air out 9.2 K warmer, at 39.2 °C.
  5. If 20 percent of it returns, the air enters at 32.3 °C, and the refrigerant condenses at 44.3 °C.
Condenser coil refrigerant at 42 °C and 10.72 bar abs Fan 90 W hot gas from the compressor, 67.7 °C air in 30 °C air out 39.2 °C liquid to the expansion valve, 38 °C heat given to the air: 3.98 kW
The condensing unit and what crosses it
OPEN, SHADED RECIRCULATION Unit 39 °C away 30 °C Unit wall 32 °C or more CLOSED PLANT ROOM Unit warm air stays in the room 38 °C the room air rises until the walls and the leaks carry the heat away
Where the entering air becomes too warm

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. The weather report says 30 °C. The unit stands close to a wall and a quarter of its warm air (9.2 K above the air it took in) returns to the inlet. The coil is clean, with a 12 K difference. At what temperature does the refrigerant condense?

2. A smaller load of 30 kWh of heat a day meets the same dirty coil (18 K, condensing at 48 °C, 2.817 kW and 1.276 kW against 3.000 kW and 1.156 kW clean, fan 90 W). What does the dirt cost in a year at 12.00 units per kWh?

3. On a cold night at 12 °C the head pressure of a unit stays at the same minimum value hour after hour, and the condenser fan switches on and off. What does this show?