Condensing temperature
Condensers, Ambient Temperature and Head Pressure
On this page
The condensing unit of a cold room stands in a corner behind the store, and its coil has turned grey with dust. The room still holds 4 °C, so nobody looks at the unit. The compressor works against a higher pressure for every minute that it runs, draws more power, cools less, and runs longer, and the bill has risen by a sixth with no visible cause. This lesson shows how the air at the condenser sets the condensing temperature and the head pressure, and how to put a yearly cost on a dirty coil and on a badly placed unit. #Refrigeration #Condenser #HeadPressure
Learning Objectives
By the end of this lesson, you will be able to:
- Calculate the condensing temperature and the head pressure from the entering air temperature and the condenser temperature difference
- Explain what raises the condenser temperature difference and what raises the temperature of the entering air
- Compute the COP, capacity, input power, run hours and daily energy at a higher condensing temperature
- Estimate the yearly cost of a dirty condenser and the yearly saving from a better position for the unit
- Recognise a condenser that rejects heat badly in a record of temperature, power and run time
Real-World System Problem: The condensing unit of the cold room
The cold room of this course has an R134a system with a cooling capacity of 3.0 kW at its design point. The condensing unit holds the compressor, the condenser coil and one fan of 90 W. The fan draws air at 30 °C through the finned coil. Inside the tubes the refrigerant arrives as hot gas, condenses at 42 °C, and leaves as liquid at 38 °C.
The condenser is the only place where heat leaves the system: everything the evaporator took from the room passes through it, with the work of the compressor. The refrigerant can give this heat to the air only if it is warmer than the air, by an amount that is not fixed. A clean coil with a free flow of air needs about 12 K; a dusty coil needs more, and each extra kelvin raises the pressure against which the compressor works.
Fundamental Theory: The air, the coil and the pressure
What the condenser must reject
The first law for the refrigerant circuit says that the heat rejected equals the heat absorbed plus the work that the compressor gives to the refrigerant:
Condensing temperature follows the air
Heat flows from the refrigerant to the air because the refrigerant is warmer. The condenser temperature difference is the condensing temperature minus the temperature of the air that enters the coil.
The compressor does not choose the condensing temperature: the condenser pressure rises until the refrigerant is warm enough to give all its heat to the air, and settles there. A simple model shows the size of the difference:
The two terms of the formula fail in different ways, and the remedy differs, so keep them apart.
What raises the difference
Anything that lowers the conductance of the coil raises
- Dust, grease, leaves or insects on the fins. They insulate the metal and block the passages.
- A blocked air path: boxes stacked against the coil, or a unit pushed against a wall.
- A fan that has failed, turns slowly, or has a damaged blade.
- Fins that are bent flat over part of the face.
Air inside the refrigerant circuit, or any other gas that cannot condense, has a similar effect from the inside. It is described below.
What raises the entering air temperature
The entering air is not always the surrounding air. The common mistake is to take the air temperature from a weather report or a thermometer across the yard, and then blame the coil for a difference that is not its fault.
At design the fan moves 0.45 m³/s, and the air leaves 9.2 K warmer, at 39.2 °C. If that warm air finds its way back to the inlet, the coil breathes its own exhaust, as a sleeper with a blanket over the head breathes warm breath. With a fraction
Head pressure
Head pressure is the pressure on the high side. In the condenser it is the saturation pressure at
| Gauge (bar) | Cycle COP | Capacity (kW) | Input (kW) | |||
|---|---|---|---|---|---|---|
| 12 | 42 | 10.722 | 9.887 | 3.053 | 3.000 | 1.156 |
| 14 | 44 | 11.301 | 10.466 | 2.889 | 2.939 | 1.197 |
| 16 | 46 | 11.903 | 11.068 | 2.738 | 2.878 | 1.237 |
| 18 | 48 | 12.529 | 11.694 | 2.596 | 2.817 | 1.276 |
| 20 | 50 | 13.179 | 12.344 | 2.464 | 2.755 | 1.315 |
The capacity and input columns use the constant-displacement compressor model of this course. Near 45 °C each kelvin adds about 0.3 bar to the head pressure.
The cost of each kelvin
Near its design point this system loses 2.78 percent of its COP for each kelvin of higher condensing temperature, so the compressor needs more electricity for the same cooling. For this room’s daily load of 36.95 kWh of heat, one kelvin adds 0.41 kWh a day to the condensing unit, about 1,800 currency units a year at 12.00 per kWh. The capacity also falls, by about 1 percent per kelvin, so the compressor runs longer.
Head-pressure control
If a low condensing temperature is good, a cold night should be the best time to run, and it is, up to a limit. The expansion valve needs a pressure difference to push enough liquid into the evaporator, and when the head pressure falls too far it cannot feed the coil. So many units hold a minimum head pressure, most often by stopping or slowing the condenser fan. The control is necessary, and it has a price: a minimum set higher than the valve needs discards the cheap running that cool hours offer. The setting belongs to the maker’s data and a qualified technician.
Non-condensable gas
Air or nitrogen that has entered the circuit cannot condense at these pressures. It collects in the condenser, adds its own pressure to the refrigerant’s, and covers tube surface that should condense vapour. The head pressure is then higher than the coil temperature explains, and the compressor pays for the excess as it pays for dirt. A record shows a condenser temperature difference that stays high after the coil is cleaned and the air flow checked. Confirming it and removing the gas are tasks for a qualified refrigeration technician, and this lesson gives no method for them.
Where a condensing unit should stand
The unit needs cool air that passes through the coil once and then leaves. So it belongs outside or in a space open to outside air, in the shade, with the clear distances that the maker states, with its warm air blown away from the inlet and from other units, and away from sources of dust, grease and lint. A unit inside a closed room heats that room with the heat from the cold room and with all of its own electricity.
What a dirty condenser looks like in a record
A dirty coil gives no alarm. It changes four readings, all in one direction, and the comparison must be made at the same entering air temperature:
| Quantity in the record | Clean coil | Dirty coil (Application 1) |
|---|---|---|
| Condensing temperature minus entering air (K) | 12 | 18 |
| Head pressure at 30 °C air (bar gauge) | 9.89 | 11.69 |
| Compressor input power (kW) | 1.156 | 1.276 |
| Discharge temperature (°C) | 67.7 | 75.0 |
| Compressor hours for the same daily load | 12.32 | 13.12 |
The suction pressure hardly moves. A high head pressure alone does not name the cause: a coil that rejects heat badly, too much refrigerant and gas that cannot condense all raise it.
Application 1: A dirty condenser coil
Step 1: Condensing temperature and head pressure
Click to reveal the temperature and the pressure
-
Condensing temperature.
The refrigerant condenses 6 K warmer than with the clean coil. ✅
-
Head pressure. The saturation pressure of R134a at 48 °C is 12.529 bar absolute. A gauge at the site reads
With the clean coil the gauge read
. The dirt has added 1.81 bar. ✅
Step 2: The cycle with the dirty coil
Click to reveal the COP, the capacity and the power
-
Refrigerating effect and work.
Each kilogram cools less and needs more work. ✅
-
Cycle COP.
The COP falls from 3.053 to 2.596, a loss of 15.0 percent. ✅
-
Capacity and input power.
The unit gives 0.183 kW less cooling and takes 0.120 kW more power. ✅
-
The same numbers as a hot day. These are exactly the figures of the hot-day case of the COP lesson, where air at 36 °C met a clean coil. The compressor cannot tell the two apart: it sees only 48 °C. The difference is that a hot day ends in the evening, and dirt stays. ✅
Step 3: Hours and energy for the same daily load
Click to reveal the daily figures
-
Clean coil.
The fan adds
, so the condensing unit uses 15.35 kWh a day. ✅ -
Dirty coil.
The fan adds
, so the condensing unit uses 17.92 kWh a day. ✅ -
Difference. The compressor runs 0.80 h longer each day (48 minutes), and the unit uses
more, which is 16.8 percent. ✅
Step 4: The yearly cost and a check
Click to reveal the cost
-
Energy in a year of 365 days. With unrounded daily values, the clean unit uses 5,602 kWh and the dirty unit 6,542 kWh. The dirt costs 939 kWh a year. ✅
-
Cost.
The script, with unrounded values, gives 11,273. ✅
-
Check with the COP ratio. For the same load, the compressor energy is the inverse of the COP.
This agrees with the 16.74 kWh of the hours method. ✅
-
What the dirt did to the coil. The dirty coil rejects
across 18 K, where . Its conductance is , which is 65 percent of the clean 332 W/K. ✅
Application 2: A closed plant room against shaded outside air
Step 1: The cycle in the plant room
Click to reveal the cycle at 50 °C
-
Condensing temperature and head pressure.
The coil is clean, and the head pressure is still 2.46 bar above its design reading. ✅
-
Refrigerating effect, work and COP.
✅
-
Capacity and input power.
✅
Step 2: Why the plant room is hot
Click to reveal the room balance
-
Boundary round the plant room. The cold room is outside this boundary. The refrigerant brings in the heat taken from the cold room, and the supply cable brings in the electricity of the compressor and the fan. All of it becomes heat in the plant-room air.
✅
-
Outside air needed for a rise of 8 K.
A room at 38 °C is one that receives about this much outside air and no more. A grille and a door gap rarely pass so much without a fan, so a real plant room can be hotter. ✅
Step 3: Daily energy and the yearly saving
Click to reveal the comparison
-
Plant room.
The fan adds
, so the unit uses 18.85 kWh a day. (The products use unrounded values.) ✅ -
Shaded outside air. The unit runs at the design point: 12.32 h and 15.35 kWh a day. ✅
-
Saving.
This is 18.6 percent of the unit’s electricity. In a year it is 1,277 kWh, worth 15,324 currency units. ✅
-
Check with the percent-per-kelvin figure. Eight kelvin at 2.78 percent each predicts a COP loss of 22 percent. The cycle gives
percent. The straight-line figure overstates a change as large as 8 K, as the COP tables showed, and it confirms the size of the answer. ✅
Verify It in Python
The script builds the cycle at any condensing temperature with CoolProp, prints the head-pressure table and both applications, and plots the yearly cost of the condensing unit against the condenser temperature difference for entering air at 30 °C and 38 °C. It needs CoolProp as well as numpy and matplotlib: pip install CoolProp.
"""Condenser of the cold room: air temperature, head pressure and the cost of each kelvin."""import numpy as npimport matplotlib.pyplot as pltfrom CoolProp.CoolProp import PropsSI
FLUID = "R134a"K0 = 273.15T_E, SUPERHEAT, SUBCOOLING = -6.0, 6.0, 4.0 # degC, K, KETA_IS, ETA_MOTOR = 0.68, 0.85CAPACITY0, T_C0 = 3.0, 42.0 # kW and degC at the design pointP_ATM = 83.5e3 # Pa, atmosphere at the siteCOND_FAN = 0.090 # kW, runs with the compressorDAILY_LOAD = 36.95 # kWh of heat a day (energy balance)PRICE = 12.00 # currency units per kWhAIR_FLOW, RHO_AIR, CP_AIR = 0.45, 0.96, 1.005 # m3/s, kg/m3, kJ/(kg.K)
def cycle(t_c): """States of the cycle at a condensing temperature in degC (kJ/kg, Pa).""" p_e = PropsSI("P", "T", T_E + K0, "Q", 1, FLUID) p_c = PropsSI("P", "T", t_c + K0, "Q", 0, FLUID) t1 = T_E + SUPERHEAT + K0 h1 = PropsSI("H", "T", t1, "P", p_e, FLUID) s1 = PropsSI("S", "T", t1, "P", p_e, FLUID) rho1 = PropsSI("D", "T", t1, "P", p_e, FLUID) h2s = PropsSI("H", "P", p_c, "S", s1, FLUID) h2 = h1 + (h2s - h1) / ETA_IS h3 = PropsSI("H", "T", t_c - SUBCOOLING + K0, "P", p_c, FLUID) t2 = PropsSI("T", "P", p_c, "H", h2, FLUID) - K0 return p_c, h1 / 1e3, h2s / 1e3, h2 / 1e3, h3 / 1e3, rho1, t2
_, H1, _, H2, H3, RHO1, _ = cycle(T_C0)MASS_FLOW = CAPACITY0 / (H1 - H3) # kg/s, fixed: the suction state does not move
def machine(t_c): """Constant displacement: COP, capacity, input, heat rejected (kW), p_c, T2.""" p_c, h1, h2s, h2, h3, _, t2 = cycle(t_c) cap = MASS_FLOW * (h1 - h3) elec = MASS_FLOW * (h2 - h1) / ETA_MOTOR return {"cop": (h1 - h3) / (h2 - h1), "cap": cap, "elec": elec, "q_c": MASS_FLOW * (h2 - h3), "p_c": p_c, "t2": t2, "h": (h1, h2s, h3)}
def day(t_c): """Run hours and daily kWh of the condensing unit for the design daily load.""" m = machine(t_c) hours = DAILY_LOAD / m["cap"] comp = hours * m["elec"] fan = hours * COND_FAN return hours, comp, fan, comp + fan
def show(name, t_air, diff): t_c = t_air + diff m = machine(t_c) hours, comp, fan, unit = day(t_c) print(f"{name}: air {t_air:.0f} degC + {diff:.0f} K = condensing {t_c:.0f} degC") print(f" head pressure {m['p_c'] / 1e5:.3f} bar abs = " f"{(m['p_c'] - P_ATM) / 1e5:.3f} bar gauge at the site") print(f" h1 {m['h'][0]:.2f}, h2s {m['h'][1]:.2f}, h3 {m['h'][2]:.2f} kJ/kg, " f"discharge {m['t2']:.1f} degC") print(f" COP {m['cop']:.3f}, capacity {m['cap']:.3f} kW, input {m['elec']:.3f} kW, " f"heat rejected {m['q_c']:.3f} kW") print(f" run {hours:.2f} h/day, compressor {comp:.2f} kWh, fan {fan:.2f} kWh, " f"unit {unit:.2f} kWh/day") print(f" {unit * 365:.0f} kWh/year, cost {unit * 365 * PRICE:.0f} per year") return unit, m
# ---------- Theory: what the condenser does at the design point ----------m0 = machine(T_C0)c_air = AIR_FLOW * RHO_AIR * CP_AIR # kW/Krise = m0["q_c"] / c_airprint("Design condenser")print(f" heat rejected {m0['q_c']:.3f} kW, conductance on entering air " f"{m0['q_c'] * 1000 / 12:.0f} W/K")print(f" air rise through the coil {rise:.1f} K, leaving air {30 + rise:.1f} degC")r = 0.20print(f" with {100 * r:.0f} % of the leaving air returning, entering air " f"{30 + r * rise / (1 - r):.1f} degC")
# ---------- Head pressure against the condenser difference, air at 30 degC ----------print("Condenser difference sweep, entering air 30 degC")print(" diff T_c bar abs bar gauge COP capacity input")for diff in (12, 14, 16, 18, 20): m = machine(30.0 + diff) print(f" {diff:3d} {30 + diff:3d} {m['p_c'] / 1e5:6.3f} " f"{(m['p_c'] - P_ATM) / 1e5:6.3f} {m['cop']:5.3f} {m['cap']:5.3f} " f"{m['elec']:5.3f}")
# ---------- Application 1: dirty coil ----------clean, _ = show("Clean coil", 30.0, 12.0)dirty, md = show("Dirty coil", 30.0, 18.0)print(f" conductance of the dirty coil {md['q_c'] * 1000 / 18:.0f} W/K " f"({100 * md['q_c'] / 18 / (m0['q_c'] / 12):.0f} % of clean)")extra = dirty - cleanprint(f" dirty against clean: {extra:+.3f} kWh/day ({100 * extra / clean:+.1f} %), " f"{extra * 365:+.0f} kWh/year, {extra * 365 * PRICE:+.0f} per year")one = day(43.0)[3]print(f" one kelvin (42 to 43 degC): {one - clean:+.3f} kWh/day " f"({100 * (one / clean - 1):+.1f} %), {(one - clean) * 365 * PRICE:+.0f} per year")
# ---------- Application 2: closed plant room against shaded outside air ----------room, mr = show("Closed plant room", 38.0, 12.0)heat_room = mr["cap"] + mr["elec"] + COND_FANprint(f" heat released in the plant room {heat_room:.3f} kW; outside air for an " f"8 K rise {heat_room / (RHO_AIR * CP_AIR * 8.0):.3f} m3/s")outside, _ = show("Shaded outside air", 30.0, 12.0)saving = room - outsideprint(f" moving the unit saves {saving:.3f} kWh/day ({100 * saving / room:.1f} %), " f"{saving * 365:.0f} kWh/year, {saving * 365 * PRICE:.0f} per year")
# ---------- Plot: yearly cost against the condenser temperature difference ----------diffs = np.arange(8.0, 24.5, 0.5)fig, ax = plt.subplots(figsize=(8, 4.5))for t_air in (30.0, 38.0): cost = [day(t_air + d)[3] * 365 * PRICE / 1000 for d in diffs] ax.plot(diffs, cost, label=f"entering air at {t_air:.0f} degC")ax.plot([12, 18], [clean * 365 * PRICE / 1000, dirty * 365 * PRICE / 1000], "o", color="black")ax.set_xlabel("condenser temperature difference (K)")ax.set_ylabel("condensing unit electricity (thousand units a year)")ax.set_title("Cost of the condenser temperature difference, load 36.95 kWh a day")ax.grid(True, linewidth=0.3)ax.legend()fig.tight_layout()fig.savefig("condenser_head_pressure.png", dpi=120)print("Saved condenser_head_pressure.png")Expected output
Design condenser heat rejected 3.983 kW, conductance on entering air 332 W/K air rise through the coil 9.2 K, leaving air 39.2 degC with 20 % of the leaving air returning, entering air 32.3 degCCondenser difference sweep, entering air 30 degC diff T_c bar abs bar gauge COP capacity input 12 42 10.722 9.887 3.053 3.000 1.156 14 44 11.301 10.466 2.889 2.939 1.197 16 46 11.903 11.068 2.738 2.878 1.237 18 48 12.529 11.694 2.596 2.817 1.276 20 50 13.179 12.344 2.464 2.755 1.315Clean coil: air 30 degC + 12 K = condensing 42 degC head pressure 10.722 bar abs = 9.887 bar gauge at the site h1 400.27, h2s 432.98, h3 253.42 kJ/kg, discharge 67.7 degC COP 3.053, capacity 3.000 kW, input 1.156 kW, heat rejected 3.983 kW run 12.32 h/day, compressor 14.24 kWh, fan 1.11 kWh, unit 15.35 kWh/day 5602 kWh/year, cost 67228 per yearDirty coil: air 30 degC + 18 K = condensing 48 degC head pressure 12.529 bar abs = 11.694 bar gauge at the site h1 400.27, h2s 436.38, h3 262.39 kJ/kg, discharge 75.0 degC COP 2.596, capacity 2.817 kW, input 1.276 kW, heat rejected 3.901 kW run 13.12 h/day, compressor 16.74 kWh, fan 1.18 kWh, unit 17.92 kWh/day 6542 kWh/year, cost 78501 per year conductance of the dirty coil 217 W/K (65 % of clean) dirty against clean: +2.574 kWh/day (+16.8 %), +939 kWh/year, +11273 per year one kelvin (42 to 43 degC): +0.410 kWh/day (+2.7 %), +1796 per yearClosed plant room: air 38 degC + 12 K = condensing 50 degC head pressure 13.179 bar abs = 12.344 bar gauge at the site h1 400.27, h2s 437.48, h3 265.43 kJ/kg, discharge 77.5 degC COP 2.464, capacity 2.755 kW, input 1.315 kW, heat rejected 3.873 kW run 13.41 h/day, compressor 17.64 kWh, fan 1.21 kWh, unit 18.85 kWh/day 6879 kWh/year, cost 82552 per year heat released in the plant room 4.160 kW; outside air for an 8 K rise 0.539 m3/sShaded outside air: air 30 degC + 12 K = condensing 42 degC head pressure 10.722 bar abs = 9.887 bar gauge at the site h1 400.27, h2s 432.98, h3 253.42 kJ/kg, discharge 67.7 degC COP 3.053, capacity 3.000 kW, input 1.156 kW, heat rejected 3.983 kW run 12.32 h/day, compressor 14.24 kWh, fan 1.11 kWh, unit 15.35 kWh/day 5602 kWh/year, cost 67228 per year moving the unit saves 3.499 kWh/day (18.6 %), 1277 kWh/year, 15324 per yearSaved condenser_head_pressure.pngIn the plot the two lines rise almost in parallel, about 8 K of entering air apart. A point on the upper line with a clean coil costs as much as a point on the lower line with a very dirty one.
Common Mistakes
- Taking the air temperature from a weather report. The condenser responds to the air that enters its coil, which may be several kelvin warmer because of recirculation, a closed room or the sun.
- Judging the condenser by the head pressure alone. A head pressure of 11.7 bar gauge is normal for this unit in 36 °C air and a fault in 30 °C air. Compare the condensing temperature with the entering air temperature.
- Treating a high head pressure as proof of a dirty coil. Too much refrigerant and gas that cannot condense give a similar reading, and separating them is a technician’s work.
- Counting only the higher power. The capacity falls too, so the compressor also runs longer: its 17.6 percent more energy came from 10.4 percent more power and 6.5 percent more hours.
Summary
- The condenser rejects the heat from the room plus the compressor’s work: 3.983 kW at the design point.
- The condensing temperature is the entering air temperature plus the condenser temperature difference. For this unit,
and 10.722 bar absolute, which is 9.887 bar gauge at this site. - Dirt, a blocked air path and a weak fan raise the difference. Recirculation, a closed room and sun raise the entering air temperature. Each kelvin costs this system about 2.8 percent of its COP.
- A dirty coil at 18 K gives 48 °C and 11.694 bar gauge, a COP of 2.596, a capacity of 2.817 kW and an input of 1.276 kW. The unit uses 17.92 kWh a day against 15.35 kWh, which costs about 11,300 currency units a year.
- A clean unit in a plant room at 38 °C condenses at 50 °C and uses 18.85 kWh a day. Moving it to shaded air at 30 °C saves 3.50 kWh a day, about 15,300 currency units a year.
- In a record, a condenser that rejects heat badly shows a higher head pressure at the same air temperature, a higher input power and a longer run time.
Exercises
1. The entering air is at 34 °C and the coil is clean (difference 12 K). Use the head-pressure table. Find the condensing temperature, the gauge reading at this site, and the run hours and daily electricity of the condensing unit (compressor and 90 W fan) for the 36.95 kWh load.
Answer
2. A high-side gauge at this site (atmosphere 83.5 kPa) reads 12.0 bar while the air entering the coil is at 30 °C. CoolProp gives the saturation temperature of R134a at 12.835 bar absolute as 49.0 °C. Find the condenser temperature difference and say whether it is normal for this unit.
Answer
3. On a cool night the entering air is at 18 °C, and the unit could condense at 30 °C. A head-pressure control holds 38 °C. CoolProp gives at 30 °C:
Answer
4. A coil is cleaned twice a year, and between cleanings its difference grows evenly from 12 K to 18 K, so the average is 15 K (
Answer
Run hours
References
- W. F. Stoecker and J. W. Jones, Refrigeration and Air Conditioning, 2nd edition, McGraw-Hill, 1982.
- R. J. Dossat and T. J. Horan, Principles of Refrigeration, 5th edition, Prentice Hall, 2001.
- ASHRAE, ASHRAE Handbook: HVAC Systems and Equipment, American Society of Heating, Refrigerating and Air-Conditioning Engineers, 2020 (chapter on condensers).
- I. H. Bell, J. Wronski, S. Quoilin and V. Lemort, “Pure and Pseudo-pure Fluid Thermophysical Property Evaluation and the Open-Source Thermophysical Property Library CoolProp”, Industrial and Engineering Chemistry Research, vol. 53, no. 6, 2014.
The condenser coil of the cold room is grey with dust, but the room still holds 4 °C all day. What does the dust cost?
The cold room's unit with every refrigerant value from CoolProp: evaporating at −6 °C, superheat 6 K, subcooling 4 K, the constant-displacement compressor of this course, a 90 W fan that runs with the compressor, and a daily load of 36.95 kWh. The air that returns is warmed by 9.2 K, its rise at design. The gauge reads above the site's 83.5 kPa atmosphere. Costs are at 12.00 currency units per kWh against the design point.
- Air enters the coil at 30 °C. The refrigerant must be 12 K warmer: it condenses at 42 °C.
- The coil passes 3,983 W ÷ 12 K = 332 W per kelvin of difference.
- Dirt lowers that conductance, so the difference grows: 18 K, condensing at 48 °C.
- Clean again. The fan blows the air out 9.2 K warmer, at 39.2 °C.
- If 20 percent of it returns, the air enters at 32.3 °C, and the refrigerant condenses at 44.3 °C.
Check yourself
Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.
1. The weather report says 30 °C. The unit stands close to a wall and a quarter of its warm air (9.2 K above the air it took in) returns to the inlet. The coil is clean, with a 12 K difference. At what temperature does the refrigerant condense?
2. A smaller load of 30 kWh of heat a day meets the same dirty coil (18 K, condensing at 48 °C, 2.817 kW and 1.276 kW against 3.000 kW and 1.156 kW clean, fan 90 W). What does the dirt cost in a year at 12.00 units per kWh?
3. On a cold night at 12 °C the head pressure of a unit stays at the same minimum value hour after hour, and the condenser fan switches on and off. What does this show?
Discussion
No comments yet. Questions, results from your own build, a better way to explain it: all welcome.