Superheat, Subcooling and the Expansion Valve

Lesson 5 of 10 25 min read
Found this useful?

A compressor is built to pump vapour. If liquid refrigerant reaches it, the liquid washes the oil from the bearings, and a cylinder that tries to compress liquid can break its valves in a single stroke. The opposite fault is quieter: an evaporator that receives too little liquid still cools, but with only part of its surface, and the compressor runs for more hours to do the same work. Both conditions show in two small temperature differences that can be calculated from two pressures and two pipe temperatures. This lesson shows how to calculate them correctly at any altitude, what each one protects, and what their patterns mean in a record. #Superheat #Subcooling #ExpansionValve

Learning Objectives

By the end of this lesson, you will be able to:

  1. Calculate superheat and subcooling from a gauge pressure, a pipe temperature and the atmospheric pressure of the site
  2. Explain what superheat protects in the compressor and what subcooling protects in the liquid line
  3. Describe how a thermostatic expansion valve senses superheat with a bulb, and what an electronic valve adds
  4. Recognise three reading patterns and state what each is consistent with, without treating a pattern as a certain diagnosis

Real-World System Problem: Four readings on a cold room’s circuit



The cold room of this course holds produce at 4 °C with an R134a system that evaporates at −6 °C and condenses at 42 °C at its design point. The vapour reaches the compressor 6 K warmer than its boiling temperature, and the liquid leaves the condenser 4 K cooler than its condensing temperature. Those two small differences are the superheat and the subcooling.

Neither can be read from one instrument. Each needs a pressure and a temperature at the same place: one pair on the suction line, between the evaporator and the compressor, and one on the liquid line, between the condenser and the expansion valve. The pressure gives the saturation temperature; the pipe gives the real temperature.

The site is about 1,600 m above sea level, where the atmosphere is at 83.5 kPa. A gauge there reads differently from the same gauge at the coast, and a superheat calculated with the sea-level atmosphere is wrong by about 2 K, one third of its design value.

EXPANSIONVALVEEVAPORATOR−6 °CCOMPRESSORliquid linepandTCONDENSER●42 °CpandT●suction line
Where the four readings are taken

Fundamental Theory: Two differences and the valve that holds one of them



The idea: how far from boiling

At one pressure a refrigerant boils and condenses at one temperature, the saturation temperature. Superheat and subcooling say how far the refrigerant at a point is from it, and on which side.

Vapour warmer than its saturation temperature is superheated: it holds no liquid, and its kelvin above saturation are the margin before liquid could be present. Liquid cooler than its saturation temperature is subcooled: it holds no bubbles, and its kelvin below saturation are the margin before it boils. A pan of water is the everyday case: it stays at 100 °C while any water is left, and only a dry pan gets hotter.

The two definitions

Superheat and subcooling

is the measured temperature of the suction line and is the saturation temperature at the measured suction pressure. is the saturation temperature at the measured liquid-line pressure and is the measured temperature of the liquid line. Both are in kelvin.

Both are written so that a healthy value is positive. A result near zero means the refrigerant at that point is at saturation, where liquid and vapour can exist together.

From a gauge reading to a saturation temperature

Property data needs absolute pressure, and a gauge reads the pressure above the air round it, so the calculation always has three steps.

  1. Add the atmospheric pressure of the site to the gauge reading: .
  2. Find the saturation temperature at that absolute pressure, from CoolProp or from a table for the correct refrigerant.
  3. Subtract: pipe temperature minus saturation temperature for superheat, saturation temperature minus pipe temperature for subcooling.

For a blend with glide, such as R449A, step 2 has two answers: use the dew point for superheat and the bubble point for subcooling, or the result is wrong by the glide, about 5 K on R449A.

With CoolProp, step 2 is one line (any quality between 0 and 1 gives the same answer for a pure refrigerant):

from CoolProp.CoolProp import PropsSI
t_sat = PropsSI("T", "P", 234300, "Q", 0.5, "R134a") - 273.15 # degC

Install the library once with pip install CoolProp. Every refrigerant property in this lesson comes from CoolProp’s reference equation of state for R134a. The lesson needs only pressures and temperatures; where energy is discussed, only enthalpy differences matter, because values depend on the reference state of their source.

The common mistake is in step 1. The atmosphere is 101.3 kPa at sea level and 83.5 kPa at this site, so a person who adds the sea-level value, or reads the scale printed on a gauge, uses an absolute pressure 17.8 kPa too high. The saturation curve of R134a rises by 8.93 kPa per kelvin near −6 °C and by 28.4 kPa per kelvin near 42 °C, so the same 17.8 kPa is worth about 2 K on the suction side and only 0.6 K on the liquid side.

What superheat protects

Inside the evaporator the refrigerant is a boiling mixture at for as long as liquid remains; only after the last liquid has boiled can the vapour warm toward the room temperature. A suction line several kelvin above is therefore evidence that boiling finished inside the evaporator and the compressor receives dry vapour. Liquid in the compressor washes the oil from the bearings and can break the valves.

T (°C)4room air0● T16 K−6●boiling●Telast liquidinlet (state 4)outlet (state 1)
Temperature along the evaporator tube

Superheat is not free. The tube that warms vapour takes very little heat, because vapour transfers heat far less well than boiling liquid. A superheat far above design means a large part of the coil does almost nothing, so the evaporating temperature falls to make the rest carry the load, which costs COP and makes the discharge gas hotter. The design value is a compromise: enough margin to keep liquid out, and no more.

What subcooling protects

The expansion valve is sized to pass liquid. Liquid R134a at 38 °C has a density of 1,156 kg/m³, about a hundred times that of the vapour at the compressor inlet, so bubbles that reach the valve take the place of liquid in the orifice, the mass flow falls and the evaporator is starved. Vapour that forms in the liquid line before the valve is called flash gas.

Liquid that leaves the condenser exactly at saturation has no margin: any fall in pressure makes it boil, and the liquid line always loses some, by friction, in the filter drier, and wherever the pipe rises. For a height the pressure falls by , where is the liquid density and . For a rise of 5 m:

At the top of the rise the pressure is , where the saturation temperature is 40.0 °C. Liquid that left the condenser at 38 °C still has 2.0 K of subcooling there, so it stays liquid. Saturated liquid at 42 °C would have started to boil on the way up.

Subcooling also adds a little cooling, because cooler liquid makes less flash gas in the valve. And it shows where the liquid is: the condenser cools liquid only in tubes full of liquid, so a high subcooling means much of the condenser is filled with liquid and less surface is left for condensing, and a subcooling near zero means the condenser holds almost no reserve of liquid.

How a thermostatic expansion valve senses superheat

The valve must feed the evaporator as much liquid as it can boil, an amount that changes with the load. A thermostatic expansion valve does this without electricity, by comparing pressures across a thin metal diaphragm, as a balance compares two weights.

A small bulb is clamped to the suction pipe at the evaporator outlet and joined to the top of the diaphragm by a fine tube. In the simplest case it holds the same refrigerant as the system and takes the pipe’s temperature, so the pressure above the diaphragm is the saturation pressure at the suction-pipe temperature. Below the diaphragm are the evaporator pressure and a spring.

DIAPHRAGMbulb on the suction pipe, at T1bulb pressure: opens the valveevaporator pressurespring pressurecloses the valvecloses the valve
Pressures on the diaphragm of a thermostatic valve

The valve is in balance when

where is the bulb pressure, is the evaporator pressure and is the spring force divided by the diaphragm area. At the cold room’s design point, with R134a in the bulb, the bulb at 0 °C holds 292.8 kPa and the evaporator at −6 °C is at 234.3 kPa. The spring balances the difference, 58.5 kPa, so the spring sets the superheat.

The control action follows. If the load rises, the liquid boils away earlier in the tube, the outlet warms, the bulb pressure rises and the valve opens further. If the load falls, the outlet cools toward , the bulb pressure falls and the valve closes.

This simple valve has limits. The same spring gives a different superheat at a different evaporating temperature, because the saturation curve is flatter at low pressure: at −20 °C a 6 K superheat is only 38.1 kPa, so a 58.5 kPa spring would hold 8.8 K there. Makers reduce this effect with bulbs that hold a different fluid. The spring is set by the maker and is changed only by a qualified technician with the maker’s data.

What an electronic expansion valve adds

An electronic expansion valve does the same task with separate parts. A pressure transducer and a temperature sensor on the suction line give the two readings; a controller converts the pressure to a saturation temperature, subtracts, and compares the superheat with a set value; a stepper motor moves the valve needle until the two agree.

This adds several things. The valve works over a wide range of flow, so it holds a steady superheat at part load and when the condensing pressure changes with the weather. The controller knows the saturation curve, so the set value holds at every evaporating temperature. The valve can close fully when the compressor stops, and the superheat exists as a number that can be recorded. The control loop stays in the valve’s own controller, which must respond in seconds and must work when a network connection is lost.

Reading patterns

The two differences are read together with the two pressures. Each of the three textbook patterns is consistent with more than one cause, which is why a pattern is a reason to call a technician and not a diagnosis.

PatternSuperheatSubcoolingPressuresConsistent with
Starved evaporatorHighLowSuction lowToo little refrigerant in the circuit
Liquid held in the condenserNear designHighHead highToo much refrigerant, or a condenser that rejects heat badly
Flooded evaporatorNear zeroNear designSuction high or normalMore liquid fed than the coil can boil

The reasoning is physical. With too little refrigerant the condenser has no liquid reserve, so the subcooling is low, and the valve cannot find enough liquid for the coil, so the superheat is high. With too much, the extra liquid fills condenser tubes that should condense and raises both the subcooling and the condensing pressure. In a flooded evaporator liquid is still present at the outlet, so the pipe is at the saturation temperature.

Other causes give similar readings. A high head pressure also fits a dirty condenser or a failed condenser fan, and a superheat near zero a frosted coil or a stopped evaporator fan, because a coil that receives no heat cannot boil its liquid. Normal values differ between systems, so compare a system with its own design values and history.

Application 1: Superheat and subcooling at the design point



Step 1: Superheat

Click to reveal the superheat
  1. Absolute suction pressure. One bar is 100 kPa.

    ✅

  2. Evaporating temperature. The saturation temperature of R134a at 234.3 kPa is . ✅

  3. Superheat.

    The suction vapour is 6.0 K above its boiling temperature, which is the design value. ✅

Step 2: Subcooling

Click to reveal the subcooling
  1. Absolute liquid-line pressure.

    ✅

  2. Condensing temperature. The saturation temperature at 1,072.2 kPa is . ✅

  3. Subcooling.

    The liquid is 4.0 K below its condensing temperature, which is the design value. ✅

Step 3: The error of the wrong atmosphere

Click to reveal the two wrong answers
  1. Sea-level atmosphere added. The suction pressure becomes , where the saturation temperature is −4.1 °C. The liquid pressure becomes , where it is 42.6 °C.

    The superheat is 1.9 K too low and the subcooling 0.6 K too high. ✅

  2. No atmosphere added. The gauge readings are used as if they were absolute: 150.8 kPa gives −17.0 °C and 988.7 kPa gives 39.0 °C.

    ✅

  3. Compare.

    Method (°C)Superheat (K) (°C)Subcooling (K)
    Site atmosphere, 83.5 kPa (correct)−6.06.042.04.0
    Sea-level atmosphere, 101.3 kPa−4.14.142.64.6
    No atmosphere added−17.017.039.01.0

    ✅

  4. Check a second way. The saturation curve rises by 8.93 kPa per kelvin near −6 °C and by 28.4 kPa per kelvin near 42 °C. An excess of 17.8 kPa is then on the suction side and on the liquid side. These estimates agree with the 1.9 K and 0.6 K from CoolProp, and the script prints all the values. ✅

Application 2: Three sets of readings



Step 1: Set A

Click to reveal set A
  1. Absolute pressures. Suction: . Liquid: . ✅

  2. Saturation temperatures. and . ✅

  3. Superheat and subcooling.

    ✅

  4. Pattern. The superheat is 10 K above design, the subcooling 3 K below and the suction pressure 0.57 bar below its design reading. This is the starved-evaporator pattern, consistent with too little refrigerant in the circuit. The suction pipe at 3.0 °C is almost at the room temperature of 4 °C, so most of the coil is warming vapour and little of it is boiling liquid. ✅

Step 2: Set B

Click to reveal set B
  1. Absolute pressures. Suction: . Liquid: . ✅

  2. Saturation temperatures. and . ✅

  3. Superheat and subcooling.

    ✅

  4. Pattern. The superheat is close to design, so the valve feeds the evaporator normally. The subcooling is 7 K above design and the condensing temperature 10 K above, with a head pressure 3.13 bar above its design reading. This is the pattern of liquid held in the condenser, consistent with too much refrigerant in the circuit. A condenser that rejects heat badly also gives a high head pressure, so one set of readings cannot separate the two. ✅

Step 3: Set C

Click to reveal set C
  1. Absolute pressures. Suction: . Liquid: . ✅

  2. Saturation temperatures. and . ✅

  3. Superheat and subcooling.

    ✅

  4. Pattern. The subcooling and the head pressure are close to design. The superheat is 0.5 K, which is smaller than the error of the measurement, so liquid may be present in the suction pipe, and no temperature reading can show how much. This is the flooded-evaporator pattern, the one that puts the compressor in danger. It is consistent with a valve that feeds more liquid than the coil can boil, or with a coil that receives too little heat because of frost or a stopped fan. ✅

Step 4: Summary and check

Click to reveal the table and the check
  1. All three sets.

    Set (°C)Superheat (K) (°C)Subcooling (K)Pattern
    Design−6.06.042.04.0Reference
    A−13.116.137.01.0Starved evaporator
    B−5.05.552.011.0Liquid held in the condenser
    C−3.00.543.05.0Flooded evaporator

    ✅

  2. Check set A with the slope. The suction pressure is below design. At 8.93 kPa per kelvin this is , so the estimate is . CoolProp gives −13.1 °C. The estimate is 0.7 K too warm because the curve is flatter at lower pressure, and it confirms the size of the answer. The script prints the same four values for each set. ✅

Verify It in Python



The script converts each gauge reading to absolute pressure, finds the saturation temperature with CoolProp, and prints the superheat and subcooling of both applications. It also prints the valve’s pressure balance and the liquid-line rise, and plots every reading against the saturation curve. It needs CoolProp as well as numpy and matplotlib: pip install CoolProp.

superheat_subcooling.py
"""Superheat and subcooling of an R134a system from gauge and pipe readings."""
import numpy as np
import matplotlib.pyplot as plt
from CoolProp.CoolProp import PropsSI
FLUID = "R134a"
P_SITE, P_SEA = 83.5, 101.3 # kPa, atmospheric pressure
def t_sat(p_abs_kpa):
"""Saturation temperature in degC at an absolute pressure in kPa."""
return PropsSI("T", "P", p_abs_kpa * 1000.0, "Q", 0.5, FLUID) - 273.15
def p_sat(t_c):
"""Saturation pressure in kPa absolute at a temperature in degC."""
return PropsSI("P", "T", t_c + 273.15, "Q", 0.5, FLUID) / 1000.0
def analyse(p_suc_g, t_suc, p_liq_g, t_liq, p_atm=P_SITE):
"""Gauge pressures in bar, temperatures in degC. Returns T_e, SH, T_c, SC."""
t_e = t_sat(p_suc_g * 100.0 + p_atm)
t_c = t_sat(p_liq_g * 100.0 + p_atm)
return t_e, t_suc - t_e, t_c, t_c - t_liq
# ---------- Application 1: the design point ----------
P_SUC, T_SUC, P_LIQ, T_LIQ = 1.508, 0.0, 9.887, 38.0
t_e, sh, t_c, sc = analyse(P_SUC, T_SUC, P_LIQ, T_LIQ)
print("Application 1: design-point readings at the site (83.5 kPa)")
print(f" suction: {P_SUC:.3f} bar gauge = {P_SUC * 100 + P_SITE:.1f} kPa abs, "
f"T_e = {t_e:.2f} degC, superheat = {sh:.2f} K")
print(f" liquid: {P_LIQ:.3f} bar gauge = {P_LIQ * 100 + P_SITE:.1f} kPa abs, "
f"T_c = {t_c:.2f} degC, subcooling = {sc:.2f} K")
for label, p_atm in (("sea-level atmosphere added", P_SEA),
("no atmosphere added", 0.0)):
e, a, c, b = analyse(P_SUC, T_SUC, P_LIQ, T_LIQ, p_atm)
print(f" {label}: T_e = {e:.1f}, superheat = {a:.1f} K, "
f"T_c = {c:.1f}, subcooling = {b:.1f} K")
slope_e = (p_sat(-5.0) - p_sat(-7.0)) / 2.0
slope_c = (p_sat(43.0) - p_sat(41.0)) / 2.0
print(f" slope of the saturation curve: {slope_e:.2f} kPa/K at -6 degC, "
f"{slope_c:.1f} kPa/K at 42 degC")
print(f" 17.8 kPa is {17.8 / slope_e:.1f} K on the low side "
f"and {17.8 / slope_c:.1f} K on the high side")
# ---------- The bulb of a thermostatic valve (same refrigerant in the bulb) ----------
p_bulb, p_evap = p_sat(0.0), p_sat(-6.0)
print("Thermostatic valve with an R134a bulb at the design point")
print(f" bulb at 0 degC: {p_bulb:.1f} kPa, evaporator at -6 degC: {p_evap:.1f} kPa, "
f"spring balances {p_bulb - p_evap:.1f} kPa")
print(f" the same 6 K at -20 degC: {p_sat(-14.0) - p_sat(-20.0):.1f} kPa")
t_same_spring = t_sat(p_sat(-20.0) + p_bulb - p_evap)
print(f" with the same spring at -20 degC the superheat would be "
f"{t_same_spring + 20.0:.1f} K")
# ---------- What subcooling protects: a 5 m rise in the liquid line ----------
rho_liq = PropsSI("D", "T", 38.0 + 273.15, "P", p_sat(42.0) * 1000.0, FLUID)
dp_rise = rho_liq * 9.81 * 5.0 / 1000.0
t_sat_top = t_sat(p_sat(42.0) - dp_rise)
print(f"Liquid at 38 degC: density {rho_liq:.0f} kg/m3, a 5 m rise loses "
f"{dp_rise:.1f} kPa")
print(f" saturation temperature at the top {t_sat_top:.1f} degC, "
f"subcooling left {t_sat_top - 38.0:.1f} K")
# ---------- Application 2: three sets of readings ----------
SETS = {
"A": (0.94, 3.0, 8.54, 36.0),
"B": (1.60, 0.5, 13.02, 41.0),
"C": (1.79, -2.5, 10.17, 38.0),
}
print("Application 2: three sets of readings at the site")
results = {"design": (P_SUC, T_SUC, P_LIQ, T_LIQ, t_e, sh, t_c, sc)}
for key, (ps, ts, pl, tl) in SETS.items():
e, a, c, b = analyse(ps, ts, pl, tl)
results[key] = (ps, ts, pl, tl, e, a, c, b)
print(f" {key}: suction {ps:.2f} bar g, {ts:5.1f} degC | "
f"liquid {pl:5.2f} bar g, {tl:.1f} degC")
print(f" T_e = {e:6.1f} degC, superheat = {a:4.1f} K, "
f"T_c = {c:.1f} degC, subcooling = {b:4.1f} K, "
f"ratio = {(pl * 100 + P_SITE) / (ps * 100 + P_SITE):.2f}")
# ---------- Sensitivity of the superheat to reading errors ----------
e_hi, _, _, _ = analyse(P_SUC + 0.05, T_SUC, P_LIQ, T_LIQ)
print(f"A gauge error of +0.05 bar on the suction side moves T_e by "
f"{e_hi - t_e:+.2f} K")
# ---------- Plot: readings against the saturation curve ----------
t_line = np.linspace(-25.0, 60.0, 200)
p_line = np.array([p_sat(t) for t in t_line]) / 100.0
fig, ax = plt.subplots(figsize=(8, 6))
ax.plot(p_line, t_line, color="black", label="R134a saturation curve")
marks = {"design": "o", "A": "s", "B": "^", "C": "D"}
for key, (ps, ts, pl, tl, e, a, c, b) in results.items():
pa, pb = (ps * 100 + P_SITE) / 100.0, (pl * 100 + P_SITE) / 100.0
ax.plot([pa, pb], [ts, tl], marks[key], linestyle="none",
label=f"{key}: superheat {a:.1f} K, subcooling {b:.1f} K")
ax.plot([pa, pa], [e, ts], color="gray", linewidth=0.8)
ax.plot([pb, pb], [c, tl], color="gray", linewidth=0.8)
ax.set_xscale("log")
ax.set_xlabel("absolute pressure (bar)")
ax.set_ylabel("temperature (degC)")
ax.set_title("Pipe readings against the saturation curve of R134a")
ax.grid(True, which="both", linewidth=0.3)
ax.legend(loc="upper left")
fig.tight_layout()
fig.savefig("superheat_subcooling.png", dpi=120)
print("Saved superheat_subcooling.png")

Expected output

Application 1: design-point readings at the site (83.5 kPa)
suction: 1.508 bar gauge = 234.3 kPa abs, T_e = -6.00 degC, superheat = 6.00 K
liquid: 9.887 bar gauge = 1072.2 kPa abs, T_c = 42.00 degC, subcooling = 4.00 K
sea-level atmosphere added: T_e = -4.1, superheat = 4.1 K, T_c = 42.6, subcooling = 4.6 K
no atmosphere added: T_e = -17.0, superheat = 17.0 K, T_c = 39.0, subcooling = 1.0 K
slope of the saturation curve: 8.93 kPa/K at -6 degC, 28.4 kPa/K at 42 degC
17.8 kPa is 2.0 K on the low side and 0.6 K on the high side
Thermostatic valve with an R134a bulb at the design point
bulb at 0 degC: 292.8 kPa, evaporator at -6 degC: 234.3 kPa, spring balances 58.5 kPa
the same 6 K at -20 degC: 38.1 kPa
with the same spring at -20 degC the superheat would be 8.8 K
Liquid at 38 degC: density 1156 kg/m3, a 5 m rise loses 56.7 kPa
saturation temperature at the top 40.0 degC, subcooling left 2.0 K
Application 2: three sets of readings at the site
A: suction 0.94 bar g, 3.0 degC | liquid 8.54 bar g, 36.0 degC
T_e = -13.1 degC, superheat = 16.1 K, T_c = 37.0 degC, subcooling = 1.0 K, ratio = 5.28
B: suction 1.60 bar g, 0.5 degC | liquid 13.02 bar g, 41.0 degC
T_e = -5.0 degC, superheat = 5.5 K, T_c = 52.0 degC, subcooling = 11.0 K, ratio = 5.69
C: suction 1.79 bar g, -2.5 degC | liquid 10.17 bar g, 38.0 degC
T_e = -3.0 degC, superheat = 0.5 K, T_c = 43.0 degC, subcooling = 5.0 K, ratio = 4.19
A gauge error of +0.05 bar on the suction side moves T_e by +0.56 K
Saved superheat_subcooling.png

In the plot a grey line joins each reading to the saturation curve at the same pressure. Its length is the superheat on the suction side (points above the curve) and the subcooling on the liquid side (points below).

Common Mistakes



  • Converting a gauge reading to a saturation temperature without adding the atmospheric pressure, or adding the sea-level value at a high site. At this site the first error changes a correct superheat of 6.0 K into 17.0 K, and the second changes it into 4.1 K.
  • Trusting a bare temperature sensor on a pipe. Without good contact and insulation it reads between the pipe and the air, so the superheat appears too high.
  • Reading a superheat of zero as dry vapour. At saturation the pipe temperature is the same for any amount of liquid.
  • Treating a pattern as a diagnosis. Several faults give similar readings, and the pattern only tells a technician where to look.
  • Believing that more superheat is always safer. Above the design value it wastes evaporator surface and lowers the evaporating temperature.

Summary



  • Superheat is the suction-line temperature minus the saturation temperature at the suction pressure. Subcooling is the saturation temperature at the liquid-line pressure minus the liquid-line temperature.
  • A gauge reading must be converted to absolute pressure with the atmosphere of the site before the saturation temperature is found. At this site the design readings give 6.0 K and 4.0 K.
  • Superheat shows that boiling ended inside the evaporator, which keeps liquid out of the compressor. Subcooling shows that the liquid line holds liquid only, which keeps flash gas out of the expansion valve.
  • A thermostatic expansion valve balances bulb pressure against evaporator pressure and a spring. An electronic valve calculates the superheat from sensors.
  • High superheat with low subcooling and low suction pressure is consistent with too little refrigerant. High subcooling with high head pressure is consistent with liquid held in the condenser. Superheat near zero is consistent with a flooded evaporator. Diagnosis and repair belong to a qualified refrigeration technician.

Exercises



Use CoolProp or an R134a table for saturation temperatures. The site’s atmospheric pressure is 83.5 kPa unless stated.

1. A suction gauge reads 1.80 bar and the suction pipe is at 3.0 °C. Find the superheat if the system is at sea level (101.3 kPa), and if it is at the site (83.5 kPa).

Answer

At sea level , and the superheat is 4.1 K. At the site , and the superheat is 5.9 K. The same two readings mean a superheat 1.8 K higher at the site.

2. At the design point the saturation curve of R134a rises by 8.93 kPa per kelvin. The suction gauge may be wrong by 0.05 bar in either direction and the pipe sensor by 1.0 K. Find the largest error in the calculated superheat, and state the range in which a calculated value of 6.0 K may really lie.

Answer

A pressure error of 5 kPa moves by . In the worst case the two errors add: . The real superheat lies between about 4.4 K and 7.6 K. A difference of 1 K between two readings is therefore not evidence of a change.

3. A record from an R134a system at the site shows: suction 0.80 bar gauge with the pipe at 2.0 °C, and liquid 8.00 bar gauge with the pipe at 34.0 °C. Find the superheat and the subcooling and name the pattern.

Answer

Suction: absolute, , superheat . Liquid: absolute, , subcooling . High superheat, low subcooling and low suction pressure: the starved-evaporator pattern, consistent with too little refrigerant. The cause must be found by a qualified technician.

4. A thermostatic valve has R134a in its bulb and a spring equal to 58.5 kPa. It is used on an evaporator at −20 °C, where the saturation pressure is 132.7 kPa. Find the bulb pressure at balance and the superheat that the valve holds. Explain why it is not 6 K.

Answer

. The saturation temperature of R134a at 191.2 kPa is −11.2 °C, so the bulb, and the suction pipe, must be at −11.2 °C. Superheat . The saturation curve is flatter at low temperature, so the same pressure difference needs more kelvin. At −6 °C the same spring gives 6.0 K.

References



  • W. F. Stoecker and J. W. Jones, Refrigeration and Air Conditioning, 2nd edition, McGraw-Hill, 1982.
  • Y. A. Çengel and M. A. Boles, Thermodynamics: An Engineering Approach, 8th edition, McGraw-Hill, 2015.
  • ASHRAE, ASHRAE Handbook: Refrigeration, American Society of Heating, Refrigerating and Air-Conditioning Engineers, 2022.
  • I. H. Bell, J. Wronski, S. Quoilin and V. Lemort, “Pure and Pseudo-pure Fluid Thermophysical Property Evaluation and the Open-Source Thermophysical Property Library CoolProp”, Industrial and Engineering Chemistry Research, vol. 53, no. 6, 2014.


© 2021-2026 SiliconWit®. All rights reserved.
Predict first

The expansion valve of the cold room holds a superheat of 6 K. Someone wants the compressor to be safer from liquid and asks for 15 K. What does the higher setting do?

0 °C−6 °C 6 K: dry vapour0 K: liquid? boiling at −6 °Cvapour warmsboiling to the end
Watch it: where the last liquid boils

Coil length still boiling
Superheat at the outlet
To the compressor

A teaching model of the cold room's coil: room air at 4 °C, the evaporating temperature held at −6 °C. The slider sets how much liquid the valve feeds, as a share of what the coil can boil. While liquid boils the tube stays at −6 °C; after the last liquid the vapour warms toward the room. The superheat cannot pass 10 K here because the evaporating temperature is held. In a real starved coil the evaporating temperature also falls, and the superheat grows further.

bulb 292.8coil 234.3 kPa, opens+ spring 58.5, closes Spring = 6 K of superheat at −6 °C
Watch it build: from the gauge to the superheat
150.8 kPa gauge +83.5 234.3 kPa absolute −6.0 °C boils at pipe 0.0 °C 6.0 K superheat +101.3? 252.1 kPa −4.1 °C, 4.1 K
  1. The suction gauge reads 150.8 kPa: the pressure above the air round it, not absolute.
  2. Add this site's air, 83.5 kPa: 234.3 kPa absolute.
  3. At 234.3 kPa absolute, R134a boils at −6.0 °C.
  4. The pipe reads 0.0 °C, so the superheat is 0.0 − (−6.0) = 6.0 K.
  5. Add the sea-level 101.3 kPa in error: 252.1 kPa, −4.1 °C, and 4.1 K, about 2 K low.
Condenser 42 °C Expansion valve Compressor Evaporator −6 °C liquid line p and T p and T suction line
Where the four readings are taken
suction pipe bulb on the suction pipe, at T1 diaphragm bulb pressure opens the valve evaporator pressure closes the valve spring pressure closes the valve
Pressures on the diaphragm of a thermostatic valve

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. An R134a cold room stands at 2,400 m, where the atmosphere is at 75.6 kPa. The suction gauge reads 1.20 bar and the suction pipe is at −2.0 °C. What is the superheat?

2. On another unit the liquid leaves the condenser at 41 °C, only 1 K of subcooling, and then rises 5 m to the expansion valve. The rise costs about 56 kPa, and at the top the saturation temperature is 40.0 °C. What reaches the valve?

3. At the site (83.5 kPa) a record shows: suction 1.10 bar gauge with the pipe at 4.0 °C, and liquid 8.60 bar gauge with the pipe at 37.0 °C. The design values are 6 K of superheat and 4 K of subcooling. What do the readings point to?