Conduction, Insulation and the Envelope

Lesson 6 of 10 26 min read
Found this useful?

A cold room panel that has taken in water looks the same as a dry one. The steel skin is still white and still flat, and the room still holds 4 °C. But the wet foam passes about two thirds more heat, every hour of every day, and the only visible result is a compressor that runs longer and an electricity bill that nobody can explain. The walls, ceiling and floor are the one load on a cold room that never stops, even when the door stays shut and no product enters. This lesson shows how to calculate that load, how thickness and moisture change it, and where water will condense on the structure. #Insulation #HeatTransfer #ColdRoom

Learning Objectives

By the end of this lesson, you will be able to:

  1. Calculate the heat flow through a flat layer by conduction, and the U-value of a panel with its two air films
  2. Add the transmission loads of walls, ceiling and floor, each with its own area and its own outside temperature
  3. Compare dry insulation, wet insulation and thicker insulation in watts, kWh a year and cost
  4. Find the temperature of a surface and decide whether it is below the dew point of the surrounding air
  5. Explain what thermal bridges, panel joints and vapour barriers do to a cold room envelope

Real-World System Problem: The envelope of a small cold room



The cold room of this course measures 4.0 m by 3.0 m by 2.5 m high inside and holds fresh produce at 4 °C. It stands inside a store building where the design air temperature is 30 °C at 60 percent relative humidity. Its floor rests on a concrete slab over ground at 22 °C. All six sides are 80 mm sandwich panels: polyurethane foam between two thin steel skins.

The six sides together are the envelope. Heat flows through it from the warm side to the cold side for all 8,760 hours of the year, full or empty, and the refrigeration system must remove it: each watt costs electricity. This load is the transmission load.

Its size is decided on the day the panels are chosen, and after that it only gets worse: wet foam conducts more heat, and joints that open let heat and moisture pass. This lesson calculates the figure for a dry, sound envelope, the reference for a measured room.

floor 12 m², to 22 °Cceiling 12 m², to 30 °CCOLD ROOM, 4 °C4.0 m × 3.0 m × 2.5 mstore building air: 30 °C, 60 % RHwalls35 m²to30°Cconcrete slab over ground: 22 °C
The room and what surrounds each side

Fundamental Theory: Heat flow through a layered wall



The idea: heat flows down a temperature difference

Hold a steel spoon in hot tea and the handle becomes warm; a wooden spoon stays cool. Heat moves through a solid from the hot side to the cold side, far more easily in some materials than in others. This movement of heat through a material that does not itself move is conduction.

For a flat layer, the heat flow rises with the temperature difference between the faces and with the area, falls as the layer gets thicker, and depends on one number for the material, its thermal conductivity.

Conduction through a flat layer

is the heat flow in W, the thermal conductivity in W/(m·K), the area in m², the temperature difference between the two faces in K, and the thickness in m.

Typical conductivities show why foam is used. Steel is about 50 W/(m·K), concrete about 1.4, water about 0.6, still air about 0.026 and dry polyurethane foam about 0.023. Foam insulates because it is mostly gas held in very small closed cells, where the gas cannot circulate.

The resistance picture

Divide the conduction equation by the area and rearrange it:

This has the form of Ohm’s law: the temperature difference drives the flow as a voltage drives a current, and resists it. It is the thermal resistance of one square metre of the layer, , in m²·K/W.

Resistances in series add: heat crosses each layer of a wall in turn, as water passes three taps in a row on one pipe, and the most closed tap decides the flow. For 80 mm of dry polyurethane, .

1/h_iL/k1/h_oroom airoutside air4 °C30 °C●●0.1253.4780.050inside filmfoamoutside filmtotal R = 3.653 m²·K/Wheat flow
A panel as three resistances in series

The thin steel skins are left out: a 0.5 mm skin has a resistance of about , nothing beside 3.48. They matter for another reason, under thermal bridges.

Air films

The air near a surface does not have the temperature of the surface. Heat passes between the air and the face by convection and radiation, and each of these two steps is described by a film coefficient , in W/(m²·K):

The resistance of a film is . This course uses typical values, inside and outside. The real coefficient depends on the air speed over the surface and is lower in a still corner, but for a well insulated wall the choice hardly matters: the films are a small part of the total resistance.

The U-value

The overall heat transfer coefficient, or U-value, is the reciprocal of the total resistance.

U-value and overall heat flow

is in W/(m²·K). is now the difference between the air temperatures on the two sides, not between the faces. The sum is taken over all layers of the wall.

A low U-value is a good wall. The common mistake is to add U-values. Resistances of layers in series add, and U-values do not: add the resistances and take the reciprocal at the end.

Area bookkeeping

One room has several surfaces facing different temperatures: here the walls and ceiling face the building air at 30 °C and the floor a slab at 22 °C. The transmission load is the sum over the surfaces, each with its own area and temperature difference:

where counts the surfaces. A table with one row for each surface keeps this in order.

Inside or outside area? The inside surface of this room is 59.0 m², the outside surface of the same box with 80 mm panels on all six sides 65.2 m², and the effective area lies between: their mean, 62.1 m², is about 5 percent above the inside area. This lesson uses inside dimensions and so understates the load by roughly 5 percent, an error that grows for small rooms with thick panels.

The floor gets the walls’ U-value, with the slab’s 22 °C in place of an air temperature. This simplifies, but the foam is 95 percent of the total resistance, so the details of the contact with the slab change the result very little. A freezer room is different: under an unheated slab the ground slowly freezes, and the ice lifts the floor, so freezer floors need a heated or ventilated base.

Why wet insulation is worse

Foam insulates because its cells hold gas. Water that enters replaces the gas with a material that conducts about 25 times better (0.6 against 0.023 W/(m·K)) and joins the cell walls with continuous wet paths, as a wet jacket stops keeping you warm. Below 0 °C the water freezes, and ice conducts about four times better than water.

No single conductivity describes wet foam, because it depends on how much water is present and where. This course takes , typical for degraded foam. Badly soaked insulation can be much worse, and it does not dry while the room is cold, because of the direction in which water vapour moves.

Condensation and vapour barriers

Air holds water vapour, and warm air can hold more of it than cold air. The dew point is the temperature to which air must be cooled before its vapour starts to condense. Any surface colder than the dew point of the air that touches it becomes wet.

The Magnus formula gives the dew point in °C from the air temperature in °C and the relative humidity in percent:

with and , a common set of constants for vapour over water. It is an approximation, good to a fraction of a kelvin at ordinary temperatures. For the building air at 30 °C and 60 percent, .

The temperature of a surface follows from the resistance picture. The same heat flux crosses every layer, so the temperature falls across each layer in proportion to its resistance. The outside face is cooler than the outside air by the fall across the outside film:

T (°C)outside30●air 30.0face 29.621dew point 21.4foam4●air4.0,face4.9inside faceoutside face
Temperature through the dry 80 mm panel

On a good panel the outside face is almost at the air temperature, far above the dew point, and stays dry. Inside the foam the temperature passes through the dew point of the outside air. If that air can enter the foam, its vapour condenses there.

Vapour moves from high to low vapour pressure, and warm humid air has a much higher vapour pressure than the cold room air, so in a cold room the vapour pushes inward from the outside. A vapour barrier, a layer vapour cannot pass, belongs on the warm side, which for a cold room is the outside: the steel skins of a sandwich panel. The weak points are where the skin is broken: joints between panels, screw holes, pipe and cable entries, and forklift damage. Vapour that enters there condenses in the foam and stays, because the cold side gives it nowhere to go.

Thermal bridges, joints and door frames

A thermal bridge is a path through the envelope with much lower resistance than the insulation around it. A panel’s U-value describes its flat middle, not a joint where the foam does not meet, a steel fixing from one skin to the other, a steel corner profile, the door frame, or the place where the floor panel meets the wall.

Steel conducts about two thousand times better than foam, so a small cross-section of steel can pass as much heat as a large area of panel. Good panels use joints with a foam tongue and groove, locks that do not join the two skins with metal, sealant on the warm side, and door frames with a thermal break. The door frame is the most exposed place: it carries hinges and a gasket, and it is struck by trolleys.

No simple formula gives the loss through thermal bridges, because it depends on construction details that differ between makers. Designers add an allowance or rely on the maker’s tested values, and this lesson gives no general percentage. A bridge does show itself: its outside face is colder than the panel around it, and in humid air it is where water appears first.

What this model leaves out

The calculation is for steady conditions, with heat flowing straight through flat layers. It ignores the sun (a room outdoors needs an allowance for sun on the roof and walls), air leakage through joints, and the heat stored in the structure when temperatures change. It gives the load of a sound envelope, and a real room has a higher one.

Application 1: U-value and transmission load at design



Step 1: U-value of the panel

Click to reveal the U-value
  1. Resistance of each part.

    ✅

  2. Total resistance.

    The foam is percent of the total. ✅

  3. U-value.

    Each square metre passes 0.274 W for each kelvin of difference between the air on its two sides. ✅

Step 2: Areas

Click to reveal the areas
  1. Walls. The perimeter is and the height is 2.5 m.

    The door is counted as wall. ✅

  2. Ceiling and floor. . ✅

  3. Total. of inside surface. ✅

Step 3: Transmission load

Click to reveal the load of each surface
  1. Temperature differences. Walls and ceiling: . Floor: . ✅

  2. One row for each surface.

    Surface (m²) (K) (W)
    Walls3526249.1
    Ceiling122685.4
    Floor121859.1
    Total59393.6

    For the walls, . ✅

  3. Transmission load.

    About 394 W enters through the envelope at the design condition. ✅

Step 4: Daily energy and the check

Click to reveal the daily energy and the check
  1. Heat in one day. The load is steady, so multiply by 24 hours.

    ✅

  2. Check with one sum. The U-value is the same for all surfaces, so add the products of area and temperature difference first.

    The two methods agree. ✅

  3. Check with a limiting case. With no air films at all, and the load is . This is the highest value the films could allow, and it is only 5 percent above the answer. An uncertain film coefficient cannot change the result much. ✅

Application 2: Wet insulation, thicker panels and condensation



Step 1: Wet 80 mm panels

Click to reveal the wet-panel load
  1. Resistance.

    ✅

  2. U-value. . ✅

  3. Load.

    This is 15.87 kWh a day, and it is 68 percent more than the dry load. ✅

Step 2: Dry 120 mm panels

Click to reveal the thicker-panel load
  1. Resistance.

    ✅

  2. U-value. . ✅

  3. Load.

    This is 6.40 kWh a day, and it is 32 percent less than the 80 mm room. ✅

Step 3: Yearly energy and cost

Click to reveal the yearly comparison
  1. Heat in a year. Multiply each load by 8,760 hours. For the dry 80 mm room: . ✅

  2. Electricity in a year. Divide the heat by the system COP. For the dry 80 mm room: . ✅

  3. All three rooms.

    Envelope (W/(m²·K))Load (W)Heat (kWh/year)Electricity (kWh/year)
    80 mm dry0.274393.63,4481,331
    80 mm wet0.460661.15,7922,236
    120 mm dry0.185266.72,336902

    ✅

  4. Cost of wet insulation. more each year, which is about 10,900 currency units at 12.00 per kWh. ✅

  5. Saving with 120 mm panels. less each year, which is about 5,150 currency units. ✅

Step 4: Surface temperature and dew point

Click to reveal the condensation check
  1. Dew point of the surrounding air.

    Any surface below 21.4 °C becomes wet. ✅

  2. Good panel. The heat flux is .

    The face is 8.2 K above the dew point. It stays dry. ✅

  3. Thermal bridge. The total resistance is , so the heat flux is , thirteen times that of the panel.

    The face is 4.7 K cooler than the air but still 3.9 K above the dew point. It stays dry at 60 percent relative humidity. The Magnus formula shows that it becomes wet when the humidity of the 30 °C air rises above about 76 percent. ✅

  4. Thermal bridge in a still corner. With the outside film resistance is , the total is and the heat flux is .

    The face is 2.5 K below the dew point. Water condenses on it. ✅

  5. Check with the script. The script calculates the three loads, the yearly figures, the dew point and the four surface temperatures, and prints the same values. ✅

air30.0°C29.6 °C●good paneldry25.3 °C●thermal bridgedrydew point 21.4 °C18.9 °C●bridge, still cornerwetroom4.0°C
Outside-face temperature against the dew point

Verify It in Python



The script calculates the U-value, the areas and the transmission load of Application 1, the three envelopes and their yearly energy for Application 2, the dew point by the Magnus formula and the surface temperatures. It draws the temperature through the wall for the three panels, and needs only numpy and matplotlib.

envelope_transmission.py
"""Transmission load of a cold room: U-value, areas, wet and thicker panels, dew point."""
import numpy as np
import matplotlib.pyplot as plt
H_I, H_O = 8.0, 20.0 # W/(m2.K), typical film coefficients
T_ROOM, T_AIR, T_GROUND = 4.0, 30.0, 22.0 # degC
RH_AIR = 60.0 # percent, surrounding air
LENGTH, WIDTH, HEIGHT = 4.0, 3.0, 2.5 # m, inside dimensions
SYSTEM_COP = 2.59 # cooling / electrical input, from the cycle
PRICE = 12.00 # currency units per kWh
A_WALLS = 2.0 * (LENGTH + WIDTH) * HEIGHT
A_CEILING = LENGTH * WIDTH
A_FLOOR = LENGTH * WIDTH
def u_value(thickness, k, h_o=H_O):
"""Overall coefficient in W/(m2.K) of a panel with inside and outside films."""
return 1.0 / (1.0 / H_I + thickness / k + 1.0 / h_o)
def load(u):
"""Transmission load in W: walls and ceiling to the air, floor to the ground."""
return (u * (A_WALLS + A_CEILING) * (T_AIR - T_ROOM)
+ u * A_FLOOR * (T_GROUND - T_ROOM))
def dew_point(t, rh):
"""Magnus formula over water: t in degC, rh in percent."""
a, b = 17.62, 243.12
gamma = np.log(rh / 100.0) + a * t / (b + t)
return b * gamma / (a - gamma)
def rh_for_dew_point(t_dew, t):
"""Relative humidity (percent) at which air at t has the dew point t_dew."""
a, b = 17.62, 243.12
return 100.0 * np.exp(a * t_dew / (b + t_dew) - a * t / (b + t))
# ---------- Application 1 ----------
u_dry = u_value(0.080, 0.023)
print("Application 1: 80 mm dry panel")
print(f" resistances: inside film {1 / H_I:.3f}, panel {0.080 / 0.023:.3f}, "
f"outside film {1 / H_O:.3f}, total {1 / u_dry:.3f} m2.K/W")
print(f" U = {u_dry:.4f} W/(m2.K)")
print(f" areas: walls {A_WALLS:.0f}, ceiling {A_CEILING:.0f}, floor {A_FLOOR:.0f} m2")
q_walls = u_dry * A_WALLS * (T_AIR - T_ROOM)
q_ceiling = u_dry * A_CEILING * (T_AIR - T_ROOM)
q_floor = u_dry * A_FLOOR * (T_GROUND - T_ROOM)
q_dry = q_walls + q_ceiling + q_floor
print(f" walls {q_walls:.1f} W, ceiling {q_ceiling:.1f} W, floor {q_floor:.1f} W")
print(f" transmission load {q_dry:.1f} W = {q_dry * 24 / 1000:.2f} kWh a day, "
f"electricity {q_dry * 24 / 1000 / SYSTEM_COP:.2f} kWh a day, "
f"{q_dry / 3000 * 100:.0f} percent of 3.0 kW")
print(f" check with sum of A x dT: {u_dry:.4f} x "
f"{(A_WALLS + A_CEILING) * 26 + A_FLOOR * 18:.0f} = "
f"{u_dry * ((A_WALLS + A_CEILING) * 26 + A_FLOOR * 18):.1f} W")
print(f" panel only, no films: U = {0.023 / 0.080:.4f}, load "
f"{load(0.023 / 0.080):.1f} W")
print(f" heat flux through a wall: {u_dry * 26:.2f} W/m2")
# outside dimensions with 80 mm panels on all six sides
t = 0.080
lo, wo, ho = LENGTH + 2 * t, WIDTH + 2 * t, HEIGHT + 2 * t
a_in = A_WALLS + A_CEILING + A_FLOOR
a_out = 2 * (lo + wo) * ho + 2 * lo * wo
print(f" inside area {a_in:.1f} m2, outside area {a_out:.1f} m2, "
f"mean {0.5 * (a_in + a_out):.1f} m2 "
f"({(0.5 * (a_in + a_out) / a_in - 1) * 100:.1f} percent above inside)")
# ---------- Application 2 ----------
print("Application 2: wet insulation and thicker panels")
cases = {"80 mm dry": (0.080, 0.023), "80 mm wet": (0.080, 0.040),
"120 mm dry": (0.120, 0.023)}
yearly = {}
for name, (thick, k) in cases.items():
u = u_value(thick, k)
q = load(u)
heat_kwh = q * 8760 / 1000
elec_kwh = heat_kwh / SYSTEM_COP
yearly[name] = elec_kwh
print(f" {name:<10} U = {u:.3f}, load {q:.1f} W, {q * 24 / 1000:.2f} kWh/day, "
f"heat {heat_kwh:.0f} kWh/yr, electricity {elec_kwh:.0f} kWh/yr, "
f"cost {elec_kwh * PRICE:.0f}")
for name in ("80 mm wet", "120 mm dry"):
d = yearly[name] - yearly["80 mm dry"]
print(f" {name} against 80 mm dry: {d:+.0f} kWh/yr, {d * PRICE:+.0f} per year")
# ---------- Surface temperature and dew point ----------
t_dew = dew_point(T_AIR, RH_AIR)
print("Condensation on the outside face")
print(f" dew point of air at {T_AIR:.0f} degC, {RH_AIR:.0f} percent: {t_dew:.1f} degC")
surfaces = {
"good panel": (0.080 / 0.023, H_O),
"wet panel": (0.080 / 0.040, H_O),
"thermal bridge": (0.10, H_O),
"thermal bridge, still air": (0.10, 6.0),
}
for name, (r_local, h_o) in surfaces.items():
u = 1.0 / (1.0 / H_I + r_local + 1.0 / h_o)
flux = u * (T_AIR - T_ROOM)
t_out = T_AIR - flux / h_o
t_in = T_ROOM + flux / H_I
verdict = "condensation" if t_out < t_dew else "dry"
print(f" {name:<26} U = {u:.3f}, flux {flux:5.1f} W/m2, outside face "
f"{t_out:.1f} degC, inside face {t_in:.1f} degC, {verdict}, "
f"wet above {rh_for_dew_point(t_out, T_AIR):.0f} percent RH")
bridge_w = 0.5 * (T_AIR - T_ROOM) / (1.0 / H_I + 0.10 + 1.0 / H_O)
print(f" 0.5 m2 of thermal bridge passes {bridge_w:.1f} W, "
f"{bridge_w / q_dry * 100:.0f} percent of the transmission load")
# ---------- Plot: temperature through the wall for the three panels ----------
fig, ax = plt.subplots(figsize=(8, 5))
for name, (thick, k) in cases.items():
flux = u_value(thick, k) * (T_AIR - T_ROOM)
t_in = T_ROOM + flux / H_I
t_out = T_AIR - flux / H_O
x = np.array([-20.0, 0.0, thick * 1000, thick * 1000 + 20.0])
ax.plot(x, [T_ROOM, t_in, t_out, T_AIR], marker="o",
label=f"{name}: {flux:.1f} W/m2")
ax.axhline(t_dew, color="gray", linestyle="--", label=f"dew point {t_dew:.1f} degC")
ax.set_xlabel("distance from the inside face (mm); films drawn as 20 mm")
ax.set_ylabel("temperature (degC)")
ax.set_title("Temperature through the cold room wall, 4 degC inside, 30 degC outside")
ax.grid(True, linewidth=0.3)
ax.legend()
fig.tight_layout()
fig.savefig("envelope_transmission.png", dpi=120)
print("Saved envelope_transmission.png")

Expected output

Application 1: 80 mm dry panel
resistances: inside film 0.125, panel 3.478, outside film 0.050, total 3.653 m2.K/W
U = 0.2737 W/(m2.K)
areas: walls 35, ceiling 12, floor 12 m2
walls 249.1 W, ceiling 85.4 W, floor 59.1 W
transmission load 393.6 W = 9.45 kWh a day, electricity 3.65 kWh a day, 13 percent of 3.0 kW
check with sum of A x dT: 0.2737 x 1438 = 393.6 W
panel only, no films: U = 0.2875, load 413.4 W
heat flux through a wall: 7.12 W/m2
inside area 59.0 m2, outside area 65.2 m2, mean 62.1 m2 (5.3 percent above inside)
Application 2: wet insulation and thicker panels
80 mm dry U = 0.274, load 393.6 W, 9.45 kWh/day, heat 3448 kWh/yr, electricity 1331 kWh/yr, cost 15976
80 mm wet U = 0.460, load 661.1 W, 15.87 kWh/day, heat 5792 kWh/yr, electricity 2236 kWh/yr, cost 26834
120 mm dry U = 0.185, load 266.7 W, 6.40 kWh/day, heat 2336 kWh/yr, electricity 902 kWh/yr, cost 10823
80 mm wet against 80 mm dry: +905 kWh/yr, +10858 per year
120 mm dry against 80 mm dry: -429 kWh/yr, -5152 per year
Condensation on the outside face
dew point of air at 30 degC, 60 percent: 21.4 degC
good panel U = 0.274, flux 7.1 W/m2, outside face 29.6 degC, inside face 4.9 degC, dry, wet above 98 percent RH
wet panel U = 0.460, flux 12.0 W/m2, outside face 29.4 degC, inside face 5.5 degC, dry, wet above 97 percent RH
thermal bridge U = 3.636, flux 94.5 W/m2, outside face 25.3 degC, inside face 15.8 degC, dry, wet above 76 percent RH
thermal bridge, still air U = 2.553, flux 66.4 W/m2, outside face 18.9 degC, inside face 12.3 degC, condensation, wet above 52 percent RH
0.5 m2 of thermal bridge passes 47.3 W, 12 percent of the transmission load
Saved envelope_transmission.png

In the plot almost all of the temperature change is inside the foam, and the short end sections are the two air films. Each line crosses the dashed dew point line inside the foam, which is where vapour would condense if it could enter.

Common Mistakes



  • Adding U-values of layers. Layers in series add their resistances. Add for each layer and the two film resistances, then take the reciprocal once.
  • Putting the thickness in millimetres into . With in W/(m·K), 80 mm must be written as 0.080 m.
  • Using one temperature difference for every surface. The floor faces the ground at 22 °C, not the air at 30 °C, and a wall shared with another cold room may face almost no difference at all.
  • Taking the catalogue conductivity for a panel that is years old and has damaged skins. The catalogue value is for dry, new foam.
  • Treating the calculated transmission load as the whole envelope loss. Joints, fixings, the door frame and air leakage are added to it.

Summary



  • Conduction through a flat layer is . Each layer has a resistance , each air film a resistance , and resistances in series add.
  • The 80 mm dry polyurethane panel with typical films has a total resistance of 3.653 m²·K/W and a U-value of 0.274 W/(m²·K).
  • The cold room’s transmission load at design is 393.6 W, or 9.45 kWh of heat a day: walls 249.1 W, ceiling 85.4 W and floor 59.1 W. Inside dimensions understate it by roughly 5 percent.
  • Wet insulation at W/(m·K) raises the load to 661.1 W and costs about 905 kWh of electricity a year. Panels of 120 mm lower it to 266.7 W and save about 429 kWh a year.
  • A surface collects water when it is colder than the dew point of the air, which is 21.4 °C for air at 30 °C and 60 percent. A sound panel stays dry, and a thermal bridge in still air does not. The vapour barrier belongs on the warm side.

Exercises



Use and unless the problem says otherwise.

1. Find the U-value of a 100 mm dry polyurethane panel, , with the typical film coefficients.

Answer

, so .

2. A larger room is 6.0 m × 4.0 m × 3.0 m high inside and is held at 2 °C. It is built of the 100 mm panel of exercise 1. The walls and ceiling face air at 32 °C and the floor faces a slab at 20 °C. Find the transmission load and the heat that enters in one day.

Answer

Walls , ceiling 24 m², floor 24 m². . Load , which is 15.66 kWh a day.

3. On a hot day the air round the cold room of this lesson is at 36 °C. The room stays at 4 °C and the ground at 22 °C. Find the transmission load with the dry 80 mm panels, and the percentage rise from the design value of 393.6 W.

Answer

. Load , a rise of 19.6 percent. The system’s capacity and COP also fall on a hot day, so the envelope asks for more when the machine can give less.

4. A designer wants a U-value of 0.20 W/(m²·K) or lower with dry polyurethane, . Find the smallest thickness, and choose from the standard thicknesses 80, 100, 120 and 150 mm.

Answer

The foam must give , so . The 100 mm panel is too thin (). Choose 120 mm, which gives .

5. A door frame has a local conduction resistance of . The room is at 4 °C and the surrounding air is at 32 °C. Find the temperature of the outside face of the frame. Then use the Magnus formula to decide whether it collects condensation when the relative humidity of the air is 75 percent, and when it is 85 percent.

Answer

Total resistance . Heat flux . . The dew point at 32 °C is 27.0 °C at 75 percent and 29.2 °C at 85 percent. The frame is dry at 75 percent (by 1.7 K) and wet at 85 percent.

References



  • T. L. Bergman, A. S. Lavine, F. P. Incropera and D. P. DeWitt, Fundamentals of Heat and Mass Transfer, 7th edition, Wiley, 2011.
  • ASHRAE, ASHRAE Handbook: Refrigeration, American Society of Heating, Refrigerating and Air-Conditioning Engineers, 2022 (chapter on refrigeration load).
  • ASHRAE, ASHRAE Handbook: Fundamentals, American Society of Heating, Refrigerating and Air-Conditioning Engineers, 2021.
  • W. F. Stoecker and J. W. Jones, Refrigeration and Air Conditioning, 2nd edition, McGraw-Hill, 1982.


© 2021-2026 SiliconWit®. All rights reserved.
Predict first

A cold room is built from 80 mm foam panels, and 394 W of heat enters through its walls, ceiling and floor. The same room is built again with 160 mm panels of the same foam. What happens to this heat gain?

See it: the temperature through the wall

U-value
Heat flow through a wall
Transmission load of the room
Outside face of the panel
Dew point of the surrounding air
Electricity for this load in a year

The panel is drawn to scale. The two air films are drawn as narrow bands, because a film is a resistance and has no fixed thickness: 1/8 m²·K/W inside and 1/20 m²·K/W outside, both typical values. The same heat crosses every layer, so the temperature falls across each layer in proportion to its resistance. The dashed line is the dew point of the surrounding air, from the Magnus formula. If the outside face is colder than that line, water condenses on it. The open ring marks where the foam itself is at the dew point: vapour that enters the foam condenses from there inward. The load uses the lesson's room: 47 m² of walls and ceiling facing the surrounding air, and 12 m² of floor on a slab at 22 °C with the same U-value. The slab stays at 22 °C when you move the air temperature. The yearly electricity divides the heat of 8,760 hours by the system COP of 2.59, taken as constant at 12.00 currency units per kWh. A real COP changes with both temperatures, and joints, fixings and the door frame add heat that this flat wall does not show.

0.9 K24.8 K0.4 K inside air filmfoam, 80 mmoutside air film
80 mm, dry80 mm, wet120 mm, dry 393.6 W661.1 W266.7 W Heat through the whole envelope, room at 4 °C
Watch it build: a panel as resistances in series
4 °C30 °C roomair 80 mm panel 26 K pushes heat in 3.478foam L ÷ k = 0.080 ÷ 0.023 0.1250.050 filmfilm two air films: small, but in the chain sum 3.653: U = 0.2747.12 W through each m² 0.274 × (47 × 26 + 12 × 18)393.6 W for the room
  1. Room air at 4 °C, store air at 30 °C: a 26 K difference drives heat through the panel.
  2. The foam resists: 0.080 ÷ 0.023 = 3.478 m²·K/W.
  3. The two air films add 0.125 and 0.050 in series with it.
  4. The sum is 3.653, so U = 0.274 W/(m²·K): 7.12 W cross each square metre.
  5. One row per surface: walls and ceiling at 26 K, floor at 18 K. The room takes 393.6 W.
store building air: 30 °C, 60 % RH ceiling 12 m², to 30 °C floor 12 m², to 22 °C Cold room, 4 °C 4.0 m × 3.0 m × 2.5 m walls 35 m² to 30 °C concrete slab over ground: 22 °C
The room and what surrounds each side
foam, 80 mm T (°C) 4 21.4 30 dew point 21.4 air 4.0, face 4.9 air 30.0, face 29.6 inside face outside face
Temperature through the dry 80 mm panel
room 4.0 °C dew point 21.4 °C air 30.0 °C good panel, 29.6 °C dry thermal bridge, 25.3 °C dry bridge, still corner, 18.9 °C wet 0 10 20 30 outside face temperature (°C)
Outside-face temperature against the dew point

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. The room has 59 m² of inside surface: 47 m² of walls and ceiling and 12 m² of floor. U is 0.2737 W/(m²·K). The room is at 4 °C, the building air at 30 °C and the slab under the floor at 22 °C. What is the transmission load?

2. The room stands in a corner with little air movement, and the outside film coefficient is 10 W/(m²·K) and not 20. The panels are 80 mm and dry. What happens to the transmission load?

3. In the figure the flat panel stays dry in the lesson's store air (30 °C, 60 percent, dew point 21.4 °C). A steel fixing makes a thermal bridge with a conduction resistance of only 0.10 m²·K/W. It sits in a still corner where ho = 6 W/(m²·K). The room is at 4 °C. What is the temperature of its outside face?