Best interval between washes in dry weather
Monitoring, Faults, Soiling and Degradation
On this page
A connector on the roof fails on a Tuesday and one of the two strings stops. The inverter keeps running on the other string, the lights stay on, and nobody notices. Three weeks later the electricity bill is higher than usual, and by then more than 400 kWh of free energy are gone. On another roof the owner pays for washing every two weeks and never asks whether the dust costs more than the wash. A solar system fails quietly, because half an array still looks like a working array on a cloudy day. This lesson shows what to measure, how to tell dust from a fault from ageing, and how to write an alarm that can be trusted. #SolarMonitoring #Soiling #FaultDetection
Learning Objectives
By the end of this lesson, you will be able to:
- List the measurements that a solar system needs and say what each one is for
- Compare measured output with expected output through a daily performance ratio
- Estimate the rate of soiling from a record and decide when a wash pays for itself
- Write an alarm rule with a stated window and limit, and count its false alarms
- Explain why slow degradation cannot be read from one year of data
Real-World System Problem: A year of daily records
The site of this course has 9.9 kWp of modules in two strings of nine, each on its own tracker of a hybrid inverter. Nameplate power is defined at standard test conditions, which a hot roof never meets, so the output is judged against the light that arrived and never against 9.9 kW.
Each day the site records two numbers: the plane-of-array insolation
The daily record can answer all three, and it needs no more than the sensors in the drawing.
Fundamental Theory: Expected against measured
What to measure
A reading has meaning only beside the reading it should have been. That needs the cause (light and heat) as well as the result (power and energy).
| Quantity | Sensor | Where | What it is for |
|---|---|---|---|
| Plane-of-array irradiance | Pyranometer or reference cell | Beside the modules, same tilt and direction | The light that the array really received |
| Module temperature | Small temperature sensor | Fixed to the back of one module, near its centre | The heat loss of the moment |
| DC voltage and current | The inverter’s own measurement, each tracker | Inverter input | Which string is weak |
| AC power and energy | Inverter or a separate energy meter | Inverter output | The result |
| Battery state of charge | Battery management system | Battery | Whether the array was held back because the battery was full |
The irradiance sensor must be kept clean. A dirty sensor reads low, the expected output falls with it, and the dust on the modules becomes invisible.
Expected power and daily performance ratio
For one moment, the expected power follows from the data sheet rule and the loss table of the system:
For a whole day the same comparison is the daily performance ratio:
with the energy and the insolation of that day. A cloudy day has a small
Soiling: a sawtooth
Dust settles a little every dry day, so the loss grows slowly and almost evenly until rain removes most of it in one day: in the record, a sawtooth, a slow slope down and a sudden step up.
The soiling rate
A straight line fitted to the daily performance ratio against the days since the last rain gives both values: the intercept is
Two limits apply. The loss does not grow for ever: wind and dew remove some dust, and at some level it stops growing. And a light shower can make things worse, moving dust into streaks without washing it away.
When washing pays
Let
Washing every
A cheap wash, a fast soiling rate or a large array each shorten the interval. The formula assumes that dry weather continues. A wash on the day before rain is wasted, so the season matters as much as the formula.
String faults: a step
A string that stops (a failed connector, a blown string fuse, a damaged cable) removes its whole share of the array at once: with two equal strings the output falls to one half, with five to four fifths. In the daily performance ratio this is a step down that stays down, with no slope before it and no recovery after rain.
On an inverter with one string for each tracker there is a second, faster test: both strings see the same light and heat, so their powers should be equal within a few percent at every moment. A lasting difference points to the weak string, and needs no irradiance sensor at all.
Alarm rules that do not cry at every cloud
An alarm that fires on every cloudy day is switched off within a month, like a smoke alarm that rings for toast, and then it protects nothing. A useful rule has four properties.
It watches the performance ratio and not the energy, so the weather is already divided out.
It compares each day with the recent past of the same array, not with a fixed number; a fixed limit of 0.70 would fire in every long dry season. The median of the last two weeks moves down with the dust and up with the rain, so only a sudden change stands out, and one odd day does not move a median as it would a mean.
Its limit lies between the ordinary scatter of healthy days and the smallest fault that must be found. If healthy days stay within 7 percent of the reference and the fault of interest removes half the output, any limit between about 0.55 and 0.90 separates them.
It latches: once on, it stays on until a person clears it, and faulty days do not update the reference. Otherwise the median slowly accepts the fault as normal, and the alarm goes silent while the string is still dead.
Slow degradation
Modules lose a little output every year: about half a percent a year is used here as an example, and the maker’s warranty gives the figure for a real module. At that rate a performance ratio of 0.780 becomes 0.741 after ten years.
Half a percent is far below the changes in one year of records: daily scatter of 2 percent and a soiling sawtooth of up to 12 percent. A straight line fitted to 365 daily values with a scatter of 2 percent has an uncertainty in its slope of 0.36 percent a year, almost as large as the degradation itself, and this is before the seasons and the dust add their own errors. With five years of records the same uncertainty is 0.03 percent a year. So degradation is a question for several years of data. The practical method is to compare like with like: the performance ratio of clean days (just after rain) in the same months of different years, with the same sensor, kept clean and checked.
Three shapes, three actions
Application 1: Soiling and the washing decision
Step 1: The daily performance ratio
Click to reveal the calculation
-
Divide each day.
for each of the 365 days. ✅ -
Count dry days. For each day,
is the number of days since the last rain, and on a rain day. Rain fell on day 0, and then not again until day 75. ✅ -
Read the first dry spell.
Day Dry days 0 (rain) 0 0.814 20 20 0.750 40 40 0.712 74 74 0.699 75 (rain) 0 0.778 The value falls by 0.10 in the first 40 days and by only 0.013 in the next 34. The loss stops growing after about 48 dry days. One rain day brings back most of it. ✅
Step 2: The soiling rate
Click to reveal the calculation
-
Fit a line in each long dry spell. Use only the first 48 dry days, where the loss still grows. The line is
, and the rate is . Dry spell Days Clean ( ) Rate (% a day) Day 1 to 48 48 0.802 0.264 Day 149 to 194 46 0.802 0.249 Day 212 to 249 38 0.807 0.268 ✅
-
Fit all healthy days together. The 317 days that are outside the fault and have at most 48 dry days give
✅
-
The level where it stops. On days 49 to 74 the mean performance ratio is 0.698, a loss of
percent. ✅ -
The mistake to avoid. A line through all of days 1 to 74 gives 0.193 percent a day, a quarter too low, because it includes the flat part. Look at the record before fitting a line to it. ✅
Step 3: What soiling cost
Click to reveal the calculation
-
Loss of each day. The estimated soiling loss on a day with
dry days is , with an upper limit of 0.129. The energy lost that day is . ✅ -
Sum of the year. The sum is 599 kWh, which is 4.2 percent of the energy of the year. At 22 currency units per kWh it is 13,182 currency units. ✅
-
Cost of one more dry day. The clean array gives 42.0 kWh on a mean day. Each dry day adds
to the daily cost of the dirt. ✅
-
One dry spell of 30 days.
currency units. ✅
Step 4: The washing decision
Click to reveal the calculation
-
Best interval by the formula.
✅
-
Test the rule on the record. The rule is: wash at the end of the
th dry day since the last rain or wash. The script applies it to the year, with the estimated rate, and counts the washes and the energy gained. (dry days) Washes Energy gained (kWh) Value Net of wash cost 10 19 459 10,100 15 12 398 8,766 20 7 353 7,767 26 5 302 6,655 30 4 282 6,207 40 3 189 4,152 48 2 139 3,049 ✅
-
Decide. Washing pays at this site, but only a little and only in the long dry spells. The best of the tested rules is a wash after 30 dry days: four washes in the year, 282 kWh recovered, and a net gain of 3,007 currency units. A wash every 10 dry days loses 5,100 currency units a year. ✅
-
Check: formula against record. The formula gives 26 days and the record prefers 30. The table is flat between 20 and 30 days, and the record has only three long dry spells, so where the washes fall against the rain decides the order. Both say the same thing: about once a month in dry weather, never in the wet season. ✅
-
Check: the payback of one wash. A wash after 30 dry days removes a loss of
currency units a day. It pays back its 800 currency units after more dry days. If rain is expected within 11 days, do not wash. ✅ -
Check: against the model. The records were generated with a soiling rate of 0.25 percent a day and an upper limit of 12 percent. The estimates from the record are 0.254 percent a day and 12.9 percent. ✅
Application 2: The string fault at day 250
Step 1: Apply the rule
Click to reveal the calculation
-
The rule in symbols. For day
, the reference is . The alarm fires if . The first day that can be tested is day 14. ✅ -
Day 250. The reference is 0.735 and the performance ratio of the day is 0.366. The ratio is 0.497, far below 0.80. The alarm fires on day 250, the first day of the fault. ✅
-
False alarms. In the other 329 tested days of healthy operation the alarm never fires. The lowest ratio of a healthy day is 0.938, on day 244. There are no false alarms in the year. ✅
-
The alarm goes silent. The rule fires on days 250 to 257, eight days, and then stops, although the string is dead until day 271. From day 258 the window of 14 days holds eight faulty days, the median is itself a faulty value, and the fault has become the new normal. This is why the alarm must latch and the reference must be frozen while it is on. ✅
Step 2: Other limits, and the energy trap
Click to reveal the calculation
-
Move the limit. The same window of 14 days with other limits gives:
Limit Alarm days False alarms 0.50 7 0 0.70 8 0 0.80 8 0 0.90 8 0 0.92 8 0 0.94 11 2 0.95 20 11 0.96 41 30 ✅
-
Read the table. From 0.70 to 0.92 the result is the same: the fault on its first day and nothing else. Above 0.93 the limit enters the ordinary scatter of 2 percent, and the false alarms multiply. At 0.50 the rule still fires on day 250, but with a margin of only 0.003. The limit of 0.80 sits well inside the safe band. It would also find the loss of one string in an array of three or four. ✅
-
The same rule on energy. With daily energy in place of daily performance ratio, and the same window and limit, the rule fires on 39 days, and 29 of them are false. Each of those 29 is a day of weaker light, not a fault. ✅
Step 3: The energy lost
Click to reveal the calculation
-
Before and during. The mean daily energy is 36.7 kWh over days 240 to 249 and 19.1 kWh over days 250 to 271. ✅
-
Expected energy. Freeze the reference at its value on day 250, 0.735. The expected energy of each faulty day is
. Over the 22 days the sum is 856.6 kWh. ✅ -
Lost energy.
At 22 currency units per kWh this is 9,586 currency units. ✅
-
Check a second way. Half of the array was lost, so the lost energy must equal the energy that the other half gave: the measured 420.9 kWh. The estimate is 3.5 percent above this. The frozen reference does not know that dust continued to collect during the fault, so it expects slightly too much. An estimate of lost energy from a record carries an uncertainty of this size, and a report should say so. ✅
Step 4: What daily monitoring would have saved
Click to reveal the calculation
-
With the alarm. The alarm fires at the end of day 250. With a repair two days later, the string is back for day 253. The loss is that of days 250 to 252: 63.7 kWh. ✅
-
Saved.
That is 8,185 currency units, 85 percent of the loss. ✅
-
In proportion. One fault of 22 days cost 436 kWh. A whole year of soiling cost 599 kWh. A single unnoticed fault did almost as much harm as all the dust of the year, and most of it was avoidable. ✅
Verify It in Python
The script forms the daily performance ratio, estimates the soiling rate, tests the washing rule and the alarm rule, and saves a plot of daily energy and daily performance ratio with the rain days and the alarm days marked.
"""One year of daily records of the 9.9 kWp site: soiling rate, washing decision, fault alarm."""import numpy as npimport matplotlib.pyplot as plt
def year_of_yield(seed=11, kwp=9.9): """One year of daily records for the 9.9 kWp array: day number, plane-of-array insolation (kWh/m2), array energy at the inverter output (kWh). True model: base performance ratio 0.80; soiling loses 0.25 % a day since the last rain or wash, up to 12 %; rain on random days in two wet seasons; a string fault from day 250 to day 271 removes half the array; noise 2 %.""" rng = np.random.default_rng(seed) d = np.arange(365) wet = ((d >= 75) & (d < 150)) | ((d >= 285) & (d < 345)) h = 5.6 + 0.6 * np.cos(2 * np.pi * (d - 40) / 365) - 0.9 * wet + rng.normal(0, 0.7, 365) h = np.clip(h, 1.5, 7.5) rain = rng.random(365) < np.where(wet, 0.45, 0.03) soil = np.zeros(365); s = 0.0 for i in range(365): s = 0.0 if rain[i] else min(s + 0.0025, 0.12) soil[i] = s pr = 0.80 * (1 - soil) * (1 + rng.normal(0, 0.02, 365)) pr[250:272] *= 0.5 e = kwp * h * pr return d, h.round(2), e.round(1), rain
KWP, VALUE, WASH_COST = 9.9, 22.0, 800.0 # kWp, currency units per kWh and per washd, h, e, rain = year_of_yield()pr = e / (KWP * h)fault = (d >= 250) & (d <= 271)
# ---------- Application 1: soiling ----------dry = np.zeros(365, int) # days since the last raincount = 0for i in range(365): count = 0 if rain[i] else count + 1 dry[i] = countprint("Application 1: soiling")print(f" daily PR: day 0 {pr[0]:.3f}, day 20 {pr[20]:.3f}, day 40 {pr[40]:.3f}, " f"day 74 {pr[74]:.3f}, day 75 (rain) {pr[75]:.3f}")print(" dry spell days clean PR rate (% a day)")for a, b in ((1, 48), (149, 194), (212, 249)): sl = np.arange(a, b + 1) m, c = np.polyfit(dry[sl], pr[sl], 1) print(f" day {a:3d} to {b:3d} {len(sl):3d} {c:.3f} {-100 * m / c:.3f}")use = ~fault & (dry <= 48)m, c = np.polyfit(dry[use], pr[use], 1)rate = -m / cflat = ~fault & (dry > 48)cap = 1 - pr[flat].mean() / cprint(f" all {use.sum()} healthy days up to 48 dry days: clean PR {c:.3f}, " f"rate {100 * rate:.3f} % a day")m74, c74 = np.polyfit(dry[1:75], pr[1:75], 1)print(f" days 49 to 74: mean PR {pr[flat].mean():.3f}, a loss of {100 * cap:.1f} %; " f"a line through days 1 to 74 gives {-100 * m74 / c74:.3f} % a day")soil = np.minimum(rate * dry, cap) # estimated soiling loss of each daylost = e * soil / (1 - soil)print(f" soiling loss of the year {lost.sum():.0f} kWh ({100 * lost.sum() / e.sum():.1f} % of " f"the energy), {lost.sum() * VALUE:,.0f} currency units")clean_day = (e / (1 - soil))[~fault].mean()day_cost = rate * clean_day * VALUEprint(f" clean array on a mean day {clean_day:.1f} kWh; one day of dirt costs " f"{day_cost:.2f} currency units a day")print(f" loss of a dry spell of 30 days {day_cost * 30 * 31 / 2:,.0f} currency units; " f"best interval {np.sqrt(2 * WASH_COST / day_cost):.1f} days")print(" wash after N dry days: washes, energy gained, value, net of the wash cost")for n_dry in (10, 15, 20, 26, 30, 40, 48): count, washes, age = 0, 0, np.zeros(365, int) for i in range(365): if rain[i]: count = 0 else: count += 1 if count > n_dry: count, washes = 1, washes + 1 age[i] = count new = np.minimum(rate * age, cap) gain = (e * ((1 - new) / (1 - soil) - 1)).sum() print(f" N = {n_dry:2d}: {washes:2d} washes, {gain:5.0f} kWh, {gain * VALUE:6,.0f}, " f"net {gain * VALUE - washes * WASH_COST:+7,.0f}")
# ---------- Application 2: the string fault ----------WINDOW, LIMIT = 14, 0.80
def alarm_days(x, window, limit): """Days on which x is below limit times the median of the `window` days before.""" return [i for i in range(window, len(x)) if x[i] < limit * np.median(x[i - window:i])]
print("Application 2: the string fault")days = alarm_days(pr, WINDOW, LIMIT)ref = np.median(pr[250 - WINDOW:250])print(f" rule: daily PR below {LIMIT:.2f} of the median of the {WINDOW} days before")print(f" alarm days {days}")print(f" reference on day 250: {ref:.3f}; PR of day 250: {pr[250]:.3f}; " f"ratio {pr[250] / ref:.3f}")ratio = np.array([pr[i] / np.median(pr[i - WINDOW:i]) for i in range(WINDOW, 365)])quiet = ~fault[WINDOW:]print(f" lowest ratio on a healthy day {ratio[quiet].min():.3f} " f"(day {d[WINDOW:][quiet][ratio[quiet].argmin()]})")print(" limit alarm days false alarms")for limit in (0.50, 0.70, 0.80, 0.90, 0.92, 0.94, 0.95, 0.96): a = alarm_days(pr, WINDOW, limit) print(f" {limit:.2f} {len(a):3d} {sum(1 for i in a if not fault[i]):3d}")a = alarm_days(e, WINDOW, LIMIT)print(f" same rule on daily energy: {len(a)} alarm days, " f"{sum(1 for i in a if not fault[i])} of them false")expected = KWP * h[250:272] * refgap = expected - e[250:272]print(f" days 240 to 249: mean {e[240:250].mean():.1f} kWh a day; " f"days 250 to 271: mean {e[250:272].mean():.1f} kWh a day")print(f" fault, 22 days: expected {expected.sum():.1f} kWh, measured {e[250:272].sum():.1f} kWh, " f"lost {gap.sum():.1f} kWh, {gap.sum() * VALUE:,.0f} currency units")print(f" second way: half the array was lost, so the loss equals the measured " f"{e[250:272].sum():.1f} kWh")print(f" repair two days after the alarm: lost {gap[:3].sum():.1f} kWh in days 250 to 252, " f"saved {gap[3:].sum():.1f} kWh, {gap[3:].sum() * VALUE:,.0f} currency units")for years in (1, 5): t = np.arange(365 * years) / 365.0 print(f" slope uncertainty from {years * 365} days of daily PR with 2 % noise: " f"{100 * 0.02 / (np.sqrt(t.size) * t.std()):.2f} % a year")
# ---------- Plot ----------fig, ax = plt.subplots(2, 1, figsize=(9, 7), sharex=True)ax[0].plot(d, e, color="tab:orange", lw=0.9)ax[0].set_ylabel("daily energy (kWh)")ax[0].set_title("One year of the 9.9 kWp array: energy hides what PR shows")ax[1].plot(d, pr, color="tab:blue", lw=0.9, label="daily PR")ax[1].plot(d[rain], np.full(rain.sum(), 0.86), "|", color="tab:green", label="rain day")ax[1].plot(days, pr[days], "rv", label="alarm")ax[1].set_xlabel("day of the year")ax[1].set_ylabel("performance ratio")ax[1].set_ylim(0.3, 0.9)ax[1].legend(loc="lower left")fig.tight_layout()fig.savefig("monitoring_record.png", dpi=120)print("Saved monitoring_record.png")Expected output
Application 1: soiling daily PR: day 0 0.814, day 20 0.750, day 40 0.712, day 74 0.699, day 75 (rain) 0.778 dry spell days clean PR rate (% a day) day 1 to 48 48 0.802 0.264 day 149 to 194 46 0.802 0.249 day 212 to 249 38 0.807 0.268 all 317 healthy days up to 48 dry days: clean PR 0.801, rate 0.254 % a day days 49 to 74: mean PR 0.698, a loss of 12.9 %; a line through days 1 to 74 gives 0.193 % a day soiling loss of the year 599 kWh (4.2 % of the energy), 13,182 currency units clean array on a mean day 42.0 kWh; one day of dirt costs 2.35 currency units a day loss of a dry spell of 30 days 1,091 currency units; best interval 26.1 days wash after N dry days: washes, energy gained, value, net of the wash cost N = 10: 19 washes, 459 kWh, 10,100, net -5,100 N = 15: 12 washes, 398 kWh, 8,766, net -834 N = 20: 7 washes, 353 kWh, 7,767, net +2,167 N = 26: 5 washes, 302 kWh, 6,655, net +2,655 N = 30: 4 washes, 282 kWh, 6,207, net +3,007 N = 40: 3 washes, 189 kWh, 4,152, net +1,752 N = 48: 2 washes, 139 kWh, 3,049, net +1,449Application 2: the string fault rule: daily PR below 0.80 of the median of the 14 days before alarm days [250, 251, 252, 253, 254, 255, 256, 257] reference on day 250: 0.735; PR of day 250: 0.366; ratio 0.497 lowest ratio on a healthy day 0.938 (day 244) limit alarm days false alarms 0.50 7 0 0.70 8 0 0.80 8 0 0.90 8 0 0.92 8 0 0.94 11 2 0.95 20 11 0.96 41 30 same rule on daily energy: 39 alarm days, 29 of them false days 240 to 249: mean 36.7 kWh a day; days 250 to 271: mean 19.1 kWh a day fault, 22 days: expected 856.6 kWh, measured 420.9 kWh, lost 435.7 kWh, 9,586 currency units second way: half the array was lost, so the loss equals the measured 420.9 kWh repair two days after the alarm: lost 63.7 kWh in days 250 to 252, saved 372.0 kWh, 8,185 currency units slope uncertainty from 365 days of daily PR with 2 % noise: 0.36 % a year slope uncertainty from 1825 days of daily PR with 2 % noise: 0.03 % a yearSaved monitoring_record.pngCommon Mistakes
- Setting an alarm on daily energy. Clouds move the energy by more than most faults do. The same rule gave 29 false alarms in the year on energy and none on the performance ratio.
- Using a fixed limit on the performance ratio. A long dry season takes the value below any fixed number that is tight enough to be useful. Compare each day with the recent median.
- Letting the reference follow the fault. A rolling median accepts a dead string as normal after about half a window. Latch the alarm and freeze the reference.
- Fitting one line through a whole dry spell. Where the loss has stopped growing, the line gives a soiling rate that is too low. Look at the plot first.
- Washing by the calendar. A wash pays only if enough dry days follow it. Before the rains it is money lost.
- Reading degradation from one year. Half a percent a year is smaller than the scatter and far smaller than the soiling. It needs several years of clean-day values.
- Forgetting the sensor. A dirty or shaded irradiance sensor makes a dirty array look healthy.
Summary
- A monitoring system needs the cause and the result: plane-of-array irradiance and module temperature, DC and AC power, daily energy, and the battery state of charge.
- The daily performance ratio divides the weather out. Soiling appears in it as a sawtooth, a string fault as a step, and degradation as a slope too slow to see in one year.
- The record of the site gives a soiling rate of 0.254 percent a day and a clean performance ratio of 0.801. Soiling cost 599 kWh in the year.
- With a wash cost of 800 currency units and energy at 22 currency units per kWh, washing after about 30 dry days gains 3,007 currency units a year. Washing every 10 dry days loses money.
- The rule “daily performance ratio below 0.80 times the median of the 14 days before” fires on day 250, the first day of the fault, with no false alarm in the year. It must latch, because the median accepts the fault after eight days.
- The fault of 22 days lost about 436 kWh, worth 9,586 currency units. A repair two days after the alarm would have saved 372 kWh.
Exercises
1. At one moment the irradiance sensor of the 9.9 kWp site reads 650 W/m² and the module temperature is 48 °C. The power coefficient is
Answer
2. The daily performance ratio of an array is 0.800 on the day after rain and 0.760 after 20 dry days. Find the soiling rate.
Answer
3. A clean array gives 120 kWh a day. The soiling rate is 0.20 percent a day, energy is worth 15 currency units per kWh and a wash costs 1,500 currency units. Find the best interval between washes in dry weather.
Answer
Each dry day adds
4. An alarm uses a limit of 0.80 on the median of the last 14 days. The median is 0.760 and the performance ratio of today is 0.590. Does the alarm fire? Would the same rule find the loss of one string in an array of three equal strings?
Answer
The limit is
5. A system has a performance ratio of 0.780 in its first year. With a degradation of 0.5 percent a year (an example value), find the performance ratio after ten years. Compare the change of one year with a daily scatter of 2 percent.
Answer
6. Run the alarm rule of Application 2 on year_of_yield() with a window of 7 days and then of 30 days, both with a limit of 0.80. On which days does it fire? What does the window length change?
Answer
With 7 days it fires on days 250 to 253 (four days). With 30 days it fires on days 250 to 265 (sixteen days). Both start on day 250 and give no false alarm. A longer window takes longer to accept the fault as normal, but it also follows the soiling more slowly. In every case the alarm goes silent before the repair on day 272, so it must latch.
References
- G. M. Masters, Renewable and Efficient Electric Power Systems, 2nd edition, Wiley, 2013.
- R. A. Messenger and A. Abtahi, Photovoltaic Systems Engineering, 4th edition, CRC Press, 2017.
- IEC 61724-1, Photovoltaic system performance, Part 1: Monitoring (named here as the standard for what a monitoring system measures and how the performance ratio is formed).
An array has two equal strings. One stops and stays out for 22 days. An alarm compares the performance ratio of each day with the median of the 14 days before it, and fires when the day is below 0.80 of that median. On how many of the 22 days does it fire?
The 365 daily values are the record of year_of_yield(), the same generated year that the lesson uses. They come from a model and are not measurements of a real plant. Day 0 is 1 January. The reference of a day is the median of the days in the window before it, and the alarm fires when the value of the day is below the limit times the reference. A false alarm is an alarm day outside days 250 to 271, when both strings worked. With the latch on, alarm days are kept out of the reference, so the reference stays frozen while the alarm is on. No person is in the figure to clear the alarm, so it clears on the first day that the value is back above the limit. Move the limit toward 0.98 and count the false alarms. Then put the same rule on daily energy.
Check yourself
Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.
1. An array has six equal strings and one of them stops. The alarm fires when the daily performance ratio is below 0.80 of the median of the 14 days before. Does it find this fault?
2. The same rule, with the same window of 14 days and the same limit of 0.80, is put on daily energy in place of the daily performance ratio. It fires on 39 days of the year, and 29 of them are false. Why?
3. Without a latch, the rule with a window of 14 days fires on days 250 to 257. The window is made 30 days long and nothing else changes. What happens?
- Two equal strings, each on its own tracker. At 800 W/m² and 55 °C each gives 3.23 kW.
- String B stops. The output falls to half, and the daily PR steps from 0.74 to 0.37.
- Both strings see the same light and heat, so 3.23 kW against 0 kW names the weak string.
- The record says which string and from what day. The repair is for a qualified person.
Discussion
No comments yet. Questions, results from your own build, a better way to explain it: all welcome.