Lesson 7 of 10 24 min read
Found this useful?

An owner sees that September gave half of January’s energy. Was September cloudy, or did something break? The energy figure cannot answer, because it mixes how much light arrived with how well the system used it. A second owner sees a good month and relaxes, while dust has already taken a tenth of the output. Both need one number that removes the weather from the reading. This lesson builds that number, the performance ratio, and the chain of losses that explains its value. #PerformanceRatio #SolarLosses #EnergyYield

Learning Objectives

By the end of this lesson, you will be able to:

  1. Name the losses between the light on the array and the energy at the inverter output, in the order in which they occur
  2. Calculate the performance ratio, the specific yield and the capacity factor of a system from its records
  3. Build a loss table of stated factors and multiply it to an expected performance ratio and a yearly energy
  4. Explain why the performance ratio is a fairer measure of health than energy alone, and what a temperature-corrected value adds
  5. Read a year of monthly performance ratios and point to the months that need a reason

Real-World System Problem: One array, twelve different months



The site of this course has 18 modules of 550 W on a workshop roof near the equator: 9.9 kWp of nameplate power. Nameplate power is defined at standard test conditions (STC: 1,000 W/m², cells at 25 °C), and a hot roof never meets them. So “how much should this array give?” has no answer in kilowatts alone, only for a given amount of light after a known list of losses.

The site keeps two daily records: the plane-of-array insolation in kWh/m², from an irradiance sensor beside the modules at the same tilt, and the energy in kWh at the inverter output. In the year studied here, January gave 1,433 kWh and April 1,204 kWh, so April looks 16 percent worse. In fact the system worked better in April than in any other month, and January was already losing output to dust. Only the ratio of the two records shows this.

inverterarray9.9 kWpirradiancesensorsunlight on the tilted planeDCH(kWh/m²)ACE(kWh)PR=E/(9.9×H)
The two records that make a performance ratio

Fundamental Theory: From reference energy to real energy



The reference energy

Imagine an array with no losses: every module gives exactly its nameplate power at 1,000 W/m² and in proportion at any other irradiance. An insolation of 1 kWh/m² is one peak sun hour, in which the perfect array gives kilowatt hours. Over a period with insolation it gives

with in kWp and in kWh/m². This is the reference energy. For the site on a day of 5.5 kWh/m² it is kWh. No real system reaches it.

The performance ratio

The performance ratio is the real energy divided by the reference energy.

Performance ratio

is the energy at the inverter output in kWh, the nameplate power of the array in kWp, and the plane-of-array insolation of the same period in kWh/m². The result has no units.

The performance ratio collects every loss between the light and the output into one number: 0.78 means that 22 percent of the reference energy did not arrive. Because the insolation is in the denominator, a cloudy month and a sunny month of a healthy system give nearly the same value. That is the whole use of the ratio, as litres per 100 km judges a car’s engine whatever the length of the trip.

Two rules keep it honest. The insolation must be measured in the plane of the array, not on a horizontal surface or from a long-term table. And the energy and the insolation must cover exactly the same period.

Specific yield and capacity factor

Two other figures appear in reports, and both are easy to confuse with the performance ratio.

The specific yield is the energy for each kilowatt of nameplate power:

It allows arrays of different size to be compared. Dividing the specific yield by the insolation gives the performance ratio: .

The capacity factor is the energy divided by what the array would give at nameplate power for every hour of the period, day and night:

Solar capacity factors are low, often below 20 percent, because the sun is down half the time. Some reports divide by the inverter rating instead of the array nameplate, so always say which is used; this course uses the array.

The specific yield and the capacity factor both rise in a sunny year and fall in a cloudy one: they describe the site and the system together. Only the performance ratio separates the system from the site.

FigureFormulaChanges with the weather?What it is for
EnergyYesThe bill
Specific yieldYesComparing arrays of different size
Capacity factorYesComparing with other power sources
Performance ratioOnly a littleThe health of the system

The loss chain

The losses occur in a fixed order from the glass to the meter, each taking a share of what the stage before passed on, like a pipe that leaks a little at every joint.

reference energyP×Hreflection and weak lighttemperature of the cellsmodule below its label, ageingsoiling (dust on the glass)modulesmismatch between moduleswiring resistanceinverterconversion lossclipping at the inverter limitavailability (hours not running)energy at the outputE
The loss chain from the light to the meter

Reflection and weak light. Light at a flat angle reflects from the glass, and a module converts weak light a little less well than strong light, as the I-V curve showed.

Temperature. Cells in the sun are 20 to 30 °C above the air, and the power falls by the coefficient for each degree above 25 °C: at a warm site, the largest loss of the chain.

Module below its label, and ageing. A module may leave the factory slightly above or below its label; silicon modules lose a little output in their first weeks in the light, then a small amount each year. The maker’s data sheet and warranty give the figures.

Soiling. Dust, pollen and bird droppings block light. The loss grows day by day in dry weather and returns to near zero when it rains.

Mismatch and wiring. Modules in a string are never identical, and the weakest limits the current. Cables and connectors lose power as heat in proportion to the square of the current.

Inverter. Its efficiency depends on the load, a few percent below 1 over most of the range.

Clipping. When the array can give more than the inverter rating, the inverter holds its limit and the surplus is not produced.

Availability. Hours when the system is stopped (a fault, a repair, a grid failure with nowhere to send the power) count fully as loss. A hybrid system does the same when the battery is full, the load small and export not allowed: the inverter moves the array away from its maximum power point, and a healthy array shows a lower performance ratio.

Factors multiply

Each loss is written as a factor, the share of the energy that passes: a soiling loss of 3 percent is a factor of 0.97. Because each stage acts on what the stage before passed on, the factors multiply:

Performance ratio from a loss table

Each is the factor of one stage, a number between 0 and 1.

The common mistake is to add the losses. Eight losses that sum to 24 percent leave more than 76 percent, because each later loss takes its share from an amount already smaller. The difference is small for small losses and grows with them.

A loss table is a statement of expectation: every line is an assumption or a data sheet value until it is measured. When the measured performance ratio is below the table, something in the chain is worse than assumed, and the table says where to look.

The temperature factor over a day

The temperature factor of a moment is . For a whole day or year, each moment must be weighted by the energy produced in it, because the cells are hottest exactly when the array gives most. The weighted cell temperature follows from the NOCT rule with the irradiance weighted by energy, :

For a clear day whose irradiance follows a smooth curve, is about three quarters of the peak. The clear day of this course peaks at 916.7 W/m², and its energy-weighted irradiance is 687.5 W/m².

Temperature-corrected performance ratio

The ordinary performance ratio still contains the weather in one way: a hot month gives a lower value than a cool month for the same healthy system. To compare months or sites fairly, the temperature loss can be removed by multiplying the reference energy of each interval by its temperature factor:

is the insolation of interval and the measured module temperature in it. With one weighted temperature for the whole period this becomes divided by the temperature factor.

An example shows the effect. A hot month has with a weighted cell temperature of 52 °C. A cooler month has at 44 °C. The corrected values are and . The gap of 0.030 was almost all heat; the system was in the same state in both months. The standard IEC 61724-1 on the monitoring of solar systems defines the performance ratio and a temperature-corrected form. This lesson gives the idea only; a contract or a formal report should follow the text of the standard.

What a good value looks like

Yearly performance ratios of well-built systems are commonly reported between about 0.75 and 0.85, hot sites in the lower part and cool sites in the upper part, for the reason just shown. These figures are common experience, not a limit from any standard. A value is judged against the loss table and the history of its own system, not against another site.

PR1.00never reached: STC is not a roof0.85common yearly values of healthy0.75systems (experience, not a rule)0.65look for a cause: dirt, shade,a weak string, clipping, stops0.40part of the array is not working
Reading a performance ratio

Application 1: A loss table for the site



Step 1: Temperature factor

Click to reveal the calculation
  1. Energy-weighted cell temperature.

    ✅

  2. Temperature factor.

    Heat alone takes 8.6 percent of the reference energy at this site. ✅

Step 2: The table

Click to reveal the calculation
  1. Reference energy of a year. kWh/m².

    ✅

  2. Multiply stage by stage.

    StageFactorRunning productEnergy after (kWh)Lost here (kWh)
    Temperature0.9140.914018,1651,709
    Reflection and weak light0.970.886617,620545
    Module below label, first ageing0.980.868817,268352
    Soiling0.970.842816,750518
    Wiring and mismatch0.970.817516,247502
    Inverter0.970.793015,760487
    Clipping0.9950.789015,68179
    Availability0.990.781115,524157

    ✅

  3. Performance ratio.

    ✅

  4. Read the column of losses. Temperature takes 1,709 kWh, more than the next three losses together. The same factor of 0.97 takes 545 kWh near the top of the table and 487 kWh lower down, because it acts on a smaller amount. ✅

Step 3: Yearly energy, specific yield and capacity factor

Click to reveal the calculation
  1. Yearly energy.

    That is 42.5 kWh on a mean day, and 4,350 kWh a year below the reference energy. ✅

  2. Specific yield.

    ✅

  3. Capacity factor.

    The array gives 17.9 percent of what its nameplate would give if it ran at full power all year. ✅

Step 4: Check the table

Click to reveal the check
  1. Against a sum of losses. The eight losses add to percent. The true loss is percent. Adding would understate the energy by 2.2 percent of the reference, which is about 440 kWh a year. ✅

  2. Against the specific yield. . The same performance ratio comes back. ✅

  3. Against the noon reading. At noon with 800 W/m² and air at 30 °C, the same array showed 6.47 kW from a reference of kW: a ratio of 0.817 at that moment, with a heat factor of 0.895 and three factors of 0.97. The yearly table has a milder heat factor (0.914, because mornings and evenings are cooler) and four more losses that one clean noon reading did not count, so a lower yearly value is expected. ✅

  4. Against the earlier estimate. The round performance ratio of 0.75 used when the resource was studied gave 14,906 kWh a year. The table gives 15,524 kWh, 4 percent more: the round value was on the careful side. ✅

  5. Without soiling. Dividing the soiling factor out gives . This is what the table expects from a clean array, for example on the day after rain. ✅

Application 2: One year of records, month by month



Step 1: Monthly values

Click to reveal the calculation
  1. Sum each month, then divide. For each month, add the daily insolation and the daily energy, then apply .

    MonthDays (kWh/m²) (kWh)Rain days
    Jan0 to 30187.81,432.90.7711
    Feb31 to 58173.21,218.70.7110
    Mar59 to 89178.71,313.70.7438
    Apr90 to 119151.51,203.80.80316
    May120 to 150143.01,128.40.7979
    Jun151 to 180163.11,242.70.7690
    Jul181 to 211155.11,156.30.7532
    Aug212 to 242151.21,156.20.7720
    Sep243 to 272158.5718.00.4581
    Oct273 to 303150.31,175.10.78910
    Nov304 to 333144.81,143.90.79815
    Dec334 to 364176.01,379.50.7927

    ✅

  2. One month by hand. April: . ✅

  3. Energy against performance ratio. January has the most energy of the year and a performance ratio of 0.771. April has 16 percent less energy and the best performance ratio, 0.803. January had more light. April had the cleaner array. ✅

Step 2: The year

Click to reveal the calculation
  1. Sums. The year has kWh/m² (a mean of 5.297 a day) and kWh. ✅

  2. Performance ratio.

    ✅

  3. Specific yield and capacity factor. kWh/kWp and . ✅

  4. Against the design. This particular year had 5.297 peak sun hours against the design 5.5: 3.7 percent less light. The energy is 8.1 percent below the 15,524 kWh of the table, so less light explains less than half; the rest is the performance ratio, 0.746 against 0.781. ✅

Step 3: The months where the performance ratio falls

Click to reveal the reading
  1. The wet months. April, May, October, November and December are between 0.789 and 0.803. Rain fell on 7 to 16 days of each. These values are close to the 0.805 that the table expects from a clean array. ✅

  2. The dry months. January (0.771), June (0.769), July (0.753) and August (0.772) had two rain days or fewer. They are 2 to 5 hundredths below the wet months, and the difference appears when the rain stops. That is the pattern of soiling. ✅

  3. February. At 0.711 it is the lowest month with a working array, after no rain in February and one day in January. At the table value of 0.781 it would have given 1,340 kWh; it gave 1,219 kWh, 121 kWh less. March recovers to 0.743 as the rain begins on day 75. ✅

  4. September. At 0.458 it is far outside anything dust can do. The daily record shows the break: days 243 to 249 have a performance ratio of 0.731, days 250 to 271 have 0.361, almost exactly half, and half of this array is one of its two strings. At the table value the month would have given 1,226 kWh; it gave 718 kWh. ✅

  5. Check: the year without the fault. Without days 250 to 271 the performance ratio of the year is 0.770. The fault of 22 days lowered the yearly value from 0.770 to 0.746. The remaining gap from 0.770 to the table value of 0.781 is about the size of the extra soiling of the dry months. ✅

  6. Check: the average trap. The mean of the twelve monthly values is 0.746 and the mean of the 365 daily values is 0.748. They are close to the true 0.746 here because the months have similar light; with unequal months the gap grows, and only the ratio of the sums is correct. ✅

Jan0.771Feb0.711dustMar0.743Apr0.803May0.797Jun0.769Jul0.753Aug0.772Sep0.458faultOct0.789Nov0.798Dec0.792
Monthly performance ratio of the year (bar length in proportion)

Verify It in Python



The script builds the loss table of Application 1 and the monthly table of Application 2, and saves a plot of monthly energy and monthly performance ratio.

performance_ratio.py
"""Performance ratio of the 9.9 kWp site: a loss table, then one year of records by month."""
import numpy as np
import matplotlib.pyplot as plt
def year_of_yield(seed=11, kwp=9.9):
"""One year of daily records for the 9.9 kWp array: day number, plane-of-array
insolation (kWh/m2), array energy at the inverter output (kWh).
True model: base performance ratio 0.80; soiling loses 0.25 % a day since the
last rain or wash, up to 12 %; rain on random days in two wet seasons; a string
fault from day 250 to day 271 removes half the array; noise 2 %."""
rng = np.random.default_rng(seed)
d = np.arange(365)
wet = ((d >= 75) & (d < 150)) | ((d >= 285) & (d < 345))
h = 5.6 + 0.6 * np.cos(2 * np.pi * (d - 40) / 365) - 0.9 * wet + rng.normal(0, 0.7, 365)
h = np.clip(h, 1.5, 7.5)
rain = rng.random(365) < np.where(wet, 0.45, 0.03)
soil = np.zeros(365); s = 0.0
for i in range(365):
s = 0.0 if rain[i] else min(s + 0.0025, 0.12)
soil[i] = s
pr = 0.80 * (1 - soil) * (1 + rng.normal(0, 0.02, 365))
pr[250:272] *= 0.5
e = kwp * h * pr
return d, h.round(2), e.round(1), rain
KWP, GAMMA, NOCT = 9.9, -0.0035, 45.0
# ---------- Application 1: the loss table ----------
H_MEAN, T_AIR, G_WEIGHTED = 5.5, 28.0, 687.5
t_cell = T_AIR + (NOCT - 20.0) * G_WEIGHTED / 800.0
f_temp = round(1 + GAMMA * (t_cell - 25.0), 3)
factors = (("temperature", f_temp),
("reflection and weak light", 0.97),
("module below label, first ageing", 0.98),
("soiling", 0.97),
("wiring and mismatch", 0.97),
("inverter", 0.97),
("clipping", 0.995),
("availability", 0.99))
e_ref = KWP * H_MEAN * 365
print("Application 1: the loss table")
print(f" energy-weighted cell temperature {t_cell:.1f} deg C, temperature factor {f_temp:.3f}")
print(f" reference energy {e_ref:,.0f} kWh a year ({H_MEAN * 365:,.1f} kWh/m2)")
print(" stage factor product energy lost here")
run, energy = 1.0, e_ref
for name, f in factors:
run *= f
print(f" {name:34s} {f:5.3f} {run:6.4f} {energy * f:6,.0f} {energy * (1 - f):5,.0f}")
energy *= f
pr_table = run
print(f" performance ratio {pr_table:.3f}; yearly energy {energy:,.0f} kWh; "
f"lost {e_ref - energy:,.0f} kWh")
print(f" specific yield {energy / KWP:,.0f} kWh/kWp; capacity factor "
f"{100 * energy / (KWP * 8760):.1f} %; mean day {energy / 365:.1f} kWh")
print(f" adding the losses gives {100 * sum(1 - f for _, f in factors):.1f} %, "
f"the true loss is {100 * (1 - pr_table):.1f} %")
print(f" without soiling the table gives {pr_table / 0.97:.3f}; "
f"at a performance ratio of 0.75 the year is {KWP * H_MEAN * 365 * 0.75:,.0f} kWh")
print(f" temperature-corrected example: 0.760 at 52 deg C gives "
f"{0.760 / (1 + GAMMA * 27):.3f}, 0.790 at 44 deg C gives {0.790 / (1 + GAMMA * 19):.3f}")
# ---------- Application 2: one year of records ----------
d, h, e, rain = year_of_yield()
names = ("Jan", "Feb", "Mar", "Apr", "May", "Jun", "Jul", "Aug", "Sep", "Oct", "Nov", "Dec")
length = (31, 28, 31, 30, 31, 30, 31, 31, 30, 31, 30, 31)
print("Application 2: one year of records")
print(" month days H (kWh/m2) E (kWh) PR rain days")
start, pr_month, e_month = 0, [], []
for name, n in zip(names, length):
sl = slice(start, start + n)
pr_m = e[sl].sum() / (KWP * h[sl].sum())
pr_month.append(pr_m); e_month.append(e[sl].sum())
print(f" {name} {start:3d} to {start + n - 1:3d} {h[sl].sum():6.1f} "
f"{e[sl].sum():7.1f} {pr_m:.3f} {rain[sl].sum():3d}")
start += n
pr_year = e.sum() / (KWP * h.sum())
print(f" year: insolation {h.sum():,.1f} kWh/m2 (mean {h.mean():.3f} a day), "
f"energy {e.sum():,.0f} kWh, PR {pr_year:.3f}")
print(f" specific yield {e.sum() / KWP:,.0f} kWh/kWp, capacity factor "
f"{100 * e.sum() / (KWP * 8760):.1f} %, rain days {rain.sum()}")
print(f" light against the design mean: {100 * (h.sum() / (H_MEAN * 365) - 1):+.1f} %; "
f"energy against the table: {100 * (e.sum() / energy - 1):+.1f} %")
print(f" mean of the 12 monthly values {np.mean(pr_month):.3f}, "
f"mean of the 365 daily values {np.mean(e / (KWP * h)):.3f}")
healthy = np.ones(365, bool); healthy[250:272] = False
print(f" September, days 243 to 249: PR {e[243:250].sum() / (KWP * h[243:250].sum()):.3f}; "
f"days 250 to 271: PR {e[250:272].sum() / (KWP * h[250:272].sum()):.3f}")
print(f" year without days 250 to 271: PR "
f"{e[healthy].sum() / (KWP * h[healthy].sum()):.3f}")
print(f" February at the table value would give {KWP * h[31:59].sum() * pr_table:,.0f} kWh; "
f"September would give {KWP * h[243:273].sum() * pr_table:,.0f} kWh")
# ---------- Plot ----------
fig, ax = plt.subplots(2, 1, figsize=(8, 7), sharex=True)
ax[0].bar(names, e_month, color="tab:orange")
ax[0].set_ylabel("energy (kWh)")
ax[0].set_title("Monthly energy and monthly performance ratio of the 9.9 kWp array")
ax[1].bar(names, pr_month, color="tab:blue")
ax[1].axhline(pr_table, color="k", ls="--", label=f"loss table {pr_table:.3f}")
ax[1].axhline(pr_year, color="r", ls=":", label=f"year {pr_year:.3f}")
ax[1].set_ylabel("performance ratio")
ax[1].set_ylim(0.3, 0.9)
ax[1].legend(loc="lower left")
fig.tight_layout()
fig.savefig("performance_ratio.png", dpi=120)
print("Saved performance_ratio.png")

Expected output

Application 1: the loss table
energy-weighted cell temperature 49.5 deg C, temperature factor 0.914
reference energy 19,874 kWh a year (2,007.5 kWh/m2)
stage factor product energy lost here
temperature 0.914 0.9140 18,165 1,709
reflection and weak light 0.970 0.8866 17,620 545
module below label, first ageing 0.980 0.8688 17,268 352
soiling 0.970 0.8428 16,750 518
wiring and mismatch 0.970 0.8175 16,247 502
inverter 0.970 0.7930 15,760 487
clipping 0.995 0.7890 15,681 79
availability 0.990 0.7811 15,524 157
performance ratio 0.781; yearly energy 15,524 kWh; lost 4,350 kWh
specific yield 1,568 kWh/kWp; capacity factor 17.9 %; mean day 42.5 kWh
adding the losses gives 24.1 %, the true loss is 21.9 %
without soiling the table gives 0.805; at a performance ratio of 0.75 the year is 14,906 kWh
temperature-corrected example: 0.760 at 52 deg C gives 0.839, 0.790 at 44 deg C gives 0.846
Application 2: one year of records
month days H (kWh/m2) E (kWh) PR rain days
Jan 0 to 30 187.8 1432.9 0.771 1
Feb 31 to 58 173.2 1218.7 0.711 0
Mar 59 to 89 178.7 1313.7 0.743 8
Apr 90 to 119 151.5 1203.8 0.803 16
May 120 to 150 143.0 1128.4 0.797 9
Jun 151 to 180 163.1 1242.7 0.769 0
Jul 181 to 211 155.1 1156.3 0.753 2
Aug 212 to 242 151.2 1156.2 0.772 0
Sep 243 to 272 158.5 718.0 0.458 1
Oct 273 to 303 150.3 1175.1 0.789 10
Nov 304 to 333 144.8 1143.9 0.798 15
Dec 334 to 364 176.0 1379.5 0.792 7
year: insolation 1,933.3 kWh/m2 (mean 5.297 a day), energy 14,269 kWh, PR 0.746
specific yield 1,441 kWh/kWp, capacity factor 16.5 %, rain days 69
light against the design mean: -3.7 %; energy against the table: -8.1 %
mean of the 12 monthly values 0.746, mean of the 365 daily values 0.748
September, days 243 to 249: PR 0.731; days 250 to 271: PR 0.361
year without days 250 to 271: PR 0.770
February at the table value would give 1,340 kWh; September would give 1,226 kWh
Saved performance_ratio.png

Common Mistakes



  • Judging a month by its energy. A cloudy month of a healthy system and a sunny month of a faulty one can give the same kilowatt hours. Divide by the reference energy first.
  • Using horizontal or long-term insolation in the performance ratio. The light must be measured in the plane of the array and in the same period as the energy.
  • Adding the losses of a table. The factors multiply. For the table of this lesson a sum gives a loss of 24.1 percent where the true loss is 21.9 percent.
  • Averaging monthly or daily performance ratios to get the yearly value. Divide the energy of the year by the reference energy of the year.
  • Treating the values of a loss table as facts. Each line is an assumption until a data sheet or a measurement replaces it.
  • Calling a low performance ratio in a hot month a fault. Heat lowers the value of a healthy system. Compare with the same month of an earlier year, or use a temperature-corrected value.

Summary



  • The reference energy is what a perfect array would give from the light that arrived. The performance ratio is the real energy divided by it.
  • The performance ratio removes the weather from the reading. Energy, specific yield and capacity factor do not.
  • The losses between the light and the meter are written as factors, and the factors multiply. For the site, eight stated factors give a performance ratio of 0.781, a yearly energy of 15,524 kWh at 5.5 peak sun hours, a specific yield of 1,568 kWh/kWp and a capacity factor of 17.9 percent.
  • Temperature is the largest loss at a warm site: a factor of 0.914 for the year. A temperature-corrected performance ratio removes it for fair comparison.
  • The generated year of the site has a performance ratio of 0.746. The wet months are near 0.80, the dry months fall to 0.711 with dust, and the month with a string fault falls to 0.458.

Exercises



1. An array of 5.0 kWp receives 150 kWh/m² in its plane in one month and gives 580 kWh at the inverter output. Find the performance ratio.

Answer

.

2. An array of 6.6 kWp gives 9,900 kWh in a year. Find the specific yield and the capacity factor on the array nameplate.

Answer

kWh/kWp. , or 17.1 percent.

3. A loss table has the factors 0.90 (temperature), 0.97, 0.96, 0.98 and 0.965. Find the performance ratio, and the yearly energy of an array of 20 kWp with 1,800 kWh/m² a year. What would a sum of the losses have given?

Answer

. Energy kWh. The losses add to 22.5 percent, which would give 0.775. The true loss is 20.7 percent.

4. Site A has 12 kWp, received 1,950 kWh/m² and gave 17,500 kWh. Site B has 12 kWp, received 1,700 kWh/m² and gave 16,400 kWh. Which site gave more energy, and which system is in better health?

Answer

Site A gave more energy. Its performance ratio is . Site B has . System B converts its light better. Site A has more sun and something to investigate, although a hotter climate at A could explain part of the gap.

5. A month has a performance ratio of 0.740 and an energy-weighted cell temperature of 58 °C. The power coefficient is % per °C. Find the temperature-corrected performance ratio.

Answer

The temperature factor is . . Apart from heat, the system is doing well.

6. Use year_of_yield() to find the performance ratio of days 0 to 74 (before the first wet season) and of days 75 to 149 (the first wet season). Explain the difference.

Answer

Days 0 to 74: kWh, kWh/m², . Days 75 to 149: kWh, kWh/m², . The dry period had more light and more energy and a lower performance ratio, because dust collected on the modules with no rain to remove it.

References



  • G. M. Masters, Renewable and Efficient Electric Power Systems, 2nd edition, Wiley, 2013.
  • R. A. Messenger and A. Abtahi, Photovoltaic Systems Engineering, 4th edition, CRC Press, 2017.
  • IEC 61724-1, Photovoltaic system performance, Part 1: Monitoring (named here as the standard that defines the performance ratio and how its inputs are measured).


© 2021-2026 SiliconWit®. All rights reserved.
Predict first

The same 9.9 kWp array gave 1,433 kWh in January and 1,204 kWh in April. The irradiance sensor in the plane of the array measured 187.8 kWh/m² in January and 151.5 kWh/m² in April. In which month did the system itself work better?

JanuaryApril light 187.8 kWh/m²energy 1,433 kWhlight 151.5 kWh/m²energy 1,204 kWh PR 0.771PR 0.803 Divide by the light, and April is the better month.
Try it: each stage takes its share of what is left

Performance ratio, factors multiplied
Yearly energy at 5.5 peak sun hours
Losses added (the mistake)

The rows are the loss table of Application 1 for the 9.9 kWp array, with the example factors of the lesson. The temperature factor uses the energy-weighted irradiance of 687.5 W/m², NOCT 45 °C and −0.35 percent per °C. Move the air temperature: heat is the largest loss, and the owner cannot remove it. Move the soiling: it is the only large loss the owner controls week by week.

heat 8.6 %glasslabeldustwiringinverterclip, stops 100 %78 % perfect arrayat the meter

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. An array of 6 kWp gave 702 kWh in a 30-day month. A sensor in the plane of the array measured 150 kWh/m² in the month. The nearest weather station reports 130 kWh/m² on a horizontal surface. What is the performance ratio of the month?

2. A system has five losses in its chain, and each one is 5 percent. What performance ratio does the loss table give?

3. A hot month has a performance ratio of 0.74 with an energy-weighted cell temperature of 55 °C. A cool month has 0.78 at 43 °C. The power coefficient is −0.35 percent per °C. What do you conclude about the system?

Watch it build: reference energy and performance ratio
54.5 clear 5.5 Perfect array9.9 kWp × 5.5 h= 54.5 kWhnothing real reaches it E PR = E ÷ (P × H)real energy overreference energy 42.5 43.433.9 cloudy 4.39 PR 0.78 both days22 % did not arrive.The weather divides out. H: sensor in theplane of the array E and H: the sameperiod, exactly
  1. A perfect array gives its nameplate for each peak sun hour: 9.9 kWp × 5.5 h = 54.5 kWh.
  2. The performance ratio divides the real energy E by that reference energy.
  3. Real 42.5 of 54.5 kWh is 0.78. A cloudy day gives 33.9 of 43.4: still 0.78.
  4. Measure H in the plane of the array, and take E and H over exactly the same period.
sun: light on the tilted plane array 9.9 kWp irradiance sensor DC inverter AC kWh E, kWh H, kWh/m² PR = E / (9.9 × H)
What the site measures
reference energy P × H reflection and weak light temperature of the cells module below its label, ageing soiling (dust on the glass) mismatch between modules wiring resistance conversion loss clipping at the inverter limit availability (hours not running) energy at the output E in the modules between modules in the inverter
The loss chain from the light to the meter
1.00 never reached: STC is not a roof 0.85 common yearly values of healthy systems 0.75 (experience, not a rule) 0.65 look for a cause: dirt, shade, a weak string, clipping, stops 0.40 part of the array is not working PR
Reading a performance ratio
Jan 0.771 Feb 0.711 dust Mar 0.743 Apr 0.803 May 0.797 Jun 0.769 Jul 0.753 Aug 0.772 Sep 0.458 fault Oct 0.789 Nov 0.798 Dec 0.792 table value 0.781
Monthly performance ratio of the year