Skip to content
You Start with one site
Amounts in Start with one site
Control, Measurement & Energy · Course

Pumps, Fans, Gears and Motors

Lesson 8 of 10 22 min read
Found this useful?

A technician finds a tall line at 290 Hz on a pump, cannot match it to running speed, and orders new bearings. The new bearings change nothing, because 290 Hz was the six impeller vanes passing the casing, a line that every healthy pump of that design has. The opposite error costs more: a line at gear mesh frequency grows new neighbours for months and nobody reads them, until a tooth breaks. This lesson gives the frequencies that pumps, fans, belts, gears and induction motors produce by design. You will calculate them for four machines and read the sidebands that show which shaft carries a problem. #VibrationAnalysis #GearMesh #ConditionMonitoring

Learning Objectives

By the end of this lesson, you will be able to:

  1. Calculate vane pass, blade pass, belt, gear mesh, slip and pole pass frequencies in hertz and in orders
  2. Distinguish a line that the design produces from a change that needs attention
  3. State what a growing line or a new pattern is consistent with, for each machine type
  4. Read the sideband spacing round a gear mesh line and name the shaft it points to
  5. Choose a record length that resolves closely spaced sidebands

Real-World System Problem: One site, four machines, many lines



The site of this course has a compressor motor (A), a borehole booster pump (B), a belt-driven condenser fan (C) and a conveyor gearbox (D). Running speed and its multiples explain unbalance, misalignment and looseness on all four. They do not explain most of the other lines in the spectra.

Those other lines come from parts that repeat an event several times each turn: an impeller with 6 vanes pushes 6 pressure pulses past the casing, a 17-tooth pinion makes 17 tooth contacts, and a motor’s magnetic field peaks twice in each supply cycle. Each gives a line that can be calculated from the nameplate and the drawing, before any measurement.

The work is to know these lines before the fault arrives. A calculated line, steady from month to month, is the machine’s signature; a line that grows, or gains sidebands, is the evidence.

1450rev/mindrumMotorGearboxConveyorpinion 17 T●mesh24.17 Hz◯gear68T410.8 Hz at the362.5 rev/mintooth contact6.04 Hz
Machine D: the conveyor gearbox

Fundamental Theory: Frequencies that the design produces



The general rule

If something happens times in each turn of a shaft that turns at (as a turnstile with 6 arms clicks 6 times a turn), the event repeats at

Pass frequency

is the number of vanes, blades or teeth, and is the shaft frequency in Hz for a speed in rev/min. In orders of that shaft, the pass frequency is simply .

Orders are always counted on a named shaft. A machine with two shafts has two sets of orders, and a table must say which one it uses.

Pumps: vane pass and cavitation

Each vane of a centrifugal impeller sends a pressure pulse as it passes the narrowest point of the casing. The vane pass frequency, vanes times running frequency, is present in every healthy pump.

A growing vane pass line is commonly described as consistent with a clearance or flow problem: an uneven gap between impeller and casing, a worn or damaged impeller, or operation far from the design flow. The line also changes when a valve is moved, so compare readings at the same flow.

Cavitation looks different. Vapour bubbles form where the pressure is too low and collapse at random, with no single frequency, so cavitation gives a raised broadband level at high frequency and no clear line, often with a noise like gravel in the casing. It is consistent with a pump running at too low a suction head, the subject known as net positive suction head. Broadband high-frequency energy is also consistent with poor bearing lubrication and with flow turbulence, so the level alone does not decide.

Fans and belts

A fan gives a blade pass frequency in the same way: the number of blades times the fan’s shaft frequency. A growing blade pass line is commonly associated with an uneven gap between the blades and the housing, or with an obstruction in the duct that disturbs the flow.

A belt adds a frequency of its own. The belt travels at the rim speed of the pulley, and one turn of the belt is one belt length:

Belt frequency

is the pitch diameter of either pulley, is the speed of that same pulley, and is the belt length in the same unit as . With in rev/min the result is in belt turns per minute. Divide by 60 for Hz.

The belt is longer than the circumference of either pulley, so the belt frequency is always below both shaft speeds. Lines at multiples of belt frequency are commonly described as consistent with a worn or damaged belt, or with mismatched belts in a set. On a drive with two pulleys, twice belt frequency is often reported as the largest.

●●motor pulleyfan pulley100 mm250 mmbelt1600mm1450 rev/min580 rev/min24.17 Hz4.75 Hz9.67 Hz7 blades
Machine C: the belt drive of the fan

Gears: mesh frequency and sidebands

Each tooth contact gives a small pulse, so a pair of gears produces the gear mesh frequency (GMF): teeth on a gear times its shaft frequency, the same for both gears because the same teeth meet. GMF is present in every healthy gearbox, and its amplitude changes strongly with load, so compare gear readings only at the same load.

The diagnostic information is in the sidebands. If a pinion tooth is damaged, or the pinion runs eccentric, the meshing is disturbed once per pinion turn, so the mesh vibration is modulated at the pinion’s shaft frequency. In the spectrum, modulation appears as lines on each side of GMF:

The spacing of the sidebands is the frequency of the shaft that carries the problem. This is the most useful single fact about gear spectra.

mm/s0.80.30.10HzGMFspacing = frequency of theshaft with the problem
Gear mesh line with sidebands

Low sidebands exist in sound gearboxes too, because no gear is perfectly round. The evidence is growth of the sidebands against the baseline, and more pairs of them.

Motors: electrical signatures

An induction motor adds lines that come from the supply and not from the mechanics.

Twice line frequency. The magnetic pull between stator and rotor peaks twice in each supply cycle, so every motor on a 50 Hz supply has some vibration at 100 Hz (120 Hz on 60 Hz). A growing line here is commonly associated with stator problems: an uneven air gap, loose stator iron, a frame distorted by a soft foot, or unbalanced supply voltages. It disappears the instant the supply is switched off, while mechanical lines fall slowly with the speed; watching a normal stop, made by the operator in the usual way, separates electrical from mechanical causes. On a motor fed by a variable speed drive the line sits at twice the drive’s output frequency (80 Hz at 40 Hz output), not at 100 Hz, and the drive adds lines of its own at its switching frequency, usually in the kilohertz range.

Slip and pole pass frequency. The field of a motor with poles on a supply of frequency turns at the synchronous speed in rev/min. The rotor turns a little slower, at . The difference, as a frequency, is the slip frequency, and the pole pass frequency is the slip frequency times the number of poles:

Slip and pole pass frequency

A cracked or broken rotor bar disturbs the rotor current once each time the bar passes a pole of the slipping field. The commonly described association is a line at 1× with sidebands at on each side. Pole pass frequency is only a few hertz, so these sidebands need a long record, and they move with load because slip changes with load. Measure at a steady load, near full load. Measure the speed too: the nameplate speed is for full load only, and on motor A an error of 10 rev/min moves the pole pass frequency by Hz, almost a third of its 2.33 Hz.

mm/s0Hz22.0824.4226.752.33Hzeachside(pole pass frequency)
Rotor bar pattern: sidebands round 1× (machine A)

What each pattern is consistent with

What grows or appearsCommonly described association
Vane pass line (pump)Uneven clearance, worn impeller, flow far from design
Broadband high-frequency level (pump)Cavitation; also lubrication, turbulence
Blade pass line (fan)Uneven blade gap, obstruction in the duct
Multiples of belt frequencyBelt wear, damage or mismatched belts
Sidebands round GMFProblem on the shaft whose speed equals the spacing
Twice line frequency (motor)Stator problems, uneven air gap, soft foot
Sidebands at round 1× (motor)Rotor bar problems

Application 1: The characteristic frequencies of four machines



Step 1: Pump B

Click to reveal the pump frequencies
  1. Running frequency.

    This is 1× for the pump. ✅

  2. Vane pass frequency.

    Vane pass is at 6 orders. ✅

Step 2: Fan C

Click to reveal the fan and belt frequencies
  1. Shaft frequencies. The motor turns at . The fan speed follows the pulley ratio:

    The fan runs at 0.400 orders of the motor. ✅

  2. Blade pass frequency.

    That is 7 orders of the fan, or 2.80 orders of the motor. ✅

  3. Belt frequency. Use the motor pulley.

    That is 0.196 orders of the motor, or 0.491 orders of the fan. ✅

  4. Check with the fan pulley. The belt has one speed, so the other pulley must give the same answer.

    The two agree, and the result is below both shaft speeds, as it must be. ✅

  5. A trap on this machine. Twice belt frequency is . The fan’s 1× is 9.67 Hz. The two are only 0.176 Hz apart, so separating them needs a record of . In a short record, belt wear and fan unbalance fall in the same line. ✅

Step 3: Gearbox D

Click to reveal the gearbox frequencies
  1. Shaft frequencies. The input turns at . The ratio is , so the output turns at , which is or 0.250 orders of the input. ✅

  2. Gear mesh frequency.

    GMF is at 17 orders of the input shaft and 68 orders of the output shaft. ✅

  3. Check from the gear. . Both gears give the same mesh frequency. ✅

Step 4: Motor A

Click to reveal the motor frequencies
  1. Running frequency. . ✅

  2. Twice line frequency. , which is orders. It is not a whole order: 4× is at 97.67 Hz. ✅

  3. Slip frequency. The synchronous speed is .

    The rotor falls behind the field 0.583 times each second. ✅

  4. Pole pass frequency.

    Sidebands at this spacing round 1× would lie at and . To see them apart from 1× needs a record of at least . ✅

Step 5: The table

MachineLineHzOrders
Pump B1×48.331
Pump BVane pass290.06
Fan CMotor 1×24.171 (motor)
Fan CFan 1×9.670.400 (motor), 1 (fan)
Fan CBlade pass67.72.80 (motor), 7 (fan)
Fan CBelt4.750.196 (motor), 0.491 (fan)
Gearbox DInput 1×24.171 (input)
Gearbox DOutput 1×6.040.250 (input), 1 (output)
Gearbox DGear mesh410.817 (input), 68 (output)
Motor A1×24.421
Motor ATwice line frequency100.04.10
Motor ASlip0.5830.024
Motor APole pass2.330.096

Application 2: Reading the sidebands of a gear mesh line



Step 1: Check the resolution, then read the lines

Click to reveal the first reading
  1. Resolution.

    The expected spacing of 24.17 Hz is steps, well above the 4 steps of the working rule. ✅

  2. Lines found between 340 and 480 Hz.

    Line (Hz)Amplitude (mm/s peak)
    362.50.117
    387.50.277
    410.00.746
    435.00.299
    460.00.114

    Five lines: a centre line and two pairs. The amplitudes read a little below the true 0.80, 0.30 and 0.12 because the true frequencies fall between the 2.5 Hz steps. ✅

  3. Centre line. 410.0 Hz is the gear mesh frequency (410.8 Hz) on a 2.5 Hz grid. ✅

  4. Spacing. The inner pair gives and . The outer pair covers four spacings and gives a better value:

    The spacing is about 24.4 Hz. ✅

  5. Which shaft. The input shaft turns at 24.17 Hz and the output shaft at 6.04 Hz. The spacing matches the input shaft. The modulation is consistent with a problem on the input shaft, which carries the 17-tooth pinion: for example an eccentric pinion or a damaged tooth on it. ✅

Step 2: Sidebands at the output shaft frequency

Click to reveal the short record failing
  1. Same record, new spacing. With sidebands at and , the spacing is steps, below the working rule. ✅

  2. Lines found. The 0.4 s record shows only two lines: 410.0 Hz (0.746) and 417.5 Hz (0.295). The four sidebands have merged with the centre line, and the one extra line is at a frequency that is not in the signal. ✅

  3. What a reader would conclude. A single gear mesh line with a rough shoulder. Nothing here points to the output shaft, and the gear would be passed as normal. ✅

Step 3: The record length that resolves them

Click to reveal the longer records
  1. Record length needed.

    The next record lengths in the usual doubling series are 0.8 s and 1.6 s. ✅

  2. Record of 0.8 s (2048 samples, step 1.25 Hz, 4.8 steps). Five lines appear: 398.75, 405.0, 411.25, 416.25 and 422.5 Hz. The inner spacings read 6.25 and 5.0 Hz, and the outer pair gives . ✅

  3. Record of 1.6 s (4096 samples, step 0.625 Hz, 9.7 steps). The lines are at 398.75, 405.0, 410.625, 416.875 and 423.125 Hz, with amplitudes 0.119, 0.279, 0.743, 0.301 and 0.113 mm/s. The outer pair gives

    which matches the output shaft frequency of 6.04 Hz. ✅

  4. Reading. The modulation is now consistent with a problem on the output shaft, which carries the 68-tooth gear. ✅

  5. Check a second way. The two records were computed separately and agree: 5.94 Hz and 6.09 Hz, each within one of its own resolution steps of 6.04 Hz. The 0.8 s record just meets the working rule and resolves the lines, and the 0.4 s record does not meet it and fails. The rule and the computed spectra agree. ✅

Verify It in Python



The script calculates every frequency of Application 1, builds the gearbox signals of Application 2 with the course generator, and lists the lines found at each record length. It saves one plot with three panels.

machine_signatures_gearbox.py
"""Characteristic frequencies of machines A to D, and reading gear mesh sidebands."""
import numpy as np
from scipy import signal
import matplotlib.pyplot as plt
def machine_signal(fs=5120, seconds=4.0, fr=24.42, amp_1x=1.2, amp_2x=0.3,
others=(), noise=0.05, seed=5):
"""Vibration velocity in mm/s. amp_* are PEAK amplitudes in mm/s.
others: sequence of (frequency_hz, peak_amplitude_mm_s, phase_rad)."""
rng = np.random.default_rng(seed)
n = int(fs * seconds); t = np.arange(n) / fs
v = amp_1x * np.sin(2 * np.pi * fr * t) + amp_2x * np.sin(2 * np.pi * 2 * fr * t + 0.7)
for f, a, ph in others:
v = v + a * np.sin(2 * np.pi * f * t + ph)
return t, v + rng.normal(0.0, noise, n)
def spectrum(x, fs):
"""Amplitude spectrum with a Hann window: amplitude = 2|X| / (n * mean of window)."""
n = len(x)
w = signal.windows.hann(n, sym=False)
return np.fft.rfftfreq(n, 1.0 / fs), 2.0 * np.abs(np.fft.rfft(x * w)) / (n * w.mean())
def row(name, hz, ref_hz, ref_name):
print(f" {name:<24}{hz:8.2f} Hz {hz / ref_hz:6.3f} orders of {ref_name}")
# ---------- Application 1: characteristic frequencies ----------
print("Pump B (2900 rev/min, 6 vanes)")
FB = 2900.0 / 60.0
row("running speed 1x", FB, FB, "pump")
row("vane pass", 6 * FB, FB, "pump")
print("Fan C (motor 1450 rev/min, pulleys 100 and 250 mm, belt 1600 mm, 7 blades)")
FM = 1450.0 / 60.0
FAN_REV = 1450.0 * 100.0 / 250.0
FF = FAN_REV / 60.0
BELT_PER_MIN = np.pi * 100.0 * 1450.0 / 1600.0
FBELT = BELT_PER_MIN / 60.0
print(f" fan speed {FAN_REV:.0f} rev/min, belt {BELT_PER_MIN:.1f} turns per minute")
print(f" belt from the fan pulley: {np.pi * 250.0 * FAN_REV / 1600.0:.1f} turns per minute")
row("motor 1x", FM, FM, "motor")
row("fan 1x", FF, FM, "motor")
row("blade pass", 7 * FF, FF, "fan")
row("blade pass", 7 * FF, FM, "motor")
row("belt frequency", FBELT, FM, "motor")
row("belt frequency", FBELT, FF, "fan")
row("2 x belt frequency", 2 * FBELT, FF, "fan")
print(f" fan 1x minus 2 x belt: {FF - 2 * FBELT:.3f} Hz, "
f"record for 4 steps: {4 / (FF - 2 * FBELT):.1f} s")
print("Gearbox D (input 1450 rev/min, 17 and 68 teeth)")
FIN = 1450.0 / 60.0
FOUT = FIN * 17.0 / 68.0
GMF = 17 * FIN
print(f" output speed {60 * FOUT:.1f} rev/min")
row("input 1x", FIN, FIN, "input")
row("output 1x", FOUT, FIN, "input")
row("gear mesh", GMF, FIN, "input")
row("gear mesh", GMF, FOUT, "output")
print(f" check from the gear: 68 x {FOUT:.3f} = {68 * FOUT:.2f} Hz")
print("Motor A (4 pole, 50 Hz, 1465 rev/min)")
FA = 1465.0 / 60.0
NS = 120.0 * 50.0 / 4
SLIP = (NS - 1465.0) / 60.0
FP = 4 * SLIP
row("running speed 1x", FA, FA, "motor")
row("twice line frequency", 100.0, FA, "motor")
row("4 x running speed", 4 * FA, FA, "motor")
print(f" synchronous speed {NS:.0f} rev/min, slip frequency {SLIP:.3f} Hz, "
f"pole pass frequency {FP:.2f} Hz")
print(f" pole pass sidebands round 1x: {FA - FP:.2f} and {FA + FP:.2f} Hz")
print(f" record for 4 steps between them and 1x: {4 / FP:.2f} s")
# ---------- Application 2: gear mesh sidebands ----------
FS = 2560
GMF_AMP, SB1, SB2 = 0.80, 0.30, 0.12 # peak amplitudes, mm/s
def gearbox_signal(spacing, seconds):
"""Gear mesh line with two pairs of sidebands at the given spacing (Hz)."""
others = [(GMF, GMF_AMP, 0.0),
(GMF - spacing, SB1, 0.4), (GMF + spacing, SB1, 1.1),
(GMF - 2 * spacing, SB2, 2.0), (GMF + 2 * spacing, SB2, 0.3)]
return machine_signal(fs=FS, seconds=seconds, fr=24.17, amp_1x=0.9, amp_2x=0.2,
others=others, noise=0.05, seed=5)
def lines(f, amp, f_low=340.0, f_high=480.0, height=0.06):
m = (f >= f_low) & (f <= f_high)
idx, _ = signal.find_peaks(amp[m], height=height)
return f[m][idx], amp[m][idx]
def report(spacing, seconds):
_, v = gearbox_signal(spacing, seconds)
f, amp = spectrum(v, FS)
fl, al = lines(f, amp)
print(f" record {seconds:.1f} s ({len(v)} samples, step {1 / seconds:.3f} Hz, "
f"spacing = {spacing * seconds:.1f} steps): {len(fl)} lines")
print(" " + ", ".join(f"{x:.3f} Hz ({y:.3f})" for x, y in zip(fl, al)))
if len(fl) == 5:
print(f" spacings {fl[2] - fl[1]:.3f} and {fl[3] - fl[2]:.3f} Hz, "
f"outer pair / 4 = {(fl[4] - fl[0]) / 4:.3f} Hz")
return f, amp
print(f"Gearbox signal, sidebands at the input shaft frequency {FIN:.2f} Hz")
fa, Aa = report(FIN, 0.4)
print(f"Gearbox signal, sidebands at the output shaft frequency {FOUT:.2f} Hz")
fb, Ab = report(FOUT, 0.4)
print(f" record needed for 4 steps: 4 / {FOUT:.2f} = {4 / FOUT:.2f} s")
fc, Ac = report(FOUT, 0.8)
fd, Ad = report(FOUT, 1.6)
# ---------- Plot ----------
fig, ax = plt.subplots(3, 1, figsize=(9, 9))
panels = ((fa, Aa, f"Sidebands at {FIN:.2f} Hz, record 0.4 s", (340, 480)),
(fb, Ab, f"Sidebands at {FOUT:.2f} Hz, record 0.4 s: not resolved", (380, 440)),
(fd, Ad, f"Sidebands at {FOUT:.2f} Hz, record 1.6 s: resolved", (380, 440)))
for axis, (f, amp, title, limits) in zip(ax, panels):
axis.plot(f, amp, marker=".", linewidth=0.8)
axis.axvline(GMF, linestyle=":", linewidth=0.8)
axis.set_xlim(*limits)
axis.set_xlabel("frequency (Hz)")
axis.set_ylabel("velocity (mm/s peak)")
axis.set_title(title)
fig.tight_layout()
fig.savefig("machine_signatures_gearbox.png", dpi=120)
print("Saved machine_signatures_gearbox.png")

Expected output

Pump B (2900 rev/min, 6 vanes)
running speed 1x 48.33 Hz 1.000 orders of pump
vane pass 290.00 Hz 6.000 orders of pump
Fan C (motor 1450 rev/min, pulleys 100 and 250 mm, belt 1600 mm, 7 blades)
fan speed 580 rev/min, belt 284.7 turns per minute
belt from the fan pulley: 284.7 turns per minute
motor 1x 24.17 Hz 1.000 orders of motor
fan 1x 9.67 Hz 0.400 orders of motor
blade pass 67.67 Hz 7.000 orders of fan
blade pass 67.67 Hz 2.800 orders of motor
belt frequency 4.75 Hz 0.196 orders of motor
belt frequency 4.75 Hz 0.491 orders of fan
2 x belt frequency 9.49 Hz 0.982 orders of fan
fan 1x minus 2 x belt: 0.176 Hz, record for 4 steps: 22.7 s
Gearbox D (input 1450 rev/min, 17 and 68 teeth)
output speed 362.5 rev/min
input 1x 24.17 Hz 1.000 orders of input
output 1x 6.04 Hz 0.250 orders of input
gear mesh 410.83 Hz 17.000 orders of input
gear mesh 410.83 Hz 68.000 orders of output
check from the gear: 68 x 6.042 = 410.83 Hz
Motor A (4 pole, 50 Hz, 1465 rev/min)
running speed 1x 24.42 Hz 1.000 orders of motor
twice line frequency 100.00 Hz 4.096 orders of motor
4 x running speed 97.67 Hz 4.000 orders of motor
synchronous speed 1500 rev/min, slip frequency 0.583 Hz, pole pass frequency 2.33 Hz
pole pass sidebands round 1x: 22.08 and 26.75 Hz
record for 4 steps between them and 1x: 1.71 s
Gearbox signal, sidebands at the input shaft frequency 24.17 Hz
record 0.4 s (1024 samples, step 2.500 Hz, spacing = 9.7 steps): 5 lines
362.500 Hz (0.117), 387.500 Hz (0.277), 410.000 Hz (0.746), 435.000 Hz (0.299), 460.000 Hz (0.114)
spacings 22.500 and 25.000 Hz, outer pair / 4 = 24.375 Hz
Gearbox signal, sidebands at the output shaft frequency 6.04 Hz
record 0.4 s (1024 samples, step 2.500 Hz, spacing = 2.4 steps): 2 lines
410.000 Hz (0.746), 417.500 Hz (0.295)
record needed for 4 steps: 4 / 6.04 = 0.66 s
record 0.8 s (2048 samples, step 1.250 Hz, spacing = 4.8 steps): 5 lines
398.750 Hz (0.119), 405.000 Hz (0.293), 411.250 Hz (0.744), 416.250 Hz (0.257), 422.500 Hz (0.112)
spacings 6.250 and 5.000 Hz, outer pair / 4 = 5.938 Hz
record 1.6 s (4096 samples, step 0.625 Hz, spacing = 9.7 steps): 5 lines
398.750 Hz (0.119), 405.000 Hz (0.279), 410.625 Hz (0.743), 416.875 Hz (0.301), 423.125 Hz (0.113)
spacings 5.625 and 6.250 Hz, outer pair / 4 = 6.094 Hz
Saved machine_signatures_gearbox.png

Common Mistakes



  • Treating vane pass, blade pass or gear mesh frequency as a fault because the line is tall. These lines belong to the design. Judge them against the machine’s own baseline at the same load and flow.
  • Reading gear sidebands from a record too short to separate them. Divide the slowest shaft frequency by the resolution first.
  • Counting orders on the wrong shaft. On a belt drive or a gearbox, name the shaft with every order value.
  • Calling a 100 Hz line “4× running speed”. On machine A, 4× is 97.67 Hz. Twice line frequency is not a whole order, and it vanishes at once when the supply is switched off.
  • Looking for pole pass sidebands at light load. Slip is then small, the sidebands move in towards 1×, and they cannot be separated.
  • Writing “cavitation” for any broadband noise on a pump. Check the suction conditions and the bearing first: the evidence is shared.

Summary



  • A part that repeats an event times per turn gives a line at times its shaft frequency: vane pass 290.0 Hz on pump B, blade pass 67.7 Hz on fan C, gear mesh 410.8 Hz on gearbox D.
  • Belt frequency is , always below both shaft speeds: 4.75 Hz on fan C.
  • A motor on a 50 Hz supply has a line at 100 Hz, and a pole pass frequency of poles times slip frequency: 2.33 Hz on motor A.
  • These lines are normal at a steady low level. Growth, or new sidebands, is the evidence, and each pattern is only consistent with its commonly described causes.
  • The spacing of sidebands round gear mesh frequency equals the frequency of the shaft with the problem. Sidebands 6.04 Hz apart were invisible in a 0.4 s record and clear in a 1.6 s record.

Exercises



1. A pump runs at 1470 rev/min and its impeller has 5 vanes. Find the running frequency and the vane pass frequency.

Answer

and vane pass is (5 orders).

2. A motor at 1460 rev/min has a 125 mm pulley and drives a fan through a 315 mm pulley with a belt 2000 mm long. Find the fan speed and the belt frequency in Hz.

Answer

Fan speed is (9.66 Hz). Belt frequency is per minute, which is 4.78 Hz.

3. A gearbox has a 23-tooth pinion on the input shaft at 1480 rev/min and a 92-tooth gear. Find the gear mesh frequency and the output shaft frequency. Sidebands round the gear mesh line are 6.2 Hz apart. Which shaft is this consistent with?

Answer

Input frequency is , so GMF is . The ratio is 4, so the output turns at 370 rev/min, 6.17 Hz. A spacing of 6.2 Hz is consistent with a problem on the output shaft, which carries the 92-tooth gear.

4. A 6 pole motor on a 50 Hz supply runs at 975 rev/min. Find the slip frequency, the pole pass frequency, and the frequencies of the pole pass sidebands round 1×.

Answer

. Slip frequency is and . With 1× at , the sidebands are at 13.75 and 18.75 Hz.

5. Motor A at full load has a pole pass frequency of 2.33 Hz. At half load its slip is about half. Using the 4 step rule, find the record length needed to separate pole pass sidebands from 1× at full load and at half load.

Answer

At full load . At half load and . The lighter the load, the longer the record.

References



  • R. B. Randall, Vibration-based Condition Monitoring: Industrial, Automotive and Aerospace Applications, 2nd edition, Wiley, 2021.
  • C. Scheffer and P. Girdhar, Practical Machinery Vibration Analysis and Predictive Maintenance, Elsevier Newnes, 2004.
  • ISO 13373-1:2002, Condition monitoring and diagnostics of machines. Vibration condition monitoring. Part 1: General procedures.


© 2021-2026 SiliconWit®. All rights reserved.
Motor 1450 rev/min 24.17 Hz Gearbox pinion 17 T gear 68 T mesh 410.8 Hz at the tooth contact drum 362.5 rev/min 6.04 Hz Conveyor
Conveyor drive D: motor, gearbox and drum
mm/s Hz 0 22.08 1× − fp 24.42 1× 26.75 1× + fp 2.33 Hz each side (pole pass frequency fp) heights show the pattern only
Rotor bar pattern: sidebands round 1× (machine A)
Predict first

A pump impeller has 6 vanes and turns at 2900 rev/min. Where in the spectrum do you expect a line made by the vanes?

cutwater one turn: 6 pulses 6 × 48.33 per second = 290 Hz
Watch it build: the fan and its belt
motor 24.17 Hz 9.67 Hz 7 blades blade pass 7 × 9.67 = 67.7 Hz 7.59 m/s rim speed π × 0.100 m × 24.17 belt 1.6 m 7.59 ÷ 1.6 = 4.75 Hz 4.75 Hz 2 × belt 9.49 Hz, fan 1× 9.67 Hz only 0.18 Hz apart
  1. The fan turns at 580 rev/min, 9.67 Hz. Its 7 blades give blade pass 7 × 9.67 = 67.7 Hz.
  2. The belt moves at the rim speed of the motor pulley: π × 0.100 m × 24.17 = 7.59 m/s.
  3. One turn of the belt is 1.6 m: 7.59 ÷ 1.6 = 4.75 Hz, the belt frequency.
  4. 4.75 Hz is below both shafts. Twice it, 9.49 Hz, is only 0.18 Hz from the fan's 1×.
switch off 100 Hz: gone at once (electrical)1×: falls with the speed (mechanical) time, a few seconds
See it: which shaft, and is the record long enough?

Resolution 1/T
Steps between sidebands
Lines found; spacing read

The signal of Application 2 for gearbox D without its noise: the mesh line at 410.8 Hz, 0.80 mm/s peak, and two pairs of sidebands (0.30 and 0.12 mm/s) spaced at the frequency of the shaft with the problem. The spectrum is computed in your browser from 2560 samples a second with a Hann window, as in the lesson. The thin marks show where the true lines are. A line is counted when it stands above its neighbours and above 0.06 mm/s.

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. An extract fan has 9 blades and turns at 980 rev/min. At what frequency is its blade pass line?

2. A gearbox has a 20-tooth pinion on a shaft at 25 Hz driving a 40-tooth gear at 12.5 Hz. The mesh line is at 500 Hz, and new sidebands appear at 487.5 and 512.5 Hz. Which shaft is the problem consistent with?

3. The slowest shaft of a gearbox turns at 3.0 Hz. With a Hann window and the working rule of 4 steps between lines, what is the shortest record that can show sidebands at that shaft's spacing?

Found this useful?

Discussion

    Comments show your name. Be kind, stay on the topic.