Skip to content
You Start with one site
Amounts in Start with one site
Case file 1 · five episodes · 10 minutes

The valve that cost a year

One question an episode. The next opens when you answer.

Episode 1 of 5

The bill

Answer the episode before this one to open it.

A bottling plant's power bill is up a third. The cooling water pump runs day and night. Someone says: the valve after it has been half closed for years.

Where would you look first?

Episode 2 of 5

Half closed

Answer the episode before this one to open it.

The plant needs 70 m³/h. The pump was bought for 100. So the valve throttles it, and the pump runs at full speed against it.

Of the 10.3 kW the pump draws, how much is burned in the valve?

See it on the simulator →
Episode 3 of 5

The fix

Answer the episode before this one to open it.

A variable-speed drive slows the pump instead. Open the valve fully, and turn the pump down until it gives exactly 70 m³/h.

The plant lifts its water 12 m. Does the drive save the two thirds the cube law promises?

See it on the simulator →
Episode 4 of 5

The price

Answer the episode before this one to open it.

The drive costs [[450000]] installed. The pump runs 6,000 hours a year, and power costs [[20]] per kWh.

How long until the drive has paid for itself?

Episode 5 of 5

Prove it

Answer the episode before this one to open it.

The drive is in. The bill is lower. But production also changed this month, and the weather was cooler.

How do you prove what the drive saved?