Skip to content
You Start with one site
Amounts in Start with one site
Simulator · Pumps and energy

Pump: valve or drive

A valve wastes what the pump pushes. See what a drive saves, in your money.

Found this useful?

Flow needed
With the valve
With the drive
Saved each year
Predict first

This pump lifts water 12 m. At 70% speed, does a drive save as much as the cube law says?

Power at each flow

Design check
Your own pump

These are example numbers. Set them close to your pump, then pass the result to whoever approves the spending, or ask us to check it against your real bills.

Try this
  1. Find the flow at which the drive uses half the power of the valve.
  2. On the borehole lift the drive saves far less than the cube law says. Lower its static head to 30 m: how much does the saving grow?
  3. On the chilled water loop, check that the saving matches the cube law.
How the numbers are worked out

The pump curve is H = H₀ r² − a Q², with r the speed as a share of full speed (the affinity laws). The pipes need H = Hs + k Q²: the static head to lift plus friction. With a valve the pump stays at full speed and the valve adds friction until the flow falls to the one needed; with a drive the pipes are left open and the pump slows until its curve meets the pipe curve at that flow. Power = ρ g Q H / (pump efficiency × motor efficiency), and the drive loses about 3% more. Pump efficiency has its best point at a flow that moves with speed. The cube law holds only when there is no static head: then slowing the pump to r of its speed gives r of the flow at r³ of the power.

The lesson Variable speed drives and the affinity laws works through it, and the concepts affinity laws and duty point explain each idea in five minutes.

Found this useful?

Discussion

    Comments show your name. Be kind, stay on the topic.