Alarm deadband and delay

One idea Beginner 5 min read
Found this useful?

A light switch that is pressed exactly halfway flickers, on, off, on. An alarm set at one limit does the same when a reading hovers near that limit: it starts, clears and starts again, and soon people ignore it. Two rules stop it. Hysteresis (a deadband) uses a lower limit to clear the alarm than to start it. A delay starts the alarm only when the reading stays beyond the limit for a set time.

The staff?People stop reading a channel that is wrong most of the time.Expected
The sensor?The sensor read correctly. The room really was near the limit.Not the cause
The alarm rule?One limit, no deadband and no delay, gives a message for every small crossing.This is the idea

See it

Predict first

A cold room alarm starts above 8.0 °C and clears at or below 8.0 °C. One reading each minute: 7.6, 8.2, 7.8, 8.3, 7.9, 8.1, 7.7 °C. How many alarm messages are sent?

See it: 100 minutes of a cold room record

Alarm messages
Room temperature when the fault is reported
Alarm still on after the room is below 8 °C

The alarm starts when the reading is above 8.0 °C for the whole delay, and clears when it falls below the clear limit. The same readings are used every time; only the two rules change.

The idea

A reading near its limit always has small ups and downs. With one limit, each crossing is a new alarm. The alarm chatters: it switches on and off with the noise, not with any real change.

The deadband gives the alarm two limits. It starts above the alarm limit and clears only below a lower clear limit, so small ups and downs inside the band change nothing.

Tclear = Talarm − deadband

Talarm is the limit that starts the alarm, Tclear the lower limit that clears it, both in °C

The delay asks the reading to stay beyond the limit for a set time before the alarm starts, so a short jump, such as a door opened for one minute, sends nothing at all.

Each rule has a cost. The deadband makes the alarm clear later, some minutes after the room has recovered. The delay makes every real fault arrive later, by the whole delay. Choose both from how fast the product is harmed, not from how quiet the phone should be.

One worked number

The question

The compressor of a cold room stops. The room warms by 0.3 K each minute, and the first reading above the 8.0 °C limit is 8.1 °C. The alarm has a delay of 10 minutes. How warm is the room when the alarm is sent?

Show the worked solution, 2 steps
  1. Find the rise during the delay

    0.3 K a minute × 10 minutes = 3.0 K.

  2. Add it to the first reading

    8.1 + 3.0 = 11.1 °C, 3.1 K above the limit before anyone knows. Check it in the figure: press Delay 10 minutes.

The mistake to avoid

A longer delay is not a safer alarm. It is a quieter one. Every minute of delay is a minute of warming before anyone is told. Use the shortest delay that removes the short jumps, and use a deadband for the hovering.

The same two rules run inside a thermostat, where they stop the compressor switching on and off every few seconds. That control stays in the controller on site, which must work when a network is down.

Check yourself

Question 1

A vaccine fridge has a limit of 5.0 °C. Its door is left open and it warms by 0.5 K each minute. The first reading above the limit is 5.2 °C, and the alarm delay is 4 minutes. What is the temperature when the alarm is sent?

Question 2

An electrical enclosure alarm starts above 30 °C with a deadband of 2 K. The enclosure is at 29 °C, after an alarm. Is the alarm still on?

Question 3

A manager asks for a 30 minute delay on a cold room alarm, to stop the messages at night. What is the main cost?

Where you meet it

  • A cold roomA temperature alarm with a deadband of about 1 K and a short delay that covers a door opening.
  • A thermostatThe compressor starts above the set point and stops below it, so it does not switch every few seconds.
  • A generatorA low fuel alarm with a deadband stops the message repeating as the fuel moves in the tank.
  • An electrical enclosureAn over temperature alert clears only when the enclosure has truly cooled.
Key points
  • One limit makes an alarm chatter when a reading hovers near it.
  • Deadband: clear at a lower limit than the start. Cost: a later clear.
  • Delay: start only after the reading stays beyond the limit. Cost: a later warning of every real fault.
  • Set both from how fast the harm happens.