A light switch that is pressed exactly halfway flickers, on, off, on. An alarm set at one limit does the same when a reading hovers near that limit: it starts, clears and starts again, and soon people ignore it. Two rules stop it. Hysteresis (a deadband) uses a lower limit to clear the alarm than to start it. A delay starts the alarm only when the reading stays beyond the limit for a set time.
See it
A cold room alarm starts above 8.0 °C and clears at or below 8.0 °C. One reading each minute: 7.6, 8.2, 7.8, 8.3, 7.9, 8.1, 7.7 °C. How many alarm messages are sent?
The alarm starts when the reading is above 8.0 °C for the whole delay, and clears when it falls below the clear limit. The same readings are used every time; only the two rules change.
The idea
A reading near its limit always has small ups and downs. With one limit, each crossing is a new alarm. The alarm chatters: it switches on and off with the noise, not with any real change.
The deadband gives the alarm two limits. It starts above the alarm limit and clears only below a lower clear limit, so small ups and downs inside the band change nothing.
Talarm is the limit that starts the alarm, Tclear the lower limit that clears it, both in °C
The delay asks the reading to stay beyond the limit for a set time before the alarm starts, so a short jump, such as a door opened for one minute, sends nothing at all.
Each rule has a cost. The deadband makes the alarm clear later, some minutes after the room has recovered. The delay makes every real fault arrive later, by the whole delay. Choose both from how fast the product is harmed, not from how quiet the phone should be.
One worked number
The compressor of a cold room stops. The room warms by 0.3 K each minute, and the first reading above the 8.0 °C limit is 8.1 °C. The alarm has a delay of 10 minutes. How warm is the room when the alarm is sent?
Show the worked solution, 2 steps
- Find the rise during the delay
0.3 K a minute × 10 minutes = 3.0 K.
- Add it to the first reading
8.1 + 3.0 = 11.1 °C, 3.1 K above the limit before anyone knows. Check it in the figure: press Delay 10 minutes.
The mistake to avoid
The same two rules run inside a thermostat, where they stop the compressor switching on and off every few seconds. That control stays in the controller on site, which must work when a network is down.
Check yourself
A vaccine fridge has a limit of 5.0 °C. Its door is left open and it warms by 0.5 K each minute. The first reading above the limit is 5.2 °C, and the alarm delay is 4 minutes. What is the temperature when the alarm is sent?
An electrical enclosure alarm starts above 30 °C with a deadband of 2 K. The enclosure is at 29 °C, after an alarm. Is the alarm still on?
A manager asks for a 30 minute delay on a cold room alarm, to stop the messages at night. What is the main cost?
Where you meet it
- A cold roomA temperature alarm with a deadband of about 1 K and a short delay that covers a door opening.
- A thermostatThe compressor starts above the set point and stops below it, so it does not switch every few seconds.
- A generatorA low fuel alarm with a deadband stops the message repeating as the fuel moves in the tank.
- An electrical enclosureAn over temperature alert clears only when the enclosure has truly cooled.
- One limit makes an alarm chatter when a reading hovers near it.
- Deadband: clear at a lower limit than the start. Cost: a later clear.
- Delay: start only after the reading stays beyond the limit. Cost: a later warning of every real fault.
- Set both from how fast the harm happens.
Discussion
No comments yet. Questions, results from your own build, a better way to explain it: all welcome.
My notes on this page
Kept on this device only. Nothing is sent anywhere.
Tip: select words in the lesson, or tap a figure or an equation, to put a note right there.
Notes on earlier wording
The lesson has changed and these words are no longer in it. Your notes are kept, with the words you chose.