Simulator · Monitoring

Alarm tuning

An alarm at every door gets ignored. Find the rule that catches the real fault.

Found this useful?

Alarms in the week
False alarms
Fault found after
Stock above 8 °C, unseen
Predict first

Doors warm the room for a few minutes and ring the alarm. What stops that, without missing a real fault?

The alarm rule
Design check
Try this
  1. Find a rule with no false alarms that still finds the fault within 90 minutes.
  2. Make the delay so long that the stock sits above 8 °C before anyone knows.
  3. With a 5 °C limit and no delay, add a deadband. What changes, and what does not?
How the numbers are worked out

The week is made the same way every time: air at about 3 °C, a compressor cycle of about 26 minutes (±0.55 °C), sensor noise, seven door openings on weekdays and two at the weekend (2 to 4.5 °C warmer for a few minutes, cooling back over about 5 minutes), and on day 5 at 14:00 an evaporator fan that stops, so the room drifts up towards 14 °C over a few hours. The alarm is raised when the reading has stayed above the limit for longer than the delay, and cleared when it falls below the limit minus the deadband. An alarm counts as false if it was raised before the fault began. "Stock above 8 °C, unseen" counts the minutes above 8 °C between the fault and the alarm.

The concept alarm deadband and delay explains the two rules in five minutes; the lesson control charts shows how to set a limit from the data instead of by feel.