Data & Statistics · Concept

Degree days

One idea Beginner 5 min read
Found this useful?

A taxi driver who drives twice as far uses about twice the fuel, so you compare fuel per kilometre, not per week. A cooling plant is driven by the weather in the same way: a hot week asks for more cooling than a mild one. Degree days measure how much heating or cooling the weather asked for, added up day by day, so that energy can be compared per unit of weather.

Yes, it uses more?More kWh alone says nothing if the month was hotter.Not enough to know
Compare the mean temperature?A mean hides the hot days that drove the plant.Close, but it misleads
Compare kWh per degree day?Energy for each unit of cooling the weather asked for.This is the idea

See it

Predict first

The daily mean temperatures of one week average 20 °C. The base is 18 °C. How many cooling degree days did the week have?

See it: one week of daily mean temperatures

Degree days, day by day
From the week's mean (wrong)
Mean temperature of the week

Each bar is the mean outdoor temperature of one day. Only the part beyond the base counts, and only on the side that needs the plant: above the base for cooling, below it for heating.

The idea

Below some outdoor temperature a cooling plant is idle. Above it, the cooling energy rises roughly in proportion to how far the day is above that temperature. That temperature is the base temperature. The cooling degree days of one day are how far its mean temperature is above the base, and never less than zero.

CDD = max(T − Tbase, 0)

T is the mean outdoor temperature of the day and Tbase the base temperature, both in °C; add the days to get a week or a month

Heating degree days are the same idea reversed, max(Tbase − T, 0), for a heated building. The base is a property of the building, not a universal number: it is found from the building's own data.

Once the weather is a number, energy can be compared per unit of it. In the office building of the lesson, each cooling degree day adds 41.6 kWh. That slope is what a baseline uses to say what a hot month should have cost.

One worked number

The question

The daily mean temperatures of a week are 16, 19.5, 22, 24.5, 21, 17 and 20 °C. The base is 18 °C. Find the cooling degree days of the week.

Show the worked solution, 3 steps
  1. Subtract the base from each day

    −2, 1.5, 4, 6.5, 3, −1 and 2.

  2. Set the negative days to zero

    A cool day needs no cooling. It does not undo a hot day: 0, 1.5, 4, 6.5, 3, 0 and 2.

  3. Add them

    0 + 1.5 + 4 + 6.5 + 3 + 0 + 2 = 17.0 cooling degree days. Check it in the figure at a base of 18 °C.

The mistake to avoid

Degree days are not the mean temperature minus the base, times the days. That shortcut lets cool days cancel hot ones. For the week above it gives 14 in place of 17.0, and at a base of 20 °C it gives zero for a week that had 7.5. Count each day on its own, then add.

A second trap: do not divide the whole bill by the degree days. Lights and machines use energy whatever the weather, so kWh per degree day is fair only for the part that the weather drives, or inside a baseline model with its base load.

Check yourself

Question 1

A heated building has a base of 15.5 °C. Three days have mean temperatures of 10, 12 and 16 °C. How many heating degree days?

Question 2

A sub-metered cooling plant used 6,000 kWh in a month of 150 cooling degree days, and 6,600 kWh in a month of 200. In which month did it cool more efficiently?

Question 3

A colleague computes degree days to a base of 18 °C for every building, because it is the usual number. What is wrong?

Where you meet it

  • An office chillerIts monthly energy is reported per cooling degree day, so a hot month does not look like a fault.
  • A hotel boilerIn a cold climate the same idea in heating degree days tells a cold winter from a failing boiler.
  • An energy saving claimThe baseline is adjusted to the weather of the reporting period before a saving is calculated.
  • A cold storeIts condenser works harder on hot days, so its energy also follows the degree days.
Key points
  • Cooling degree days of a day = max(T − Tbase, 0). Add the days.
  • Count each day on its own. Never start from the mean of the period.
  • The base temperature belongs to the building and is found from its data.
  • Compare the weather driven energy per degree day, not the whole bill.