Control, Measurement & Energy · Course

Feedback: Open Loop Against Closed Loop

Lesson 1 of 11 24 min read
Found this useful?

A cold room compressor that starts twelve times an hour can fail years before it should, and the stock inside is lost on the night it fails. A pump that runs at one fixed speed gives good pressure at dawn and poor pressure at noon, when every tap is open. In both cases the machine is sound and the way it is controlled is the fault. This lesson shows the difference between a machine that follows a fixed plan and a machine that measures its own result and corrects it. You will calculate how often an on-off controller starts a compressor, and how far a pump’s pressure falls with and without feedback. #ControlEngineering #Feedback #OnOffControl

Learning Objectives

By the end of this lesson, you will be able to:

  1. Distinguish an open loop from a closed loop on real equipment
  2. Name the four parts of a control loop and the five signals on its block diagram
  3. Calculate the cycle time, duty and starts per hour of an on-off controller with a band
  4. Choose direct or reverse action for a given process
  5. Explain what feedback cannot do when the final element reaches its limit

Real-World System Problem: A cold room that starts its compressor too often



A cold room for milk, vaccines or vegetables must stay near 4 °C. Heat enters all day through the walls, through the door each time it opens, and with every warm crate that is carried in. A compressor removes that heat. The compressor in a small cold room has only two states, running or stopped, so the only decision the controller makes is when to switch.

The simplest plan is a timer: run for 7 minutes, rest for 20 minutes. On the day the plan was made it holds 4 °C. On a hot afternoon with the door in use it does not, because the timer does not know the room is warmer. A thermostat does know, because it measures the air. That one measurement is the whole difference between the two methods.

The thermostat brings its own problem. If it switches the compressor the moment the air passes 4 °C in either direction, the compressor starts and stops every few seconds. Each start draws several times the running current and heats the motor windings, and oil that leaves the compressor at start needs running time to return. Makers therefore state a limit, often about 6 starts per hour. The designer must choose a switching band wide enough to respect that limit and narrow enough to protect the stock.

SensorThermostatCompressorCOLDROOM(airnear4°C)doorwarm airEvaporatorenters(cooling)yon/offr=4°Cu
The cold room and its control loop

Fundamental Theory: Measure, compare, correct



Open loop: act on a plan

An open-loop controller sends a command to the machine and does not look at the result. A timer on a compressor, a pump set to one fixed speed, and a heater left at one fixed power are all open loop. The command depends only on the plan.

TimerProcesselementuytime plan
Open loop: nothing comes back from the output

Open loop is cheap and can never become unstable. It is right when the process does not change and nothing disturbs it, as in a conveyor oven that always carries the same product. When the heat load, the demand or the machine changes, the output changes and nothing corrects it.

Closed loop: act on the result

A closed-loop controller repeats three actions without stopping. It measures the output. It compares the measurement with the value that is wanted. It corrects the command to make the difference smaller. Because the measurement travels back from the output to the input, the method is called feedback. A car’s cruise control is a closed loop: it measures the speed and adds fuel when a hill slows the car.

The four parts of a loop

Every control loop, on any machine, has the same four parts.

PartWhat it doesCold roomBooster pump
SensorMeasures the outputAir temperature probePressure transmitter
ControllerCompares and decidesThermostatController inside the drive
Final elementChanges the energy or flow going inCompressor and its contactorVariable speed drive and motor
ProcessThe equipment that is being heldThe room and its airPump, pipe and the water in it

When a loop behaves badly, one of these four parts is the cause. A good technician checks them one at a time and does not start with the controller settings.

The block diagram and its five signals

A block diagram draws each part as a box and each signal as an arrow. This course uses the same five letters in every lesson.

  • is the setpoint, the value that is wanted (4 °C, or 4.0 bar).
  • is the measured process variable, the value the sensor reports.
  • is the error, the difference between the two.
  • is the controller output, in percent from 0 to 100. It is the command to the final element.
  • is a disturbance, anything other than that changes .
SensorProcessFinalelementControllerdreuy(+)-
Closed loop with the five signals

The error

The circle in the diagram is the comparison. The setpoint enters with a plus sign and the measurement enters with a minus sign. A positive error means the process variable is below the setpoint.

Negative feedback

The minus sign at the comparison is the reason the loop works. When rises above , the loop must act to bring down. When falls below , the loop must act to bring up. The correction always opposes the error. This is negative feedback.

If the sign is wrong, the correction pushes in the same direction as the error. The room gets warmer, so the controller stops the compressor, so the room gets warmer still. This is positive feedback, and the output runs to one of its limits and stays there. On a new installation, a loop that goes directly to 0 or 100 percent and stays there usually has the wrong action selected.

Direct and reverse action

The controller cannot know by itself which direction of lowers the error. That depends on the process, and the engineer sets it with one parameter, the controller action.

  • Reverse acting: the output falls when the process variable rises. Heating is reverse acting: a warmer tank needs less heater power. A pump that holds pressure is reverse acting: a higher pressure needs less speed.
  • Direct acting: the output rises when the process variable rises. Cooling is direct acting: a warmer cold room needs more compressor running.

On-off control and the band

The simplest feedback controller has an output with two values, 0 and 100 percent. For the cold room, which is direct acting, the rule could be “run the compressor when the air is above 4 °C, stop it when the air is below 4 °C”. With a real, slightly noisy sensor this rule switches many times a second near 4 °C, and no contactor or compressor survives that.

The cure is a band, also called hysteresis or a differential. The controller uses two switching temperatures in place of one:

  • switch on when the air rises to the upper limit,
  • switch off when the air falls to the lower limit,
  • between the two limits, do not change anything.
Air temperature5 °Cswitch on3 °Cswitch offCompressorONOFFslow warmingfast cooling
On-off control with a 2 °C band

The temperature never settles: it travels up and down inside the band for as long as the machine runs. This is called cycling, and in on-off control it is normal, not a fault.

Cycle time, duty and starts per hour

Let be the width of the band. Let be the rate at which the air cools while the compressor runs, and the rate at which it warms while the compressor is stopped. Both rates are taken as constant, which is a fair model when the band is small.

On-off cycle with a band

Two results surprise new learners. First, the duty does not depend on the band: cancels out of the ratio, and the duty is set by the heat load against the cooling capacity. A narrower band adds no running time; it cuts the same running time into more, shorter pieces.

Second, the starts per hour are inversely proportional to the band: halve the band and the starts double. That is the designer’s trade. A narrow band holds the temperature closely and wears the compressor; a wide band protects the compressor and lets the temperature move further.

Setpoint change and disturbance

A loop is asked to do two different jobs. A setpoint change is a new value of , as when the operator changes the cold room from 4 °C to 2 °C: the loop must move to the new value. A disturbance is a change in , as when the door opens or a tap opens downstream of the pump: the setpoint has not changed, and the loop must hold where it was.

Most industrial loops run at one setpoint for months, so holding against disturbances is their main work. A tuning test that only steps the setpoint has tested the less common job.

What a loop cannot do

Feedback corrects an error only while the final element has something left to give. A pump at 100 percent speed cannot go faster, and a compressor that already runs without stopping cannot cool more. When the output reaches 0 or 100 percent the loop is saturated: it then behaves as an open loop, and the error stays however good the controller is.

Feedback also cannot correct what it does not measure. If the sensor reads 1 °C low, the loop holds the room 1 °C warm with full confidence. And feedback always acts late, because an error must exist before the controller can respond to it.

Application 1: On-off control of a cold room compressor



Step 1: Cycle with the 2 °C band

Click to reveal the cycle calculation
  1. On time. The air must fall through the whole band at the cooling rate.

    The compressor runs for 6.67 minutes in each cycle. ✅

  2. Off time. The air must rise through the whole band at the warming rate.

    The compressor rests for 20.0 minutes in each cycle. ✅

  3. Cycle time.

    One full cycle lasts 26.7 minutes. ✅

  4. Duty.

    The compressor runs for 25 percent of the time, which is 6 hours in every 24. ✅

  5. Starts per hour. There is one start in each cycle.

    This is well below the limit of 6. ✅

Step 2: Narrow the band to 1 °C

Click to reveal the effect of the narrow band
  1. New switching temperatures. The band stays centred on the setpoint: switch on at , switch off at . ✅

  2. New times. Both times halve because the band halved.

    The cycle is half as long as before. ✅

  3. Duty. . The duty is still 25 percent, as the theory said: the band does not change the total running time. ✅

  4. Starts per hour.

    The starts have doubled, from 2.25 to 4.50 per hour. ✅

  5. Smallest band at this load. Six starts per hour means a cycle of 10 minutes.

    At this heat load, any band narrower than breaks the maker’s limit. ✅

Step 3: Test the worst day

The rates in the problem are for one heat load. On a hot day with the door in use, the room warms faster when the compressor is off and cools more slowly when it is on. The limit must hold on that day too.

Click to reveal the worst-case check
  1. Separate the machine from the load. With the compressor on, the net cooling rate is the capacity of the machine minus the heat load. With it off, the warming rate is the heat load alone. So the capacity, written as a rate, is

    and for any load the cooling rate is . ✅

  2. Starts per hour for any load.

    The product is largest when , which is a duty of 50 percent. The compressor starts most often when it runs exactly half of the time. ✅

  3. Worst case value. Put per minute into the expression.

    With the worst case is 3.0 starts per hour. With it is 6.0 starts per hour, exactly on the limit with no margin. ✅

  4. Check a second way. The Python script below steps the room through 4 hours in small time steps and counts the starts. It counts 9 starts with the band and 18 starts with the band, which is 2.25 and 4.50 per hour, and it reports a duty of 25 percent in both cases. The formulas and the simulation agree. ✅

Application 2: A booster pump at fixed speed and under feedback



Step 1: Fixed speed (open loop)

Click to reveal the open-loop result
  1. Nothing reacts. The speed command stays at 60 percent because nothing measures the pressure. ✅

  2. Pressure after the demand rises.

    The building receives 3.4 bar for as long as the demand lasts. The fall of 0.6 bar is called droop. ✅

Step 2: What the loop must do

Click to reveal the required speed
  1. Extra speed needed. The pump must add back the 0.6 bar that the demand removed.

    The speed must rise by 6 percent. ✅

  2. New speed. percent. A loop that holds 4.0 bar exactly must arrive at 66 percent. It finds this value by itself, from the pressure measurement, and nobody has to calculate the demand. ✅

  3. Action. When the pressure rises, the speed must fall. The controller is set to reverse acting. ✅

Step 3: A simple proportional controller

A proportional controller makes the correction in proportion to the error: , with percent per bar.

Click to reveal the closed-loop pressure
  1. Write the pressure at rest. The pressure is the setpoint, minus the fall from demand, plus what the extra speed adds.

    The pressure now depends on the error. ✅

  2. Solve for the error. Use .

    The error at rest is 0.30 bar. ✅

  3. Pressure and speed. bar and percent. Feedback has halved the droop, from 0.6 bar to 0.3 bar. ✅

  4. Why an error remains. This controller raises the speed only while an error exists. With no error it returns to 60 percent, and 60 percent is not enough. So it rests at a compromise. The general result is

    A larger gain leaves a smaller error but never zero. ✅

Step 4: The limit of the pump

Click to reveal the saturation limit
  1. Speed in reserve. From 60 percent the drive can add percent. ✅

  2. Largest fall it can cancel.

    On the straight-line model, a demand that would cost more than 4.0 bar at fixed speed cannot be corrected. ✅

  3. Check with the script. The Python script simulates the pump with its real delay. At fixed speed it ends at 3.400 bar. With the proportional controller it ends at 3.700 bar and 63.0 percent. With a controller that also has integral action it ends at 4.000 bar and 66.0 percent, the speed found in Step 2. All three agree with the hand values. ✅

Verify It in Python



The script calculates the cold room cycle from the formulas, then simulates the room in small time steps and counts the starts. It then simulates the booster pump three ways: at fixed speed, with the proportional controller, and with a proportional and integral controller. The pump model includes the short time the pressure takes to respond, which the hand calculation ignored.

feedback_on_off_and_pump.py
"""On-off cold room (cycle, duty, starts) and a booster pump with and without feedback."""
import numpy as np
import matplotlib.pyplot as plt
# ---------- Part 1: cold room, on-off control with a band ----------
COOL = 0.30 # degC per minute, compressor on
WARM = 0.10 # degC per minute, compressor off
SETPOINT = 4.0 # degC
LIMIT = 6.0 # maker's limit, starts per hour
def cycle_numbers(band, cool=COOL, warm=WARM):
"""Return on time, off time, cycle time (min), duty (%), starts per hour."""
t_on = band / cool
t_off = band / warm
t_cycle = t_on + t_off
return t_on, t_off, t_cycle, 100.0 * t_on / t_cycle, 60.0 / t_cycle
def simulate_room(band, minutes=120.0, dt=0.01, cool=COOL, warm=WARM):
"""Step the room through time and count compressor starts."""
high = SETPOINT + band / 2.0
low = SETPOINT - band / 2.0
n = int(round(minutes / dt))
t = np.arange(n) * dt
temp = np.empty(n)
state = np.zeros(n)
y, on, starts = high, False, 0
for i in range(n):
if not on and y >= high - 1e-9:
on, starts = True, starts + 1
elif on and y <= low + 1e-9:
on = False
temp[i], state[i] = y, 1.0 if on else 0.0
y += (-cool if on else warm) * dt
return t, temp, state, starts
print("Cold room, on-off control")
for band in (2.0, 1.0):
t_on, t_off, t_cyc, duty, sph = cycle_numbers(band)
_, _, state, starts = simulate_room(band, minutes=240.0)
print(f" band {band:.1f} degC: on {t_on:.2f} min, off {t_off:.2f} min, "
f"cycle {t_cyc:.2f} min, duty {duty:.1f} %, starts/h {sph:.2f}")
print(f" simulated over 4 h: {starts} starts, "
f"duty {100.0 * state.mean():.1f} %")
band_min = (60.0 / LIMIT) / (1.0 / COOL + 1.0 / WARM)
print(f" smallest band for {LIMIT:.0f} starts/h at this load: {band_min:.2f} degC")
capacity = COOL + WARM # cooling the machine gives with no heat load
worst_warm = capacity / 2.0 # heat load that gives the most starts
for band in (2.0, 1.0):
*_, sph = cycle_numbers(band, cool=capacity - worst_warm, warm=worst_warm)
print(f" worst load (warming {worst_warm:.2f} degC/min), band {band:.1f} degC: "
f"starts/h {sph:.2f}")
# ---------- Part 2: booster pump, fixed speed against feedback ----------
K, TAU, THETA = 0.10, 3.0, 0.5 # bar per percent, s, s
SP, U0 = 4.0, 60.0 # bar, percent speed
DROOP = 0.6 # bar lost at fixed speed when demand rises
KC = 10.0 # percent per bar, proportional gain
TI = 3.0 # s, integral time for the PI case
def simulate_pump(mode, t_end=60.0, dt=0.01, t_dist=5.0):
"""mode: 'open', 'P' or 'PI'. Returns time, pressure, speed."""
n = int(round(t_end / dt))
delay = int(round(THETA / dt))
t = np.arange(n) * dt
y = np.empty(n)
u = np.full(n, U0)
x = 0.0 # pressure change caused by the speed change, bar
integral = 0.0
for i in range(n):
d = -DROOP if t[i] >= t_dist else 0.0
y[i] = SP + x + d
e = SP - y[i]
if mode == "P":
u[i] = U0 + KC * e
elif mode == "PI":
integral += e * dt
u[i] = U0 + KC * (e + integral / TI)
u[i] = min(100.0, max(0.0, u[i]))
u_delayed = u[i - delay] if i >= delay else U0
x += dt * (K * (u_delayed - U0) - x) / TAU
return t, y, u
print("Booster pump, demand rises at t = 5 s")
results = {}
for mode in ("open", "P", "PI"):
t, y, u = simulate_pump(mode)
results[mode] = (t, y, u)
print(f" {mode:>4}: final pressure {y[-1]:.3f} bar, "
f"final speed {u[-1]:.1f} %, lowest pressure {y.min():.3f} bar")
print(f" hand value, P only: droop {DROOP / (1.0 + K * KC):.3f} bar")
print(f" speed needed to remove the droop: {U0 + DROOP / K:.1f} %")
print(f" largest fall the pump can cancel: {(100.0 - U0) * K:.1f} bar")
# ---------- Plot ----------
fig, ax = plt.subplots(2, 1, figsize=(8, 7))
for band, style in ((2.0, "-"), (1.0, "--")):
t, temp, _, _ = simulate_room(band, minutes=90.0)
ax[0].plot(t, temp, style, label=f"band {band:.0f} degC")
ax[0].axhline(SETPOINT, color="gray", linewidth=0.8)
ax[0].set_xlabel("time (min)")
ax[0].set_ylabel("room temperature (degC)")
ax[0].set_title("Cold room under on-off control")
ax[0].legend()
labels = {"open": "fixed speed", "P": "P control", "PI": "PI control"}
for mode in ("open", "P", "PI"):
t, y, _ = results[mode]
ax[1].plot(t, y, label=labels[mode])
ax[1].axhline(SP, color="gray", linewidth=0.8)
ax[1].set_xlabel("time (s)")
ax[1].set_ylabel("discharge pressure (bar)")
ax[1].set_title("Booster pump when demand rises")
ax[1].legend()
fig.tight_layout()
fig.savefig("feedback_on_off_and_pump.png", dpi=120)
print("Saved feedback_on_off_and_pump.png")

Expected output

Cold room, on-off control
band 2.0 degC: on 6.67 min, off 20.00 min, cycle 26.67 min, duty 25.0 %, starts/h 2.25
simulated over 4 h: 9 starts, duty 25.0 %
band 1.0 degC: on 3.33 min, off 10.00 min, cycle 13.33 min, duty 25.0 %, starts/h 4.50
simulated over 4 h: 18 starts, duty 25.1 %
smallest band for 6 starts/h at this load: 0.75 degC
worst load (warming 0.20 degC/min), band 2.0 degC: starts/h 3.00
worst load (warming 0.20 degC/min), band 1.0 degC: starts/h 6.00
Booster pump, demand rises at t = 5 s
open: final pressure 3.400 bar, final speed 60.0 %, lowest pressure 3.400 bar
P: final pressure 3.700 bar, final speed 63.0 %, lowest pressure 3.400 bar
PI: final pressure 4.000 bar, final speed 66.0 %, lowest pressure 3.400 bar
hand value, P only: droop 0.300 bar
speed needed to remove the droop: 66.0 %
largest fall the pump can cancel: 4.0 bar
Saved feedback_on_off_and_pump.png

The simulated duty of 25.1 percent for the narrow band differs from 25.0 only because 4 hours is not a whole number of cycles. In the lower plot all three pressure curves fall to 3.4 bar at the same instant: the model applies the demand as a sudden step, and no controller can act before the error exists.

Common Mistakes



  • Choosing the narrowest band the thermostat allows “for better control”. The band sets the starts per hour. Calculate the worst-case starts before you narrow it.
  • Believing that a wider band saves energy because the compressor rests longer. In this model the duty is the same for every band, because the heat that enters must still be removed.
  • Selecting the action from the name of the equipment. Ask what the output must do when the measurement rises, then test it in manual before you switch to automatic.
  • Changing controller settings when the output is already at 0 or 100 percent. A saturated loop is an equipment or load problem.
  • Treating cycling in on-off control as a fault to be removed. It is how on-off control works. The engineering task is to choose its size and its frequency.

Summary



  • An open loop acts on a plan and cannot correct a change it does not know about. A closed loop measures the result, compares it with the setpoint and corrects the command.
  • Every loop has a sensor, a controller, a final element and a process, connected by the signals , , , and , with .
  • The correction must oppose the error. The engineer selects reverse action when the output must fall as the measurement rises, and direct action when it must rise.
  • On-off control with a band cycles for ever. The band does not change the duty. It sets the starts per hour, which double when the band is halved and are highest at a duty of 50 percent.
  • Feedback halves, or removes, the pressure droop of a pump without any knowledge of the demand, but only while the drive has speed in reserve.

Exercises



1. A cold room cools at per minute with the compressor on and warms at per minute with it off. The band is . Find the cycle time, the duty and the starts per hour.

Answer

min and min, so the cycle is 20.0 min. The duty is percent and there are starts per hour.

2. State the controller action, direct or reverse, for each loop: (a) an electric heater that holds a tank at 60 °C, (b) a fan that cools an electrical cabinet, with fan speed as the output, (c) a pump that fills a tank and holds its level, with pump speed as the output.

Answer

(a) Reverse: a higher temperature needs less heat. (b) Direct: a higher temperature needs more fan speed. (c) Reverse: a higher level needs less inflow. In each case ask what the output must do when the measurement rises.

3. An electric room heater with a thermostat warms the room at per minute when on. The room cools at per minute when the heater is off. The band is . Find the switching cycles per hour and the duty. Then find the band that limits the relay to 4 cycles per hour.

Answer

min and min. The cycle is 6.0 min, so there are 10 cycles per hour, and the duty is percent. For 4 cycles per hour the cycle must be 15 min, so .

4. The booster pump of Application 2 ( bar per percent, 4.0 bar at 60 percent) meets a larger demand that lowers the pressure by 0.9 bar at fixed speed. Find (a) the speed that restores 4.0 bar, and (b) the pressure and speed held by a proportional controller with percent per bar.

Answer

(a) percent, so the speed is 69 percent. (b) bar, so the pressure is 3.70 bar and the speed is percent.

5. A pipe fails downstream of the same pump. At fixed speed the pressure would fall by 4.6 bar. The controller has integral action, so it raises the speed for as long as an error remains. Using the straight-line model, find the final speed and the final pressure.

Answer

The loop needs percent more speed, which is 106 percent. The drive stops at 100 percent, so it adds only bar. The pressure is bar, with the output saturated. The loop cannot remove the remaining 0.6 bar.

6. A larger cold room has a compressor whose capacity, written as a rate, is per minute. The band is . Find the largest number of starts per hour on any day, and the warming rate at which it happens.

Answer

The worst case is a duty of 50 percent, at a warming rate of per minute. Then min, the cycle is 12.0 min, and there are 5.0 starts per hour. The formula gives the same 5.0.

References



  • K. J. Åström and R. M. Murray, Feedback Systems: An Introduction for Scientists and Engineers, 2nd edition, Princeton University Press, 2021.
  • D. E. Seborg, T. F. Edgar, D. A. Mellichamp and F. J. Doyle, Process Dynamics and Control, 4th edition, Wiley, 2016.
  • K. Ogata, Modern Control Engineering, 5th edition, Prentice Hall, 2010.


© 2021-2026 SiliconWit®. All rights reserved.
Predict first

A thermostat switches a cold room compressor on at 5 °C and off at 3 °C. You halve the band: on at 4.5 °C, off at 3.5 °C. What happens to the fraction of time the compressor runs?

See it: two hours of an on-off thermostat

Time on
Time off
Cycle time
Duty
Starts per hour
Switch on / off

The line is the air temperature. It is made of exact straight pieces, calculated from the two rates. The dashed lines are the two switching temperatures and the dotted line is the setpoint, 4 °C. The strip shows when the compressor runs. The numbers are for the steady cycle. The door opens at 40 minutes. While it is open, heat enters three times as fast, and the thermostat uses the same rule as before.

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. A cold room cools at 0.30 °C per minute with the compressor on and warms at 0.10 °C per minute with it off. With a 2 °C band the compressor starts 2.25 times an hour. A technician sets the band to 0.5 °C "for better control". How many starts per hour are there now?

2. On a hot day the same room warms at 0.20 °C per minute with the compressor off. The machine is the same, so with the compressor on the air now cools at only 0.20 °C per minute. The band is 2 °C. What are the duty and the starts per hour?

3. A cold room is set to switch on at 5 °C and off at 3 °C. On a very hot afternoon the compressor runs without stopping and the air stays at 6 °C. What should the technician do?

Open loop: fixed pedalClosed loop: cruise control slows on the hillholds 80 km/h
2 °C band1 °C band 2 starts4 starts Same running time, cut into shorter pieces
Watch it build: the cold room loop
Compressor Cold room heat in fixed plan Nothing measures the air Thermostat Probe controller final element process sensor r e u y d 4 °C 5 °C + − e = 4 − 5 = −1 °C runs + + air rises, u stays 0 % off
  1. Open loop: the compressor cools the room, heat leaks in, and nothing measures the air.
  2. Closed loop: a probe measures the air, a thermostat compares it and corrects the compressor.
  3. Every loop has the same four parts: sensor, controller, final element, process.
  4. Five signals: setpoint r, error e, output u, measurement y, disturbance d.
  5. Air at 5 °C, setpoint 4 °C: e = 4 − 5 = −1 °C. The correction opposes it: the compressor runs.
  6. Wrong sign: the warmer room stops the compressor, the room warms further, and u stays at 0 %.
Cold room (air near 4 °C) Evaporator (cooling) Sensor door warm air enters Compressor Thermostat y measured air temperature on/off u r = 4 °C setpoint
The cold room and its control loop
Air temperature 3 °C 4 °C 5 °C switch on switch off setpoint slow warming: 0.10 °C per min for 20 min fast cooling, 6.67 min 0.30 °C per min Compressor ON OFF 0 10 20 30 40 50 60 time, min cycle 26.67 min, 2.25 starts per hour
On-off control with a 2 °C band (cold room, Application 1)