First-Order Processes and Dead Time

Lesson 2 of 11 26 min read
Found this useful?

A technician changes a controller setting, sees no change in the temperature after one minute, and changes it again. Twenty minutes later the tank is 8 °C too hot and the high temperature alarm sounds. The controller was not at fault: the tank was slow and the sensor was late, and nobody had measured how slow or how late. This lesson gives you three numbers that describe almost any industrial process, and one simple test that finds them. With those numbers you can predict what the process will do before you touch it. #ControlEngineering #StepTest #DeadTime

Learning Objectives

By the end of this lesson, you will be able to:

  1. Describe a process with three numbers: process gain, time constant and dead time
  2. Calculate the response of a first-order process to a step at any time after the step
  3. Run a step test safely and read the three numbers from the record by two methods
  4. Judge how difficult a loop will be from the ratio of dead time to time constant
  5. Recognise an integrating process, which needs a different model

Real-World System Problem: A hot water tank that answers late



A hot water tank with an electric heater supplies a wash line. The temperature sensor is not in the tank. It is on the outlet pipe, some metres away, where it was easy to fit. When the heater power rises, the water in the tank warms slowly because there is a large mass of it. Then the warmer water must travel along the pipe before the sensor feels anything.

So the tank answers a change in two stages: first nothing happens at the sensor, then the temperature climbs, quickly at the start and more slowly as it nears its new level. To control it well you need three numbers, which are the model of the process: how far the temperature moves for each percent of power, how long the climb takes, and how long the silent stage lasts.

Sensorcold water inTANKoutlet pipeusershot waterHeateryuheater power, 0 to 100 percent
Hot water tank with the sensor on the outlet pipe

Fundamental Theory: Three numbers that describe a process



What a model is for

A model is a short description of how the output of a process answers a change of its input. It does not need to describe the physics inside the tank. It needs to be good enough for three jobs:

  • to predict the response before you make a change,
  • to calculate controller settings in place of guessing them,
  • to compare the process with itself over months, so that a change in the equipment shows as a change in the numbers.

The model in this lesson is simple, and most tuning rules in industry are written for it.

The first-order process

Many processes store one quantity and lose it at a rate that grows with the amount stored. A tank stores heat and loses it with the water that leaves and through its walls. A pipe system stores water under pressure. For such a process the rate of change of the output is proportional to the distance that remains to the final value:

Here is the change of the process variable from its starting value, is the change of the controller output from its starting value, is the process gain and is the time constant. A process that obeys this equation is called first order.

If the controller output is changed in one sudden step of size and then held, the solution is the step response.

Step response of a first-order process

The output moves by in total. It starts at its fastest rate, , and slows continuously as it approaches the final value.

The fraction of the total change that is complete depends only on the number of time constants that have passed.

Time after the response beginsFraction complete
28.3 percent
63.2 percent
86.5 percent
95.0 percent
98.2 percent
99.3 percent

After one time constant the response is 63.2 percent complete, after three 95 percent, and after four 98 percent, when engineers call the process settled. So a tank with needs about 20 minutes to settle after any change.

Process gain, with its units

The process gain is the final change of the process variable divided by the change of the controller output that caused it:

For the tank, the units are °C per percent of heater power. For a pump on a variable speed drive they are bar per percent of speed. Always write the units. A gain of 0.5 has no meaning until you know it is 0.5 °C per percent.

The gain also has a sign. More heater power gives a higher temperature, so the gain is positive. More compressor running in a cold room gives a lower temperature, so the gain is negative.

Dead time

Dead time is the time between a change of the controller output and the first movement of the measured value. Its symbol is . During the dead time the measurement shows nothing at all.

The usual causes are these:

  • Transport. Material must travel from where the change is made to where it is measured. Water moving at needs to cover 12 m of pipe.
  • Sensor position. The same thing, seen from the other side: a sensor fitted far from the process adds dead time that the process itself does not have.
  • Slow instruments. A sensor in a thick protective pocket, an analyser that takes a sample every minute, or a controller that updates slowly.
  • Several small lags in a row. A heating element must warm before the water does, and the water before the sensor does. Each lag is small, and together they look like a delay.

Dead time is the hard part of control because the controller is blind while it lasts: it cannot see the result of any action until has passed, so it must act carefully or it will act too much. A shower with a long pipe shows it: you turn the tap, feel nothing, turn it further, and the water arrives too hot. A long time constant makes a loop slow and safe. A long dead time makes a loop slow and difficult.

First order plus dead time

The two ideas together are the model used in the rest of this course: first order plus dead time, written FOPDT. The output waits for the dead time, then follows the first-order curve.

Dead timewait θFirst ordergain K, τuy
The FOPDT model as two blocks in a row

FOPDT step response

Time is measured from the instant of the step, and is the change from the starting value.

100 %●●●●●●●●●●●●●●63.2 %●● ●●●0 %●●●●0θθ+τtime
Step response with dead time and time constant marked

The step test

The step test, also called a bump test, is the standard way to find , and on real equipment. You put the controller in manual, change its output once, and record the measured value until it settles.

A safe and useful test follows a few rules.

  • Agree the test with the person who is responsible for the process. Know the limits you must not pass, and decide beforehand what you will do if the value approaches one.
  • Make the step in the safe direction first. On a heater, a step down is safer than a step up when the process is near a temperature limit.
  • Make the step large enough to see. The response should be several times larger than the noise on the signal. A step of 5 to 10 percent of output is usual.
  • Make the step in one movement and write the exact time. A slow ramp of the output gives a false dead time.
  • Record faster than the process moves: at least ten readings in one time constant, and several readings inside the dead time if you can.
  • Leave all safety devices in service. A high temperature cut-out or a pressure relief valve is never bypassed for a test.
  • Repeat the step in the opposite direction. If the two results differ, the process is not linear and you should use the result that gives the more careful tuning.

Reading the three numbers from the record

The gain comes directly from the start and end values. For and there are two common methods.

Find the dead time first: it is the time from the step to the first clear movement of the measured value. Then find , the time at which the response has completed 63.2 percent of its total change. The time constant is the difference:

This method is quick and easy to do on a paper chart. Its weak point is the dead time, because the first movement is small and is hidden in noise.

The controllability ratio

The ratio of dead time to time constant, , tells you how difficult the loop will be before you tune anything.

Ratio What to expect
Below about 0.3Easy. The time constant dominates and a standard controller works well.
About 0.3 to 1Moderate. Tuning must be careful and the loop cannot be made fast.
Above about 1Difficult. Dead time dominates and the loop must be tuned slowly.

These limits are a guide from experience and not a law. The idea behind them is exact: no feedback controller can correct a disturbance in less time than the dead time, so the dead time sets the best speed the loop can ever reach.

Self-regulating and integrating processes

All of the above describes a self-regulating process, which settles by itself at a new value after a step. The hot water tank does this because a warmer tank loses more heat, until loss and supply balance.

Some processes never settle. A storage tank whose outflow is set by demand is the standard example. Take a tank of cross-section whose inlet valve passes litres per second for each percent of opening. If inflow and outflow are equal and the valve is opened by 10 percent more, the extra litres per second raises the level at , which is 12 mm per minute, and it continues to rise until the tank overflows. Such a process is called integrating. It has no final value, so it has no process gain in the sense above and no 63.2 percent point. Its model is a rate: here of level for each percent of valve opening. Do not run a long open step test on an integrating process. Make a short step, record the slope, and return the output.

Where the model stops being true

The FOPDT model is a straight-line model around one operating point. The gain of a heater loop changes with the water flow through the tank, the gain of a pump with speed and demand, and the dead time with the flow in the pipe. So a model from a test at one condition is true near that condition only. When the process works over a wide range, test at the two ends of the range and compare.

Application 1: Step test on the hot water tank



Step 1: Process gain

Click to reveal the gain
  1. Confirm that the test finished. The last two readings are 54.8 °C at 1200 s and 55.0 °C at 1800 s. The curve is flat within the 0.1 °C resolution of the record, so 55.0 °C is taken as the final value. ✅

  2. Total changes.

    The temperature moved by 10.0 °C for 20 percent of power. ✅

  3. Process gain.

    Each percent of heater power is worth half a degree at the sensor. ✅

Step 2: The 63.2 percent method

Click to reveal the 63.2 percent method
  1. The 63.2 percent level.

    This level lies between the readings at 300 s (50.8 °C) and 360 s (51.6 °C). ✅

  2. Interpolate for the time. Take a straight line between the two readings.

    The response is 63.2 percent complete at 339 s. ✅

  3. Dead time from the first movement. The reading at 30 s is still 45.0 °C and the reading at 60 s is 45.6 °C. So the table alone says only that the dead time is between 30 s and 60 s. To do better, extend the early slope back to the starting temperature. Between 60 s and 90 s the slope is .

    The dead time is about 40 s. ✅

  4. Time constant.

    The 63.2 percent method gives and . ✅

Step 3: The two-point method

Click to reveal the two-point method
  1. The 28.3 percent level.

    This level lies between the readings at 120 s (47.3 °C) and 150 s (48.1 °C). ✅

  2. Interpolate for the time.

    The response is 28.3 percent complete at 139.9 s. ✅

  3. Time constant. Use from Step 2.

    The time constant is 298.7 s. ✅

  4. Dead time.

    The two-point method gives and . ✅

Step 4: Compare, and find the ratio

Click to reveal the comparison
  1. Side by side. The 63.2 percent method gives . The two-point method gives . They differ by 0.3 s in each number, which is far smaller than the 30 s between readings. ✅

  2. Controllability ratio.

    The ratio is well below 0.3. The time constant dominates, and this is an easy loop if it is tuned with respect for the 40 s of dead time. ✅

  3. Rounded model for use. Report the model to the precision the test supports: per percent, , . ✅

Step 5: Check the model against the record

Click to reveal the check
  1. Predict a reading that was not used. The reading at 600 s played no part in either method. The two-point model predicts

    The record shows 53.5 °C. The model agrees within the rounding of the record. ✅

  2. Check every reading. The Python script below compares each model with all fifteen readings. The largest difference is 0.05 °C for the 63.2 percent method and 0.04 °C for the two-point method. Both are inside the 0.1 °C resolution of the data. ✅

  3. Compare with the source of the data. The readings in this lesson were calculated from an exact model with per percent, and , then rounded to 0.1 °C. The hand methods recover the time constant within about 1.3 s (0.4 percent) and the dead time within 0.3 s. The small differences come from the rounding of the readings and from the straight-line interpolation of a curve. ✅

  4. A third method. The script also fits the model to all fifteen readings by least squares. That fit gives and , slightly further from the source values than the hand methods, because it follows the rounding of the readings. No method recovers more than the data contain. ✅

Application 2: A fast step test on a booster pump



Step 1: Gain and the two levels

Click to reveal the gain and levels
  1. Process gain.

    Each percent of speed is worth 0.10 bar near this operating point. ✅

  2. The two levels.

    These are the two pressures given in the problem, so and . ✅

Step 2: Time constant, dead time and ratio

Click to reveal the model
  1. Time constant.

    The pump loop is 100 times faster than the tank. ✅

  2. Dead time.

    Half a second passes before the pressure moves. On a pump this comes mostly from the drive, which changes speed along a ramp, and from the filter in the pressure transmitter. ✅

  3. Controllability ratio.

    This is an easy loop by the ratio, and close to the tank’s 0.135. ✅

  4. Check with the third reading. At 6.5 s the model predicts

    The log shows 4.43 bar. The model fits a point that was not used to build it, and the script gives the same 4.432 bar. ✅

Verify It in Python



The script creates the step test record of Application 1, applies both hand methods exactly as in the steps, fits all fifteen readings by least squares, and then repeats the pump calculation. It saves one plot of the readings with the two-point model drawn through them.

step_test_identification.py
"""Identify a first order plus dead time model from a step test (hot water tank)."""
import numpy as np
from scipy.optimize import curve_fit
import matplotlib.pyplot as plt
# ---------- True process, used only to make the test data ----------
K_TRUE, TAU_TRUE, THETA_TRUE = 0.5, 300.0, 40.0 # degC per percent, s, s
U0, U1 = 40.0, 60.0 # heater power before and after, percent
Y0 = 45.0 # degC before the step
def fopdt_step(t, K, tau, theta, du=U1 - U0, y0=Y0):
"""Temperature after a step of size du made at t = 0."""
t = np.asarray(t, dtype=float)
rise = K * du * (1.0 - np.exp(-np.clip(t - theta, 0.0, None) / tau))
return y0 + rise
# ---------- The step test record (what the technician writes down) ----------
t_data = np.array([0, 30, 60, 90, 120, 150, 180, 240, 300, 360,
420, 600, 900, 1200, 1800], dtype=float)
y_data = np.round(fopdt_step(t_data, K_TRUE, TAU_TRUE, THETA_TRUE), 1)
print("Step test record: heater 40 to 60 percent at t = 0")
print(" t (s) T (degC)")
for t, y in zip(t_data, y_data):
print(f" {t:5.0f} {y:6.1f}")
def time_at(level):
"""Time at which the record crosses a temperature, by straight-line interpolation."""
return float(np.interp(level, y_data, t_data))
# ---------- Process gain ----------
du = U1 - U0
dy = y_data[-1] - y_data[0]
K = dy / du
print(f"Change in temperature {dy:.1f} degC for {du:.0f} percent: K = {K:.3f} degC per percent")
# ---------- Method 1: 63.2 percent point and the first movement ----------
y63 = y_data[0] + 0.632 * dy
t63 = time_at(y63)
slope = (y_data[3] - y_data[2]) / (t_data[3] - t_data[2]) # between 60 s and 90 s
theta_1 = t_data[2] - (y_data[2] - y_data[0]) / slope # back to the start level
tau_1 = t63 - theta_1
print("Method 1 (63.2 percent)")
print(f" 63.2 percent level {y63:.2f} degC reached at t63 = {t63:.1f} s")
print(f" early slope {slope:.4f} degC/s, dead time = {theta_1:.1f} s")
print(f" tau = {tau_1:.1f} s")
# ---------- Method 2: two points ----------
y28 = y_data[0] + 0.283 * dy
t28 = time_at(y28)
tau_2 = 1.5 * (t63 - t28)
theta_2 = t63 - tau_2
print("Method 2 (two points)")
print(f" 28.3 percent level {y28:.2f} degC reached at t28 = {t28:.1f} s")
print(f" tau = {tau_2:.1f} s, dead time = {theta_2:.1f} s")
# ---------- Check: least-squares fit of all fifteen readings ----------
popt, _ = curve_fit(fopdt_step, t_data, y_data, p0=[K, tau_2, theta_2])
print("Least-squares fit of all readings")
print(f" K = {popt[0]:.3f}, tau = {popt[1]:.1f} s, dead time = {popt[2]:.1f} s")
for name, (k, tau, theta) in (("method 1", (K, tau_1, theta_1)),
("method 2", (K, tau_2, theta_2)),
("least squares", tuple(popt))):
err = fopdt_step(t_data, k, tau, theta) - y_data
print(f" {name:>13}: largest model error {np.abs(err).max():.2f} degC, "
f"ratio theta/tau = {theta / tau:.3f}")
# ---------- Booster pump: two readings from a fast log ----------
p0, p1, du_pump = 4.00, 4.50, 5.0 # bar, bar, percent
t28_p, t63_p = 1.5, 3.5 # s
K_p = (p1 - p0) / du_pump
tau_p = 1.5 * (t63_p - t28_p)
theta_p = t63_p - tau_p
print("Booster pump")
print(f" K = {K_p:.3f} bar per percent, tau = {tau_p:.2f} s, dead time = {theta_p:.2f} s")
print(f" ratio theta/tau = {theta_p / tau_p:.3f}")
p_check = fopdt_step(6.5, K_p, tau_p, theta_p, du=du_pump, y0=p0)
print(f" predicted pressure at 6.5 s = {float(p_check):.3f} bar")
# ---------- Plot ----------
t_fine = np.linspace(0.0, 1800.0, 901)
plt.figure(figsize=(8, 4.5))
plt.plot(t_data, y_data, "o", label="step test readings")
plt.plot(t_fine, fopdt_step(t_fine, K, tau_2, theta_2), label="two-point model")
plt.axhline(y63, color="gray", linewidth=0.8, linestyle="--")
plt.axvline(t63, color="gray", linewidth=0.8, linestyle="--")
plt.xlabel("time since the step (s)")
plt.ylabel("outlet temperature (degC)")
plt.title("Hot water tank: step test and fitted model")
plt.legend()
plt.tight_layout()
plt.savefig("step_test_fit.png", dpi=120)
print("Saved step_test_fit.png")

Expected output

Step test record: heater 40 to 60 percent at t = 0
t (s) T (degC)
0 45.0
30 45.0
60 45.6
90 46.5
120 47.3
150 48.1
180 48.7
240 49.9
300 50.8
360 51.6
420 52.2
600 53.5
900 54.4
1200 54.8
1800 55.0
Change in temperature 10.0 degC for 20 percent: K = 0.500 degC per percent
Method 1 (63.2 percent)
63.2 percent level 51.32 degC reached at t63 = 339.0 s
early slope 0.0300 degC/s, dead time = 40.0 s
tau = 299.0 s
Method 2 (two points)
28.3 percent level 47.83 degC reached at t28 = 139.9 s
tau = 298.7 s, dead time = 40.3 s
Least-squares fit of all readings
K = 0.500, tau = 296.4 s, dead time = 41.7 s
method 1: largest model error 0.05 degC, ratio theta/tau = 0.134
method 2: largest model error 0.04 degC, ratio theta/tau = 0.135
least squares: largest model error 0.05 degC, ratio theta/tau = 0.141
Booster pump
K = 0.100 bar per percent, tau = 3.00 s, dead time = 0.50 s
ratio theta/tau = 0.167
predicted pressure at 6.5 s = 4.432 bar
Saved step_test_fit.png

Common Mistakes



  • Reading the time constant as the time to finish. The response is only 63.2 percent complete after one time constant and needs about four to settle.
  • Ending the test too early. If the value is still climbing, the final value is too low, and then the gain, the 63.2 percent level and the time constant are all wrong together.
  • Measuring time from the wrong instant. All times are counted from the moment the output was stepped, not from the first movement of the measured value.
  • Writing a gain without units, or mixing °C per percent with percent per percent. The number entered into the controller can be wrong by the ratio of the transmitter range.
  • Logging too slowly. If the interval between readings is longer than the dead time, the dead time cannot be read from the record with any confidence.
  • Using a self-regulating model on a tank level. An integrating process has no final value, and a long open step empties or overflows the tank.

Summary



  • A first-order process moves by after a step and is 63.2 percent complete after one time constant, 95 percent after three and 98 percent after four.
  • Dead time is the wait before the measured value first moves. It comes from transport, sensor position and slow instruments, and it limits how fast any loop can be.
  • A step test in manual gives the FOPDT model. The two-point method, and , is the better choice on noisy data.
  • The ratio (0.135 for the tank, 0.167 for the pump) says how difficult the loop is. An integrating process such as a tank level has no such model and is described by a rate.

Exercises



1. A first-order process with no dead time has per percent and . The controller output is stepped by 10 percent. Find the change in temperature after 120 s and after 360 s, and the time at which engineers would call the process settled.

Answer

The total change is . After one time constant it is . After three it is . The process is settled (98 percent) after .

2. A control valve is moved from 30 to 45 percent. The flow rises from 12.0 to 16.5 litres per minute and settles. Find the process gain with its units.

Answer

litres per minute per percent.

3. The temperature sensor of a water heater is on a pipe 6 m from the heater. The water moves at . Find the dead time caused by transport. Find it again if the sensor is moved to 1 m from the heater.

Answer

. At 1 m it is . Moving the sensor removes 12.5 s of dead time.

4. An oven is steady at 180 °C with the heater at 50 percent. The output is stepped to 60 percent and the temperature settles at 204 °C. The response passes 28.3 percent of its change at 95 s and 63.2 percent at 215 s after the step. Find , , and the controllability ratio.

Answer

per percent. . . The ratio is , an easy loop.

5. The hot water tank of Application 1 ( per percent, , ) is steady at 45.0 °C with the heater at 40 percent. The heater is stepped to 55 percent. Find the temperature 340 s after the step, and the time at which the temperature reaches 50.0 °C.

Answer

The total change is . At 340 s, one time constant after the dead time, . For 50.0 °C the response must complete of its change, so and .

6. A storage tank has a cross-section of . Its inlet valve passes 0.04 litres per second for each percent of opening. Inflow and outflow are equal with the valve at 50 percent. The valve is moved to 60 percent and the outflow does not change. Find the rate of rise of the level in mm per minute and the rise after 10 minutes. Say why the 63.2 percent method cannot be used.

Answer

The extra inflow is litres per second. One metre of level holds 2000 litres, so the level rises at , which is 12 mm per minute, and 120 mm after 10 minutes. The level never settles, so there is no final value from which to take 63.2 percent. The process is integrating.

References



  • D. E. Seborg, T. F. Edgar, D. A. Mellichamp and F. J. Doyle, Process Dynamics and Control, 4th edition, Wiley, 2016.
  • K. J. Åström and T. Hägglund, Advanced PID Control, ISA, 2006.
  • K. J. Åström and R. M. Murray, Feedback Systems: An Introduction for Scientists and Engineers, 2nd edition, Princeton University Press, 2021.


© 2021-2026 SiliconWit®. All rights reserved.
Predict first

A tank has a time constant of 300 s and no dead time. The heater power is raised in one step and held. How much of the total temperature change is complete 300 s after the step?

See it: one step, three numbers

Final change, K·Δu
Final value
Time to 63.2 %, θ + τ
Time to 98 %, θ + 4τ
Ratio θ/τ
Fit error (RMS)

The shaded interval is the dead time: the input has changed and the output has not moved. The gold lines mark the 63.2 percent point, which comes one time constant after the dead time ends. The second dot is the 28.3 percent point, at θ + τ/3. These are the two points of the two-point method. The dots of the test data are the readings from the step test in Application 1 and in Application 2 below. The tests used a step of 20 percent on the tank and 5 percent on the pump. The fit error is the root mean square difference between the curve and the readings.

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. A hot water tank has K = 0.5 °C per percent, τ = 300 s and θ = 40 s. It is steady at 45.0 °C. The heater is stepped from 40 to 60 percent. What does the sensor read 340 s after the step?

2. In a step test the response passes 28.3 percent of its total change 50 s after the step, and 63.2 percent 110 s after the step. What are the time constant and the dead time?

3. Loop A is a tank with τ = 300 s and θ = 40 s. Loop B is a small pressure line with τ = 3 s and θ = 2 s. Which loop is more difficult to control?

turned to hot hot water still in the pipe still cold now too hot Turn more while waiting, and it overshoots
θτK step 63 % θ how lateτ how fastK how far
Watch it build: the bump test on the hot water tank
45 °C 40 60 heater output u, % Manual: one step, then wait 55 θ = 40 s 51.3 °C τ = 340 − 40 = 300 s 10 °C K = 0.50 °C/%
  1. Controller in manual. At time 0 the heater output steps once, from 40 to 60 percent.
  2. The tank answers: 45 °C rises toward 55 °C, a change far larger than the noise.
  3. The exact step time matters: for 40 s nothing moves. That is the dead time θ.
  4. 63.2 percent of the change, 51.3 °C, arrives at 340 s, so τ = 340 − 40 = 300 s.
  5. Gain: 10 °C of change for 20 percent of output, K = 0.50 °C per percent.
Tank cold water in Heater u heater power, 0 to 100 percent users outlet pipe, hot water Sensor y some metres of pipe: dead time
Hot water tank with the sensor on the outlet pipe
Dead time wait θ First order gain K, time constant τ u y
The FOPDT model as two blocks in a row
0 % 45.0 °C 63.2 % 51.3 °C 100 % 55.0 °C τ = 300 s 0 θ θ + τ time dead time θ = 40 s 63.2 % at 340 s
Step response with dead time and time constant marked (the tank)