Control, Measurement & Energy · Course

Tuning a PID Loop

Lesson 7 of 11 27 min read
Found this useful?

A temperature loop that was tuned by guessing can swing for an hour after every change, and a loop that was tuned from a textbook table can do the same thing one month later, when the plant has changed a little. In both cases someone switches the controller to manual, and the loop stops earning its cost. Tuning is the work of choosing three numbers so that the loop is fast enough for the job and still has margin when the process is not exactly what the model says. This lesson gives you the three common step-test rules as formulas, tests each one on the same two machines, and shows how to choose between them. #PIDTuning #ProcessControl #LambdaTuning

Learning Objectives

By the end of this lesson, you will be able to:

  1. Calculate PI and PID settings in ISA form from a first order plus dead time model, using the Ziegler-Nichols open-loop rule, the Cohen-Coon rule and the lambda rule
  2. Compare tuning rules by overshoot, settling time, integrated absolute error and the size of the first controller move
  3. Choose the closed-loop time constant for lambda tuning and predict the response it gives
  4. Tune a loop by trial in a safe order when no model is available
  5. Convert a controller gain between engineering units and the dimensionless gain that many controllers ask for

Real-World System Problem: A hot water tank that must not overshoot



A hot water tank with an electric heater supplies a wash line. The controller reads the temperature at the outlet and sets the heater power between 0 and 100 percent. The water takes time to travel from the heater to the sensor, so the sensor sees nothing for 40 seconds after the heater changes. After that the temperature moves slowly, with a time constant of 300 seconds.

heater0-100%PIDKcTiTdtank andpipeK, tau,thetasetpoint rload d(deg C)eu(cold draw)ΣΣ+%-y(degC)outlet sensor
The hot water loop

Whoever tunes this loop must choose. Large settings bring the water to temperature quickly, but throw the heater to full power at every change, and the temperature passes the setpoint before it settles. Small settings are gentle, but recover slowly when a tap opens and cold water enters the tank. Water that is too hot can scald; water that is too cold fails the wash.

Fundamental Theory: From a step test to three numbers



Tuning is a choice between speed and margin

A higher controller gain and a shorter integral time make a loop faster, and the same two changes bring it closer to the point where it oscillates without stopping. The distance from that point is the margin.

Margin matters because the model is never exact: the dead time of a water heater changes with the flow through it, and the process gain with the supply voltage and the inlet temperature. A loop tuned with no margin works on the day of the test and oscillates on another day.

yaggressive: fast, overshoots, ringsrmoderatesluggisht
Three answers to the same setpoint step

The three numbers from a step test

Every rule in this lesson starts from a first order plus dead time (FOPDT) model of the process:

Here is the process gain (change in the measured value per percent of controller output), is the time constant in seconds and is the dead time in seconds. You find the three numbers from a step test with the controller in manual.

y............ final●●●●●●●●●●●●●●●●●●●●●●●●63.2%●●K x (step in u)●●●●●tstepin utautheta
Reading K, tau and theta from a step test

All settings in this lesson are for the ISA standard form of the controller:

is the controller gain in percent of output per unit of the measured value, is the integral time and is the derivative time, both in seconds. If your controller uses the parallel form, convert with , and .

Two ratios appear in every rule. The ratio says how hard the process is to control. The group is the gain scale: every rule gives a controller gain that is this group multiplied by a factor near 1.

Ziegler-Nichols open-loop rule

Ziegler and Nichols published two tables in 1942. This is the first one, the open-loop table, also called the reaction-curve or step-response method. It must not be confused with their second table, which uses the ultimate gain and is given later in this lesson.

Controller
Pnonenone
PInone
PID

The value 3.33 is , as in the original paper. Some books print this table without the process gain , which is correct only when . The table above includes , as Åström and Hägglund write it.

The aim of the rule was a quarter-amplitude decay after a load disturbance: each peak of the oscillation is one quarter of the peak before it. Today this is seen as too oscillatory for most loops, and it leaves little margin.

Cohen-Coon rule

Cohen and Coon (1953) kept the same quarter-amplitude aim but corrected the settings for the ratio . The rule was made for processes with a larger dead time.

Controller
Pnonenone
PInone
PID

When is small the Cohen-Coon gains are close to the Ziegler-Nichols gains and the integral times are shorter, so Cohen-Coon is then the more aggressive of the two.

Lambda tuning

Lambda tuning comes from internal model control (IMC). In place of a fixed response shape, you choose how fast the closed loop should be, as a closed-loop time constant in seconds, and the rule gives the settings that produce it.

Controller
PInone
PID

These are the IMC-based settings for an FOPDT model as tabulated by Seborg and co-authors. With the PI settings, a setpoint step gives a response close to a first-order curve: nothing for the dead time , then a rise with time constant . The measured value reaches 63.2 percent of the step at about and is settled at about .

Choosing lambda

A small gives a fast loop with little margin. A large gives a slow loop with a large margin. Do not choose smaller than the dead time . A common choice is for a tight loop and for a smooth loop that tolerates a poor model.

Lambda tuning has one known weakness: the integral time equals the process time constant, so on a slow process with a short dead time the integral term is slow, and the loop takes a long time to return after a load disturbance.

Ultimate-gain Ziegler-Nichols and why it is aggressive

The second Ziegler-Nichols table needs no model. With integral and derivative switched off, the gain is raised until the loop oscillates with a constant amplitude. That gain is the ultimate gain , and the period of the oscillation is the ultimate period .

Controller
Pnonenone
PInone
PID

A P-only gain of is, by definition, a factor of 2 from the stability limit. The PI row uses and then adds integral action, which adds lag, so less than a factor of 2 remains. The aim is again quarter-amplitude decay, so the loop oscillates several times after each disturbance.

Trial tuning in a safe order

When a step test is not possible, tune by trial: one setting at a time, and one test after each change.

  1. Check in manual that the output moves the process in the expected direction, and set the controller action (reverse acting for heating).

  2. Start with a low gain, a very long integral time and no derivative.

  3. Make a small setpoint step. Raise the gain in steps of about 50 percent until the response is quick with one small overshoot. If the loop begins to oscillate, halve the gain.

  4. Shorten the integral time in steps until the offset is removed in an acceptable time without a new oscillation.

  5. Add derivative only on a slow, clean signal such as temperature, and only if the loop needs it. Begin with a derivative time of about one tenth of the integral time.

  6. Finish with a load test (open a valve, switch a load), because the load response is the one the loop meets every day.

Which loops want which rule

Most pressure, flow and level loops are best served by lambda tuning with PI. Ziegler-Nichols and Cohen-Coon settings are useful as an upper limit: they show the largest gain anyone would try.

The units trap

The formulas above give in percent of output per unit of the measured value, for example percent per °C. Many industrial controllers do not use that unit. They scale the measured value to 0 to 100 percent of the transmitter span, so their gain is dimensionless (percent per percent):

A gain of 7.5 percent per °C with a transmitter ranged 0 to 100 °C is a dimensionless gain of 7.5. With a transmitter ranged 0 to 200 °C the same loop needs a dimensionless gain of 15. Some controllers ask for the proportional band, which is in percent. Some ask for the integral setting in repeats per minute and not in seconds.

Application 1: Three rules on the hot water tank



Step 1: Compute the settings

Click to reveal the settings from each rule
  1. The two groups. The gain scale and the dead time ratio are

    A ratio this small means the process is not hard to control. ✅

  2. Ziegler-Nichols open loop. For PI: , s. For PID: , s, s. ✅

  3. Cohen-Coon, PI.

    ✅

  4. Cohen-Coon, PID.

    ✅

  5. Lambda, PI, with s.

    ✅

  6. Lambda, PID, with s.

    ✅

Rule (percent per °C) (s) (s)
Ziegler-Nichols PI13.50133.20
Ziegler-Nichols PID18.0080.020.0
Cohen-Coon PI13.67104.20
Cohen-Coon PID20.5093.314.2
Lambda PI7.50300.00
Lambda PID10.67320.018.8

Step 2: The first controller move

Click to reveal the first move and the output that is available
  1. What the first move is. At the instant of the setpoint step the error jumps to 5 °C. The integral has not yet added anything, and the derivative acts on the measurement, which has not moved. So the output jumps by percent. ✅

  2. What is available. The heater is at 40 percent, so only percent is available above the operating point. ✅

  3. Compare. Ziegler-Nichols PI asks for percent, Ziegler-Nichols PID for percent, Cohen-Coon PI for percent and Cohen-Coon PID for percent. All four ask for more than the heater has. ✅

  4. Lambda. Lambda PI asks for percent and lambda PID for percent. Both stay inside the limit. ✅

The four quarter-amplitude settings drive the heater to 100 percent for a 5 °C change. At the limit the linear model no longer describes the loop.

Step 3: Simulate and compare

Click to reveal the simulation method and results
  1. Method. The time step is fixed at 0.1 s. The dead time is a buffer of stored samples, so it is exact. The output is limited to 0 to 100 percent and the integral is stopped while the output is at a limit. ✅

  2. Tests. The setpoint steps from 45 to 50 °C at time zero. At 4000 s a load equal to 10 percent of heater power is removed. Without control this load would lower the temperature by °C. ✅

  3. Measures. Overshoot is in percent of the 5 °C step. Settling time is the last time the temperature is more than 2 percent of the step (0.1 °C) from the setpoint. IAE is the area between the temperature and the setpoint, in °C·s. ✅

  4. Results. The table below is the output of the script in the Python section. ✅

RuleFirst move (percent)Overshoot (percent)Settling (s)IAE, setpoint (°C·s)Largest dip, load (°C)Recovery, load (s)IAE, load (°C·s)
Ziegler-Nichols PI67.525.9489515368105
Ziegler-Nichols PID90.016.526743815453
Cohen-Coon PI68.329.2598568376116
Cohen-Coon PID102.521.527940514351
Lambda PI37.54.1243434857400
Lambda PID53.33.1443429774300

For the setpoint step, lambda PI is the best PI loop on every measure: 4.1 percent overshoot (0.2 °C) against 25.9 and 29.2 percent, and it settles in half the time. For the load disturbance the order is reversed. The quarter-amplitude PI settings return to the setpoint in 368 to 376 s. Lambda PI needs 857 s, because its integral time is the full 300 s.

The largest dip changes much less than the recovery time. For the first 40 s after the load arrives the sensor has seen nothing, so no setting can help.

Four of the six rows ask for a first move the heater cannot deliver. Their overshoot in the table is smaller than a simulation without the limit would show, because the limit clips the first move.

Step 4: Test the settings against a wrong model

Click to reveal the test with a dead time of 60 s
  1. Why. At a lower flow the water takes longer to reach the sensor. Suppose the real dead time is 60 s while the settings were computed for 40 s. ✅

  2. Run. The same setpoint step is simulated for 6000 s with no load step. The script reports the peak temperature and the swing (highest minus lowest temperature) in the last 1000 s. ✅

  3. Ziegler-Nichols PI and both Cohen-Coon sets. These never settle. The temperature still swings by 7.07 °C, 7.30 °C and 5.53 °C after 5000 s, and the heater switches between its limits. ✅

  4. Ziegler-Nichols PID. This set settles in the end, but slowly: it is still swinging by more than 1 °C at 2000 s, and the swing has fallen to 0.08 °C after 5000 s. Its peak is 52.2 °C. ✅

  5. Lambda PI and PID. Both settle fully, with peaks of 51.3 °C and 51.2 °C. The overshoot has grown to about 1.3 °C, but the loop is stable. ✅

Step 5: Check one result by hand

Click to reveal the hand check of the load IAE
  1. Idea. After a load step the controller output must end 10 percent higher than before, to replace the lost power. When the loop has settled the error is zero, so the whole change comes from the integral term: . ✅

  2. Rearrange. The integral of the error after the load step is

    ✅

  3. Compare. The lambda PI response does not cross the setpoint during the recovery, so the IAE equals this integral. The simulation gives 400 °C·s, the same value. ✅

  4. Same check for Ziegler-Nichols PI. °C·s. The simulation gives 105 °C·s. It is a little larger because that response oscillates across the setpoint, and IAE counts both sides as positive. ✅

Application 2: Lambda tuning of the booster pump



pumplinePIKc, Tidrivespeedr=4.0bardemand dΣΣy+%bar-pressure transmitter
The pump pressure loop

Step 1: Settings for lambda equal to three dead times

Click to reveal the settings and the predicted response
  1. Choose lambda. s. ✅

  2. Controller gain.

    ✅

  3. Integral time. s. ✅

  4. First move. For a 0.5 bar step the drive speed jumps by percent, from 60 to 67.5 percent. This is well inside the range of the drive. ✅

  5. Predicted response. The pressure reaches 63.2 percent of the step at about s and is settled at about s, with no overshoot. ✅

  6. Simulation. With a time step of 0.001 s the simulation gives 63.2 percent at 2.02 s, a 2 percent settling time of 6.09 s and an overshoot of 0.0 percent. The prediction holds. ✅

Step 2: Double lambda

Click to reveal the effect of the larger lambda
  1. New settings. s gives

    Only the gain changes. The integral time stays at . ✅

  2. Setpoint step. The first move falls to percent. The simulated settling time is 12.11 s, twice the earlier value, and there is still no overshoot. ✅

  3. Load disturbance, s. The pressure dips by 0.204 bar and returns within 0.01 bar of the setpoint after 13.54 s. ✅

  4. Load disturbance, s. The pressure dips by 0.259 bar and returns after 18.58 s. ✅

  5. Check by hand. The load IAE is . For s this is bar·s, and for s it is bar·s. The simulation gives 1.20 and 2.10 bar·s. ✅

Measure s s
(percent per bar)15.008.57
(s)3.03.0
First move for 0.5 bar (percent)7.504.29
Settling time, setpoint (s)6.0912.11
Largest dip, load (bar)0.2040.259
Recovery, load (s)13.5418.58
IAE, load (bar·s)1.202.10

Verify It in Python



The script computes the six settings for the hot water tank, simulates the setpoint step and the load step, repeats the test with a dead time of 60 s, and runs the two lambda settings on the booster pump. It saves one plot.

tuning_rules_compare.py
import numpy as np
import matplotlib.pyplot as plt
def step_test_rules(K, tau, theta, lam):
"""ISA-form settings (Kc, Ti, Td) from an FOPDT model."""
r = theta / tau
a = tau / (K * theta)
return {
"ZN PI": (0.9 * a, 3.33 * theta, 0.0),
"ZN PID": (1.2 * a, 2.0 * theta, 0.5 * theta),
"CC PI": (a * (0.9 + r / 12), theta * (30 + 3 * r) / (9 + 20 * r), 0.0),
"CC PID": (a * (4 / 3 + r / 4), theta * (32 + 6 * r) / (13 + 8 * r),
4 * theta / (11 + 2 * r)),
"Lambda PI": (tau / (K * (lam + theta)), tau, 0.0),
"Lambda PID": ((tau + theta / 2) / (K * (lam + theta / 2)), tau + theta / 2,
tau * theta / (2 * tau + theta)),
}
def simulate(K, tau, theta, Kc, Ti, Td, dr, dd, t_dist, t_end, dt, u_lo, u_hi):
"""Closed loop in deviation variables. Dead time is a ring buffer of
theta/dt samples. Derivative acts on the measurement. The integral
stops while the output is at a limit."""
n, nd = int(round(t_end / dt)), int(round(theta / dt))
buf, pos = np.zeros(nd), 0
a = np.exp(-dt / tau) # exact first-order step
t = np.arange(n) * dt
y_log, u_log = np.zeros(n), np.zeros(n)
y = y_prev = integ = 0.0
for k in range(n):
d = dd if t[k] >= t_dist else 0.0
e = dr - y
u_raw = Kc * (e + integ / Ti - Td * (y - y_prev) / dt)
u = min(max(u_raw, u_lo), u_hi)
if u == u_raw:
integ += e * dt
y_prev = y
y_log[k], u_log[k] = y, u
delayed = buf[pos] # what entered theta seconds ago
buf[pos] = u + d
pos = (pos + 1) % nd
y = a * y + (1 - a) * K * delayed
return t, y_log, u_log
def measures(t, y, dr, t_dist, dt):
band = 0.02 * abs(dr)
sp, ld = t < t_dist, t >= t_dist
overshoot = max(0.0, (y[sp].max() - dr) / dr * 100)
outside = np.where(np.abs(y[sp] - dr) > band)[0]
settle = t[sp][outside[-1] + 1]
iae_sp = np.sum(np.abs(dr - y[sp])) * dt
dev = y[ld] - dr
outside = np.where(np.abs(dev) > band)[0]
recover = t[ld][outside[-1] + 1] - t_dist
return overshoot, settle, iae_sp, dev.min(), recover, np.sum(np.abs(dev)) * dt
# ---------- Plant A: hot water tank, 45 C at 40 percent ----------
K, tau, theta = 0.5, 300.0, 40.0
dr, dd = 5.0, -10.0 # +5 C setpoint, -10 percent load
print("Plant A: K = 0.5 C/percent, tau = 300 s, theta = 40 s, lambda = 40 s")
print(f"{'rule':11s}{'Kc':>7s}{'Ti':>7s}{'Td':>6s}{'move':>7s}{'OS%':>6s}"
f"{'ts':>6s}{'IAE':>6s}{'dip':>7s}{'trec':>6s}{'IAEd':>6s}")
rules_a = step_test_rules(K, tau, theta, lam=40.0)
fig, ax = plt.subplots(2, 1, figsize=(8, 7), sharex=True)
for name, (Kc, Ti, Td) in rules_a.items():
t, y, u = simulate(K, tau, theta, Kc, Ti, Td, dr, dd, 4000.0, 8000.0, 0.1,
u_lo=-40.0, u_hi=60.0)
m = measures(t, y, dr, 4000.0, 0.1)
print(f"{name:11s}{Kc:7.2f}{Ti:7.1f}{Td:6.1f}{Kc * dr:7.1f}{m[0]:6.1f}"
f"{m[1]:6.0f}{m[2]:6.0f}{m[3]:7.2f}{m[4]:6.0f}{m[5]:6.0f}")
ax[0].plot(t, 45 + y, label=name)
ax[1].plot(t, 40 + u)
ax[0].axhline(50, color="k", lw=0.5)
ax[0].set_ylabel("temperature (C)"); ax[0].legend(ncol=3, fontsize=8, loc="lower right")
ax[1].set_ylabel("heater output (percent)"); ax[1].set_xlabel("time (s)")
ax[0].set_title("Plant A: setpoint step at 0 s, load step at 4000 s")
fig.tight_layout(); fig.savefig("tuning_rules_plant_a.png", dpi=120)
# Trial change after the rule: shorter integral time on the lambda PI loop
t, y, u = simulate(K, tau, theta, 7.5, 150.0, 0.0, dr, dd, 4000.0, 8000.0, 0.1,
u_lo=-40.0, u_hi=60.0)
m = measures(t, y, dr, 4000.0, 0.1)
print(f"{'Kc 7.5, Ti 150':15s} OS% {m[0]:.1f}, ts {m[1]:.0f}, dip {m[3]:.2f}, "
f"trec {m[4]:.0f}, IAEd {m[5]:.0f}")
# Same settings, but the real dead time is 60 s, not the 40 s in the model
print("\nPlant A with a real dead time of 60 s (no load step)")
for name, (Kc, Ti, Td) in rules_a.items():
t, y, u = simulate(K, tau, 60.0, Kc, Ti, Td, dr, 0.0, 9e9, 6000.0, 0.1,
u_lo=-40.0, u_hi=60.0)
late = y[t >= 5000.0]
print(f"{name:11s} peak {45 + y.max():5.1f} C, swing after 5000 s "
f"{late.max() - late.min():5.2f} C")
# ---------- Plant B: booster pump, lambda tuning ----------
K, tau, theta = 0.10, 3.0, 0.5
print("\nPlant B: K = 0.10 bar/percent, tau = 3 s, theta = 0.5 s")
print(f"{'lambda':>7s}{'Kc':>7s}{'Ti':>5s}{'move':>6s}{'OS%':>6s}{'ts':>6s}"
f"{'dip':>7s}{'trec':>6s}{'IAEd':>6s}")
for lam in (3 * theta, 6 * theta):
Kc, Ti = tau / (K * (lam + theta)), tau
t, y, u = simulate(K, tau, theta, Kc, Ti, 0.0, 0.5, -6.0, 30.0, 60.0, 0.001,
u_lo=-60.0, u_hi=40.0)
m = measures(t, y, 0.5, 30.0, 0.001)
print(f"{lam:7.1f}{Kc:7.2f}{Ti:5.1f}{Kc * 0.5:6.2f}{m[0]:6.1f}{m[1]:6.2f}"
f"{m[3]:7.3f}{m[4]:6.2f}{m[5]:6.2f}")

Expected output

Plant A: K = 0.5 C/percent, tau = 300 s, theta = 40 s, lambda = 40 s
rule Kc Ti Td move OS% ts IAE dip trec IAEd
ZN PI 13.50 133.2 0.0 67.5 25.9 489 515 -0.88 368 105
ZN PID 18.00 80.0 20.0 90.0 16.5 267 438 -0.65 154 53
CC PI 13.67 104.2 0.0 68.3 29.2 598 568 -0.87 376 116
CC PID 20.50 93.3 14.2 102.5 21.5 279 405 -0.66 143 51
Lambda PI 7.50 300.0 0.0 37.5 4.1 243 434 -1.07 857 400
Lambda PID 10.67 320.0 18.8 53.3 3.1 443 429 -0.76 774 300
Kc 7.5, Ti 150 OS% 24.0, ts 412, dip -1.05, trec 378, IAEd 200
Plant A with a real dead time of 60 s (no load step)
ZN PI peak 53.5 C, swing after 5000 s 7.07 C
ZN PID peak 52.2 C, swing after 5000 s 0.08 C
CC PI peak 53.6 C, swing after 5000 s 7.30 C
CC PID peak 52.8 C, swing after 5000 s 5.53 C
Lambda PI peak 51.3 C, swing after 5000 s 0.00 C
Lambda PID peak 51.2 C, swing after 5000 s 0.00 C
Plant B: K = 0.10 bar/percent, tau = 3 s, theta = 0.5 s
lambda Kc Ti move OS% ts dip trec IAEd
1.5 15.00 3.0 7.50 0.0 6.09 -0.204 13.54 1.20
3.0 8.57 3.0 4.29 0.0 12.11 -0.259 18.58 2.10

The simulation has no sensor noise and a heater that responds at once. Treat the results as a ranking of the rules, and confirm the chosen settings with a small step on the real equipment.

Common Mistakes



  • Using the open-loop Ziegler-Nichols table with numbers from an ultimate-gain test, or the reverse. The two tables take different inputs. Name the table you are using.
  • Entering an ISA gain and integral time into a controller that uses the parallel form, or seconds into a field that expects minutes or repeats per minute. Check the form and the units in the manual first.
  • Forgetting the process gain in the formula, or using a gain in percent per °C in a controller that expects a dimensionless gain based on the transmitter span.
  • Judging a tuning only by the setpoint step. Most loops spend their life rejecting load disturbances, and the two rankings can be opposite, as the hot water tank shows.
  • Making the step test too small to see above the noise, or running it while the load is changing. The model is then wrong and every rule built on it is wrong too.

Summary



  • Tuning is a choice between speed and margin. Each rule is one fixed answer to it.
  • The Ziegler-Nichols open-loop rule and the Cohen-Coon rule aim at quarter-amplitude decay. They recover quickly from load disturbances, ask for large output moves and leave little margin.
  • Lambda tuning lets the engineer choose the closed-loop time constant. For PI the settings are and , and the setpoint response settles at about .
  • On the hot water tank, lambda PI gave 4.1 percent overshoot against 25.9 percent for Ziegler-Nichols PI, and stayed stable when the dead time grew from 40 s to 60 s. Its cost was a load recovery of 857 s against 368 s.
  • The load IAE of a PI loop that does not oscillate is .
  • Before you enter a setting, check the controller form, the time unit and whether the gain is dimensionless.

Exercises



1. The booster pump has bar per percent, s, s. Compute the PI settings by the Ziegler-Nichols open-loop rule. How large is the first move for a 0.5 bar setpoint step?

Answer

percent per bar. percent per bar and s. The first move is percent, against 7.5 percent for lambda tuning with s.

2. For the hot water tank ( °C per percent, s, s), compute lambda PI settings for . Find the first move for a 5 °C setpoint step and the load IAE for a load of 10 percent.

Answer

s. percent per °C, s. First move: percent. Load IAE: °C·s, twice the value for s.

3. A controller needs a dimensionless gain and a proportional band. The tuning result is percent per °C. Find both values for a transmitter ranged 0 to 100 °C, and again for a transmitter ranged 0 to 200 °C.

Answer

Span 100 °C: dimensionless gain , proportional band percent. Span 200 °C: dimensionless gain , proportional band percent. The loop is the same in both cases.

4. An oscillation test on the hot water tank gives an ultimate gain percent per °C and an ultimate period s. Compute the PI and PID settings from the ultimate-gain Ziegler-Nichols table.

Answer

PI: percent per °C, s. PID: percent per °C, s, s. These are close to the open-loop Ziegler-Nichols values (13.5 and 133.2 s for PI).

5. The drive of the booster pump must not move by more than 5 percent for a 0.5 bar setpoint step. Find the smallest that meets this with lambda PI tuning, the settings, the expected settling time and the load IAE for a demand rise equal to 6 percent of speed.

Answer

The first move is , so percent per bar. Then s, so s. Settings: percent per bar, s. Settling at about s (simulation gives 10.1 s). Load IAE: bar·s.

References



  • Åström, K. J. and Hägglund, T., Advanced PID Control, ISA, 2006. Step-response and ultimate-gain forms of the Ziegler-Nichols rules, the Cohen-Coon rule and lambda tuning.
  • Seborg, D. E., Edgar, T. F., Mellichamp, D. A. and Doyle, F. J., Process Dynamics and Control, 3rd edition, Wiley, 2011. IMC-based PID settings for the first order plus dead time model.
  • Ziegler, J. G. and Nichols, N. B., “Optimum settings for automatic controllers”, Transactions of the ASME, vol. 64, 1942.
  • Cohen, G. H. and Coon, G. A., “Theoretical consideration of retarded control”, Transactions of the ASME, vol. 75, 1953.


© 2021-2026 SiliconWit®. All rights reserved.
Predict first

Two people tune the same hot water tank. With setting A a new setpoint is passed by 25.9 percent before the water settles. With setting B it is passed by only 4.1 percent. Someone now opens a tap and cold water enters the tank. Which setting brings the temperature back sooner?

See it: three rules on one loop

RuleOvershootSettling time

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. A step test on the tank gives K = 0.5 °C per percent, τ = 300 s and θ = 40 s. What is the PI gain by the Ziegler-Nichols open-loop rule?

2. The tank has lambda PI settings for λ = 40 s: a gain of 7.5 percent per °C and an integral time of 300 s. The engineer wants a gentler loop and changes λ to 120 s. Which settings change?

3. The settings were computed for a dead time of 40 s. On a day of low flow the real dead time is 60 s. Which PI setting still brings the tank to rest?

lambda = 3θlambda = θZiegler-Nichols PI slowsmoothfast no overshoot4 % over26 % over
Watch it build: three PI rules on one tank
K 0.5 τ 300 s θ 40 s One step test, three numbers θ/τ = 0.13, easy τ ÷ (Kθ) = 15 ruleKc Tiover ZN PI 13.5 133 s26 % CC PI 13.7 104 s29 % λ PI 7.5 300 s4 % After a load: λ PI error area 400, ZN 105
  1. Every rule starts from the step test: K = 0.5 °C per percent, τ = 300 s, θ = 40 s.
  2. θ/τ = 0.13, an easy process. Each rule's gain is the scale τ ÷ (Kθ) = 15 times a factor near 1.
  3. Ziegler-Nichols PI: Kc = 0.9 × 15 = 13.5, Ti = 3.33 × 40 = 133 s. It overshoots 26 percent.
  4. Cohen-Coon PI: Kc = 13.7, a shorter Ti of 104 s, and still more overshoot, 29 percent.
  5. Lambda PI with λ = 40 s: Kc = 300 ÷ (0.5 × 80) = 7.5, Ti = 300 s. Only 4 percent over.
  6. The cost of Ti = τ: after a load the lambda loop returns slowly, error area 400 against 105.
PID Kc, Ti, Td Heater 0 to 100 % Tank and pipe K, τ, θ r (°C) e u (%) y (°C) − + load d (cold draw) outlet sensor
The hot water loop
r 0 y Ziegler-Nichols PI: fast, overshoots 26 %, rings λ = θ: moderate, 4 % λ = 3θ: sluggish, no overshoot 0 400 800 1200 t, s setpoint step at t = 0, hot water tank (plant A)
Three answers to the same setpoint step. Try it on the PID simulator
y, °C 45 51.3 55 final 63.2 % at θ + τ = 340 s K × (step in u) = 0.5 × 20 = 10 °C θ = 40 s τ = 300 s 40 % 60 % step in u at t = 0 t
Reading K, τ and θ from a step test (the tank)
PI Kc, Ti Drive speed Pump line r = 4.0 bar e % y, bar − + demand d pressure transmitter
The pump pressure loop