One phase
Real, Reactive and Apparent Power
On this page
A factory owner reads 72 kW on the energy display and concludes that a 200 kVA transformer is almost empty, then finds that the main cable runs warm and the supplier has billed a demand far above 72. A technician adds the kVA of three loads and orders a cable that is the wrong size. Both mistakes come from treating all electrical power as one quantity. An alternating supply carries three: the power that does work, the power that only travels out and back, and the total that the cables must carry. This lesson separates them, shows what each one means in terms of energy, and adds the loads of a real site the correct way. #ReactivePower #PowerTriangle #ThreePhasePower
Learning Objectives
By the end of this lesson, you will be able to:
- Explain reactive power as energy that leaves the supply and returns in every cycle
- Calculate the real, reactive and apparent power of a single-phase or balanced three-phase load
- Draw the power triangle of a load and read the power factor from it
- Add several loads by their kW and kvar to find the kVA, power factor and line current of a site
- Identify what an electronic meter records in each of its four quadrants
Real-World System Problem: A cold store site with three kinds of load
A cold store, called site E in this course, takes its supply from a 200 kVA transformer (transformer D) at 415 V, three-phase, 50 Hz. At one moment in the working day three groups of load are running: the 22 kW compressor motor at full load, the lighting and sockets, and three smaller motors on fans and conveyors. The energy display on the main board shows 72.2 kW.
That figure is true and it is not enough. The transformer, the main cable and the main breaker are not sized in kW. They are sized by current, and the current depends on a second quantity that the kW display does not show. The motors need a magnetic field to work, and the energy for that field travels from the supply into the motor and back again 100 times every second. This traffic does no work at the shaft, but it is real current in a real cable.
This is why an industrial bill often has a charge for kVA of maximum demand (the highest average kVA over any 30 minutes of the month), and a penalty for a low power factor, in addition to the charge for kWh. To read that bill, or to decide whether one more machine can be added to the transformer, you need all three quantities.
Fundamental Theory: Three kinds of power in one cable
The supply in this course is three-phase, four-wire, 50 Hz, with 415 V between lines and 240 V from line to neutral. These are the nominal figures in Kenya and much of East Africa. The IEC nominal is 400/230 V and many countries use it. Every formula below works for both. All voltages and currents are RMS values unless the text says otherwise.
Power at one instant
Power at any instant is the voltage at that instant multiplied by the current at that instant:
Take one phase, with RMS voltage
Here
The first term is constant. The second term is a wave at twice the supply frequency (100 Hz on a 50 Hz supply) and its mean over a cycle is zero. So the mean power is
For a heater,
The numbers in the drawing are one phase of the compressor motor at full load. The power is negative while the voltage has already crossed zero and the current,
Two parts: one that works and one that only moves
Expand
The first part pulses but never changes sign. Its mean is
The second part has a mean of exactly zero. For a quarter of a cycle it carries energy into the magnetic field of the motor, and for the next quarter the field gives the same energy back. Its peak value is
So reactive power is not power that is used and it is not power that is wasted in the load. It is the size of an exchange of energy between the supply and the load that repeats in every cycle. A motor cannot run without it, because the exchange is what keeps its field alive.
Real, reactive and apparent power
The units W, var and VA are all volts multiplied by amperes. The three names exist to stop people adding quantities that do not add. In practice the values are in kW, kvar and kVA.
By convention, a lagging (inductive) load such as a motor has positive
The power triangle
Because
Power triangle and power factor
The power factor is the share of the apparent power that does work. It has no unit and lies between 0 and 1. Always state whether it is lagging or leading.
Why the supplier cares about kVA
A cable does not know what the current is used for. Its heating is
A site at a power factor of 0.85 puts
Three-phase power
A balanced three-phase load is three equal single-phase loads, so its power is three times the power of one phase. With the phase voltage
Balanced three-phase load
The three-phase total is constant
Add the instantaneous power of the three phases of a balanced load. The constant terms add to
because a phase shift of
Each phase still pulses, and each phase still returns energy for part of its cycle, but the total that reaches the motor is steady. This is why a three-phase motor delivers smooth torque and a single-phase motor of the same size vibrates at 100 Hz.
The steady total does not mean the reactive power has gone. The exchange of energy continues in each phase conductor, and each conductor carries the full current
Adding loads
Energy is conserved, so real power adds: the total
How to add loads
Add kW to kW and kvar to kvar. Find the kVA last. Never add kVA to kVA, and never add or average power factors.
When all the loads have nearly the same power factor, the error from adding kVA is small, and this hides the mistake. When one of the loads is a capacitor, with negative
Measuring three-phase power with two wattmeters
A three-wire load (no neutral) needs only two wattmeters to measure its total power. Each meter has its current coil in one line (a and c) and its voltage coil from that line to the third line (b). The sum of the two readings is the total real power,
What a meter records in each quadrant
An electronic energy meter measures
A site with motors and no generation lives in quadrant 1. A site with too much capacitance connected at light load moves into quadrant 4. A site with solar generation that exceeds its own load moves to the left half, into quadrant 2 or 3.
From these measurements the meter keeps several registers. The kWh register is the integral of
Site E uses
Application 1: The compressor motor from its nameplate
Step 1: Apparent power from voltage and current
Click to reveal the apparent power
-
Choose the formula. The nameplate gives the line voltage and the line current, so use
with 415 V. ✅ -
Apparent power.
The motor loads its cable and the transformer with 28.75 kVA. ✅
Step 2: Real and reactive power
Click to reveal the two sides of the triangle
-
Angle.
, so . The current lags the voltage by . ✅ -
Real power.
This is the electrical input, not the shaft output. ✅
-
Reactive power.
The motor absorbs 15.60 kvar to keep its magnetic field. ✅
-
Check the triangle.
, which is the value of Step 1. ✅
Step 3: Check against the shaft power
Click to reveal the efficiency check
-
Input from the shaft power. The nameplate power of a motor is the mechanical power at the shaft. The electrical input is larger by the losses.
The two routes give 24.15 kW and 24.18 kW. ✅
-
Judge the difference. The values differ by 0.1 percent, which is less than the rounding of the nameplate figures. The nameplate is consistent. This course uses
for this motor. ✅
Step 4: The power of one phase in time
Click to reveal the instantaneous power
-
One phase. The phase voltage is
and the current is 40.0 A, so . ✅ -
Mean.
. Three phases give , the value of Step 2. ✅ -
Highest and lowest values. The power swings by
about the mean.At its lowest point, one phase sends 1.53 kW back to the supply. ✅
-
Share of the cycle with negative power.
The power of one phase is negative for 18.3 percent of every cycle. ✅
-
Check with the script. The Python script below builds the three voltage and current waves point by point and multiplies them. For one phase it finds a mean of 8051 W, a highest value of 17,635 W and a lowest value of -1533 W, negative for 18.25 percent of the cycle. For the sum of the three phases, the lowest and the highest values are both 24,152 W: the total is constant. ✅
Application 2: The whole site from its loads
Step 1: Reactive power of each load
Click to reveal the kvar of each load
-
Method. For each load,
with . ✅ -
Compressor motor.
.This agrees with Application 1, where 24.15 kW gave 15.60 kvar. ✅
-
Lighting and sockets.
.A load close to unity power factor adds little reactive power. ✅
-
Smaller motors.
.This group has the lowest power factor and the most kvar. ✅
Step 2: Add kW and kvar separately
Click to reveal the totals
-
Real power.
This is the value on the energy display. ✅
-
Reactive power.
All three loads are lagging, so all three values are positive. ✅
Step 3: Apparent power, power factor and current
Click to reveal the site totals
-
Apparent power.
The site uses 42.3 percent of the 200 kVA transformer at this moment. ✅
-
Power factor.
The site power factor lies between the best and the worst of its loads, weighted by their size. ✅
-
Line current.
Each of the three line conductors of the main cable carries 117.7 A. ✅
Step 4: Check, and test the wrong method
Click to reveal the checks
-
The wrong method. The kVA of the loads are
, and . Their sum is 85.26 kVA, which is 0.68 kVA more than the true 84.58 kVA. ✅ -
Why the error is small here. The three power factors are close together, so the three triangles point in nearly the same direction. The method is still wrong. Add a 25 kvar capacitor to this site and the true total falls to 74.67 kVA, while the sum of kVA rises to 110.26 kVA. ✅
-
Current at unity power factor. The same 72.2 kW at a power factor of 1.00 needs
. The reactive power adds 17.3 A to the cable and raises the cable heating by a factor of . ✅ -
Check with the script. The Python script computes each load, the totals and the current from the same data. It prints 72.2 kW, 44.05 kvar, 84.58 kVA, a power factor of 0.854 and 117.7 A. ✅
Verify It in Python
The script calculates the compressor motor from its nameplate and the site from its three loads. It then builds the voltage and current of each phase of the motor as sine waves over two cycles, multiplies them point by point, and reports the power of one phase and of the three phases together. The plot shows both powers in time, with the negative spells shaded, and the power triangle of the site.
"""Real, reactive and apparent power: motor A, the site total, and power in time."""import numpy as npimport matplotlib.pyplot as plt
V_L = 415.0 # line voltage, VF = 50.0 # frequency, HzROOT3 = np.sqrt(3.0)
def from_p_and_pf(p_kw, pf): """Return Q (kvar) and S (kVA) of a lagging load from P and power factor.""" phi = np.arccos(pf) return p_kw * np.tan(phi), p_kw / pf
def line_current(s_kva, v_line=V_L): """Line current in A of a balanced three-phase load.""" return s_kva * 1000.0 / (ROOT3 * v_line)
# ---------- Part 1: motor A from its nameplate ----------I_FL, PF_A, P_SHAFT, EFF = 40.0, 0.84, 22.0, 0.91phi_a = np.arccos(PF_A)s_a = ROOT3 * V_L * I_FL / 1000.0p_a = s_a * PF_Aq_a = s_a * np.sin(phi_a)print("Motor A from the nameplate")print(f" phase angle {np.degrees(phi_a):.2f} deg, sin(phi) {np.sin(phi_a):.4f}")print(f" S = {s_a:.2f} kVA, P = {p_a:.2f} kW, Q = {q_a:.2f} kvar")print(f" check: sqrt(P^2 + Q^2) = {np.hypot(p_a, q_a):.2f} kVA")print(f" check: shaft power / efficiency = {P_SHAFT / EFF:.2f} kW")
# ---------- Part 2: the site at one moment ----------loads = [ ("Compressor motor A", 24.2, 0.84), ("Lighting and sockets", 18.0, 0.95), ("Three smaller motors", 30.0, 0.80),]print("Site E at one moment")p_tot = q_tot = s_sum = 0.0for name, p, pf in loads: q, s = from_p_and_pf(p, pf) p_tot, q_tot, s_sum = p_tot + p, q_tot + q, s_sum + s print(f" {name:<21} P {p:5.1f} kW Q {q:5.2f} kvar S {s:5.2f} kVA")s_tot = np.hypot(p_tot, q_tot)pf_tot = p_tot / s_totprint(f" total P = {p_tot:.1f} kW, total Q = {q_tot:.2f} kvar")print(f" S = {s_tot:.2f} kVA, power factor = {pf_tot:.3f} lagging, " f"angle {np.degrees(np.arccos(pf_tot)):.1f} deg")print(f" line current = {line_current(s_tot):.1f} A")print(f" wrong method, adding kVA: {s_sum:.2f} kVA " f"({s_sum - s_tot:.2f} kVA too high)")print(f" current at the same kW and unity power factor: " f"{line_current(p_tot):.1f} A")print(f" share of transformer D (200 kVA): {100.0 * s_tot / 200.0:.1f} %")print(f" cable heating against unity power factor: " f"{(1.0 / pf_tot) ** 2:.2f} times")kwh, pf_month = 42000.0, 0.78kvarh = kwh * np.tan(np.arccos(pf_month))print(f" month: {kwh:.0f} kWh at average power factor {pf_month:.2f} " f"means {kvarh:.0f} kvarh")
# ---------- Part 3: power of motor A in time ----------v_ph = V_L / ROOT3w = 2.0 * np.pi * Ft = np.linspace(0.0, 0.04, 40001) # two cycles, 1 microsecond stepsshift = 2.0 * np.pi / 3.0p_phase = []for k in range(3): v = np.sqrt(2.0) * v_ph * np.sin(w * t - k * shift) i = np.sqrt(2.0) * I_FL * np.sin(w * t - k * shift - phi_a) p_phase.append(v * i)p_one = p_phase[0]p_three = p_phase[0] + p_phase[1] + p_phase[2]dt = t[1] - t[0]one_cycle = t < 0.02e_back = -np.sum(p_one[one_cycle & (p_one < 0.0)]) * dtprint("Power of motor A in time")print(f" phase voltage {v_ph:.1f} V, V I = {v_ph * I_FL:.0f} VA per phase")print(f" one phase: mean {p_one[one_cycle].mean():.0f} W, " f"highest {p_one.max():.0f} W, lowest {p_one.min():.0f} W")print(f" one phase is negative for {100.0 * np.mean(p_one[one_cycle] < 0.0):.2f} % " f"of the cycle (phi / 180 deg = {100.0 * np.degrees(phi_a) / 180.0:.2f} %)")print(f" energy returned by one phase in one cycle: {e_back:.2f} J")print(f" three phases together: lowest {p_three.min():.0f} W, " f"highest {p_three.max():.0f} W")
# ---------- Plot ----------fig, ax = plt.subplots(2, 1, figsize=(8, 7))ms = t * 1000.0ax[0].plot(ms, p_one / 1000.0, label="one phase")ax[0].plot(ms, p_three / 1000.0, label="three phases together")ax[0].fill_between(ms, p_one / 1000.0, 0.0, where=p_one < 0.0, alpha=0.4, label="energy going back")ax[0].axhline(0.0, color="gray", linewidth=0.8)ax[0].set_xlabel("time (ms)")ax[0].set_ylabel("power (kW)")ax[0].set_title("Motor A at full load: power in time")ax[0].legend(loc="center right")start = 0.0for name, p, pf in loads: ax[1].bar(0, p, bottom=start, width=0.5) ax[1].text(0.3, start + p / 2.0, name, va="center") start += pax[1].plot([1.5, 1.5 + p_tot / 40.0], [0.0, 0.0], "k-")ax[1].plot([1.5 + p_tot / 40.0] * 2, [0.0, q_tot], "k-")ax[1].plot([1.5, 1.5 + p_tot / 40.0], [0.0, q_tot], "k--")ax[1].text(1.6, q_tot + 4.0, f"S = {s_tot:.1f} kVA, pf {pf_tot:.3f}")ax[1].text(1.5 + p_tot / 40.0 + 0.05, q_tot / 2.0, f"Q = {q_tot:.1f} kvar")ax[1].set_xlim(-0.5, 4.5)ax[1].set_xticks([])ax[1].set_ylabel("kW (bar) and kvar (triangle side)")ax[1].set_title("Site E: kW by load, and the power triangle of the total")fig.tight_layout()fig.savefig("power_triangle_site.png", dpi=120)print("Saved power_triangle_site.png")Expected output
Motor A from the nameplate phase angle 32.86 deg, sin(phi) 0.5426 S = 28.75 kVA, P = 24.15 kW, Q = 15.60 kvar check: sqrt(P^2 + Q^2) = 28.75 kVA check: shaft power / efficiency = 24.18 kWSite E at one moment Compressor motor A P 24.2 kW Q 15.63 kvar S 28.81 kVA Lighting and sockets P 18.0 kW Q 5.92 kvar S 18.95 kVA Three smaller motors P 30.0 kW Q 22.50 kvar S 37.50 kVA total P = 72.2 kW, total Q = 44.05 kvar S = 84.58 kVA, power factor = 0.854 lagging, angle 31.4 deg line current = 117.7 A wrong method, adding kVA: 85.26 kVA (0.68 kVA too high) current at the same kW and unity power factor: 100.4 A share of transformer D (200 kVA): 42.3 % cable heating against unity power factor: 1.37 times month: 42000 kWh at average power factor 0.78 means 33696 kvarhPower of motor A in time phase voltage 239.6 V, V I = 9584 VA per phase one phase: mean 8051 W, highest 17635 W, lowest -1533 W one phase is negative for 18.25 % of the cycle (phi / 180 deg = 18.26 %) energy returned by one phase in one cycle: 3.71 J three phases together: lowest 24152 W, highest 24152 WSaved power_triangle_site.pngOne phase of the motor returns only 3.71 J in each cycle, in two short spells. It matters because the current that carries this exchange flows through the whole length of the cable.
Common Mistakes
- Adding the kVA of several loads, or averaging their power factors. Add kW, add kvar with its sign, and calculate kVA and power factor from the two totals.
- Reading the kW on a motor nameplate as the power it takes from the supply. The nameplate kW is the shaft output. Divide by the efficiency to get the input.
- Using
with the phase voltage of 240 V, or 3 with the line voltage of 415 V. - Saying that reactive power is wasted energy. The load does not consume it and the kWh register does not count it. Its cost is the extra current, with the extra heating and voltage drop that the current causes in cables and transformers.
- Sizing a cable, a breaker or a generator from kW alone. These are sized by current, so start from kVA.
- Treating one reading of power factor as the power factor of the site. It changes with the load through the day, and the bill uses the average or the value at the maximum demand.
Summary
- Instantaneous power is
. When the current lags the voltage, the power of each phase is negative for part of every cycle, and energy returns to the supply. - Real power
in kW is the mean rate of energy conversion. Reactive power in kvar is the peak rate of the exchange that keeps magnetic fields alive. Apparent power in kVA is voltage multiplied by current, and it is what the conductors carry. - The three form a right-angled triangle:
and . - For a balanced three-phase load,
, and the total instantaneous power is constant. - Loads add by kW and by kvar. The compressor motor takes 24.15 kW, 15.60 kvar and 28.75 kVA, and the three loads of site E together take 72.2 kW, 44.05 kvar and 84.58 kVA at a power factor of 0.854 and 117.7 A.
- A meter sorts energy into four quadrants by the signs of
and , and the month’s average power factor comes from its kWh and kvarh registers.
Exercises
1. A single-phase motor on a 240 V supply takes 8.0 A at a power factor of 0.70 lagging. Find
Answer
2. A balanced three-phase load on a 415 V supply takes a line current of 65 A at a power factor of 0.88 lagging. Find
Answer
3. A load has a power factor of 0.60 lagging. For what share of each cycle is the instantaneous power of one phase negative? Compare with the compressor motor.
Answer
4. A workshop runs a 40 kW motor load at a power factor of 0.70 lagging and 25 kW of heaters at unity power factor, on 415 V. Find the total
Answer
5. A 25 kvar capacitor is connected at the main board of site E at the moment of Application 2 (72.2 kW and 44.05 kvar). A capacitor has
Answer
6. Two wattmeters on a balanced three-wire motor read
Answer
References
- S. J. Chapman, Electric Machinery Fundamentals, 5th edition, McGraw-Hill, 2012.
- J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and Design, 6th edition, Cengage Learning, 2017.
- A. Hughes and B. Drury, Electric Motors and Drives: Fundamentals, Types and Applications, 5th edition, Newnes, 2019.
A 24 kW heater (power factor 1.0) and a motor that takes 24 kW at power factor 0.84 run on the same 415 V supply. Which one draws more current from the supply?
One phase of the compressor supply: 239.6 V and 40.0 A rms at 50 Hz, two cycles (40 ms). The grey line is the voltage, the dark line the current, and the gold line their product, the power of that phase. Its mean is the real power. The shaded parts below zero are energy that goes back to the supply. The three-phase readouts multiply one phase by three.
Check yourself
Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.
1. A workshop runs a 40 kW motor load at power factor 0.80 and a 20 kW heater at power factor 1.00. What is the total apparent power?
2. A three-phase motor takes 15 kW of electrical input at 415 V and power factor 0.80. What line current does it draw?
3. A lightly loaded motor runs at power factor 0.50. For what share of each cycle is the power of one phase below zero?
- Phase a of the motor pulses at 100 Hz between 17.6 and −1.5 kW. Its mean is 8.05 kW.
- Phase b is the same pulse, one third of a 50 Hz period later.
- Phase c follows. At 100 Hz the three are 240° apart, so their swings cancel.
- The sum is 3 × 8.05 = 24.2 kW at every instant, so the torque is smooth.
- The exchange in each phase continues: every line still carries the full 40 A.
Discussion
No comments yet. Questions, results from your own build, a better way to explain it: all welcome.
My notes on this page
Kept on this device only. Nothing is sent anywhere.
Tip: select words in the lesson, or tap a figure or an equation, to put a note right there.
Notes on earlier wording
The lesson has changed and these words are no longer in it. Your notes are kept, with the words you chose.