Thermocouples and the Cold Junction

Lesson 4 of 10 26 min read
Found this useful?

A generator exhaust that reads 417 °C looks healthy, but the engine is at 450 °C and overloaded. Nothing is broken: thermocouple, cable and instrument all work, but the instrument was never told the temperature of its own terminals. In another plant a technician repairs a damaged thermocouple cable with ordinary copper wire, and from that day the reading is 44 °C low. Both faults have one cause, often taught wrongly: a thermocouple does not measure its tip, it measures the difference between the tip and the terminals. This lesson explains where the voltage comes from and how to convert it to a temperature in the right order. #Instrumentation #Thermocouple #ColdJunction

Learning Objectives

By the end of this lesson, you will be able to:

  1. Explain the Seebeck effect correctly, including where along the circuit the voltage is generated
  2. Calculate the voltage of a type K thermocouple from the ITS-90 reference function for any tip and terminal temperature
  3. Apply cold junction compensation in the right order, and find the error of the two common wrong methods
  4. Predict the error from copper wire in the run, reversed polarity and a wrong terminal temperature
  5. Choose a thermocouple type, cable and junction style for a given duty

Real-World System Problem: Exhaust temperature of a diesel generator



The exhaust temperature of a diesel generator is one of the best single signs of its health. At a given electrical load a healthy engine has a known exhaust temperature. A rise at the same load means more fuel for the same work: a blocked air filter, a worn injector or a failing turbocharger. Above the maker’s limit, valves and the turbocharger are damaged.

The exhaust runs near 450 °C, too hot for most sensors and well inside the range of a thermocouple. A sheathed type K thermocouple is fitted into the exhaust pipe, and its two wires run to an instrument in the control enclosure, where the terminals sit at about 35 °C.

The signal is very small, about 17 mV for the 415 °C between tip and terminals, or about 41 µV per degree, and it depends on both temperatures. An instrument that does not know its terminals are at 35 °C, or corrects for them the wrong way, gives a steady, believable and wrong reading.

terminals at 35 °Cinstrument readsabout 17 mVexhaust pipe, gas at 450 °Csheathed type Ktwo wires, + and -(thermocouple cable)control enclosure
Exhaust thermocouple and its instrument

Fundamental Theory: A voltage from a temperature difference



The Seebeck effect, told correctly

Hold the two ends of one metal wire at different temperatures. Electrons at the hot end have more energy and spread toward the cold end until a small voltage builds and stops them: the Seebeck effect. The voltage appears only in the parts of the wire where the temperature changes, as a road loses height only where it slopes. A part at one even temperature generates nothing.

The size of the effect is described by the Seebeck coefficient of the material, in µV per °C. A short piece of wire with a temperature change along it generates

One wire alone cannot be used: the voltmeter needs a second wire, and a second wire of the same metal passes through the same temperatures and generates the same voltage in the opposite direction around the loop, so the total is zero. A thermocouple therefore uses two different metals, A and B, with different Seebeck coefficients, joined at the hot end. The voltmeter sees the difference between what each wire generates:

Voltage of a thermocouple

Here is the temperature of the joined end (the measuring junction), is the temperature of the open ends at the instrument terminals (the cold junction or reference junction), and is the Seebeck coefficient of the pair, about 41 µV per °C for type K.

tipwireinthewallterminals450 °Ctemperature falls35 °Co +wire A (nickel-chromium)Vwire B (nickel-aluminium)o -no voltagevoltage generatedno voltageherehere, along bothwhere the(one point)wireswires are atone temperature
Where the voltage is generated

Three practical results follow from the correct explanation.

  1. A thermocouple measures a difference. The voltage depends on and on . The tip alone decides nothing.
  2. The wire in the temperature gradient is the sensor. If the wires are uniform, only the two end temperatures matter, not the path between them. Wire that is damaged, contaminated or of the wrong alloy where the temperature changes gives a wrong reading, however good the tip is.
  3. A third metal does no harm if both its ends are at the same temperature. A brass terminal or a copper track at one even temperature generates nothing. With its ends at different temperatures it does harm, because it replaces thermocouple wire in the gradient.

The reference function

The Seebeck coefficient of a real pair changes with temperature, so the voltage is not a straight line. The standards therefore give, for each thermocouple type, a reference function : the voltage of the pair with the measuring junction at and the terminals at exactly 0 °C. The functions are published in NIST Monograph 175 on the ITS-90 temperature scale (the International Temperature Scale of 1990, the agreed definition of temperature that every calibration follows), and the same functions are used in IEC 60584-1.

For type K above 0 °C the function is a polynomial of degree nine plus one exponential term:

with in mV and in °C. Below 0 °C it is a polynomial of degree ten with no exponential term. Nobody evaluates this by hand. Use the printed table, or the script in this lesson, which contains all the coefficients. A few values that this lesson needs:

(°C)03580100410420450500
(mV)0.0001.4073.2674.09616.82017.24318.51620.644

Because the integral from the terminals to the tip is the integral from 0 °C to the tip minus the integral from 0 °C to the terminals, the voltage at real terminals is a difference of two table values.

Voltage at the terminals

Cold junction compensation in the right order

The instrument measures and wants . Rearranging the result above gives . So the instrument must measure the temperature of its own terminals with a separate sensor (a small thermistor or Pt100 in the terminal block), and then work in this order:

add voltagesconvert mVto °Cconvert to mVE(t_term)terminal sensorthermocouplet_term = 35 °CV measured (mV)t_hot
Cold junction compensation: the right order

Cold junction compensation

  1. Convert the terminal temperature to a voltage with the reference function: .
  2. Add it to the measured voltage: .
  3. Convert the sum back to a temperature with the inverse of the reference function.

The tempting short method, converting to a temperature and then adding in degrees, is wrong because the function is curved. For type K the slope is 40.9 µV per °C at 35 °C and 42.5 µV per °C at 450 °C, so 35 °C at the terminals is not worth the same voltage as 35 °C at the tip. The mistake costs one or two degrees for type K and far more for strongly curved types such as S or B. Add voltages, never temperatures.

Types and their ranges

The standards define several pairs of metals, each with a letter. The table gives typical ranges and sensitivities near room temperature; exact limits depend on the wire diameter and sheath, so take them from the maker.

TypeMetals (positive / negative)Typical working rangeTypical sensitivity near 25 °C
Knickel-chromium / nickel-aluminium−200 to 1200 °C41 µV per °C
Jiron / copper-nickel−40 to 750 °C52 µV per °C
Tcopper / copper-nickel−200 to 350 °C41 µV per °C
Enickel-chromium / copper-nickel−200 to 900 °C61 µV per °C
Nnickel-chromium-silicon / nickel-silicon−200 to 1200 °C27 µV per °C
Splatinum-rhodium / platinum0 to 1600 °C6 µV per °C

Type K is the general industrial choice: cheap, wide in range and good in oxidising gas such as engine exhaust. Type T suits cold and damp work. Type N is more stable than K at high temperature. Type S is costly with a very small signal, but stable enough for furnaces and reference work.

The tolerance of the wire comes from IEC 60584-1. For type K, class 1 is ±1.5 °C or ±0.4 percent of the temperature in °C, whichever is greater, from −40 °C to 1000 °C; class 2 is ±2.5 °C or ±0.75 percent. At 450 °C a new class 1 thermocouple may be wrong by . A thermocouple is less exact than a Pt100 and is chosen for range, small size and strength, not accuracy. Type K wire also changes slowly when held hot for a long time, so an old exhaust thermocouple can be several degrees away from the table (a typical figure, not a standard one).

Extension cable and compensating cable

The run from the sensor head to the instrument can be tens of metres, and thermocouple-grade wire is expensive. Two kinds of cheaper cable exist for this run.

  • Extension cable is made from the same alloys as the thermocouple, to a wider tolerance and for a limited temperature range. For type K it is marked KX.
  • Compensating cable is made from different, cheaper alloys that give nearly the same voltage as the thermocouple over a limited range of temperature, typically up to 100 °C or 200 °C. For type K it is marked KCA or KCB.

Both exist because the cable between the sensor head and the instrument terminals lies in a temperature gradient, so it is part of the sensor. Ordinary copper there generates nothing, and the voltage that part of the run should add is lost. Application 2 calculates how much.

Common wiring faults

  • Reversed at one place. If the two wires are exchanged at the instrument, the voltage changes sign. The indication falls when the process gets hotter. This fault is easy to see.
  • Reversed at two places. If an extension cable is reversed at both ends, the exchanges cancel for the thermocouple but not for the cable: the voltage the cable should add is subtracted. The reading looks reasonable and is low by about twice the temperature difference along the cable. This fault is hard to see.
  • Copper wire in the run. The voltage the replaced length should generate is lost; the error nearly equals the temperature difference between the two ends of the copper.
  • Wrong type selected in the instrument. A type K thermocouple read as type J gives an error that grows with temperature. Check the type setting first.

Noise and grounded junctions

A signal of 41 µV per °C is easy to disturb: interference of only 0.1 mV is an error of 2.4 °C. Use screened twisted pair with the screen earthed at one end only, keep it away from power and drive cables, and use an input with a filter that rejects the mains frequency.

A sheathed thermocouple is sold with one of three junction styles.

  • Grounded junction: the wires are welded to the tip of the sheath. The response is fast, but the measuring circuit is connected to the metal of the machine. If the instrument input is also earthed, a current can flow between the two earth points through the thermocouple wires and add a false voltage. A grounded junction needs an isolated input.
  • Ungrounded (insulated) junction: the wires are insulated from the sheath. The response is slower, and the circuit is free of the machine’s earth: the safer choice on a generator or near a variable speed drive.
  • Exposed junction: the wires extend beyond the sheath. It is the fastest and the least protected, for clean dry gas only.

A thermocouple also fails in a known way: the wire breaks and the circuit opens. A good instrument tests for this and drives its indication to the top or bottom of the scale, so a broken sensor cannot pass as a normal temperature.

Application 1: Exhaust at 450 °C with the terminals at 35 °C



Step 1: The voltage at the terminals

Click to reveal the measured voltage
  1. Voltage of the pair. The wires pass from 450 °C at the tip to 35 °C at the terminals.

    The instrument measures 17.109 mV. ✅

  2. Sense check. The difference is 415 °C at about 41 µV per °C, which is about 17 mV. The value is of the right size. ✅

Step 2: Compensation in the right order

Click to reveal the correct conversion
  1. Convert the terminal temperature to a voltage. mV. ✅

  2. Add the voltages.

    This is the voltage the pair would give with its terminals at 0 °C. ✅

  3. Convert back. In the table, 18.516 mV is 450 °C.

    The right order returns the true temperature. ✅

Step 3: Compensation forgotten

Click to reveal the error with no compensation
  1. Convert the measured voltage directly. The instrument treats 17.109 mV as if the terminals were at 0 °C. This value lies between and . Interpolate.

    The instrument indicates 416.8 °C. ✅

  2. Error.

    The reading is 33.2 °C low. ✅

  3. Why it is not exactly 35 °C. The missing 1.407 mV was generated near 35 °C at 40.9 µV per °C, but is converted near 450 °C, where one degree is worth 42.4 µV. So . ✅

Step 4: Compensation by adding temperatures

Click to reveal the error of the short method
  1. Convert the voltage first, then add the terminal temperature.

    The short method indicates 451.8 °C. ✅

  2. Error.

    The reading is 1.8 °C high. ✅

  3. Compare with the tolerance. The class 1 tolerance at 450 °C is the greater of 1.5 °C and . The wrong order of two additions adds as much error as the standard allows for the whole thermocouple. ✅

Step 5: Check the answer a second way

Click to reveal the check
  1. The script. The Python script below uses the full reference function and a numerical inverse, with no interpolation. It prints 17.109 mV, then 450.00 °C for the right order, 416.83 °C (error −33.17 °C) with no compensation and 451.83 °C (error +1.83 °C) for added temperatures. The hand values agree. ✅

  2. The limiting case. With the terminals at 0 °C, and all three methods give the same answer. They differ only because the terminals are not at 0 °C, and more as the enclosure gets hotter. ✅

Application 2: A copper repair in the cable run



tipjunction boxterminals450 °C80 °C35 °Ctype Kcoppero +Vtype Kcoppero -generatesgeneratesE(450) - E(80)nothing
Copper cable replaces part of the run

Step 1: The voltage that arrives

Click to reveal the voltage at the instrument
  1. Thermocouple section. From the tip to the box the wires are type K and pass from 450 °C to 80 °C.

    This section generates 15.249 mV. ✅

  2. Copper section. Both cores are one metal and pass through the same temperatures, 80 °C to 35 °C, so their small voltages cancel around the loop.

    The copper adds nothing. ✅

  3. Voltage at the terminals. mV. With thermocouple cable all the way it would be 17.109 mV. The copper has lost mV. ✅

Step 2: The indication and the error

Click to reveal the error
  1. The instrument compensates for 35 °C.

    The instrument converts 16.656 mV. ✅

  2. Convert back. This value lies between and .

    The instrument indicates 406.1 °C. ✅

  3. Error.

    The reading is 43.9 °C low. ✅

Step 3: Check the answer a second way

Click to reveal the check
  1. By the lost voltage. The copper replaced type K wire across and lost 1.859 mV. Near 430 °C one degree is worth about 42.4 µV, so the loss is , which agrees with Step 2 within the rounding of the hand interpolation; the script gives −43.87 °C. ✅

  2. The real cold junction has moved. The thermocouple alloys now end at the box, so the true cold junction is at 80 °C, while the instrument compensates for 35 °C, the temperature of the wrong place. ✅

  3. The limiting case. If the box were also at 35 °C, the lost voltage would be and the script confirms an indication of 450.00 °C. Copper does no harm when both of its ends are at the same temperature. ✅

Check it on the engine. Between them, three checks find the compensation and wiring faults of this lesson.

  1. Cold and stopped. After the engine has stood for some hours, the tip, the cable and the terminals are all at the air temperature, so the indication must equal it within about 2 °C. A reading near 0 °C means the cold junction compensation is off. This check cannot find copper in the run or a cable reversed at both ends, because with no temperature difference those faults give no error.
  2. Hot, at steady load. Put a reference thermocouple with its own calibrated indicator in a spare pocket (a closed metal tube in the pipe, also called a thermowell) beside the fixed one, with the engine stopped and cool while you fit it. The two must agree within the sum of their limits, about 3 °C for a class 1 sensor and a 1 °C reference at 450 °C. A reading many degrees low that changes with the temperature of the junction box is the copper repair or a double reversal.
  3. Walk the run. At every joint, check that both cores are thermocouple or matching cable: the magnet test on type K, and the colour code of one standard.

Verify It in Python



The script holds the NIST Monograph 175 coefficients for type K, with the exponential term above 0 °C. It tests itself against six published table values and stops if one is wrong by more than 0.6 µV. The inverse is a root search on the reference function itself, so it is exact to the precision of the function. It then reproduces both applications and plots the two wrong methods against terminal temperature.

type_k_cold_junction.py
"""Type K thermocouple: ITS-90 reference function, its inverse, and cold junction errors."""
import numpy as np
import matplotlib.pyplot as plt
from scipy.optimize import brentq
# NIST Monograph 175 (ITS-90), type K, E in mV for t in degC.
C_NEG = [0.0, 0.394501280250e-01, 0.236223735980e-04, -0.328589067840e-06,
-0.499048287770e-08, -0.675090591730e-10, -0.574103274280e-12,
-0.310888728940e-14, -0.104516093650e-16, -0.198892668780e-19,
-0.163226974860e-22] # -270 to 0 degC
C_POS = [-0.176004136860e-01, 0.389212049750e-01, 0.185587700320e-04,
-0.994575928740e-07, 0.318409457190e-09, -0.560728448890e-12,
0.560750590590e-15, -0.320207200030e-18, 0.971511471520e-22,
-0.121047212750e-25] # 0 to 1372 degC
A0, A1, A2 = 0.118597600000e+00, -0.118343200000e-03, 0.126968600000e+03
def emf(t):
"""Reference function: voltage in mV for a junction at t degC, reference at 0 degC."""
if t < 0.0:
return sum(c * t**i for i, c in enumerate(C_NEG))
poly = sum(c * t**i for i, c in enumerate(C_POS))
return poly + A0 * np.exp(A1 * (t - A2) ** 2) # exponential term above 0 degC
def temp(e_mv):
"""Inverse: temperature in degC for a voltage in mV (reference at 0 degC)."""
return brentq(lambda t: emf(t) - e_mv, -270.0, 1372.0, xtol=1e-9)
def seebeck(t, dt=0.01):
"""Slope of the reference function in microvolt per degC."""
return 1000.0 * (emf(t + dt) - emf(t - dt)) / (2.0 * dt)
print("Check against the published table")
for t, table in ((-200.0, -5.891), (-100.0, -3.554), (0.0, 0.000),
(100.0, 4.096), (500.0, 20.644), (1000.0, 41.276)):
print(f" {t:7.0f} degC: computed {emf(t):8.3f} mV, table {table:8.3f} mV")
assert abs(emf(t) - table) < 0.0006
# ---------- Application 1: exhaust at 450 degC, terminals at 35 degC ----------
T_HOT, T_TERM = 450.0, 35.0
e_hot, e_term = emf(T_HOT), emf(T_TERM)
v = e_hot - e_term
print("Application 1: exhaust 450 degC, terminals 35 degC")
print(f" E(450) = {e_hot:.3f} mV, E(35) = {e_term:.3f} mV")
print(f" voltage at the terminals: {v:.3f} mV")
print(f" Seebeck coefficient: {seebeck(35):.1f} uV/degC at 35 degC, "
f"{seebeck(450):.1f} uV/degC at 450 degC")
t_right = temp(v + e_term)
t_none = temp(v)
t_add = temp(v) + T_TERM
print(f" correct order: {t_right:.2f} degC, error {t_right - T_HOT:+.2f} degC")
print(f" no compensation: {t_none:.2f} degC, error {t_none - T_HOT:+.2f} degC")
print(f" adding temperatures: {t_add:.2f} degC, error {t_add - T_HOT:+.2f} degC")
t_cjc = temp(v + emf(T_TERM + 1.0))
print(f" terminal sensor 1 degC high: reading {t_cjc - T_HOT:+.2f} degC")
print(f" class 1 tolerance at 450 degC: {max(1.5, 0.004 * T_HOT):.1f} degC")
# ---------- Application 2: copper wire from a junction box at 80 degC ----------
T_BOX = 80.0
v_cu = e_hot - emf(T_BOX)
t_cu = temp(v_cu + e_term)
print("Application 2: copper from a box at 80 degC to terminals at 35 degC")
print(f" E(80) = {emf(T_BOX):.3f} mV, voltage lost: {emf(T_BOX) - e_term:.3f} mV")
print(f" voltage at the terminals: {v_cu:.3f} mV")
print(f" indication: {t_cu:.2f} degC, error {t_cu - T_HOT:+.2f} degC")
t_cu_same = temp(e_hot - emf(T_TERM) + e_term)
print(f" box also at 35 degC: indication {t_cu_same:.2f} degC")
# ---------- Plot ----------
t_term = np.linspace(0.0, 60.0, 61)
err_none, err_add = [], []
for tt in t_term:
vv = e_hot - emf(tt)
err_none.append(temp(vv) - T_HOT)
err_add.append(temp(vv) + tt - T_HOT)
t_axis = np.linspace(-200.0, 1300.0, 301)
fig, ax = plt.subplots(2, 1, figsize=(8, 7))
ax[0].plot(t_axis, [emf(x) for x in t_axis])
ax[0].set_xlabel("junction temperature (degC), reference at 0 degC")
ax[0].set_ylabel("voltage (mV)")
ax[0].set_title("Type K reference function (ITS-90)")
ax[1].plot(t_term, err_none, label="no compensation")
ax[1].plot(t_term, err_add, label="temperatures added")
ax[1].axhline(0.0, color="gray", linewidth=0.8, label="correct order")
ax[1].set_xlabel("terminal temperature (degC)")
ax[1].set_ylabel("error at 450 degC (degC)")
ax[1].set_title("Cold junction errors for an exhaust at 450 degC")
ax[1].legend()
fig.tight_layout()
fig.savefig("type_k_cold_junction.png", dpi=120)
print("Saved type_k_cold_junction.png")

Expected output

Check against the published table
-200 degC: computed -5.891 mV, table -5.891 mV
-100 degC: computed -3.554 mV, table -3.554 mV
0 degC: computed 0.000 mV, table 0.000 mV
100 degC: computed 4.096 mV, table 4.096 mV
500 degC: computed 20.644 mV, table 20.644 mV
1000 degC: computed 41.276 mV, table 41.276 mV
Application 1: exhaust 450 degC, terminals 35 degC
E(450) = 18.516 mV, E(35) = 1.407 mV
voltage at the terminals: 17.109 mV
Seebeck coefficient: 40.9 uV/degC at 35 degC, 42.5 uV/degC at 450 degC
correct order: 450.00 degC, error +0.00 degC
no compensation: 416.83 degC, error -33.17 degC
adding temperatures: 451.83 degC, error +1.83 degC
terminal sensor 1 degC high: reading +0.96 degC
class 1 tolerance at 450 degC: 1.8 degC
Application 2: copper from a box at 80 degC to terminals at 35 degC
E(80) = 3.267 mV, voltage lost: 1.859 mV
voltage at the terminals: 15.249 mV
indication: 406.13 degC, error -43.87 degC
box also at 35 degC: indication 450.00 degC
Saved type_k_cold_junction.png

In the lower plot the error with no compensation is almost a straight line that falls by nearly one degree for each degree of terminal temperature. The error of added temperatures is small and positive, and it grows with the terminal temperature. Both are zero at a terminal temperature of 0 °C, where the reference function needs no correction.

Common Mistakes



  • Saying that the junction generates the voltage. It is generated along the wires where the temperature changes, so a good tip with bad wire in the gradient gives a bad reading.
  • Converting millivolts from a plain voltmeter directly with the table, which assumes terminals at 0 °C. Add first.
  • Compensating by adding the terminal temperature in degrees. Convert it to a voltage, add voltages, then convert back.
  • Extending or repairing a thermocouple run with copper wire. Use extension or compensating cable of the same type, and connect it with the right polarity at both ends.
  • Trusting the colour red to mean positive. In the North American code the red wire is negative. Check the code, or test type K with a magnet.
  • Connecting a grounded junction to an input that is not isolated. The earth current between machine and instrument adds a false voltage that changes with the load on the plant.

Summary



  • A thermocouple voltage is generated along the two wires where the temperature changes, in proportion to the difference of their Seebeck coefficients. The junction only joins the wires.
  • The voltage depends on two temperatures: , where is the reference function of the type (NIST Monograph 175, IEC 60584-1).
  • Cold junction compensation is done in voltage: convert the terminal temperature to millivolts, add, convert back.
  • For type K at 450 °C with terminals at 35 °C, the signal is 17.109 mV. Forgetting the compensation reads 33.2 °C low, and adding temperatures reads 1.8 °C high.
  • Copper wire between a box at 80 °C and terminals at 35 °C reads 43.9 °C low. Every metre between the tip and the terminals must be the correct thermocouple alloy or its matching cable.
  • A class 1 type K thermocouple is good to about ±1.8 °C at 450 °C when new. It is chosen for range and strength, not for fine accuracy.

Exercises



1. A type K thermocouple has its tip at 250 °C and its terminals at 25 °C. Given mV and mV, find the voltage at the terminals.

Answer

mV.

2. A type K input measures 8.500 mV with its terminals at 30 °C. Given mV, mV and mV, find the temperature of the tip.

Answer

Add the voltages: mV. Interpolate: .

3. A type K thermocouple in a furnace is at 1000 °C and its terminals are at 40 °C. Given mV, mV, mV and mV, find the error (a) with no compensation and (b) with compensation by adding temperatures. Explain the sign of (b).

Answer

mV. Direct conversion: , so (a) the error is . (b) , an error of . The sign is negative here because at 1000 °C the slope of the function (39.0 µV per °C) is lower than at 40 °C (41.0 µV per °C), the opposite of the case at 450 °C.

4. A type K thermocouple with its tip at 100 °C is connected with reversed polarity to an instrument whose terminals are at 35 °C. The instrument compensates correctly. Given mV, mV, mV and mV, find the indication.

Answer

The instrument sees mV. It adds : mV. Interpolate: . The indication falls as the tip gets hotter, which is the sign of reversed polarity.

5. In Application 2, the copper is replaced by correct type K extension cable, but the cable is connected with reversed polarity at both ends. The tip is at 450 °C, the box at 80 °C and the terminals at 35 °C. Given the values in Application 2 and mV, mV, find the indication and the error.

Answer

The thermocouple section gives mV. The reversed cable subtracts what it should add: mV. At the terminals mV. Add : mV. Interpolate: . The error is , twice the error of the copper repair.

6. In Application 1 the wiring is correct, but the sensor in the terminal block reads 38 °C when the terminals are at 35 °C, because it sits next to a warm power supply. Given mV, mV and mV, find the indication and the error.

Answer

The measured voltage is still 17.109 mV. The instrument adds : mV. Interpolate: . The error is , almost equal to the 3 °C error of the terminal sensor.

References



  • G. W. Burns, M. G. Scroger, G. F. Strouse, M. C. Croarkin and W. F. Guthrie, Temperature-Electromotive Force Reference Functions and Tables for the Letter-Designated Thermocouple Types Based on the ITS-90, NIST Monograph 175, National Institute of Standards and Technology, 1993.
  • IEC 60584-1:2013, Thermocouples, Part 1: EMF specifications and tolerances, International Electrotechnical Commission.
  • ASTM Committee E20, Manual on the Use of Thermocouples in Temperature Measurement, 4th edition, ASTM Manual Series MNL 12, 1993.
  • J. P. Bentley, Principles of Measurement Systems, 4th edition, Pearson, 2005.


© 2021-2026 SiliconWit®. All rights reserved.
exhaust pipe, gas at 450 °C tip sheathed type K two wires, + and - (thermocouple cable) terminals at 35 °C instrument reads about 17 mV control enclosure
tip 450 °C wire in the wall temperature falls terminals 35 °C + - V wire A (nickel-chromium) wire B (nickel-aluminium) no voltage here (one point) voltage generated here, along both wires no voltage where the wires are at one temperature
terminal sensor tterm = 35 °C thermocouple V measured (mV) convert to mV E(tterm) add voltages convert mV to °C thot 1 2 3
tip 450 °C junction box 80 °C terminals 35 °C + - V type K type K copper copper generates E(450) − E(80) generates nothing
Watch it build: four wiring faults on one run
450 °C80 °C35 °C type K extension cable 450 °Cevery metre type K or KX: right falls hotter tip, lower reading: easy to see 362 °C −88 °C, about 2 × 45 °C: hard to see copper 406 °C −44 °C, near 80 − 35 = 45 °C extension cable set to J error grows with temperature
  1. Tip 450 °C, head 80 °C, terminals 35 °C: with type K and KX all the way, 450 °C.
  2. Reversed at the instrument: the voltage changes sign, so the reading falls as the tip heats.
  3. The cable reversed at both ends: its 45 °C is subtracted, not added, so 362 °C.
  4. Copper from the head: the 45 °C along it generates nothing, so 406 °C.
  5. Type J set for a type K sensor: the error grows with temperature. Check the setting first.
Predict first

A type K thermocouple sits in an exhaust at a steady 450 °C. During the afternoon the instrument enclosure warms from 20 °C to 40 °C. What happens to the voltage at the instrument terminals?

tip 450 °Cterminals 35 °C nothing madenothing made voltage made here A wire at one temperature makes nothing.
See it: the same millivolts, read three ways

Measured voltage
Compensation forgotten
Temperatures added

The curve is the type K reference function, with the terminals at 0 °C. The dark bar is the voltage the instrument measures, from the terminal point to the tip point. The right order adds E(tterm) and so lifts the bar back to where it belongs: it always returns the tip temperature. The coral bar is the same voltage stood on 0 mV, which is what an instrument with no compensation assumes.

tip 450 °Cbox 80 °C35 °C 1.86 mV lost: 44 °C low type K: 15.25 mVcopper: nothing

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. A type K thermocouple at 300 °C runs to a junction box at 60 °C. From the box to the instrument, whose terminals are at 25 °C, someone used ordinary copper cable. The instrument compensates correctly for 25 °C. About what does it read?

2. You read a type K thermocouple with a plain millivoltmeter and get 12.000 mV. The terminals are at 25 °C, where E(25) = 1.000 mV. What is the temperature of the tip?

3. In the exhaust of the lesson (tip 450 °C, terminals 35 °C) the wiring is correct, but a small fan cools the terminal sensor, and it reads 33 °C. What does the instrument show?