Gauge and absolute pressure
Pressure, Level and Flow
On this page
A borehole pump runs dry and burns its motor because the level reading said there was half a metre more water than there was. A water bill is disputed because the flow meter counted 7 cubic metres an hour through a pipe with the valve shut. In both cases the sensor was inside its maker’s accuracy. The error came from the step between what the sensor feels, a pressure, and what the screen shows, a level or a flow. This lesson follows that step for pressure, level and flow, and puts a number on what each conversion costs. #PressureMeasurement #LevelMeasurement #FlowMeasurement
Learning Objectives
By the end of this lesson, you will be able to:
- Distinguish gauge, absolute and differential pressure and choose the correct one for a task
- Calculate a liquid level from hydrostatic pressure and the error that a change of density causes
- Calculate flow from the differential pressure of an orifice meter
- Carry a transmitter’s percent of span accuracy through the square root to a percent of reading in flow
- Explain where electromagnetic, ultrasonic and turbine meters fail, and how a totaliser accumulates error
Real-World System Problem: A borehole, a pump and a tank
A farm takes its water from a borehole. A submersible pump lifts the water through a rising pipe to a storage tank. Three questions decide whether the system is safe and whether it is paid for correctly. How much water stands above the pump? How much water is in the tank? How much water was pumped today?
All three are usually answered with pressure sensors. A transmitter hung in the borehole feels the weight of the water above it and reports a depth. A transmitter at the bottom of the tank does the same. A plate with a hole in the delivery pipe creates a pressure difference that grows with the flow, and a third transmitter reports that difference as a flow.
None of these instruments measures the measurand directly. Each measures a pressure and converts it with a physical law. The law brings in other quantities (the density of the water, the pressure of the air, a square root), and when one of them is not what the conversion assumed, the indication is wrong while the sensor works perfectly.
Fundamental Theory: From pressure to level and flow
Gauge, absolute and differential pressure
Pressure is force divided by area. The unit is the pascal (Pa), which is one newton per square metre. Industry also uses the bar:
Every pressure measurement is a comparison with a reference pressure, and the reference decides the name.
- Absolute pressure is measured against a perfect vacuum. The sensor has a sealed, evacuated chamber on its reference side.
- Gauge pressure is measured against the air around the sensor. The reference side is open to the atmosphere.
- Differential pressure is the difference between two pressures, each brought to one side of the same sensor.
The standard atmosphere is defined as 101.325 kPa, at sea level. The real value changes with the weather by a few kilopascals, and it falls with altitude: at 1660 m above sea level the standard atmosphere model gives about 83 kPa. A gauge sensor does not care, because the atmosphere acts on both of its sides. An absolute sensor reports every change of the weather as a change of pressure.
The choice follows from the task. Pump discharge pressure and tank level use gauge pressure, because the air acts on the liquid surface too. Vacuum and boiling point work use absolute pressure. Flow through a restriction, and the state of a filter, use differential pressure.
Hydrostatic level
A column of liquid presses down on whatever is below it. The pressure depends on the height of the column and not on its shape or its volume.
Hydrostatic pressure
For water at 20 °C, with
The effect of density
The transmitter measures
The relative level error equals the relative density error. The transmitter weighs the column; it cannot see the surface, as a scale cannot tell your height. Warm water is less dense than cold water, so a warm tank reads low. A liquid that is not water needs its own density: a transmitter scaled for water and placed in diesel reads far too low.
Two limits of the method follow. The reading is the height above the sensor, so the position of the sensor must be known and fixed (a transmitter hanging on its cable in a borehole must be fixed in height). And the tank must be open to the atmosphere: in a closed tank with gas pressure above the liquid, a single gauge sensor adds the gas pressure to the reading, so a differential pressure transmitter is used, its second side connected to the gas space.
Flow by differential pressure
When a liquid passes through a restriction, it must speed up, and its pressure falls. An orifice plate is the simplest restriction: a thin plate with a round hole, clamped between two flanges. A differential pressure transmitter measures the pressure just before the plate and just after it.
For a liquid, the volume flow
where
For one installed meter everything except
Square-root relation of a differential pressure flow meter
The square has a hard consequence: half the flow gives a quarter of the differential pressure, and a tenth of the flow a hundredth. The transmitter’s accuracy is a fixed fraction of its span, so at low flow the same fixed error meets a very small signal.
To find how much, take a small error
The square root halves the relative error. That helps at full flow; at low flow,
Turndown is the ratio of the largest to the smallest flow that a meter measures within a stated accuracy. A differential pressure meter with one transmitter has a turndown of about 3 to 1 for normal accuracy targets, as Application 2 shows.
Other flow meters and where each fails
Electromagnetic meter. A liquid that conducts electricity moves through a magnetic field across the pipe, and a voltage proportional to its mean velocity appears between two electrodes in the pipe wall. The pipe is clear, with no moving part and almost no pressure loss, and the output is linear with flow, so the turndown is far better than an orifice meter’s. It fails when the liquid does not conduct: it cannot measure oil, fuel or gas, and it has trouble with very pure water (makers state a minimum conductivity, typically a few microsiemens per centimetre). It fails when the pipe is not full, because it measures velocity and assumes the whole cross-section is liquid. Air bubbles are counted as liquid, and deposits on the electrodes disturb the signal.
Ultrasonic transit-time meter. A pulse of sound travels faster with the flow than against it. The meter sends pulses both ways along a slanted path and converts the time difference to a velocity. The clamp-on version is fitted to the outside of an existing pipe with no cutting, which makes it the usual tool for a temporary survey. It fails when the sound cannot cross: bubbles, a high load of solids, a pipe that is not full, or a thick layer of scale all weaken or block the pulse. A clamp-on meter also needs the true inside diameter and wall thickness, and an error there becomes a flow error directly. It samples the velocity on one path, so it needs a long straight pipe before it, and after a bend or a valve it reads wrongly.
Turbine meter. The flow turns a small rotor, and each passing blade gives a pulse, so the pulse rate follows the velocity and the pulse count follows the volume. In a clean liquid of low viscosity it repeats very well, and counting pulses makes totalising simple. It fails through its moving parts: bearings wear, and sand, fibres or scale slow or jam the rotor, so a strainer is fitted before it. A change of viscosity changes its calibration. At low flow, bearing friction makes it read low and finally stop. Gas or air in the liquid drives the rotor fast and it reads high.
Totalising and the error that time accumulates
A flow meter reports a rate. A totaliser adds the rate over time to give a volume:
where
The two kinds of error behave differently under this sum. Random error, positive in one sample and negative in the next, mostly cancels: its share of the total falls as samples are added. A bias does not cancel, as a dripping tap fills a bucket in the end. A constant bias
The worst bias is a zero error, counted during every hour that the pipe is still. So flow meters have a low-flow cut-off: below a set flow, the meter reports zero and the totaliser stops. The cut-off also hides any real small flow, such as a leak, so its value must be chosen and recorded.
The sample interval matters too. A sum of samples assumes the flow is constant between them, so a pump that starts and stops between two samples is counted wrongly. Sample much faster than the flow changes, or count pulses in the meter itself.
Application 1: A hydrostatic level transmitter in warm water
Step 1: Pressure and current at the reference density
Click to reveal the pressure and current
-
Pressure at the sensor.
The sensor feels 60.70 kPa above atmospheric pressure. ✅
-
Pressure at the top of the range.
At 10 m the transmitter sends 20 mA. ✅
-
Loop current. The fraction of span is
. The transmitter sends 13.92 mA, and the receiver shows 6.20 m. ✅
Step 2: The same level in warm water
Click to reveal the density error
-
Pressure with the lower density.
The same column of water is lighter by 0.49 kPa. ✅
-
Current.
. ✅ -
Indicated level. The receiver still divides by the reference density.
The screen shows 6.150 m. ✅
-
Level error. Error is the indication minus the true value.
Carried without rounding, the error is -49.7 mm. The transmitter reads 50 mm low. ✅
Step 3: Check with the density ratio
Click to reveal the check
-
Use the ratio directly.
The error is
, or -49.7 mm, the same as Step 2. ✅ -
As a percentage.
percent of the level. The error is a percentage of the reading, so it grows with the level: 80 mm at 10 m, 8 mm at 1 m. ✅ -
Compare with the transmitter. A typical accuracy of ±0.5 percent of span is ±50 mm on a 10 m span. The density change alone has used an amount equal to the whole of that limit, and it is a bias in one direction, not a scatter. ✅
Application 2: An orifice meter at a quarter of its range
Step 1: Differential pressure at 25 cubic metres per hour
Click to reveal the differential pressure
-
Fraction of full flow.
. ✅ -
Fraction of full differential pressure. The pressure follows the square of the flow:
, which is 6.25 percent of span. ✅ -
Differential pressure.
A quarter of the flow gives one sixteenth of the pressure, 15.6 mbar. ✅
-
What the loop carries. If the transmitter’s output is linear with differential pressure, the current is
. A quarter of the flow uses only 1 mA of the 16 mA span. ✅
Step 2: The transmitter limit in millibar
Click to reveal the limit
-
Percent of span to millibar.
The limit is ±1.25 mbar at every point of the range, large flow or small. ✅
-
As a share of the reading at 25 m³/h.
, which is 8.0 percent of the differential pressure there. An accuracy of 0.5 percent of span has become 8 percent of reading in pressure. ✅
Step 3: Through the square root
Click to reveal the flow error at four flows
-
Rule. The relative flow error is half the relative pressure error.
The differential pressure at each flow is
. ✅ -
At 100 m³/h.
, so percent of reading. ✅ -
At 50 m³/h.
, so percent of reading. ✅ -
At 25 m³/h.
, so percent of reading, which is ±1.0 m³/h. ✅ -
At 10 m³/h.
, so percent of reading. The limit of the transmitter is half of the whole signal. ✅
| Flow (m³/h) | Differential pressure (mbar) | Percent of span | Flow error limit (percent of reading) |
|---|---|---|---|
| 100 | 250.0 | 100 | ±0.25 |
| 50 | 62.5 | 25 | ±1.0 |
| 25 | 15.625 | 6.25 | ±4.0 |
| 10 | 2.5 | 1.0 | ±25 |
Each time the flow halves, the error as a percentage of reading becomes four times larger.
Step 4: Turndown, and an exact check
Click to reveal the turndown and the check
-
General form. Put
into the rule. With the accuracy in percent of span, The error grows with the square of the turndown. ✅
-
Lowest flow for ±2 percent of reading.
The meter holds ±2 percent of reading only from 35.4 to 100 m³/h. The turndown is 2.8 to 1. For ±1 percent it is 2.0 to 1. ✅
-
Exact check at 25 m³/h. Convert the two limits of pressure to flow without the small-error rule.
These are +3.92 and -4.08 percent of 25. The rule’s ±4.0 percent is confirmed. ✅
-
Exact check at 10 m³/h. The limits are 12.25 and 7.07 m³/h, which is +22.5 and -29.3 percent. The rule gave ±25 percent. It is no longer exact, because the error is not small compared with the signal, but the conclusion is the same: the reading has no value there. ✅
Check it on site. Each conversion in this lesson can be tested against a reference that needs no laboratory.
- Level against a dip. Measure the water with a dip tape or an electric water level meter from a marked point, and compare it with the screen. The pattern of the difference names the fault: a constant offset is a wrong sensor height; a difference that grows with the level is a density or scaling error (0.8 percent for warm water); a difference that follows the weather is a blocked vent tube.
- Zero of a dp flow meter. With the pump stopped, open the equalising valve of the three-valve manifold (two isolation valves and one valve that joins the two sides) so both sides see one pressure. The transmitter must read 0 within ±1.25 mbar, and the flow must show zero below the cut-off.
- Total against a tank fill. With the tank outlet closed, pump for a measured time. The rise of level times the floor area of the tank is a second measurement of the same volume; the meter’s total must agree with it within the uncertainty of both.
Verify It in Python
The script repeats the hydrostatic calculation at both densities, builds the orifice table with the small-error rule and with the exact limits, finds the turndown for two accuracy targets, and totalises a meter with a zero error, with and without a low-flow cut-off. The plot shows the square law and the flow error limit against flow.
"""Hydrostatic level with a density change, and an orifice meter at low flow."""import numpy as npimport matplotlib.pyplot as plt
G = 9.81 # m/s2
# ---------- Part 1: hydrostatic level transmitter ----------RHO_CAL = 998.0 # kg/m3, density the transmitter was ranged forRHO_WARM = 990.0 # kg/m3, water at 45 degCSPAN_M = 10.0 # m of water for 4 to 20 mALEVEL = 6.20 # m, true depth of water above the sensor
def pressure_pa(level_m, rho): return rho * G * level_m
def current_ma(p_pa): """Transmitter output: it knows only the pressure.""" return 4.0 + 16.0 * p_pa / pressure_pa(SPAN_M, RHO_CAL)
def indicated_level(i_ma): return (i_ma - 4.0) / 16.0 * SPAN_M
print("Hydrostatic level, range 0 to 10 m of water")print(f" 1 m of water at 998 kg/m3: {pressure_pa(1.0, RHO_CAL) / 1000:.3f} kPa")print(f" pressure at 10 m: {pressure_pa(SPAN_M, RHO_CAL) / 1000:.2f} kPa")for rho in (RHO_CAL, RHO_WARM): p = pressure_pa(LEVEL, rho) i = current_ma(p) shown = indicated_level(i) print(f" density {rho:.0f}: pressure {p / 1000:.2f} kPa, current {i:.3f} mA, " f"indicated {shown:.4f} m, error {1000 * (shown - LEVEL):+.1f} mm")print(f" error as a share of the level: {100 * (RHO_WARM / RHO_CAL - 1):+.2f} %")print(f" 1 kPa of air pressure change equals " f"{1000 * 1000 / (RHO_CAL * G):.0f} mm of water")
# ---------- Part 2: orifice meter and the square root ----------Q_MAX = 100.0 # m3/h at full differential pressureDP_MAX = 250.0 # mbarACC = 0.5 # percent of span, differential pressure transmitterd_dp = ACC / 100.0 * DP_MAX # mbar
def dp_from_flow(q): return DP_MAX * (q / Q_MAX) ** 2
def flow_from_dp(dp): return Q_MAX * np.sqrt(np.maximum(dp, 0.0) / DP_MAX)
print("Orifice meter, 0 to 100 m3/h at 0 to 250 mbar")print(f" transmitter limit: +/-{d_dp:.2f} mbar at every point of the range")print(" flow dp dp/span linear exact low / high")for q in (100.0, 50.0, 25.0, 10.0): dp = dp_from_flow(q) linear = 0.5 * d_dp / dp * 100.0 low = (flow_from_dp(dp - d_dp) / q - 1.0) * 100.0 high = (flow_from_dp(dp + d_dp) / q - 1.0) * 100.0 print(f" {q:5.0f} {dp:7.3f} {100 * dp / DP_MAX:6.2f} % " f"+/-{linear:5.2f} % {low:+6.2f} % / {high:+6.2f} %")dp25 = dp_from_flow(25.0)print(f" current at 25 m3/h, output linear in dp: {4 + 16 * dp25 / DP_MAX:.2f} mA")print(f" current at 25 m3/h, output linear in flow: {4 + 16 * 25 / Q_MAX:.2f} mA")print(f" a zero shift of +{d_dp:.2f} mbar on a still pipe shows " f"{flow_from_dp(d_dp):.2f} m3/h")for target in (1.0, 2.0): q_low = Q_MAX * np.sqrt(0.5 * ACC / target) print(f" for +/-{target:.0f} % of reading: flow above {q_low:.1f} m3/h, " f"turndown {Q_MAX / q_low:.1f} to 1")
# ---------- Part 3: a totaliser with a zero error ----------ZERO = 0.3 # m3/h shown when the pipe is stillRUN_H, Q_RUN = 8.0, 40.0true_day = RUN_H * Q_RUNprint("Totaliser with a zero error of 0.3 m3/h")print(f" true volume per day: {true_day:.0f} m3")print(f" counted over 24 h: {true_day + ZERO * 24:.1f} m3 " f"({100 * ZERO * 24 / true_day:+.2f} %)")print(f" counted with a low-flow cut-off: {true_day + ZERO * RUN_H:.1f} m3 " f"({100 * ZERO * RUN_H / true_day:+.2f} %)")print(f" extra volume in one year without the cut-off: " f"{ZERO * (24 - RUN_H) * 365:.0f} m3")
# ---------- Plot ----------q = np.linspace(5.0, 100.0, 300)dp = dp_from_flow(q)fig, ax = plt.subplots(1, 2, figsize=(10, 4.2))ax[0].plot(q, dp)ax[0].plot([25.0], [dp25], "o")ax[0].set_xlabel("flow (m3/h)")ax[0].set_ylabel("differential pressure (mbar)")ax[0].set_title("Square law of an orifice meter")ax[1].plot(q, (flow_from_dp(dp + d_dp) / q - 1.0) * 100.0, label="high limit")ax[1].plot(q, (flow_from_dp(dp - d_dp) / q - 1.0) * 100.0, label="low limit")ax[1].axhline(2.0, color="gray", linestyle="--", linewidth=0.8)ax[1].axhline(-2.0, color="gray", linestyle="--", linewidth=0.8)ax[1].set_ylim(-30.0, 30.0)ax[1].set_xlabel("flow (m3/h)")ax[1].set_ylabel("flow error limit (percent of reading)")ax[1].set_title("Effect of +/-0.5 percent of span")ax[1].legend()fig.tight_layout()fig.savefig("level_and_orifice_flow.png", dpi=120)print("Saved level_and_orifice_flow.png")Expected output
Hydrostatic level, range 0 to 10 m of water 1 m of water at 998 kg/m3: 9.790 kPa pressure at 10 m: 97.90 kPa density 998: pressure 60.70 kPa, current 13.920 mA, indicated 6.2000 m, error +0.0 mm density 990: pressure 60.21 kPa, current 13.840 mA, indicated 6.1503 m, error -49.7 mm error as a share of the level: -0.80 % 1 kPa of air pressure change equals 102 mm of waterOrifice meter, 0 to 100 m3/h at 0 to 250 mbar transmitter limit: +/-1.25 mbar at every point of the range flow dp dp/span linear exact low / high 100 250.000 100.00 % +/- 0.25 % -0.25 % / +0.25 % 50 62.500 25.00 % +/- 1.00 % -1.01 % / +1.00 % 25 15.625 6.25 % +/- 4.00 % -4.08 % / +3.92 % 10 2.500 1.00 % +/-25.00 % -29.29 % / +22.47 % current at 25 m3/h, output linear in dp: 5.00 mA current at 25 m3/h, output linear in flow: 8.00 mA a zero shift of +1.25 mbar on a still pipe shows 7.07 m3/h for +/-1 % of reading: flow above 50.0 m3/h, turndown 2.0 to 1 for +/-2 % of reading: flow above 35.4 m3/h, turndown 2.8 to 1Totaliser with a zero error of 0.3 m3/h true volume per day: 320 m3 counted over 24 h: 327.2 m3 (+2.25 %) counted with a low-flow cut-off: 322.4 m3 (+0.75 %) extra volume in one year without the cut-off: 1752 m3Saved level_and_orifice_flow.pngIn the totaliser part, a pump delivers 40 m³/h for 8 hours a day, and the meter shows 0.3 m³/h when the pipe is still. Counted through all 24 hours the day’s volume is 2.25 percent high. With a cut-off that stops the count while the pump is off, only the 8 running hours carry the bias and the error falls to 0.75 percent. The cut-off saves 1752 m³ a year that never passed through the pipe, counted while the pipe was still.
Common Mistakes
- Using a hydrostatic transmitter scaled for water in another liquid, or in water at a very different temperature, without changing the density in the scaling.
- Fitting an absolute or sealed sensor where a gauge sensor is needed, or blocking the vent tube of a gauge sensor, so that the level reading follows the weather.
- Reading a differential pressure flow signal as linear. A current of 12 mA on a transmitter that is linear with pressure is 50 percent of pressure and 70.7 percent of flow.
- Trusting an orifice meter at the bottom of its range because the transmitter is “0.5 percent”. That figure is percent of span in pressure, not percent of reading in flow.
- Averaging the differential pressure and then taking the square root. Convert each sample to flow first.
- Totalising with no low-flow cut-off, so that a zero error is counted through every idle hour.
Summary
- Gauge pressure is measured against the atmosphere, absolute pressure against a vacuum, and differential pressure between two points. The task decides which one is correct.
- A hydrostatic level transmitter measures pressure and converts it with
. A density error gives an equal relative level error: water at 990 kg/m³ read with a scaling for 998 kg/m³ shows 6.20 m as 6.150 m, which is 49.7 mm low. - In a differential pressure flow meter the pressure follows the square of the flow, so 25 percent of flow is 6.25 percent of the pressure span.
- A transmitter accuracy of ±0.5 percent of span becomes ±0.25, ±1.0, ±4.0 and ±25 percent of reading at 100, 50, 25 and 10 percent of flow. The useful turndown is about 3 to 1.
- Electromagnetic, ultrasonic and turbine meters are linear with flow and each has its own condition for failure: a liquid that does not conduct or a pipe that is not full, bubbles and unknown pipe dimensions, wear and dirt.
- A totaliser cancels most random error and keeps every bias, so a small zero error becomes a large volume.
Exercises
1. A gauge on a pump discharge reads 3.20 bar at a site where the atmospheric pressure is 0.83 bar. Find the absolute pressure.
Answer
2. The level transmitter of Application 1 (0 to 10 m, 998 kg/m³,
Answer
3. The same transmitter, still scaled for water at 998 kg/m³, is placed in a diesel tank. Take the density of the diesel as 840 kg/m³. The loop current is 15.20 mA. Find the indicated level and the true level.
Answer
Indicated:
4. The orifice meter of Application 2 (100 m³/h at 250 mbar, transmitter ±0.5 percent of span) reads 90 mbar. Find the flow and its error limit in percent of reading and in m³/h.
Answer
5. A differential pressure transmitter has an output that is linear with pressure, 4 to 20 mA for 0 to 250 mbar, on the meter of Application 2. The loop current is 8.00 mA. Find the flow. A technician reads the same current as “25 percent, so 25 m³/h”. What is the technician’s error?
Answer
8.00 mA is
6. A pump delivers 40 m³/h for 8 hours each day and is stopped for the other 16 hours. Its flow meter has a zero error of +0.3 m³/h at all times. Find the percentage error of the daily total (a) with no low-flow cut-off and (b) with a cut-off that stops the count when the pump is off.
Answer
True volume:
References
- J. P. Bentley, Principles of Measurement Systems, 4th edition, Pearson Education, 2005.
- R. S. Figliola and D. E. Beasley, Theory and Design for Mechanical Measurements, 7th edition, Wiley, 2019.
- ISO 5167-2, Measurement of fluid flow by means of pressure differential devices inserted in circular cross-section conduits running full. Part 2: Orifice plates, International Organization for Standardization, 2022.
- R. C. Baker, Flow Measurement Handbook, 2nd edition, Cambridge University Press, 2016.
- The sensor at the bottom feels the weight of the column above it: p = ρ g h.
- At 998 kg/m³, 6.20 m of water gives 60.70 kPa and 13.92 mA: shown 6.20 m.
- Warm water, 990 kg/m³: 60.21 kPa and 13.84 mA, so 6.15 m is shown, 50 mm low.
- The reading is the height above the sensor, and only in a tank open to the air.
- In a tank with vertical sides the mass is still right, while the height reads low.
An orifice flow meter has a differential pressure transmitter with an accuracy of ±0.5 percent of span. The pipe now carries one quarter of the meter's full flow. About how large is the possible flow error, as a percentage of the reading?
The meter of Application 2: 0 to 250 mbar for 0 to 100 m³/h. The transmitter's limit is a percent of its span, so it is the same number of millibar everywhere on the left curve. Near zero that curve is flat and the signal is tiny, so on the right the same limit becomes a large share of the flow. Each halving of the flow makes the error four times larger. The right curve uses the small-error rule; the readout gives the exact limits.
The pump of the lesson's script: 40 m³/h for 8 hours a day, 320 m³. The meter shows its zero error whenever the pipe is still. With the cut-off on, readings below 2 m³/h count as zero, so the idle hours add nothing; the bias during the 8 running hours remains.
Check yourself
Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.
1. An orifice meter is spanned 0 to 100 m³/h. Its transmitter is linear with differential pressure, 4 to 20 mA. The loop current is 12.0 mA. What is the flow?
2. A hydrostatic level transmitter scaled for water (998 kg/m³) is used in a brine tank. The brine has a density of 1100 kg/m³, and the true level is 5.00 m. What does the screen show?
3. A flow meter shows 0.2 m³/h when the pipe is still. The pump is stopped for 20 hours each day, and the totaliser has no low-flow cut-off. How much volume does the meter count in a year during the hours the pipe is still?
Discussion
No comments yet. Questions, results from your own build, a better way to explain it: all welcome.