Uncertainty Budgets

Lesson 2 of 10 28 min read
Found this useful?

A contract says the pump must deliver at least 3.95 bar, the logged reading is 4.00 bar, and the client’s own gauge says 3.9 bar. Neither number ends the argument, because nobody can say how far each may be from the truth. A reading without an uncertainty cannot prove that a limit is met, that a filter is blocked, or that a saving is real. This lesson builds an uncertainty budget, a table that lists every source of doubt in a measuring chain and combines them into one stated figure, for a pressure transmitter read by a converter, and shows why money spent on the smallest term is wasted. #MeasurementUncertainty #UncertaintyBudget #Instrumentation

Learning Objectives

By the end of this lesson, you will be able to:

  1. Distinguish a limit of error from a standard deviation, and a Type A evaluation from a Type B evaluation
  2. Convert a maker’s limit, a calibration certificate and a set of repeated readings into standard uncertainties
  3. Combine standard uncertainties through sensitivity coefficients by the root sum of squares
  4. State a result with its expanded uncertainty and coverage factor in the standard form
  5. Identify the dominant term of a budget and judge what an improvement to any term is worth

Real-World System Problem: A pressure reading that must settle a dispute



A booster pump supplies a building. The supply contract requires at least 3.95 bar in the discharge line. A pressure transmitter with a range of 0 to 10 bar sends 4 to 20 mA to a small controller in the plant room, and the log shows 4.00 bar. The pump supplier says the contract is met. The client asks one question: how sure is that number?

The reading is the end of a chain, and every link adds doubt. The transmitter has a maker’s limit of error, it sits in a room at 40 °C, and it was calibrated a year ago. The current passes through a sense resistor with a tolerance. An analogue to digital converter (ADC) turns the voltage into a whole number of counts, against a reference voltage that is itself not exact.

Transmitter0 to 10 barpressure Paccuracy, temperature, driftI150 ΩV12-bitNsenseADC4to20resistormAtolerance3.3 V reference0.1 %0.5%,andonecount of step
The measuring chain and where doubt enters

Six sources of doubt act on one number. Adding the six limits is too pessimistic: it assumes all six at their worst, in the same direction, at once. Ignoring five of them is too hopeful. The uncertainty budget is the agreed method between those two, set out in the Guide to the Expression of Uncertainty in Measurement, known as the GUM (JCGM 100:2008).

Fundamental Theory: From limits and readings to one stated uncertainty



Error and uncertainty are different things

The error of a reading is the indication minus the true value. It is one number with a sign, and it is unknown. The uncertainty is a statement about how large that unknown error could reasonably be. It has no sign, and it is known, because you calculate it.

The terms have the meanings of the international vocabulary (VIM, JCGM 200:2012), as in what a reading is worth.

Standard uncertainty

A tolerance, a spread of readings and a line on a certificate cannot be combined until they are in one common form. That form is the standard uncertainty, written : the doubt expressed as one standard deviation.

There are two ways to arrive at a standard uncertainty. They are named by the method of evaluation, not by the kind of error.

Type A evaluation: from repeated readings

A Type A evaluation uses statistics on readings you took yourself. Take readings under the same conditions and calculate their mean and their experimental standard deviation .

Type A standard uncertainty

Use when the result you report is the mean. Use when the result is a single reading from an instrument whose spread you found earlier.

Ten readings of a transmitter with bar give a mean with bar. A Type A evaluation sees only what varied during the readings. A bias that stayed constant is invisible to it.

Type B evaluation: from any other information

A Type B evaluation uses information that does not come from your own repeated readings: a datasheet, a tolerance class, a calibration certificate, a handbook. Most terms in an industrial budget are Type B.

The information usually arrives as a limit, written ±. The maker promises that the error is inside the interval from to and says nothing about where. To turn the limit into a standard deviation you must assume a shape for the distribution inside it.

rectangular: any valuetriangular: values nearinside is equally likelythe centre: more likely−a0+a−a0+au=a/√3u=a/√6
Two shapes inside the same limits
What you are givenDistributionDivisorStandard uncertainty
A maker’s limit ±, nothing moreRectangular
A limit ±, with values near the centre known to be more likelyTriangular
A certificate that states an expanded uncertainty with Normal2
A standard deviation, from readings or stated as suchNormal1the value itself
A digital step of size (a display digit or one ADC count)Rectangular, half-width on

The rectangular distribution is the honest choice when a limit is all you have. Its standard deviation is because the variance of a value spread evenly over a width of is . The digital step in the last row is the same rule: the rounding error lies evenly between and , so .

Sensitivity coefficients

A source of uncertainty is often not in the unit of the result. The tolerance of a resistor is in ohms and the result is in bar. The sensitivity coefficient makes the conversion: it is the change of the result for one unit of change of the input, with everything else held constant.

Here is the result and is one input. You can find by differentiating the measurement equation, or numerically: change the input by a small amount, recalculate the result, and divide the two changes. The product is the contribution of that source, in the unit of the result. When a source is already stated in the unit of the result, .

Two simple cases cover much field work. For a sum or a difference, both coefficients have the size 1, so the standard uncertainties in units combine directly. For a product or a quotient, the same holds for the relative uncertainties in percent.

Combining the terms

Combined standard uncertainty

This is the root sum of squares. Each contribution is squared, the squares (the variances) are added, and the root is taken. It is valid when the sources are independent of each other.

Variances add, and standard uncertainties do not. Two independent errors rarely reach their worst values together and in the same direction, so the combined doubt is less than the plain sum, as 4 steps east and 3 steps north take you 5 steps from the start, not 7.

Expanded uncertainty and the form of the result

One standard deviation covers only about 68 percent of cases for a normal distribution. To state an interval that a reader can rely on, multiply by a coverage factor .

Expanded uncertainty

With the interval covers about 95 percent of cases when the combined distribution is close to normal. Always state . A ”±” without it cannot be used by the next person.

Write with one or two significant figures, and round the value to the same decimal place: 4.00 bar ± 0.08 bar (k = 2), not 4.0031 bar ± 0.0808 bar.

Which term dominates

Because the terms are squared before they are added, the large ones count far more than their size suggests. The share of a term is its variance divided by the total variance:

A term that is one third of the largest term adds only about 5 percent to the combined value, since . A term that is one tenth adds 0.5 percent. So find the largest share and work on that. Halving a small term buys nothing that can be seen in the result.

The limit of the method

The root sum of squares assumes independent sources. Two readings taken through the same converter share its reference error. Shared errors are called correlated, and they do not combine by squares: in a sum they add directly, and in a difference they cancel. Application 2 shows a case. The budget also covers only the sources you listed. A blocked impulse line or a wrong range typed into the controller is a mistake, not an uncertainty, and no budget contains it.

Application 1: Budget for a pressure transmitter read through an ADC



Step 1: The measurement equation and the working point

Click to reveal the equation and the nominal values
  1. Chain. The current is in milliamperes. The voltage across the resistor is . The ADC returns counts, rounded to a whole number. ✅

  2. What the software calculates. It reverses the chain with the nominal values and :

    The factor 1000 changes amperes to milliamperes, and bar per milliampere. ✅

  3. Working point at 4.0 bar.

    Note that 4.0 bar is 40 percent of the span but 10.4 mA is 52 percent of 20 mA, because of the 4 mA live zero. ✅

Step 2: Turn each source into a standard uncertainty

Every source here is a maker’s limit, so every one is a Type B evaluation with a rectangular distribution and a divisor of .

Click to reveal the six conversions
  1. Maker’s accuracy. 0.5 percent of the 10 bar span is a limit of ±0.050 bar.

    The limit is the same at every pressure because it is a percent of span. ✅

  2. Temperature effect. The room is away from the reference temperature. The limit is percent of span, which is ±0.030 bar.

    The maker gives a limit for the temperature coefficient, not its value or its sign, so it cannot be corrected and is treated as a doubt. ✅

  3. Drift. One year at 0.2 percent of span per year is a limit of ±0.020 bar.

    ✅

  4. Sense resistor. 0.1 percent of 150 Ω is a limit of ±0.150 Ω.

    This is in ohms and needs a sensitivity coefficient. ✅

  5. ADC quantisation. The converter rounds to a whole count, so the rounding error lies between and count. This is one count over :

    ✅

  6. Reference voltage. 0.5 percent of 3.3 V is a limit of ±0.0165 V.

    ✅

Step 3: Sensitivity coefficients

Click to reveal the sensitivity coefficients
  1. Transmitter terms. Accuracy, temperature effect and drift are already in bar at the transmitter, and the chain passes them on unchanged: . ✅

  2. Sense resistor. If the real resistor is larger than 150 Ω by some fraction, the voltage is larger by the same fraction, and the software reads that as more current. The error is a percentage of the whole current, 10.4 mA, not of the pressure.

    As a check: 0.1 percent of 10.4 mA is 0.0104 mA, and bar, which equals the limit . ✅

  3. One ADC count.

    One count is 0.806 mV, or 5.37 µA, or 0.0034 bar. This is the resolution of the reading. ✅

  4. Reference voltage. The ADC measures the voltage as a fraction of its reference. If the real reference differs from 3.3 V by some percentage, every voltage reading is wrong by that percentage of the reading. Again the error is a percentage of the whole current.

    As a check: 0.5 percent of 10.4 mA is 0.052 mA, and bar. That is 0.8 percent of the 4.0 bar reading, because the live zero is included. ✅

Step 4: The budget, the combined and the expanded uncertainty

Click to reveal the budget table and the result
  1. The budget. Each contribution is the standard uncertainty multiplied by the sensitivity coefficient.

    SourceValue (limit)DistributionDivisorStandard uncertaintySensitivity coefficientContribution (bar)
    Maker’s accuracy±0.050 barRectangular0.02887 bar10.02887
    Temperature effect, 15 °C±0.030 barRectangular0.01732 bar10.01732
    Drift, one year±0.020 barRectangular0.01155 bar10.01155
    Sense resistor, 0.1 %±0.150 ΩRectangular0.0866 Ω0.04333 bar/Ω0.00375
    ADC quantisation±0.5 countRectangular0.2887 count0.003357 bar/count0.00097
    Reference voltage, 0.5 %±0.0165 VRectangular0.00953 V1.970 bar/V0.01876

    All six rows are Type B. ✅

  2. Squares. In units of the six variances are 833.3, 300.0, 133.3, 14.1, 0.9 and 352.1. Their sum is 1633.8. ✅

  3. Combined standard uncertainty.

    ✅

  4. Expanded uncertainty.

    ✅

  5. Result in the standard form.

    The pressure is between 3.92 and 4.08 bar with a coverage of about 95 percent. The expanded uncertainty is 2.0 percent of the reading. ✅

Step 5: Shares, and what an improvement is worth

Click to reveal the shares and the two improvements
  1. Share of each term. Divide each variance by 1633.8.

    SourceContribution (bar)Share of the variance
    Maker’s accuracy0.0288751.0 %
    Reference voltage0.0187621.6 %
    Temperature effect0.0173218.4 %
    Drift0.011558.2 %
    Sense resistor0.003750.9 %
    ADC quantisation0.000970.1 %

    The transmitter’s own accuracy is half of the variance. The reference voltage of the converter is second, ahead of temperature and drift. ✅

  2. Halve the smallest term. Replace the 12-bit ADC by a 13-bit one, so that one count is half as large. The variance of that term falls from 0.9 to 0.2.

    is still 0.0808 bar. The result does not change in any figure that is reported. ✅

  3. Halve the largest term. Replace the transmitter by one with ±0.25 percent of span. The variance of that term falls to a quarter, from 833.3 to 208.3.

    The result becomes 4.00 bar ± 0.06 bar (k = 2). The expanded uncertainty falls by 21 percent. ✅

  4. Compare with adding the limits. The plain sum of the six limits in bar is

    This worst case is 1.7 times the expanded uncertainty, and it has no stated coverage. It would be reached only if all six errors were at their limits with the same sign. ✅

  5. Check a second way. The Python script simulates 400 000 instruments. For each one it draws the errors at random inside their limits and passes a true pressure of 4.0 bar through the full chain, with rounding to whole counts. The standard deviation of the indications is 0.0404 bar, equal to , and 96.1 percent of them are inside ±0.0808 bar. The budget and the simulation agree. ✅

Check it on site. A budget is a prediction, so test it once. Connect a reference gauge with a certificate ( bar, k = 2) to the test port, at the height of the transmitter, and compare it with the controller. The difference should be within bar. One comparison inside that band does not prove the budget, but it has not found a fault. A larger difference means a source the budget does not contain: a blocked impulse line, the wrong range typed into the controller, a height difference, or a damaged transmitter. Find it before you quote to anyone.

Application 2: The pressure drop across a filter from two transmitters



T2T1FilterP1=4.00barP2=3.70barflowdrop=P1−P2=0.30bar
Two transmitters across one filter

Step 1: Independent channels

Click to reveal the simple difference
  1. The drop. bar. ✅

  2. Uncertainty of each reading. From Application 1, bar. For the six variances in units of are 833.3, 300.0, 133.3, 12.8, 0.9 and 320.4, with a sum of 1600.8.

    ✅

  3. Uncertainty of the difference. For both sensitivity coefficients have the size 1. The minus sign disappears when the terms are squared, so the variances add even though the readings are subtracted.

    ✅

  4. Result. (k = 2). The expanded uncertainty is 38 percent of the drop, although each reading alone is known to 2 percent. ✅

Step 2: Both channels on one ADC reference

In a real controller both transmitters are read by the same converter, so the two readings share one reference error.

Click to reveal the effect of the shared reference
  1. Separate the shared term. Remove the reference term from each reading. The variances that remain are for and for , in units of . These terms are independent and add: 2562.1. ✅

  2. Sensitivity of the difference to the reference. A reference error moves both readings in the same direction, so only the difference of the two coefficients acts on the drop.

    The contribution is bar, in place of 0.01876 and 0.01790 bar taken separately. The shared error almost cancels. ✅

  3. Combined.

    ✅

  4. Result. (k = 2). The gain is small, because the transmitters’ own terms dominate and those are independent. ✅

Step 3: One differential pressure transmitter

Click to reveal the alternative
  1. Why it is different. A differential transmitter measures the drop directly. Its limits are percentages of its own span of 1 bar, not of 10 bar, so every transmitter term is ten times smaller. ✅

  2. Combined. The six variances in units of are 8.35, 2.99, 1.32, 0.10, 0.01 and 2.53, with a sum of 15.3.

    ✅

  3. Result. (k = 2), which is 2.6 percent of the drop. The expanded uncertainty is 13 times smaller than with two gauge transmitters. ✅

  4. Check a second way. The script simulates the two-transmitter arrangement with one shared reference and finds a standard deviation of 0.0506 bar for the difference, equal to the value of Step 2. ✅

Verify It in Python



The script builds the budget of Application 1 from the datasheet values, prints each row with its share, repeats it with the smallest and the largest term halved, checks it by simulation, and calculates the pressure drop of Application 2 in the three ways. It saves two plots in one image: the shares as bars, and the simulated distribution of errors with the limits ±.

uncertainty_budget.py
"""Uncertainty budget of a 0 to 10 bar transmitter read by a 12-bit ADC,
and the uncertainty of a pressure difference from two such transmitters."""
import numpy as np
import matplotlib.pyplot as plt
SPAN = 10.0 # bar
R_NOM = 150.0 # ohm, sense resistor
VREF = 3.3 # V, ADC reference
COUNTS = 4096 # 12-bit converter
BAR_PER_MA = SPAN / 16.0
ROOT3 = np.sqrt(3.0)
def budget(pressure, span=SPAN, room_temp=40.0, years=1.0,
acc=0.5, temp_coef=0.02, drift=0.2,
r_tol=0.1, ref_tol=0.5, adc_counts=COUNTS):
"""Return a list of (name, limit, unit, u, c, contribution in bar)."""
bar_per_ma = span / 16.0
current = 4.0 + pressure / bar_per_ma # mA
count_bar = VREF / adc_counts / R_NOM * 1000.0 * bar_per_ma
rows = []
a = acc / 100.0 * span
rows.append(("accuracy", a, "bar", a / ROOT3, 1.0))
a = temp_coef / 100.0 * span * abs(room_temp - 25.0)
rows.append(("temperature", a, "bar", a / ROOT3, 1.0))
a = drift / 100.0 * span * years
rows.append(("drift", a, "bar", a / ROOT3, 1.0))
a = r_tol / 100.0 * R_NOM
rows.append(("resistor", a, "ohm", a / ROOT3, bar_per_ma * current / R_NOM))
a = 0.5
rows.append(("ADC step", a, "count", a / ROOT3, count_bar))
a = ref_tol / 100.0 * VREF
rows.append(("reference", a, "V", a / ROOT3, bar_per_ma * current / VREF))
return [(n, a, unit, u, c, u * c) for n, a, unit, u, c in rows]
def combine(rows):
contrib = np.array([r[5] for r in rows])
return np.sqrt(np.sum(contrib**2))
def show(rows, title):
uc = combine(rows)
print(title)
print(" source limit u c u*c (bar) share")
for name, a, unit, u, c, uc_i in rows:
print(f" {name:<12} {a:>7.4f} {unit:<5} {u:>9.5f} {c:>10.6f} "
f"{uc_i:>10.5f} {100.0 * uc_i**2 / uc**2:>5.1f} %")
print(f" combined standard uncertainty u_c = {uc:.4f} bar")
print(f" expanded uncertainty U = 2 u_c = {2.0 * uc:.4f} bar")
return uc
# ---------- Part 1: the budget at 4.0 bar ----------
P = 4.0
current = 4.0 + P / BAR_PER_MA
volt = current / 1000.0 * R_NOM
print(f"At {P:.1f} bar: {current:.1f} mA, {volt:.3f} V, "
f"{volt / VREF * COUNTS:.0f} counts")
rows = budget(P)
uc = show(rows, "Budget at 4.0 bar, 40 degC, one year after calibration")
print(f" result: {P:.2f} bar +/- {2.0 * uc:.2f} bar (k = 2), "
f"{100.0 * 2.0 * uc / P:.1f} % of the reading")
print(f" sum of all the limits (worst case): {sum(r[1] * r[4] for r in rows):.4f} bar")
print(f" as built: u_c = {uc:.5f}, U = {2 * uc:.4f} bar")
uc_adc = combine(budget(P, adc_counts=2 * COUNTS))
uc_acc = combine(budget(P, acc=0.25))
print(f" smallest term halved (13-bit ADC): u_c = {uc_adc:.5f}, U = {2 * uc_adc:.4f} bar")
print(f" largest term halved (0.25 % of span): u_c = {uc_acc:.5f}, U = {2 * uc_acc:.4f} bar")
# ---------- Part 2: check by simulation (Monte Carlo) ----------
rng = np.random.default_rng(1)
N = 400_000
def simulate(pressure, n, span=SPAN, vref_true=None, rng=rng):
"""Indicated pressure for n random instruments, every limit rectangular."""
bar_per_ma = span / 16.0
e_tx = (rng.uniform(-0.005, 0.005, n) + rng.uniform(-0.003, 0.003, n)
+ rng.uniform(-0.002, 0.002, n)) * span # bar
i_true = 4.0 + (pressure + e_tx) / bar_per_ma # mA
r_true = R_NOM * (1.0 + rng.uniform(-0.001, 0.001, n))
if vref_true is None:
vref_true = VREF * (1.0 + rng.uniform(-0.005, 0.005, n))
v = i_true / 1000.0 * r_true
counts = np.round(v / vref_true * COUNTS)
v_calc = counts * VREF / COUNTS
return (v_calc / R_NOM * 1000.0 - 4.0) * bar_per_ma
ind = simulate(P, N)
print("Simulation of 400000 instruments at 4.0 bar")
print(f" standard deviation {ind.std():.4f} bar, "
f"inside +/- U: {100.0 * np.mean(np.abs(ind - P) <= 2.0 * uc):.1f} %")
# ---------- Part 3: pressure drop across a filter ----------
P1, P2 = 4.00, 3.70
rows1, rows2 = budget(P1), budget(P2)
u1, u2 = combine(rows1), combine(rows2)
u_ind = np.hypot(u1, u2)
print("Pressure drop from two transmitters")
print(f" u(P1) = {u1:.4f} bar, u(P2) = {u2:.4f} bar")
print(f" separate references: u = {u_ind:.4f} bar, U = {2 * u_ind:.3f} bar, "
f"{100.0 * 2 * u_ind / (P1 - P2):.0f} % of the drop")
# shared reference: its error acts on both readings, so only the difference feels it
var_rest = sum(r[5]**2 for r in rows1[:-1]) + sum(r[5]**2 for r in rows2[:-1])
c_ref = rows1[-1][4] - rows2[-1][4]
u_ref_diff = c_ref * rows1[-1][3]
u_shared = np.sqrt(var_rest + u_ref_diff**2)
print(f" shared reference: reference term {u_ref_diff:.5f} bar, "
f"u = {u_shared:.4f} bar, U = {2 * u_shared:.3f} bar")
vref_same = VREF * (1.0 + rng.uniform(-0.005, 0.005, N))
d_sim = simulate(P1, N, vref_true=vref_same) - simulate(P2, N, vref_true=vref_same)
print(f" simulated, shared reference: standard deviation {d_sim.std():.4f} bar")
rows_dp = budget(P1 - P2, span=1.0)
u_dp = combine(rows_dp)
print(f" one differential transmitter, 0 to 1 bar: u = {u_dp:.5f} bar, "
f"U = {2 * u_dp:.4f} bar, {100.0 * 2 * u_dp / (P1 - P2):.1f} % of the drop")
print(f" ratio of the two expanded uncertainties: {u_shared / u_dp:.0f}")
# ---------- Plot ----------
names = [r[0] for r in rows]
share = [100.0 * r[5]**2 / uc**2 for r in rows]
order = np.argsort(share)
fig, ax = plt.subplots(1, 2, figsize=(10, 4.2))
ax[0].barh([names[i] for i in order], [share[i] for i in order])
ax[0].set_xlabel("share of the variance (%)")
ax[0].set_title("Budget at 4.0 bar")
ax[1].hist(ind - P, bins=120, density=True)
for x in (-2 * uc, 2 * uc):
ax[1].axvline(x, color="black", linestyle="--")
ax[1].set_xlabel("error of the indication (bar)")
ax[1].set_title("Simulated errors, dashed lines at +/- U")
fig.tight_layout()
fig.savefig("uncertainty_budget.png", dpi=120)
print("Saved uncertainty_budget.png")

Expected output

At 4.0 bar: 10.4 mA, 1.560 V, 1936 counts
Budget at 4.0 bar, 40 degC, one year after calibration
source limit u c u*c (bar) share
accuracy 0.0500 bar 0.02887 1.000000 0.02887 51.0 %
temperature 0.0300 bar 0.01732 1.000000 0.01732 18.4 %
drift 0.0200 bar 0.01155 1.000000 0.01155 8.2 %
resistor 0.1500 ohm 0.08660 0.043333 0.00375 0.9 %
ADC step 0.5000 count 0.28868 0.003357 0.00097 0.1 %
reference 0.0165 V 0.00953 1.969697 0.01876 21.6 %
combined standard uncertainty u_c = 0.0404 bar
expanded uncertainty U = 2 u_c = 0.0808 bar
result: 4.00 bar +/- 0.08 bar (k = 2), 2.0 % of the reading
sum of all the limits (worst case): 0.1407 bar
as built: u_c = 0.04042, U = 0.0808 bar
smallest term halved (13-bit ADC): u_c = 0.04041, U = 0.0808 bar
largest term halved (0.25 % of span): u_c = 0.03176, U = 0.0635 bar
Simulation of 400000 instruments at 4.0 bar
standard deviation 0.0404 bar, inside +/- U: 96.1 %
Pressure drop from two transmitters
u(P1) = 0.0404 bar, u(P2) = 0.0400 bar
separate references: u = 0.0569 bar, U = 0.114 bar, 38 % of the drop
shared reference: reference term 0.00087 bar, u = 0.0506 bar, U = 0.101 bar
simulated, shared reference: standard deviation 0.0506 bar
one differential transmitter, 0 to 1 bar: u = 0.00391 bar, U = 0.0078 bar, 2.6 % of the drop
ratio of the two expanded uncertainties: 13
Saved uncertainty_budget.png

The column c is the sensitivity coefficient and u*c is the contribution in bar. The simulated distribution is a sum of rectangular terms, so its tails are slightly shorter than normal. That is why 96.1 percent, a little more than 95 percent, falls inside ±.

Common Mistakes



  • Putting a maker’s ± limit into the root sum of squares without dividing by , or dividing a standard deviation that needs no divisor. Decide for every row whether the figure is a limit, a standard deviation or an expanded uncertainty.
  • Applying a percentage tolerance of the resistor or the reference to the pressure reading. In a 4 to 20 mA chain it acts on the whole current, which includes the 4 mA live zero, so its effect in bar is larger than the same percentage of the pressure.
  • Writing “±0.08 bar” with no coverage factor. The reader cannot tell whether it is one standard deviation, two, or a limit.
  • Subtracting two readings and quoting the uncertainty of one of them. The variances add in a difference, and the relative uncertainty of a small difference can be very large.

Summary



  • An uncertainty is a calculated statement of how large the unknown error could reasonably be. A result needs one before it can prove anything.
  • Every source is first turned into a standard uncertainty: or from readings (Type A), and a limit divided by , or a certificate value divided by its , from documents (Type B).
  • Each standard uncertainty is multiplied by its sensitivity coefficient to bring it into the unit of the result, and the contributions combine by the root sum of squares when the sources are independent.
  • The expanded uncertainty is , and the result is written as value ± with stated. For the transmitter at 4.0 bar it is 4.00 bar ± 0.08 bar (k = 2).
  • The largest variance share decides the result. Halving the ADC step changed nothing, and halving the transmitter’s limit reduced from 0.081 to 0.064 bar.
  • A difference of two large readings carries the uncertainty of both. Measure a small difference directly where you can.

Exercises



1. Convert each statement to a standard uncertainty: (a) a thermometer with a maker’s limit of ±0.3 °C, (b) a calibration certificate that states °C with , (c) the mean of 10 readings whose standard deviation is 0.08 °C.

Answer

(a) Rectangular: °C. (b) °C. (c) °C.

2. The three sources of exercise 1 act on one temperature result, each with a sensitivity coefficient of 1. Find the expanded uncertainty for . Which source dominates?

Answer

°C and °C. The maker’s limit dominates: its share is , about 90 percent of the variance.

3. The power of a single-phase heater is found from . The voltage is 230 V with a relative standard uncertainty of 0.5 percent. The current is 12.0 A with a relative standard uncertainty of 1.0 percent. Find the power and its expanded uncertainty () in watts.

Answer

W. For a product the relative uncertainties combine: percent, which is 30.9 W. Then W, so (k = 2).

4. Repeat the budget of Application 1 for an indication of 8.0 bar, with all other data unchanged. Which term is now the largest?

Answer

The current is 16.8 mA. The three transmitter terms are unchanged (0.02887, 0.01732, 0.01155 bar) and so is the ADC term (0.00097 bar). The resistor term is bar and the reference term is bar. Then bar and bar, so (k = 2). The reference voltage is now the largest term, with 41 percent of the variance.

5. A chilled water circuit has a supply temperature of 7.0 °C and a return temperature of 12.0 °C. Each is measured with an independent standard uncertainty of 0.15 °C. Find the temperature difference with its expanded uncertainty (), in °C and as a percent of the difference. Repeat for a day when the difference is only 2.0 °C.

Answer

°C, so °C. The difference is °C (k = 2), which is 8.5 percent. With a difference of 2.0 °C the same 0.42 °C is 21 percent.

References



  • JCGM 100:2008, Evaluation of Measurement Data: Guide to the Expression of Uncertainty in Measurement (GUM), Joint Committee for Guides in Metrology, 2008.
  • JCGM 200:2012, International Vocabulary of Metrology: Basic and General Concepts and Associated Terms (VIM), 3rd edition, Joint Committee for Guides in Metrology, 2012.
  • R. S. Figliola and D. E. Beasley, Theory and Design for Mechanical Measurements, 6th edition, Wiley, 2015.
  • J. P. Bentley, Principles of Measurement Systems, 4th edition, Pearson Education, 2005.


© 2021-2026 SiliconWit®. All rights reserved.
pressure P Transmitter 0 to 10 bar I 4 to 20 mA 150 Ω sense resistor V 12-bit ADC N accuracy, temperature, drift tolerance 0.1 % 3.3 V reference 0.5 %, and one count of step
Rectangular: any value inside is equally likely u = a / √3 −a 0 +a Triangular: values near the centre are more likely u = a / √6 −a 0 +a
flow Filter T1 P1 = 4.00 bar T2 P2 = 3.70 bar drop = P1 − P2 = 0.30 bar
Watch it build: one source through the budget
sense resistor, 0.1 % of 150 Ω limit ±0.150 Ω ÷ √3 0.0866 Ω × 0.0433 0.0038 bar with 5 others 0.0404 bar × k = 2 U 0.081 bar its share 0.9 %
  1. A maker's limit: the sense resistor is within ±0.150 Ω, which is 0.1 % of 150 Ω.
  2. A limit and nothing more is rectangular: divide by √3 to get u = 0.0866 Ω.
  3. The sensitivity coefficient turns ohms into bar: 0.0866 × 0.0433 = 0.0038 bar.
  4. Square it, add the five other squares, take the root: uc = 0.0404 bar.
  5. Multiply by k = 2: U = 0.081 bar, so the result is 4.00 bar ± 0.08 bar.
  6. The resistor holds only 0.9 % of the variance, so halving it changes nothing you can see.
Predict first

A pressure reading has six sources of uncertainty. One of them is the step of a 12-bit converter. You replace it with a 13-bit converter, so that this one term is halved. What happens to the uncertainty of the reading?

See it: the budget at 4.0 bar, term by term

Combined standard uncertainty, u_c
Expanded uncertainty, U (k = 2)
Simple sum of the limits
Result
Dominant term

Each slider is the limit of one source, from zero to three times the lesson's value. Every limit here is a maker's limit, so it is divided by √3 and multiplied by its sensitivity coefficient to give a contribution in bar. The bar of a row is its share of the variance: its contribution squared, divided by the sum of all six squares. The gold bar is the dominant term. The simple sum adds the six limits in bar as if all were at their worst with the same sign. It has no stated coverage.

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. A datasheet gives the accuracy of a transmitter as ±0.050 bar and says nothing more. What standard uncertainty goes into the budget?

2. The 0 to 10 bar transmitter reads 4.0 bar, which is 10.4 mA. The reference voltage of the converter has a tolerance of ±0.5 percent. What is this limit in bar?

3. In the lesson's budget U = 0.0808 bar, and the maker's accuracy holds 51 percent of the variance. You fit a transmitter with half the limit (±0.025 bar). What is the new expanded uncertainty?

doubt A: 4doubt B: 3together: 5, not 7 √(4² + 3²) = 5
51%22%18%8%1%0.1% accuracyreferencetemperaturedriftresistorADC Halve the biggest: ±0.08 becomes ±0.06 bar.