What a Reading Is Worth: Accuracy, Precision and Resolution

Lesson 1 of 10 25 min read
Found this useful?

Two meters on one pipe show different numbers, and nobody on site knows which to believe. One person trusts the meter with more digits, another trusts the newer one, and the pump setting is changed on a guess. The cost comes later: a report that a client rejects, a pump that is replaced when only its gauge was wrong, an energy saving that cannot be shown. This lesson gives the exact words for what a reading is worth, and the arithmetic: turn a maker’s figure into a pressure, choose a range for a real line, and find from ten readings which part of an error can be removed. #Instrumentation #Measurement #Accuracy

Learning Objectives

By the end of this lesson, you will be able to:

  1. Define measurand, indication, error, accuracy, trueness, precision and resolution as the international vocabulary defines them
  2. Convert a limit stated as a percent of span into a percent of the reading at any point of the range
  3. Choose an instrument range for a given working band and a required limit of error
  4. Separate bias from repeatability in a set of repeated readings taken against a reference
  5. Recognise zero error, span error, non-linearity and hysteresis in calibration data

Real-World System Problem: Two pressure instruments on one booster pump line



A booster pump supplies a building, and its controller must hold 4.0 bar in the discharge line. Two instruments are fitted to that line. An old dial gauge with a range of 0 to 16 bar shows 4.1 bar. A pressure transmitter with a range of 0 to 10 bar sends its signal to the controller, which shows 3.90 bar. One instrument says the pressure is above the setpoint and the other says it is below.

The argument about which is “more accurate” is usually settled by the number of digits on the display. That is the wrong test. The dial gauge is of class 1.6: its error may be as large as 1.6 percent of its 16 bar span, 0.26 bar. The maker of the transmitter states ±0.5 percent of its 10 bar span, 0.05 bar. So the gauge says only that the pressure is between 3.84 and 4.36 bar, and the transmitter that it is between 3.85 and 3.95 bar. They do not contradict each other: both put the pressure near 3.9 bar, and one says it much more closely.

TGPumpdial gaugetransmitter0to16bar0to10barshows 4.1shows 3.904to20mAbuilding
Two instruments on one pipe

Fundamental Theory: The words for the quality of a reading



The terms in this course have the meanings given in the International Vocabulary of Metrology, known as the VIM (JCGM 200:2012). Everyday speech on site is looser, and the difference causes real disputes, so the places where the two differ are pointed out.

Measurand, indication and error

The measurand is the quantity that is intended to be measured: here, the gauge pressure of the water at the tapping point. The indication is what the instrument shows. The two are never exactly equal.

Error

A positive error means the instrument reads high. The true value is never known exactly, so in practice it is replaced by a reference value from a better instrument.

If the error were known, you would subtract it and the problem would end. It is not known. What a maker can state is a limit that the error should not pass.

Accuracy, trueness and precision

Measure the same pressure ten times. The indications differ a little from each other, and their average differs a little from the true value: two separate faults, with separate names.

  • Trueness is the closeness of the average of many indications to the true value. The amount by which the average is wrong is the bias, also called the systematic error. Bias has a sign and a unit, for example +0.03 bar.
  • Precision is the closeness of repeated indications to each other. It says nothing about the true value. It is expressed by a standard deviation, the typical distance of one reading from the average of all of them (the formula comes later in this lesson): a small standard deviation is a high precision.
  • Accuracy is the closeness of one indication to the true value. A reading is accurate only when the instrument is both true and precise.

The target board is the usual picture. The cross is the true value and each dot is one reading.

• ••+ •• ••• ••• + ••• ••••••+ •••••+••••true and preciseprecise, not truesmall bias,large bias,small spreadsmall spreadtrue, not preciseneithersmall bias,large bias,large spreadlarge spread
Four sets of readings around one true value

The top right board matters most in practice: the instrument repeats so well that its user trusts it, and every reading is wrong by the same amount. Repeating a measurement cannot find a bias; only a comparison with a reference can.

Repeatability and reproducibility

Precision depends on how much is allowed to change between the readings.

Repeatability is the precision when nothing is changed: the same instrument, the same person, the same place and method, readings taken one after another in a short time. Reproducibility is the precision when conditions do change: another day, another person, another ambient temperature, another instrument of the same model. Reproducibility is always the worse of the two. When a datasheet or a report gives a spread, ask which one it is.

Resolution is not accuracy

Resolution is the smallest change of the measurand that gives a noticeable change of the indication. On a digital display it is one step of the last digit. On an analogue to digital converter (ADC) it is one count.

Resolution says how finely an instrument divides its range, not where the divisions are: a ruler with fine millimetre marks, glued a few millimetres from its end, still reads wrong. The transmitter of this lesson is read through a 12-bit ADC with a 3.3 V reference, across a 150 Ω resistor. One count is , which corresponds to 0.0034 bar. The maker’s limit of error is 0.05 bar, about 15 counts. The display may show 3.903 bar, but the true pressure can be anywhere from 3.853 to 3.953 bar: the last digit carries no information, and the one before it very little.

Range, span and the two kinds of percentage

The range of an instrument is stated by its two end values: 0 to 10 bar. The span is the difference between them: 10 bar. For a range of 2 to 10 bar the span is 8 bar.

Makers state a limit of error in one of two ways, and the two behave very differently.

  • Percent of span (also called percent of full scale): the limit is a fixed amount in the unit of the measurand, the same at every point of the range. Most pressure, level and temperature transmitters are stated this way.
  • Percent of reading: the limit is a fixed fraction of the present value, so it becomes smaller as the reading falls. Energy meters and many flow meters are stated this way.

From percent of span to percent of reading

Here is the limit in percent of span and is the same limit written in percent of the reading. For a range that starts at zero, at half of the span the percentage doubles, and at one tenth of the span it is ten times larger.

0246810 bar2.0±0.05bar8.0±0.05bar2.5 % of reading0.63 % of reading
One band of ±0.05 bar along a 0 to 10 bar range

So an instrument with a wide range is poor at the bottom of it: the fixed band does not shrink when the reading does. A person who buys a 0 to 25 bar transmitter “to be safe” for a line that runs at 3 bar has bought a limit of error more than four times larger than a 0 to 6 bar transmitter of the same class gives.

Static characteristics: zero, span, linearity and hysteresis

An ideal transmitter gives an indication equal to the true value at every point of its range: a straight line through the origin with a slope of one. A real transmitter departs from that line in four recognisable ways. They are called static characteristics because they are found with the measurand held steady at each test point.

Zero error is a shift of the whole line. The instrument reads, for example, 0.02 bar high at every point, including at zero pressure. Span error is a wrong slope. The error is zero at the bottom of the range and grows in proportion to the reading.

indicationindicationzero errorspan erroridealidealtrue valuetrue value
Zero error and span error against the ideal line

Non-linearity is what remains after zero and span are correct: the line is curved, so the error is zero at both ends and largest somewhere between them. Hysteresis is a difference between the indication reached with the pressure rising and the indication reached at the same pressure with it falling. Friction in a mechanism and slow recovery of a diaphragm both cause it.

Zero and span errors are biases with a simple form, so they can be adjusted or corrected in software. Non-linearity needs a correction curve. Hysteresis cannot be corrected, because the instrument does not know from which direction the pressure arrived. A maker’s limit such as ±0.5 percent of span normally covers non-linearity, hysteresis and repeatability together, at the reference temperature and on the day of calibration. Temperature effects and drift over the years are stated separately and are added to it.

Finding bias and repeatability from readings

Hold the measurand steady, connect a reference instrument to the same point, and take readings . Three numbers summarise them.

Mean, bias and standard deviation

is the mean of the readings, is the reference value, and is the experimental standard deviation, which measures the repeatability of one reading.

The mean of readings is itself uncertain, because another ten readings would give a slightly different mean. Its standard deviation is . Compare the bias with this value. A bias several times larger than is real. A bias of about the same size could be chance.

Application 1: The same limit at two pressures, and the choice of a range



Step 1: The limit in bar and in milliamperes

Click to reveal the limit of error
  1. Span. The range is 0 to 10 bar, so the span is 10 bar. ✅

  2. Limit in bar.

    The error should not pass ±0.05 bar at any pressure in the range. ✅

  3. Limit as a current. The output span is .

    A loop current that is within 0.08 mA of the ideal value is within the maker’s limit. ✅

  4. Ideal currents. The current for a pressure is in milliamperes.

    These are the currents a perfect transmitter would give. ✅

Step 2: The same limit as a percent of the reading

Click to reveal the percent of reading
  1. At 2.0 bar.

    The true pressure is between 1.95 and 2.05 bar. ✅

  2. At 8.0 bar.

    The true pressure is between 7.95 and 8.05 bar. Rounded, this is 0.63 percent. ✅

  3. Compare. The band of ±0.05 bar is the same in both cases. As a fraction of the reading it is four times worse at 2.0 bar, because the reading is four times smaller. ✅

Step 3: Choose the range for the line at 3 to 5 bar

The worst point of the working band is its bottom, 3 bar, because the percentage of reading is largest there.

Click to reveal the choice of range
  1. Limit of each range in bar.

    The limit grows in proportion to the span. ✅

  2. Percent of reading at 3 bar and at 5 bar.

    RangeLimitAt 3 barAt 5 bar5.6 bar as a share of span
    0 to 6 bar±0.03 bar1.00 %0.60 %93 %
    0 to 10 bar±0.05 bar1.67 %1.00 %56 %
    0 to 16 bar±0.08 bar2.67 %1.60 %35 %

    Only the 0 to 6 bar range stays at or below 1.5 percent of reading through the whole band. ✅

  3. Check the top of the range. The highest pressure, 5.6 bar, is inside the 0 to 6 bar range, at 93 percent of its span. The transmitter is not driven past its range. ✅

  4. Choice. The 0 to 6 bar transmitter meets both conditions. The 0 to 10 bar transmitter fails at the bottom of the band, and the 0 to 16 bar transmitter fails through the whole band. ✅

  5. Check a second way. Reverse the question and ask at what pressure each range reaches 1.5 percent of reading.

    The 0 to 6 bar range is good from 2.00 bar upwards, which covers the band. The 0 to 10 bar range fails from 3 to 3.33 bar. The 0 to 16 bar range is good only above 5.33 bar, outside the band. The Python script prints the same three pressures. ✅

Application 2: Bias and repeatability from ten readings



Step 1: Mean and bias

Click to reveal the bias
  1. Sum and mean. The ten readings add to 40.30 bar.

    The mean indication is 4.030 bar. ✅

  2. Bias.

    On average the transmitter reads 0.030 bar high at this pressure. ✅

Step 2: Repeatability

Click to reveal the standard deviation
  1. Deviations from the mean. In units of 0.01 bar the ten deviations are . They add to zero, as deviations from a mean must. ✅

  2. Sum of squares. , in units of . ✅

  3. Standard deviation. Divide by , not by 10, because the mean was calculated from the same readings.

    One reading of this transmitter scatters with a standard deviation of about 0.012 bar. This is its repeatability at 4 bar. ✅

  4. Standard deviation of the mean.

    The mean of ten readings is known about three times better than one reading. ✅

Step 3: Is the bias real, and is the transmitter within its limit?

Click to reveal the judgement
  1. Compare the bias with the uncertainty of the mean.

    The bias is about eight times larger than the scatter of the mean can explain. It is real and not a matter of chance. ✅

  2. Compare each error with the maker’s limit. The single errors run from bar to bar. The limit is ±0.05 bar. Nine readings are inside the limit, and the largest one is exactly on it. The display shows steps of 0.01 bar, so a shown +0.05 bar can be a true error anywhere from +0.045 to +0.055 bar. Write this result as “on the limit, not a clear pass”: the reading at +0.05 bar cannot prove the transmitter is inside it. ✅

  3. What a correction gains. Subtract the bias, 0.030 bar, from every reading. The corrected readings run from 3.98 to 4.02 bar, so the errors that remain are within ±0.02 bar. ✅

  4. Check a second way. The mean of the squared errors can be split into a part from bias and a part from spread:

    The left side, from the ten errors in units of 0.01 bar, is . The right side is . The two agree, and the bias carries percent of the total. The script reports the same share. ✅

Verify It in Python



The script repeats both applications: the limit of error at 2.0 bar and at 8.0 bar, the three ranges tested against 1.5 percent of reading, and the bias and repeatability of the ten readings. It saves two plots in one image: the percent of reading along the range for the three transmitters, and the ten readings against the reference.

reading_worth.py
"""Percent of span against percent of reading, and bias against repeatability."""
import numpy as np
import matplotlib.pyplot as plt
# ---------- Part 1: one limit of error, seen at different pressures ----------
ACC = 0.5 # maker's limit of error, percent of span
SPAN_A = 10.0 # bar, the transmitter of the problem
def limit_bar(span, acc=ACC):
"""Limit of error in bar for a transmitter of the given span."""
return acc / 100.0 * span
def percent_of_reading(span, pressure, acc=ACC):
"""The same limit written as a percentage of the reading."""
return 100.0 * limit_bar(span, acc) / pressure
print("Transmitter 0 to 10 bar, limit 0.5 percent of span")
print(f" limit of error: {limit_bar(SPAN_A):.3f} bar at every pressure")
for p in (2.0, 8.0):
current = 4.0 + 16.0 * p / SPAN_A
print(f" at {p:.1f} bar: {current:.1f} mA, limit "
f"{percent_of_reading(SPAN_A, p):.3f} percent of reading, "
f"true value between {p - limit_bar(SPAN_A):.2f} and "
f"{p + limit_bar(SPAN_A):.2f} bar")
print(f" limit as current: {16.0 * ACC / 100.0:.3f} mA")
P_LOW, P_HIGH, P_MAX = 3.0, 5.0, 5.6 # bar: working band and highest pressure
TARGET = 1.5 # percent of reading allowed
print("Choice of range for a line at 3 to 5 bar")
for span in (6.0, 10.0, 16.0):
worst = percent_of_reading(span, P_LOW)
ok = "meets" if worst <= TARGET and P_MAX <= span else "fails"
print(f" 0 to {span:>4.1f} bar: limit {limit_bar(span):.3f} bar, "
f"{worst:.2f} % at 3 bar, {percent_of_reading(span, P_HIGH):.2f} % at 5 bar, "
f"5.6 bar is {100.0 * P_MAX / span:.0f} % of span, {ok}")
for span in (6.0, 10.0, 16.0):
print(f" 0 to {span:>4.1f} bar reaches {TARGET} % of reading at "
f"{limit_bar(span) / (TARGET / 100.0):.2f} bar and above")
better = percent_of_reading(10.0, P_LOW, acc=0.25)
print(f" 0 to 10 bar at 0.25 % of span: limit {limit_bar(10.0, 0.25):.3f} bar, "
f"{better:.2f} % at 3 bar")
# Resolution of the 12-bit converter that reads the 0 to 10 bar transmitter
count_volt = 3.3 / 4096.0
count_bar = count_volt / 150.0 * 1000.0 / 16.0 * SPAN_A
print(f" one ADC count: {1000.0 * count_volt:.3f} mV = {count_bar:.5f} bar, "
f"the limit of error is {limit_bar(SPAN_A) / count_bar:.1f} counts")
# ---------- Part 2: ten readings against a reference ----------
REFERENCE = 4.000 # bar, from the reference gauge
MAKER_LIMIT = 0.05 # bar
readings = np.array([4.03, 4.02, 4.04, 4.03, 4.01, 4.03, 4.05, 4.02, 4.03, 4.04])
n = readings.size
mean = readings.mean()
bias = mean - REFERENCE
s = readings.std(ddof=1) # experimental standard deviation
u_mean = s / np.sqrt(n) # standard uncertainty of the mean
errors = readings - REFERENCE
corrected = readings - bias
print("Ten readings against a reference of 4.000 bar")
print(f" mean {mean:.4f} bar, bias {bias:+.4f} bar")
print(f" standard deviation s = {s:.4f} bar (repeatability)")
print(f" standard uncertainty of the mean s/sqrt(n) = {u_mean:.4f} bar")
print(f" bias is {bias / u_mean:.1f} times the uncertainty of the mean")
print(f" errors from {errors.min():+.2f} to {errors.max():+.2f} bar, "
f"maker's limit {MAKER_LIMIT:.2f} bar")
print(f" share of the mean square error from bias: "
f"{100.0 * bias**2 / np.mean(errors**2):.0f} %")
print(f" after the correction of {-bias:+.3f} bar: errors from "
f"{(corrected - REFERENCE).min():+.2f} to {(corrected - REFERENCE).max():+.2f} bar")
# ---------- Plot ----------
fig, ax = plt.subplots(2, 1, figsize=(8, 7))
p = np.linspace(0.5, 16.0, 400)
for span in (6.0, 10.0, 16.0):
inside = p <= span
ax[0].plot(p[inside], percent_of_reading(span, p[inside]),
label=f"0 to {span:.0f} bar")
ax[0].axhline(TARGET, color="gray", linewidth=0.8)
ax[0].axvspan(P_LOW, P_HIGH, color="gray", alpha=0.15)
ax[0].set_ylim(0, 6)
ax[0].set_xlabel("pressure (bar)")
ax[0].set_ylabel("limit of error (% of reading)")
ax[0].set_title("The same 0.5 % of span, as a percentage of the reading")
ax[0].legend()
ax[1].plot(np.arange(1, n + 1), readings, "o", label="readings")
ax[1].axhline(REFERENCE, color="black", label="reference")
ax[1].axhline(mean, color="tab:red", linestyle="--", label="mean of readings")
ax[1].axhline(REFERENCE + MAKER_LIMIT, color="gray", linewidth=0.8)
ax[1].axhline(REFERENCE - MAKER_LIMIT, color="gray", linewidth=0.8)
ax[1].set_xlabel("reading number")
ax[1].set_ylabel("indication (bar)")
ax[1].set_title("Bias (mean against reference) and repeatability (spread)")
ax[1].legend()
fig.tight_layout()
fig.savefig("reading_worth.png", dpi=120)
print("Saved reading_worth.png")

Expected output

Transmitter 0 to 10 bar, limit 0.5 percent of span
limit of error: 0.050 bar at every pressure
at 2.0 bar: 7.2 mA, limit 2.500 percent of reading, true value between 1.95 and 2.05 bar
at 8.0 bar: 16.8 mA, limit 0.625 percent of reading, true value between 7.95 and 8.05 bar
limit as current: 0.080 mA
Choice of range for a line at 3 to 5 bar
0 to 6.0 bar: limit 0.030 bar, 1.00 % at 3 bar, 0.60 % at 5 bar, 5.6 bar is 93 % of span, meets
0 to 10.0 bar: limit 0.050 bar, 1.67 % at 3 bar, 1.00 % at 5 bar, 5.6 bar is 56 % of span, fails
0 to 16.0 bar: limit 0.080 bar, 2.67 % at 3 bar, 1.60 % at 5 bar, 5.6 bar is 35 % of span, fails
0 to 6.0 bar reaches 1.5 % of reading at 2.00 bar and above
0 to 10.0 bar reaches 1.5 % of reading at 3.33 bar and above
0 to 16.0 bar reaches 1.5 % of reading at 5.33 bar and above
0 to 10 bar at 0.25 % of span: limit 0.025 bar, 0.83 % at 3 bar
one ADC count: 0.806 mV = 0.00336 bar, the limit of error is 14.9 counts
Ten readings against a reference of 4.000 bar
mean 4.0300 bar, bias +0.0300 bar
standard deviation s = 0.0115 bar (repeatability)
standard uncertainty of the mean s/sqrt(n) = 0.0037 bar
bias is 8.2 times the uncertainty of the mean
errors from +0.01 to +0.05 bar, maker's limit 0.05 bar
share of the mean square error from bias: 88 %
after the correction of -0.030 bar: errors from -0.02 to +0.02 bar
Saved reading_worth.png

In the upper plot only the 0 to 6 bar curve is under the 1.5 percent line through the whole shaded band. In the lower plot the dashed mean line is above the reference line by the bias, and the dots scatter round the mean by the repeatability.

Common Mistakes



  • Judging an instrument by the number of digits it shows. Digits are resolution. The maker’s limit of error is found on the datasheet, not on the display.
  • Reading “±0.5 percent” as 0.5 percent of the present value when the datasheet means percent of span. At one fifth of the span the limit is 2.5 percent of the reading.
  • Choosing a range far wider than the working pressure “for safety”. The limit of error in bar grows in proportion to the span. Choose the smallest range that contains the highest pressure, and check the overpressure rating.
  • Believing that readings which repeat well must be correct. Repeated readings show precision only. A bias appears only in a comparison with a reference.
  • Averaging many readings to remove an error. Averaging reduces the spread by and leaves the bias exactly as it was.

Summary



  • Error is the indication minus the true value. It is never known exactly, so makers state a limit for it.
  • Accuracy is a quality with two parts: trueness (a small bias) and precision (a small spread). Precision under unchanged conditions is repeatability, and under changed conditions it is reproducibility.
  • Resolution is the smallest change an instrument can show. It is not accuracy, and many digits do not make a reading true.
  • A limit in percent of span is a fixed band in engineering units. Written as a percent of reading it grows as the reading falls, so the range must be matched to the working band.
  • Ten readings against a reference give the bias (mean minus reference) and the repeatability (standard deviation). A known bias can be corrected, and the spread cannot.
  • Zero error, span error, non-linearity and hysteresis are the four ways a real instrument leaves the ideal straight line.

Exercises



1. A pressure transmitter has a range of 0 to 25 bar and a maker’s accuracy of ±0.25 percent of span. Find the limit of error in bar, and as a percent of the reading at 5 bar.

Answer

The limit is bar. At 5 bar this is percent of the reading.

2. Flow meter X has a limit of ±0.5 percent of its span of 0 to 100 m³/h. Flow meter Y has a limit of ±1 percent of reading. Below what flow does meter Y have the smaller limit? Give the limit of each at 20 m³/h.

Answer

Meter X has a fixed limit of 0.5 m³/h. Meter Y has a limit of . They are equal at m³/h, so Y is better below 50 m³/h. At 20 m³/h, X is ±0.5 m³/h (2.5 percent of reading) and Y is ±0.2 m³/h.

3. A transmitter is compared with a reference that shows 6.050 bar. Eight indications are recorded: 6.12, 6.10, 6.13, 6.11, 6.12, 6.14, 6.11, 6.13 bar. Find the bias, the repeatability and the standard deviation of the mean.

Answer

The mean is bar, so the bias is bar. The deviations in units of 0.01 bar are , with a sum of squares of 12, so bar. The standard deviation of the mean is bar. The bias is 15 times that value, so it is real.

4. A line runs between 6 bar and 9 bar and can reach 11 bar. Transmitters of ±0.5 percent of span are available in ranges of 0 to 10 bar, 0 to 16 bar and 0 to 25 bar. The limit must not pass 1.5 percent of reading in the working band. Choose the range.

Answer

The 0 to 10 bar range does not contain 11 bar. The 0 to 16 bar range has a limit of 0.08 bar, which is percent at 6 bar: it passes. The 0 to 25 bar range has a limit of 0.125 bar, which is 2.08 percent at 6 bar: it fails. Choose 0 to 16 bar.

5. A 0 to 10 bar transmitter with a limit of ±0.05 bar is tested against a reference at five points, first with the pressure rising and then with it falling.

Reference (bar)02.55.07.510.0
Rising (bar)0.022.535.047.5510.06
Falling (bar)0.032.565.087.5810.06

From the rising readings find the zero error and the span error. Find the largest hysteresis. Does the transmitter pass?

Answer

Zero error: bar (the error at 0 bar). Span error: the indicated span is bar against a true span of 10 bar, so bar, which is 0.4 percent of span. Hysteresis is the falling reading minus the rising reading at the same point: 0.01, 0.03, 0.04, 0.03 and 0 bar, so the largest is 0.04 bar at 5 bar. The largest error is bar (falling, at 5.0 and at 7.5 bar), which is outside ±0.05 bar. The transmitter fails.

References



  • JCGM 200:2012, International Vocabulary of Metrology: Basic and General Concepts and Associated Terms (VIM), 3rd edition, Joint Committee for Guides in Metrology, 2012.
  • J. P. Bentley, Principles of Measurement Systems, 4th edition, Pearson Education, 2005.
  • R. S. Figliola and D. E. Beasley, Theory and Design for Mechanical Measurements, 6th edition, Wiley, 2015.


© 2021-2026 SiliconWit®. All rights reserved.
Pump building G dial gauge 0 to 16 bar shows 4.1 bar T 4 to 20 mA transmitter 0 to 10 bar shows 3.90 bar
true and precise small bias, small spread precise, not true large bias, small spread true, not precise small bias, large spread neither large bias, large spread
indication true value ideal zero error the same offset at every point indication true value ideal span error the error grows with the value
Watch it build: percent of span, percent of reading
0246810 range 0 to 10 bar, span 10 bar ±0.05 bar at every point 1 % of reading grows with it ±0.02 bar at 2, ±0.08 bar at 8 2.5 % 0.63 % the same ±0.05 bar, as % of reading 1 % of a 16 bar span: ±0.16 bar 1 % of 4 bar: ±0.04 bar at 4 bar: which percent?
  1. A range of 0 to 10 bar has a span of 10 bar.
  2. Percent of span: 0.5 % of 10 bar is a band of ±0.05 bar, the same at every point.
  3. Percent of reading: the band grows with the value, ±0.02 bar at 2 bar for 1 %.
  4. The fixed ±0.05 bar is 2.5 % of a 2 bar reading and 0.63 % of an 8 bar one.
  5. Say which: 1 % of a 16 bar span is ±0.16 bar, 1 % of a 4 bar reading is ±0.04 bar.
Predict first

A transmitter gives ten readings of one steady pressure. All ten agree within 0.02 bar. What does this tell you?

See it: bias, spread, and one fixed band
Target board: 30 readings

Mean error (bias found)
Standard deviation, s
Doubt of the mean, s/√30
Inside ±0.05 bar
The same band along the range

Limit of error
Percent of span0.50 %
Percent of reading

The board: the cross is the true value. The position of a dot to the left or right of the cross is the error of that reading. The height of a dot is drawn only to make a board. The dashed lines are the maker's limit of error of the lesson's transmitter, ±0.05 bar. The solid line is the mean of the 30 readings. It is not exactly at the bias you set, because 30 readings are a sample: take 30 new ones and it moves a little. The plot: all three transmitters are ±0.5 percent of span. The band in bar is fixed, so as a percent of the reading it grows when the reading falls. The shaded band is the working band of 3 to 5 bar in Application 1, and the dashed line is its requirement of 1.5 percent of reading.

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. A transmitter has a range of 0 to 16 bar and a maker's accuracy of ±0.5 percent of span. It is used at 3 bar. What is the limit of error as a percent of the reading?

2. Ten readings against a reference give a bias of +0.030 bar and a standard deviation of 0.0115 bar. You take 100 readings and use their mean. What happens to the bias and to the standard deviation of the mean?

3. The 0 to 10 bar transmitter (±0.5 percent of span) is read by a 12-bit converter. One count is 0.0034 bar, and the display shows 3.903 bar. How closely is the true pressure known from this one reading?

true, preciseprecise, not truetrue, not preciseneither Repeating cannot find a bias. Only a reference can.
3.903 bar 3.853.903.95 one count: 0.0034 bar true value: anywhere in ±0.05 bar