Control, Measurement & Energy · Course

Calibration, Drift and Traceability

Lesson 9 of 10 26 min read
Found this useful?

A pressure transmitter carries a green sticker that says “calibrated”, dated two years ago. An auditor asks what it read against a reference on that day, and nobody can find the sheet. The technician remembers that he “set it right”, but nobody recorded how wrong it was, so the readings before that day cannot be judged either. A calibration that leaves no numbers proves nothing about the past and little about the future. This lesson shows how to run a five-point calibration, read its ten readings, decide pass or fail honestly, and choose the next calibration date from evidence. #Calibration #Traceability #Instrumentation

Learning Objectives

By the end of this lesson, you will be able to:

  1. Distinguish calibration from adjustment, and as-found data from as-left data
  2. Calculate zero error, span error, hysteresis and the largest error from a five-point calibration up and down the range
  3. Decide pass or fail against a tolerance with the uncertainty of the reference taken into account
  4. Estimate a drift rate from past as-found errors and set a calibration interval with a stated margin
  5. Read a calibration certificate and say whether it gives traceability

Real-World System Problem: A transmitter that has not been checked for two years



A booster pump line has a pressure transmitter with a range of 0 to 10 bar and an output of 4 to 20 mA. Its maker states an accuracy of ±0.5 percent of span and a long-term drift of ±0.2 percent of span per year. The site uses the reading to prove that the delivery pressure meets a contract, so the site’s tolerance for the transmitter is the same ±0.5 percent of span.

The maker’s figure describes a new instrument. Two years later, three questions are open. How large is the error today? Was the transmitter inside its tolerance for the whole period, so that the old records can be trusted? When must it be checked again?

Only a comparison with a better instrument can answer them. A technician isolates the transmitter, connects a hand pump and a reference gauge to its test port, and reads the loop current with a milliammeter at known pressures.

Before the first valve is closed, two things are done. The pump controller is put into manual or its operator is told, because the controller will read the test pressures as real ones and start or stop the pump. And the trapped pressure behind the isolation valve is vented through the test port before the hand pump is connected.

Hand pumpTransmitterunder testMilliammeter(calibrated)Referencegauge(calibrated)pressure4to20mAknown input: barindication: mA
The calibration arrangement

The result is a table of differences, and it is worth exactly as much as the two references behind it.

Fundamental Theory: Comparing with a reference, and what follows from it



Calibration is not adjustment

The international vocabulary (VIM, JCGM 200:2012) keeps two acts apart, and this lesson uses its meanings.

Calibration is a comparison. Known values from a reference are applied, the indications of the instrument are recorded, and the differences are stated together with the uncertainty of the comparison. Nothing on the instrument is changed.

Adjustment is a change made to the instrument so that its indications agree better with the reference: turning the zero and span settings, or entering new values in its memory.

The common mistake is to adjust first and record afterwards. The error that the instrument had during its years of service is then lost for ever.

As-found and as-left

A full calibration has two sets of data. The as-found data are recorded before anything is touched, as a fuel gauge is read before the tank is filled. They answer the question about the past: was the instrument inside its tolerance in service? The as-left data are recorded after any adjustment and start the next period.

If the as-found error is outside the tolerance, every decision taken from that instrument since the last good calibration is in doubt and must be reviewed. This is the real cost of an interval that is too long.

Traceability

A reference gauge is itself an instrument with an error. It is trusted because it was calibrated against a better one, which was calibrated against a better one again, up to the national standard that realises the unit.

Traceability is this unbroken chain of calibrations, each with a stated uncertainty, from the reading on site to the national standard.

Transmitter on the lineSite reference gaugeAccredited laboratoryworking standardNational standard(pressure balance)smallestuncertaintylargestuncertainty
The traceability chain for a pressure reading

The uncertainty grows at each step down, because each comparison adds its own doubt to the doubt it inherits, as each photocopy of a photocopy adds a little blur. Unlike the blur, this doubt is stated as a number on each certificate. Traceability is proved by documents. A reference gauge without a current certificate breaks the chain, however good the gauge is.

How good must the reference be

The reference must be clearly better than the instrument under test. The old guideline asks for a ratio of at least 4 to 1.

Test uncertainty ratio

is the tolerance of the instrument under test (the half-width, such as 0.5 percent of span). is the expanded uncertainty () of the whole comparison: every reference instrument used, combined by the root sum of squares. Both are in the same unit.

At 4 to 1 or better, the doubt of the reference is small beside the tolerance and is usually ignored. The guideline gives no method for a lower ratio, which good field references often have.

Modern practice compares the uncertainties directly, with a stated decision rule. The simplest rule takes off the tolerance to give an acceptance limit; the strip between the two is a guard band:

−T−A+A+Tfailnotpassnotfailproven0provenguard band = U of the reference
Three zones for the measured error

Picture the found error as a point with a bar of ± around it: the true error is somewhere on the bar. An error inside ± keeps the whole bar inside the tolerance, a pass that the reference can prove. An error beyond ± is recorded as a fail. Between and the comparison cannot decide: record “inside the tolerance, not proven”, then adjust or repeat with a better reference.

A five-point calibration, up and down

One test point gives one error and cannot tell a zero error from a span error. The usual field procedure uses five points at 0, 25, 50, 75 and 100 percent of the span, first with the pressure rising, then falling. Approach each point from one side only, without passing it and coming back, or the hysteresis is hidden.

For a transmitter with a current output, the error at each point is stated in percent of span:

is the measured current and is the current that a perfect transmitter would give at the reference pressure. The ten errors then show four things.

WhatHow to find it from the ten readings
Zero errorThe error at 0 percent
Span errorMeasured span (output at 100 percent minus output at 0 percent) compared with the ideal 16 mA
HysteresisThe falling reading minus the rising reading at the same point; quote the largest
Non-linearityWhat is left of the mean errors after a straight line through the two end points is taken away

The pass or fail decision uses the largest of all ten errors, whatever its cause.

Correction

A known error can be removed without touching the instrument. A correction is the value added to an indication to compensate for a known error: the error with the opposite sign. For a zero error and a span error together, the correction is a straight line, which can go in the controller’s scaling.

A correction is not free of doubt. It carries the uncertainty of the calibration that produced it, does not remove hysteresis, and holds only until the instrument drifts again.

Drift and the calibration interval

Drift is a slow change of the error with time. A maker states a limit for it, such as ±0.2 percent of span per year. The as-found records of your own unit say how it really behaves.

The calibration interval is the time allowed between calibrations. Too long, and the instrument leaves its tolerance unseen. Too short, and money and downtime confirm what was already known. Between calibrations the error climbs with the drift; each adjustment brings it back. With a steady drift rate , an error after adjustment and an acceptance limit :

Interval from a steady drift rate

All three quantities are in percent of span, with per year, so the interval is in years. Using in place of the full tolerance keeps a margin equal to the uncertainty of the reference.

The limit of this method: drift is not always a straight line. Some sensors settle in their first year and then stay; some jump after an overpressure or a knock. A straight line through a few points is a working estimate. Review the interval at every calibration, shorten it after any as-found result outside the acceptance limit, and lengthen it only after several results in a row show room.

Reading a calibration certificate

A certificate from a laboratory is the proof of traceability for your reference. Read each part with a question.

Part of the certificateWhat to check
Laboratory and accreditation markIs the laboratory accredited (ISO/IEC 17025) for this quantity and this range?
Item, maker, model, serial numberIs it the instrument in your hand, by serial number?
Date of calibrationThe date of the work. A due date is the owner’s choice, and many laboratories do not print one.
ConditionsRoom temperature, and for pressure the medium and the position. Do they suit your use?
Reference standards usedAre they identified, with their own traceability?
Table of resultsReference value, indication and error at each point. Are these as-found, as-left, or both?
UncertaintyAn expanded uncertainty with its coverage factor, such as . This is the value for your budget.
Statement of conformityIf it says “pass”, which tolerance and which decision rule were used?

The value you take into your own budget is the expanded uncertainty. Divide it by its to obtain a standard uncertainty. If you apply the certificate’s errors as corrections, the uncertainty of the certificate replaces the maker’s much larger limit in your budget.

Field checks between calibrations

A field check is a quick comparison at one or two points. It does not replace calibration, but it catches a large change in the months between.

  • Temperature: the ice point. A stirred mixture of crushed ice and clean water, made with care, is at 0.0 °C within a few hundredths of a degree, and needs no certificate. A probe left in it for some minutes checks the sensor, the cable and the readout together at one temperature.
  • Pressure: zero and one point. With the transmitter isolated and vented to the air, a gauge transmitter must give 4.00 mA. That checks the zero. A reference gauge on the test port, or a deadweight tester, gives one known pressure for the span. A deadweight tester makes its pressure from known masses on a piston of known area.

Record every field check with its numbers. A zero that moves the same way at each visit is drift, seen early.

Application 1: Five-point as-found calibration of a pressure transmitter



Step 1: The error at each point

Click to reveal the ten errors
  1. Ideal current. A perfect transmitter gives mA: 4.00, 8.00, 12.00, 16.00 and 20.00 mA at the five pressures. ✅

  2. One step of the milliammeter. The readings are recorded to 0.01 mA, and

    so every error in the table is a whole multiple of 0.0625. ✅

  3. Errors. For example, rising at 2.50 bar: percent of span.

    Pressure (bar)Error rising (%)Error falling (%)Mean error (%)Falling minus rising (mA)
    0.00+0.25+0.25+0.250.00
    2.50+0.125+0.25+0.18750.02
    5.00+0.0625+0.1875+0.1250.02
    7.500.00+0.0625+0.03130.01
    10.00−0.0625−0.0625−0.06250.00

    The error is positive at the bottom of the range and falls steadily to a small negative value at the top. ✅

Step 2: Zero error, span error and hysteresis

Click to reveal the three characteristics
  1. Zero error. At 0 bar the transmitter gives 4.04 mA in both directions.

    ✅

  2. Span error. The measured span is mA.

    The slope is too low, so the positive error at zero shrinks as the pressure rises. ✅

  3. Hysteresis. The largest difference between falling and rising is 0.02 mA, at 2.50 and 5.00 bar.

    It is only two steps of the milliammeter, so its value is coarse. ✅

  4. Non-linearity. A straight line through the two end points gives mean errors of +0.25, +0.1719, +0.0938, +0.0156 and −0.0625 percent. The mean errors found are above that line by 0, 0.016, 0.031, 0.016 and 0 percent. The largest, 0.03 percent of span, is half of one step: no curvature can be shown with this milliammeter. ✅

  5. Largest error. The largest of the ten errors is +0.25 percent of span. It occurs at 0 bar, and again at 2.50 bar with the pressure falling. ✅

Step 3: Pass or fail, with the reference taken into account

Click to reveal the decision
  1. Plain comparison. The largest error, 0.25 percent of span, is half of the tolerance of 0.5 percent. Without any thought for the reference, the transmitter passes. ✅

  2. Uncertainty of the comparison. Put both certificates in percent of span as standard uncertainties.

    ✅

  3. Test uncertainty ratio.

    The ratio is below 4. The doubt of the references is not small beside the tolerance, so it cannot be ignored. ✅

  4. What a ratio below 4 means. An error found close to the tolerance could truly be on either side of it: with these references, a found 0.45 percent could be a true 0.29 or 0.61 percent. The decision needs a guard band. ✅

  5. Acceptance limit.

    The largest error, 0.25 percent, is inside ±0.342 percent. The transmitter passes, and these references are good enough to prove it. ✅

Step 4: The correction

Click to reveal the correction and its check
  1. Form of the correction. Take away the zero error, then stretch the measured span back to 16 mA.

    ✅

  2. At a working point. The controller receives 10.40 mA. Uncorrected, that is bar. Corrected:

    The correction is −0.013 bar at this pressure. ✅

  3. What remains. With the correction applied to all ten readings, the largest error left is 0.015 mA, which is 0.09 percent of span. It is the hysteresis and the rounding, and no correction can remove either. ✅

  4. Check a second way. The script fits a least squares line through all ten errors, not only the two end points. It finds a zero of +0.042 mA and a span error of −0.31 percent of span, the end-point result within one step. The script made the data from a zero shift of +0.04 mA, a span error of −0.3 percent and a hysteresis of 0.02 mA, and the calibration recovered all three. ✅

Application 2: The calibration interval from three years of as-found errors



Step 1: The drift rate

Click to reveal the fitted line
  1. Slope. The least squares line is the straight line that makes the sum of the squared differences between the line and the points as small as possible. For three points at equal spacing, its slope is the last value minus the first, divided by the time between them.

    ✅

  2. The line. It passes through the mean point: year 2, error percent.

    ✅

  3. Scatter. The line gives 0.0733, 0.2233 and 0.3733 percent. The differences from the record are −0.0133, +0.0267 and −0.0133. With three points and two fitted values, one degree of freedom is left:

    ✅

  4. Compare with the maker. The maker’s limit is 0.2 percent of span per year. This unit drifts at about three quarters of the limit, always in the same direction. ✅

Step 2: What the year 3 result requires

Click to reveal the decision for year 3
  1. Against the tolerance. The as-found error of 0.36 percent is inside the tolerance of 0.5 percent. ✅

  2. Against the acceptance limit. It is above the acceptance limit of 0.342 percent. The result is “inside the tolerance, not proven”. The transmitter must be adjusted now. ✅

  3. Without adjustment. The fitted line reaches 0.5 percent at years. A fourth year without adjustment would end outside the tolerance. ✅

Step 3: The interval

Click to reveal the interval and its margin
  1. Room for drift. After adjustment the error is 0.03 percent, and it must stay below 0.342 percent.

    ✅

  2. Interval at the fitted rate.

    ✅

  3. How well the rate is known. The standard error of the slope is divided by the root of the sum of squared distances of the years from their mean, which is .

    A cautious rate is percent per year, which is also close to the maker’s limit of 0.2. ✅

  4. Interval at the cautious rate.

    ✅

  5. Choice. Set the interval to 12 months. The predicted error at the next calibration is then percent at the fitted rate and 0.23 percent at the cautious rate. The margin to the acceptance limit is at least 0.11 percent of span, and the margin to the tolerance is at least 0.27 percent. ✅

  6. Check a second way. The script fits the same data with a general least squares routine and prints a rate of 0.150, a cautious rate of 0.196, and intervals of 25 and 19 months. ✅

Verify It in Python



The script makes the as-found readings of Application 1 from a known zero shift, span error and hysteresis, rounds them to 0.01 mA, and analyses them as a technician would. It then fits the three yearly errors of Application 2, and saves two plots: the ten errors against the tolerance, and the drift line against the two limits.

calibration_drift.py
"""Five-point as-found calibration of a 0 to 10 bar, 4 to 20 mA transmitter,
and a calibration interval from three years of as-found errors."""
import numpy as np
import matplotlib.pyplot as plt
SPAN_BAR = 10.0
SPAN_MA = 16.0
TOL = 0.5 # percent of span, the tolerance
# ---------- Part 1: make the as-found data from known faults ----------
ZERO_SHIFT = 0.04 # mA, known zero shift
SPAN_ERR = -0.3 # percent of span, known span error
HYST = 0.02 # mA, largest hysteresis (at mid range)
frac = np.array([0.0, 0.25, 0.50, 0.75, 1.0]) # fraction of span
p_ref = frac * SPAN_BAR # bar, reference pressure
ideal = 4.0 + SPAN_MA * frac # mA
base = ideal + ZERO_SHIFT + SPAN_ERR / 100.0 * SPAN_MA * frac
loop = HYST * 4.0 * frac * (1.0 - frac) # zero at both ends
up = np.round(base - loop / 2.0, 2) # pressure rising
down = np.round(base + loop / 2.0, 2) # pressure falling
e_up = (up - ideal) / SPAN_MA * 100.0 # percent of span
e_down = (down - ideal) / SPAN_MA * 100.0
mean_ma = (up + down) / 2.0
e_mean = (mean_ma - ideal) / SPAN_MA * 100.0
hyst = down - up
print("As-found calibration, error in percent of span")
print(" P ref ideal up down e up e down mean hyst")
print(" (bar) (mA) (mA) (mA) (%) (%) (%) (mA)")
for i in range(5):
print(f" {p_ref[i]:5.2f} {ideal[i]:6.2f} {up[i]:6.2f} {down[i]:6.2f} "
f"{e_up[i]:+7.4f} {e_down[i]:+7.4f} {e_mean[i]:+7.4f} {hyst[i]:5.2f}")
zero_ma = mean_ma[0] - 4.0
span_meas = mean_ma[-1] - mean_ma[0]
span_err = (span_meas - SPAN_MA) / SPAN_MA * 100.0
worst = max(np.max(np.abs(e_up)), np.max(np.abs(e_down)))
print(f"Zero error: {zero_ma:+.3f} mA = {zero_ma / SPAN_MA * 100:+.3f} % of span "
f"= {zero_ma / SPAN_MA * SPAN_BAR:+.4f} bar")
print(f"Measured span: {span_meas:.3f} mA, span error {span_err:+.4f} % of span")
print(f"Largest error: {worst:.3f} % of span, tolerance {TOL} %: "
f"{'PASS' if worst <= TOL else 'FAIL'}")
print(f"Largest hysteresis: {hyst.max():.2f} mA = {hyst.max() / SPAN_MA * 100:.3f} % of span")
# what is left after zero and span are removed (terminal line through the ends)
line = mean_ma[0] + span_meas * frac
resid = (mean_ma - line) / SPAN_MA * 100.0
print("Left after zero and span are removed (% of span):",
" ".join(f"{r:+.4f}" for r in resid))
# ---------- reference uncertainty and the decision ----------
U_P = 0.015 # bar, k = 2, reference pressure gauge
U_I = 0.008 # mA, k = 2, milliammeter
u_ref = np.hypot(U_P / 2 / SPAN_BAR * 100, U_I / 2 / SPAN_MA * 100)
U_ref = 2.0 * u_ref
tur = TOL / U_ref
accept = TOL - U_ref
print(f"Reference: U = {U_ref:.3f} % of span (k = 2), ratio {tur:.2f} to 1")
print(f"Acceptance limit with guard band: {accept:.3f} % of span, "
f"largest error {worst:.3f} %: "
f"{'PASS' if worst <= accept else 'not proven'}")
# ---------- correction ----------
gain = SPAN_MA / span_meas
print(f"Correction: I_corr = 4 + {gain:.5f} x (I - {mean_ma[0]:.3f}) mA")
corr_up = 4.0 + gain * (up - mean_ma[0])
corr_down = 4.0 + gain * (down - mean_ma[0])
left = max(np.max(np.abs(corr_up - ideal)), np.max(np.abs(corr_down - ideal)))
print(f"Largest error after correction: {left:.4f} mA = "
f"{left / SPAN_MA * 100:.3f} % of span")
i_test = 10.40
p_raw = (i_test - 4.0) / SPAN_MA * SPAN_BAR
p_cor = (gain * (i_test - mean_ma[0])) / SPAN_MA * SPAN_BAR
print(f"At {i_test:.2f} mA: uncorrected {p_raw:.3f} bar, corrected {p_cor:.3f} bar")
# check: least squares line through all ten points
x_all = np.concatenate([frac, frac])
y_all = np.concatenate([up, down]) - np.concatenate([ideal, ideal])
slope_ma, zero_fit = np.polyfit(x_all, y_all, 1)
print(f"Least squares through ten points: zero {zero_fit:+.4f} mA, "
f"span error {slope_ma / SPAN_MA * 100:+.3f} % of span")
# ---------- Part 2: drift and the calibration interval ----------
years = np.array([1.0, 2.0, 3.0])
found = np.array([0.06, 0.25, 0.36]) # largest as-found error, % of span
n = len(years)
rate, start = np.polyfit(years, found, 1)
fit = start + rate * years
res = found - fit
s = np.sqrt(np.sum(res**2) / (n - 2))
se_rate = s / np.sqrt(np.sum((years - years.mean())**2))
rate_hi = rate + 2.0 * se_rate
print("Drift from three as-found errors")
print(f" line: error = {start:+.4f} + {rate:.4f} x years (% of span)")
print(" residuals:", " ".join(f"{r:+.4f}" for r in res), f" s = {s:.4f}")
print(f" drift rate {rate:.3f} % of span per year, standard error {se_rate:.4f}")
print(f" cautious rate (rate + 2 standard errors): {rate_hi:.3f} % per year")
print(f" 95 % interval of the rate with 1 degree of freedom: +/- {12.706 * se_rate:.2f}")
AS_LEFT = 0.03 # % of span after adjustment
room = accept - AS_LEFT
print(f" room for drift: {accept:.3f} - {AS_LEFT} = {room:.3f} % of span")
print(f" interval at the fitted rate: {room / rate:.2f} years = {12 * room / rate:.0f} months")
print(f" interval at the cautious rate: {room / rate_hi:.2f} years = {12 * room / rate_hi:.0f} months")
print(f" time for the fitted line to reach {accept:.3f} %: {(accept - start) / rate:.2f} years, "
f"and {TOL} %: {(TOL - start) / rate:.2f} years")
for m in (12, 18):
print(f" predicted error after {m} months: fitted {AS_LEFT + rate * m / 12:.3f} %, "
f"cautious {AS_LEFT + rate_hi * m / 12:.3f} %")
# ---------- Plot ----------
fig, ax = plt.subplots(1, 2, figsize=(10, 4.2))
ax[0].plot(frac * 100, e_up, "o-", label="rising")
ax[0].plot(frac * 100, e_down, "s-", label="falling")
for lim in (TOL, -TOL):
ax[0].axhline(lim, color="black", linestyle="--")
ax[0].axhline(0.0, color="grey", linewidth=0.8)
ax[0].set_xlabel("pressure (% of span)")
ax[0].set_ylabel("error (% of span)")
ax[0].set_title("As-found errors, dashed lines at the tolerance")
ax[0].legend()
t = np.linspace(0.0, 4.0, 50)
ax[1].plot(years, found, "o", label="as-found")
ax[1].plot(t, start + rate * t, label="fitted line")
ax[1].axhline(TOL, color="black", linestyle="--")
ax[1].axhline(accept, color="grey", linestyle=":")
ax[1].set_xlabel("years since the first calibration")
ax[1].set_ylabel("largest error (% of span)")
ax[1].set_title("Drift, tolerance and acceptance limit")
ax[1].legend()
fig.tight_layout()
fig.savefig("calibration_drift.png", dpi=120)
print("Saved calibration_drift.png")

Expected output

As-found calibration, error in percent of span
P ref ideal up down e up e down mean hyst
(bar) (mA) (mA) (mA) (%) (%) (%) (mA)
0.00 4.00 4.04 4.04 +0.2500 +0.2500 +0.2500 0.00
2.50 8.00 8.02 8.04 +0.1250 +0.2500 +0.1875 0.02
5.00 12.00 12.01 12.03 +0.0625 +0.1875 +0.1250 0.02
7.50 16.00 16.00 16.01 +0.0000 +0.0625 +0.0313 0.01
10.00 20.00 19.99 19.99 -0.0625 -0.0625 -0.0625 0.00
Zero error: +0.040 mA = +0.250 % of span = +0.0250 bar
Measured span: 15.950 mA, span error -0.3125 % of span
Largest error: 0.250 % of span, tolerance 0.5 %: PASS
Largest hysteresis: 0.02 mA = 0.125 % of span
Left after zero and span are removed (% of span): +0.0000 +0.0156 +0.0312 +0.0156 +0.0000
Reference: U = 0.158 % of span (k = 2), ratio 3.16 to 1
Acceptance limit with guard band: 0.342 % of span, largest error 0.250 %: PASS
Correction: I_corr = 4 + 1.00313 x (I - 4.040) mA
Largest error after correction: 0.0150 mA = 0.094 % of span
At 10.40 mA: uncorrected 4.000 bar, corrected 3.987 bar
Least squares through ten points: zero +0.0420 mA, span error -0.313 % of span
Drift from three as-found errors
line: error = -0.0767 + 0.1500 x years (% of span)
residuals: -0.0133 +0.0267 -0.0133 s = 0.0327
drift rate 0.150 % of span per year, standard error 0.0231
cautious rate (rate + 2 standard errors): 0.196 % per year
95 % interval of the rate with 1 degree of freedom: +/- 0.29
room for drift: 0.342 - 0.03 = 0.312 % of span
interval at the fitted rate: 2.08 years = 25 months
interval at the cautious rate: 1.59 years = 19 months
time for the fitted line to reach 0.342 %: 2.79 years, and 0.5 %: 3.84 years
predicted error after 12 months: fitted 0.180 %, cautious 0.226 %
predicted error after 18 months: fitted 0.255 %, cautious 0.324 %
Saved calibration_drift.png

The span error printed from the readings is −0.3125 percent, not the −0.3 percent used to make them, because the readings were rounded to 0.01 mA. A calibration can never report finer than the resolution of its reference.

Common Mistakes



  • Adjusting the instrument before the as-found readings are written down. The error it had in service is lost, and no past record can be judged.
  • Calling a sticker or a factory test sheet “traceable”. Traceability needs a certificate for the reference, with a stated uncertainty and an unbroken chain to a national standard.
  • Checking one point, usually zero, and declaring the instrument good. One point cannot show a span error. Use at least the two ends, and five points when the result supports a claim.
  • Passing an error just inside the tolerance with a reference whose own uncertainty is a third of that tolerance. The result is “not proven”. Apply the acceptance limit.
  • Fixing the interval at one year because the last site did so. Set it from the as-found history, and review it at every calibration.

Summary



  • Calibration is a recorded comparison with a reference of known uncertainty. Adjustment is a change to the instrument. As-found data are taken before any adjustment and as-left data after it.
  • Traceability is an unbroken chain of calibrations to a national standard, proved by certificates that state an uncertainty.
  • Five points taken rising and falling give the zero error, the span error, the hysteresis and the largest error. Here they were +0.25, −0.31, 0.125 and 0.25 percent of span.
  • The ratio of tolerance to reference uncertainty was 3.2, below 4, so an acceptance limit of 0.342 percent replaced the tolerance of 0.5 percent. The largest error of 0.25 percent was a proven pass.
  • Three yearly as-found errors gave a drift of 0.15 percent of span per year. The interval was set to 12 months, with the plain statement that three points are weak evidence.

Exercises



1. A 0 to 10 bar transmitter with a 4 to 20 mA output is tested at a reference pressure of 6.00 bar and gives 13.66 mA. Find the error in mA, in percent of span and in bar.

Answer

The ideal current is mA. The error is +0.06 mA, which is percent of span, or +0.0375 bar.

2. A cold room thermometer has a tolerance of ±0.5 °C. It is compared with a reference thermometer whose certificate states °C (). The error found is +0.38 °C. Find the ratio, the acceptance limit and the result.

Answer

The ratio is , below 4. The acceptance limit is °C. The error of 0.38 °C is inside the tolerance and outside the acceptance limit: “inside the tolerance, not proven”. Adjust, or repeat with a better reference.

3. A hydrostatic level transmitter, 0 to 10 m and 4 to 20 mA, gives 3.95 mA at 0 m and 20.03 mA at 10 m. Find the zero error and the span error in percent of span. Write the correction, and find the corrected level for a reading of 12.00 mA.

Answer

Zero error: percent of span. The measured span is 16.08 mA, so the span error is +0.50 percent of span. The correction is . At 12.00 mA, mA, which is 5.006 m (uncorrected: 5.000 m).

4. A class B Pt100 with its cable and readout is placed in a well-made ice bath and indicates +0.6 °C. The sensor tolerance at 0 °C is ±0.30 °C and the readout limit is ±0.13 °C. Can the two limits explain the indication? If the sensitivity is 0.39 Ω per °C, what extra resistance in the circuit would explain it?

Answer

Even with both limits at their worst and in the same direction, the error could be only °C. An indication of +0.6 °C is outside that, so there is a fault. It corresponds to too much resistance: look for a poor terminal or an unequal lead.

5. A transmitter has as-found errors of +0.05, +0.12, +0.22 and +0.27 percent of span after 1, 2, 3 and 4 years without adjustment. Fit a straight line by least squares. With an acceptance limit of 0.40 percent of span and an as-left error of 0.02 percent after adjustment, find the interval at the fitted rate, and at the fitted rate plus two standard errors.

Answer

The slope is 0.076 percent of span per year. The residuals are −0.001, −0.007, +0.017 and −0.009, so , and the standard error of the slope is . The cautious rate is 0.089 percent per year. The room for drift is 0.38 percent, which gives 5.0 years at the fitted rate and 4.3 years at the cautious rate.

References



  • JCGM 200:2012, International Vocabulary of Metrology: Basic and General Concepts and Associated Terms (VIM), 3rd edition, Joint Committee for Guides in Metrology, 2012.
  • JCGM 106:2012, Evaluation of Measurement Data: The Role of Measurement Uncertainty in Conformity Assessment, Joint Committee for Guides in Metrology, 2012.
  • ISO/IEC 17025:2017, General Requirements for the Competence of Testing and Calibration Laboratories, International Organization for Standardization.
  • J. P. Bentley, Principles of Measurement Systems, 4th edition, Pearson Education, 2005.


© 2021-2026 SiliconWit®. All rights reserved.
Hand pump pressure Reference gauge (calibrated) Transmitter under test 4 to 20 mA Milliammeter (calibrated) known input: bar indication: mA
National standard (pressure balance) Accredited laboratory working standard Site reference gauge Transmitter on the line smallest uncertainty largest uncertainty
Watch it build: ten errors, then a correction
+0.50−0.5 0510 bar 5 points, up, then downerror in % of span ● rising ○ falling zero +0.25 %, span −0.31 % hysteresis 0.125 % tolerance ±0.5 accept ±0.342 largest +0.25 %: a pass corrected: within 0.09 % left: the hysteresis
  1. Five pressures, 0 to 10 bar, first rising and then falling.
  2. The ten errors in % of span: +0.25 % at 0 bar, falling to −0.06 % at 10 bar.
  3. Zero +0.25 %, span −0.31 %, and up to 0.125 % between rising and falling.
  4. The largest error, +0.25 %, is inside the ±0.342 % acceptance limit: a pass.
  5. A straight-line correction removes zero and span: every error is now within 0.09 %.
  6. What is left is the hysteresis, which no correction can remove.
Predict first

A transmitter has a tolerance of ±0.5 percent of span. A calibration finds its largest error is 0.45 percent. The reference used has an expanded uncertainty of 0.158 percent. What is the result?

EFEF 1. Read it: as-found2. Fill, read again: as-left Fill first, and you never know what you used.
passnot provenfail found 0.20found 0.45found 0.70 0A = 0.34T = 0.50 error, percent of span
See it: pass, fail or not proven

Ratio T / U
Acceptance limit A
Result

The tolerance T is ±0.5 percent of span, as in the lesson. The bar around the dot is the uncertainty of the reference, so the true error lies somewhere on it. A pass is proven only when the whole bar stays inside the tolerance, which is the same as the dot inside the acceptance limit A = T − U. Make the reference better (a smaller U) and watch the not proven zone shrink.

See it: drift between calibrations

Error found at each calibration
Margin to the acceptance limit
Longest interval inside A

The lesson's transmitter: drift 0.150 percent of span per year, as-left error 0.03 percent, acceptance limit 0.342 percent, tolerance 0.5 percent. At each calibration it is adjusted back to 0.03 percent. Real drift is not always a straight line, so this is the working estimate of the lesson, to be checked at every calibration.

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. A 4 to 20 mA transmitter gives 4.03 mA at 0 percent of its range and 20.05 mA at 100 percent. What is its span error, in percent of span?

2. A transmitter drifts 0.10 percent of span per year. Its tolerance is ±0.5 percent and the acceptance limit is ±0.40 percent. After adjustment the as-left error is 0.05 percent. What is the longest interval at this rate?

3. A technician finds that a transmitter reads high. He adjusts it at once, and then writes down 4.00 mA at zero and 20.00 mA at full range. An auditor asks if the readings of the last year can be trusted. What can the site say?