The 4 to 20 mA Current Loop

Lesson 5 of 10 27 min read
Found this useful?

A screen shows 0.0 bar on a pump line. Either the pump has stopped, or a wire has broken in a junction box 400 m away, and with a badly chosen signal the screen cannot tell you which. A second site has the opposite problem: the reading is correct all morning and wrong at high pressure, because the transmitter does not have enough voltage exactly when it must send its largest current. Both faults come from the signal between the transmitter and the controller, not from the sensor. This lesson shows how the 4 to 20 mA current loop works, how to check its voltage budget, and how to turn the current into a pressure in software without hiding a fault. #Instrumentation #CurrentLoop #ProcessMeasurement

Learning Objectives

By the end of this lesson, you will be able to:

  1. Explain why a measurement is sent as a current and why its zero is 4 mA
  2. Calculate the voltage left at a two-wire transmitter and the longest cable a loop can use
  3. Choose a sense resistor and its power rating
  4. Convert ADC counts to engineering units and state the resolution
  5. Recognise a broken wire, a transmitter fault and an out-of-range reading from the current alone

Real-World System Problem: A pressure transmitter 400 m from its panel



A booster pump station supplies a housing estate. The pressure transmitter sits on the pump discharge line. The control panel, with the 24 V supply and the controller, is in a building 400 m away. One thin two-core cable joins them, and it runs in the same trench as the pump’s power cable.

That cable has resistance, about 28 Ω for the two conductors together, and it collects noise from the power cable beside it. Sent as a voltage, the pressure would change with the cable length, the temperature of the copper and the load on the pump motor, and nobody could trust the last few percent.

The same two wires must also power the transmitter. So one pair has three jobs: power the transmitter, carry the measurement, and report a failure. The 4 to 20 mA loop does all three, but only when its voltage budget is correct.

Pressuretransmitter0 to 10 bar24 V DC supplySense resistorADC inputPUMP STATIONCONTROL PANEL400 m, 2 wires4to20mApump line
The transmitter, the cable and the panel

Fundamental Theory: A measurement carried by a current



Why a current and not a voltage

In a series circuit the same current flows through every part, however long the wire and whatever its resistance: the current that leaves the transmitter arrives at the panel, as the water that leaves a valve in a closed pipe reaches the meter. A voltage falls along the wire in proportion to the current and the resistance, as pressure falls along a pipe.

Take a sensor with a 0 to 10 V output and three wires, where the supply current returns through the same conductor as the signal reference. If the sensor draws 20 mA and that conductor has 14 Ω, the reference at the sensor sits above the reference at the panel. That is 2.8 percent of the 10 V span, and it changes when the copper warms. A current signal over the same cable has no such error.

Noise is the second reason. A current-output transmitter is a current source: it adjusts its own voltage to hold the current it wants. A noise voltage induced in series with the loop is absorbed by a small change of that terminal voltage, and the current, which is the signal, hardly changes. The receiving end is also a low resistance (150 to 250 Ω), so a small stray current coupled into the cable produces only a small voltage.

The live zero

The bottom of the measuring range is 4 mA, not 0 mA. This is called a live zero, and it gives two things.

First, it lets the receiver separate “the measurand is at the bottom of its range” from “no signal is arriving”. With a 0 to 20 mA signal, zero pressure and a cut wire both give 0 mA. With 4 to 20 mA, zero pressure gives 4 mA and a cut wire gives 0 mA.

Second, the 4 mA that always flows is the transmitter’s power supply. A two-wire transmitter must run its sensor and its electronics on less than the smallest current it will ever send.

Current for a given measurand

is the measurand, is the value at 4 mA and is the value at 20 mA. The span of the signal is 16 mA, not 20 mA.

For the 0 to 10 bar transmitter, 5.0 bar gives . A common mistake is to treat 12 mA as 60 percent because 12 is 60 percent of 20. It is 50 percent, because the zero is at 4.

Signal levels for failure: NAMUR NE 43

A transmitter that knows it has failed (for example a broken sensor element) can say so by driving the current outside the measuring range. The recommendation NAMUR NE 43 (NAMUR is an association of companies that use process automation) gives the levels that many makers follow. The figures below are the levels of that recommendation, not a law of physics, and a transmitter’s datasheet states whether it follows them.

Loop currentMeaning under NE 43
At or below 3.6 mAFailure signalled low
3.8 to 20.5 mAMeasuring range (4.0 to 20.0 mA is 0 to 100 percent)
At or above 21.0 mAFailure signalled high

The measuring range extends a little beyond 4 and 20 mA so that a small overshoot of the measurand is still reported as a measurement. The gaps from 3.6 to 3.8 mA and from 20.5 to 21.0 mA keep a measurement and a failure signal apart.

0 mA3.63.820.5 21.0FAULTMEASURING RANGEFAULTlow4.0=0%20.0=100%highno current at all: open loop or no supply
Signal levels along the current scale

Most transmitters let the installer choose whether a failure is signalled high or low. One case is not a choice: a broken wire always gives 0 mA.

Two-wire loop power and the voltage budget

The supply, the cable, the sense resistor and the transmitter are in series. The supply voltage is shared between them. The cable and the resistor each take a voltage equal to the current times their resistance, and the transmitter receives what is left.

250 Ω24 VsupplyTransmitterneeds 10 Vcable conductor, 14 Ω++--cable conductor, 14 Ωto ADC
One series loop: the same current in every part

Voltage budget of a two-wire loop

is the supply voltage, the voltage at the transmitter terminals, the least voltage the transmitter needs (from its datasheet), the resistance of both conductors together, the sense resistor, and the largest current the transmitter can send.

The range of terminal voltage over which a transmitter can hold its current is called its compliance. The budget is tightest at the largest current, because the drops across the cable and the resistor are then largest.

The largest current is not 20 mA. A transmitter that signals failure high sends 21.0 mA or more, and that is the moment when the reading matters most. If the budget is checked only at 20 mA, a loop can work in normal service and then be unable to reach its fault current. This lesson uses 21.0 mA, the NE 43 level. Some transmitters can be set to a higher fault current, so read the datasheet and use its figure.

The cable resistance comes from the resistivity of copper, , the conductor area and the length. A loop has two conductors, so a run of length has of copper in it.

With at 20 °C, a conductor has 0.035 Ω per metre. Forgetting the factor of two is the most common error in this calculation.

Choosing the sense resistor

The receiver cannot read a current directly. It reads the voltage across a resistor that the current flows through, by Ohm’s law . The resistor value is a compromise.

Sense resistorVoltage at 4 mAVoltage at 20 mASuits
250 Ω1.000 V5.000 V5 V analogue inputs
150 Ω0.600 V3.000 V3.3 V converters
100 Ω0.400 V2.000 VLow supply voltage, long cables

A larger resistor gives a larger signal for the converter. It also takes more of the supply voltage away from the transmitter. The power turned to heat in the resistor is

and it must be calculated at the largest current. The resistor’s tolerance becomes a span error of the same percentage, so a 1 percent resistor adds more error than a good transmitter does. A 0.1 percent resistor with a low temperature coefficient is the usual choice, with a power rating several times the calculated value so that it stays cool and its resistance stays constant.

Scaling to engineering units

An analogue to digital converter (ADC) with bits and a reference voltage reports a whole number of counts . This course takes one count as .

From counts to engineering units

and are the counts at 4 mA and 20 mA.

Convert counts to current first, test the current against the fault levels, and only then convert to the measurand. If the software goes directly from counts to bar, a cut wire becomes a believable negative pressure, or a zero if the code limits the result.

Resolution here has its exact meaning: the smallest change of the measurand that changes the indication. It says nothing about accuracy. The difference is explained in accuracy, precision and resolution.

Isolation and ground loops

A loop should be connected to earth at one point only, normally at the supply negative in the panel. If the transmitter’s circuit also touches earth in the field (through a damaged cable, moisture in a junction box, or a sensor that is not isolated from its housing), a second path exists. The two earth points are rarely at the same voltage, especially near large motors, so a current flows through the second path, partly through or around the sense resistor. The reading shifts, and the shift moves with the load on the plant.

The cures are to keep one earth point, to connect the cable shield at one end only, and to use isolated inputs or a loop isolator where several loops share one receiver. Many input cards join the negative sides of all channels together. On such a card the sense resistor must be on the negative side of every loop, or the channels disturb each other.

Two-wire, three-wire and four-wire transmitters

A two-wire transmitter takes its power from the loop, as described above. It must work on less than 3.6 mA, so it suits sensors that need little power, such as pressure and temperature.

A three-wire transmitter has a separate supply wire, a signal wire and a common wire. It is used when the sensor needs more power than a loop can give. The current output returns through the common wire.

A four-wire transmitter has its own power supply on two wires and an output on two others, usually isolated from the supply. Electromagnetic flow meters and analysers are often of this kind. Its output is active: it drives the current itself. A common wiring fault connects an active output to an input that also supplies 24 V to the loop; the two sources act against each other or add, and the reading is wrong or the input is damaged. Check whether the input is passive or active before connecting.

HART in one paragraph

HART is a digital signal carried on the same two wires as the 4 to 20 mA current. It adds a small alternating current of about ±0.5 mA at two frequencies, 1200 Hz for a binary one and 2200 Hz for a binary zero. The average of this alternating current is zero, so the analogue reading is not changed. Through HART a technician can read the transmitter’s range, its tag, its diagnostics and the measurand as a number. HART needs a loop resistance of at least 230 Ω to develop its voltage signal, which is one reason 250 Ω is so widely used. A loop that ends in 150 Ω will carry the analogue signal correctly and will not support a HART modem without added resistance.

Application 1: Voltage budget for a transmitter on 400 m of cable



Step 1: Resistance of the cable

Click to reveal the cable resistance
  1. One conductor, per metre.

    Each metre of one conductor has 0.035 Ω. ✅

  2. Both conductors of the run. The current goes out on one conductor and returns on the other, so the copper length is .

    The cable adds 28.0 Ω to the loop. ✅

  3. Total loop resistance outside the transmitter. . The sense resistor is nine times larger than the cable. ✅

Step 2: Voltage left at the transmitter

Click to reveal the voltage budget
  1. At 20 mA. The cable drops and the resistor drops .

    The transmitter has 18.44 V at full scale. ✅

  2. At 21.0 mA. The cable drops and the resistor drops .

    The transmitter has 18.16 V when it signals a failure high. ✅

  3. Margin. above the minimum. The loop works with a large margin. ✅

Step 3: Longest cable that still works

Click to reveal the longest run
  1. Largest loop resistance. The cable and the resistor together may take at 21.0 mA.

    Everything in the loop outside the transmitter must stay under 666.7 Ω. ✅

  2. Resistance allowed for the cable. . ✅

  3. Run length. Each metre of run has two conductors, so it adds .

    The longest run is about 5950 m. ✅

  4. The wrong answer at 20 mA. With 20 mA the same calculation gives and a run of 6429 m. A cable of that length would work at every pressure and fail on the day the transmitter tried to send 21.0 mA. ✅

Step 4: Power in the sense resistor, and a check

Click to reveal the power and the check
  1. Power at the largest current.

    The resistor turns 110 mW into heat. A 0.25 W part is inside its rating but it warms, and a warm resistor changes its value, so choose 0.5 W or more. ✅

  2. Power in a fault. If the cable is short-circuited at the transmitter end, the resistor is the only thing that limits the current: and . No small precision resistor survives that for long, and the full 24 V appears at the converter input. This is why loop inputs carry a fuse or a current limit and an input clamp. ✅

  3. Check by adding the voltages. At 21.0 mA the three voltages must add to the supply: . They do. ✅

  4. Check with the script. The Python script below prints 18.44 V at 20 mA, 18.16 V at 21 mA, a longest run of 5952 m and 110.3 mW, the same as the hand values. ✅

Application 2: Scaling ADC counts to bar



Step 1: Counts at the ends of the range

Click to reveal the counts
  1. Voltages. At 4 mA the resistor gives . At 20 mA it gives . ✅

  2. Counts at 4 mA.

    The converter reports 744. ✅

  3. Counts at 20 mA.

    The converter reports 3723. ✅

  4. Room above 20 mA. The converter reaches its top code at . So 21.0 mA, which is 3.150 V, is still inside its range and a failure signalled high can be seen. With a 165 Ω resistor the 3.3 V limit would be reached at exactly 20 mA and every high fault would look like a full-scale reading. ✅

Step 2: Counts to bar

Click to reveal the conversion
  1. Counts to current.

    Each count is 5.371 µA. ✅

  2. Current to pressure.

    This is the general formula with and . ✅

  3. A reading of 2234 counts. , so

    The line is at 5.00 bar. ✅

Step 3: Resolution

Click to reveal the resolution
  1. Counts across the span. . Only 2979 of the 4096 codes carry the measurement. The rest lie below 4 mA and above 20 mA. ✅

  2. Resolution.

    One count is 3.36 mbar. ✅

  3. Compare with the accuracy. The maker’s accuracy of the transmitter is ±0.5 percent of span, which is ±0.05 bar, about 15 counts. The display can show steps of 0.003 bar and the reading is still only good to ±0.05 bar. ✅

Step 4: Counts that indicate a fault

Click to reveal the fault limits
  1. Failure signalled low. 3.6 mA gives and counts. A reading of 670 counts or fewer is a fault, not a pressure. ✅

  2. Failure signalled high. 21.0 mA gives and 3909.8 counts, which the converter rounds down to 3909. So a reading of 3909 counts or more is a fault. Do not set the limit at 3910: a transmitter that sends exactly 21.0 mA would then never be seen as failed. ✅

  3. Measuring range. 3.8 mA is 707.5 counts and 20.5 mA is 3816.7 counts. Readings from 708 to 3816 counts are measurements. Readings from 671 to 707 and from 3817 to 3908 are outside the measuring range and are neither a valid pressure nor a clear failure signal. Flag them. ✅

  4. Broken wire. With no current the resistor holds the input at 0 V, and the converter reports 0 counts, or a few counts of offset and noise. A count below about 20 (under 0.11 mA) means an open loop or a lost supply. ✅

  5. Check by going backwards. Start from 5.00 bar: , , , which the converter reports as 2234. This is the count that Step 2 started from. ✅

Check it: the loop check at commissioning. Prove the whole chain before you trust the first reading. Disconnect the transmitter and drive the loop from a loop calibrator in its place, at the currents below. The worst-case limits come from a 0.5 percent ADC reference and a 0.1 percent resistor, as in the uncertainty budget.

CalibratorCountsScreen shows
4.00 mA7440.00 bar, within 0.02 bar
12.00 mA22345.00 bar, within 0.05 bar
20.00 mA372310.00 bar, within 0.08 bar
3.60 mA670failure signalled low
21.0 mA3909failure signalled high
loop opened0no current

An error that grows with the current (small at 4 mA, largest at 20 mA) points to the resistor, the ADC reference or a scaling constant. The same error at every point points to the 4 mA offset in the code. Then reconnect the transmitter and compare it with a reference gauge at the test port.

Verify It in Python



The script calculates the voltage budget of Application 1 at 4, 20 and 21 mA, the longest cable run and the resistor power, then scales counts to bar for Application 2 and classifies five example counts. The plot shows the voltage at the transmitter against cable length for three values of resistance in the loop.

loop_budget_and_scaling.py
"""4 to 20 mA loop: voltage budget, sense resistor power, and ADC scaling."""
import numpy as np
import matplotlib.pyplot as plt
# ---------- Part 1: voltage budget ----------
RHO = 0.0175 # ohm mm2 per m, copper at 20 degC
AREA = 0.5 # mm2, conductor cross-section
V_SUPPLY = 24.0 # V DC
V_MIN = 10.0 # V, least voltage the transmitter needs at its terminals
I_FAULT = 0.0210 # A, largest current the transmitter sends (fault high)
I_FULL = 0.0200 # A, top of the measuring range
LENGTH = 400.0 # m, one-way cable run
R_SENSE = 250.0 # ohm
r_per_m = RHO / AREA # one conductor, ohm per metre
def cable_resistance(run_m):
"""Resistance of both conductors of a cable run."""
return 2.0 * r_per_m * run_m
def volts_at_transmitter(i_amp, run_m, r_sense, v_supply=V_SUPPLY):
return v_supply - i_amp * (cable_resistance(run_m) + r_sense)
def longest_run(i_amp, r_sense, v_supply=V_SUPPLY):
r_total = (v_supply - V_MIN) / i_amp
return (r_total - r_sense) / (2.0 * r_per_m), r_total
r_cable = cable_resistance(LENGTH)
print("Voltage budget, 24 V supply, 400 m of 0.5 mm2 cable, 250 ohm")
print(f" one conductor: {r_per_m:.4f} ohm/m, loop cable resistance {r_cable:.1f} ohm")
for label, i in (("4 mA", 0.004), ("20 mA", I_FULL), ("21 mA", I_FAULT)):
v_cable = i * r_cable
v_sense = i * R_SENSE
v_tx = volts_at_transmitter(i, LENGTH, R_SENSE)
print(f" at {label:>5}: cable {v_cable:.3f} V, resistor {v_sense:.3f} V, "
f"transmitter {v_tx:.2f} V, margin {v_tx - V_MIN:.2f} V")
run_21, r_tot_21 = longest_run(I_FAULT, R_SENSE)
run_20, r_tot_20 = longest_run(I_FULL, R_SENSE)
print(f" largest loop resistance at 21 mA: {r_tot_21:.1f} ohm, "
f"longest run {run_21:.0f} m")
print(f" largest loop resistance at 20 mA: {r_tot_20:.1f} ohm, "
f"longest run {run_20:.0f} m")
print(f" resistor power at 21 mA: {1000 * I_FAULT**2 * R_SENSE:.1f} mW")
i_short = V_SUPPLY / R_SENSE
print(f" transmitter shorted: {1000 * i_short:.0f} mA, "
f"{i_short**2 * R_SENSE:.2f} W in the resistor")
# ---------- Part 2: scaling ADC counts to bar ----------
R_ADC = 150.0 # ohm, sense resistor at the ADC
V_REF = 3.3 # V
N_CODES = 4096 # 12-bit converter
P_LOW, P_HIGH = 0.0, 10.0 # bar at 4 mA and at 20 mA
def counts_from_ma(i_ma):
return i_ma * 1e-3 * R_ADC / V_REF * N_CODES
def ma_from_counts(n):
return n * V_REF / N_CODES / R_ADC * 1e3
def bar_from_counts(n):
return P_LOW + (ma_from_counts(n) - 4.0) / 16.0 * (P_HIGH - P_LOW)
print("Scaling, 150 ohm and a 12-bit ADC with a 3.3 V reference")
lsb_mv = 1000 * V_REF / N_CODES
lsb_ua = 1000 * ma_from_counts(1)
print(f" one count: {lsb_mv:.4f} mV, {lsb_ua:.3f} uA, "
f"{1000 * (bar_from_counts(1) - bar_from_counts(0)):.2f} mbar")
for i_ma in (3.6, 3.8, 4.0, 12.0, 20.0, 20.5, 21.0):
print(f" {i_ma:5.1f} mA: {i_ma * R_ADC / 1000:.3f} V, "
f"{counts_from_ma(i_ma):7.1f} counts")
print(f" counts between 4 and 20 mA: {counts_from_ma(20) - counts_from_ma(4):.1f}")
print(f" largest current the ADC can read: {1000 * V_REF / R_ADC:.1f} mA")
for n in (2234, 2979, 3840, 596, 0):
i_ma = ma_from_counts(n)
if i_ma < 0.1:
state = "no current: open loop or no supply"
elif i_ma <= 3.6:
state = "fault signalled low"
elif i_ma >= 20.99: # 21.0 mA arrives as 3909 counts, 20.995 mA
state = "fault signalled high"
elif i_ma < 3.8 or i_ma > 20.5:
state = "outside the measuring range"
else:
state = f"{bar_from_counts(n):.3f} bar"
print(f" count {n:4d}: {i_ma:6.3f} mA, {state}")
print(f" resistor power at 21 mA: {1000 * I_FAULT**2 * R_ADC:.1f} mW")
print(f" transmitter voltage at 21 mA, 400 m: "
f"{volts_at_transmitter(I_FAULT, LENGTH, R_ADC):.2f} V")
# ---------- Plot ----------
runs = np.linspace(0.0, 8000.0, 200)
fig, ax = plt.subplots(figsize=(8, 4.5))
for r_s in (150.0, 250.0, 500.0):
ax.plot(runs, volts_at_transmitter(I_FAULT, runs, r_s),
label=f"{r_s:.0f} ohm in the loop")
ax.axhline(V_MIN, color="gray", linestyle="--", linewidth=0.9)
ax.text(100.0, V_MIN + 0.3, "least voltage the transmitter needs")
ax.set_xlabel("cable run (m), 0.5 mm2 copper")
ax.set_ylabel("voltage at the transmitter at 21 mA (V)")
ax.set_title("Voltage budget of a 24 V loop")
ax.legend()
fig.tight_layout()
fig.savefig("loop_budget_and_scaling.png", dpi=120)
print("Saved loop_budget_and_scaling.png")

Expected output

Voltage budget, 24 V supply, 400 m of 0.5 mm2 cable, 250 ohm
one conductor: 0.0350 ohm/m, loop cable resistance 28.0 ohm
at 4 mA: cable 0.112 V, resistor 1.000 V, transmitter 22.89 V, margin 12.89 V
at 20 mA: cable 0.560 V, resistor 5.000 V, transmitter 18.44 V, margin 8.44 V
at 21 mA: cable 0.588 V, resistor 5.250 V, transmitter 18.16 V, margin 8.16 V
largest loop resistance at 21 mA: 666.7 ohm, longest run 5952 m
largest loop resistance at 20 mA: 700.0 ohm, longest run 6429 m
resistor power at 21 mA: 110.3 mW
transmitter shorted: 96 mA, 2.30 W in the resistor
Scaling, 150 ohm and a 12-bit ADC with a 3.3 V reference
one count: 0.8057 mV, 5.371 uA, 3.36 mbar
3.6 mA: 0.540 V, 670.3 counts
3.8 mA: 0.570 V, 707.5 counts
4.0 mA: 0.600 V, 744.7 counts
12.0 mA: 1.800 V, 2234.2 counts
20.0 mA: 3.000 V, 3723.6 counts
20.5 mA: 3.075 V, 3816.7 counts
21.0 mA: 3.150 V, 3909.8 counts
counts between 4 and 20 mA: 2978.9
largest current the ADC can read: 22.0 mA
count 2234: 11.999 mA, 4.999 bar
count 2979: 16.000 mA, 7.500 bar
count 3840: 20.625 mA, outside the measuring range
count 596: 3.201 mA, fault signalled low
count 0: 0.000 mA, no current: open loop or no supply
resistor power at 21 mA: 66.2 mW
transmitter voltage at 21 mA, 400 m: 20.26 V
Saved loop_budget_and_scaling.png

Count 2234 prints as 4.999 bar and not 5.000 because the converter rounded 2234.2 down to a whole count. The difference of 0.001 bar is less than one count of resolution. In the plot, the line for 500 Ω (two 250 Ω devices in series) crosses the 10 V limit at about 2380 m, which shows how quickly a second device uses the budget.

Common Mistakes



  • Counting the cable length once. The current flows out and back, so a 400 m run has 800 m of copper.
  • Checking the voltage budget at 20 mA. The transmitter needs its minimum voltage at the largest current it can send, which is its fault current of 21 mA or more.
  • Scaling as if 0 mA were zero. The span is 16 mA and starts at 4 mA, so 12 mA is 50 percent.
  • Limiting a negative result to zero in software. Test the current against the fault levels first, then scale.
  • Choosing a sense resistor that puts 20 mA at the top code of the converter. Leave room to read 21 mA or the high fault cannot be seen.
  • Adding a second indicator or isolator in series without repeating the voltage budget.

Summary



  • A current is the same in every part of a series loop, so cable resistance does not change the signal, and a current source resists induced noise.
  • The live zero at 4 mA powers a two-wire transmitter and separates a low measurement from a missing signal.
  • Under NAMUR NE 43, 3.8 to 20.5 mA is the measuring range, and currents at or below 3.6 mA or at or above 21.0 mA signal a failure. A current of 0 mA means the loop itself is open or unpowered.
  • The supply voltage minus the drops across the cable and the sense resistor must leave the transmitter its minimum voltage at the fault current, not at 20 mA.
  • Convert counts to current, test for faults, then scale to engineering units. The resolution of the converter is not the accuracy of the measurement.

Exercises



1. The 0 to 10 bar transmitter measures 6.5 bar. Find the loop current and the voltage across a 250 Ω sense resistor.

Answer

. The voltage is .

2. A loop has a 24 V supply, a 250 Ω sense resistor and a cable run of 150 m with copper conductors (0.035 Ω per metre for each conductor). Find the voltage at the transmitter at 21.0 mA.

Answer

. .

3. During a power cut the supply of the loop in Application 1 (28.0 Ω of cable) falls to 18 V. A 250 Ω local indicator has been added in series with the 250 Ω sense resistor. The transmitter needs 10 V. Does the loop still work at 21.0 mA? What is the largest total resistance of the devices in the panel?

Answer

, which is below 10 V, so the loop fails. The largest loop resistance is , and after the 28 Ω of cable the devices may total 353 Ω.

4. With the 150 Ω resistor and the 12-bit, 3.3 V converter of Application 2, the reading is 1490 counts. Find the current and the pressure.

Answer

. .

5. The same input gives three readings on three days: 596 counts, 3840 counts and 0 counts. State what each one means.

Answer

596 counts is 3.20 mA: below 3.6 mA, so the transmitter is powered and signals a failure low. 3840 counts is 20.63 mA: above 20.5 mA and below 21.0 mA, so it is outside the measuring range and is not a clear failure signal. The pressure is above 10 bar or the transmitter is saturated, and the value must be flagged. 0 counts is 0 mA: the loop is open or has no supply.

6. A designer fits a 100 Ω sense resistor rated 0.25 W on a 24 V loop. Find the power in the resistor at 21.0 mA. Then find the current and the power if the cable is short-circuited at the transmitter end, ignoring the cable resistance.

Answer

At 21.0 mA, , well inside the rating. With a short circuit, and , 23 times the rating. The input needs a fuse or a current limit.

References



  • J. P. Bentley, Principles of Measurement Systems, 4th edition, Pearson Education, 2005.
  • NAMUR Recommendation NE 43, Standardisation of the Signal Level for the Failure Information of Digital Transmitters, NAMUR.
  • IEC 60381-1, Analogue signals for process control systems. Part 1: Direct current signals, International Electrotechnical Commission, 1982.
  • B. G. Lipták (editor), Instrument Engineers’ Handbook, Volume 1: Process Measurement and Analysis, 4th edition, CRC Press, 2003.


© 2021-2026 SiliconWit®. All rights reserved.
Pump station Control panel Pressure transmitter 0 to 10 bar 24 V DC supply Sense resistor ADC input 400 m, 2 wires 4 to 20 mA pump line
fault low measuring range fault high 0 3.6 3.8 4.0 20.0 20.5 21.0 mA 0 % 100 % no current at all: open loop or no supply ends drawn wider than to scale
24 V supply Transmitter needs 10 V cable conductor, 14 Ω 250 Ω cable conductor, 14 Ω to ADC + - + - I I the same current I in every part
Watch it build: from the loop current to bar
PT 150 Ω ADC 0 to 10 bar 12 bit, 3.3 V 4 to 20 mA 4 to 20 mA0.6 to 3.0 V 0 7443723 4 mA20 mA 0 to 4095 faultfault 2234 12.00 mA 1.800 V 2234 5.00 bar 2979 counts for 10 bar 3.36 mbar 0 to 10 bar
  1. The transmitter's current flows through a 150 Ω resistor; the ADC can read only a voltage.
  2. On 150 Ω, 4 to 20 mA becomes 0.600 to 3.000 V, inside the 3.3 V reference.
  3. 12 bits on 3.3 V: 4 mA is 744 counts and 20 mA is 3723 counts.
  4. 2234 counts is 12.00 mA, outside both fault zones, so the line is at 5.00 bar.
  5. Only 2979 codes carry the 10 bar span, so one count is 3.36 mbar.
Predict first

A two-wire transmitter is 400 m from its panel, on a thin cable of 0.5 mm². The supply is 24 V and the current is read across a 250 Ω resistor. At 21 mA, which takes more of the supply voltage?

See it: where the supply voltage goes

Cable drop
Sense resistor drop
Left at the transmitter
Cable resistance, both wires
Longest cable at 21.0 mA
Power in the sense resistor
0 mA: broken wireat or below 3.6 mA: fault low3.8 to 20.5 mA: measuring rangeat or above 21.0 mA: fault high

The bar is the supply voltage. The cable and the sense resistor each take the current times their resistance, and the transmitter receives what is left. The dashed line marks the last 10 V of the supply. The transmitter of the lesson needs at least that much, so the two drops must end to the left of the line. The budget is tightest at the largest current, 21.0 mA, which the transmitter sends to signal a failure high. The longest cable is calculated at that current, whatever the slider shows. The levels on the current scale are those of NAMUR NE 43 as the lesson states them. Between 3.6 and 3.8 mA, and between 20.5 and 21.0 mA, a value is not a valid measurement and not a clear failure signal.

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. A two-core cable with 0.5 mm² conductors has 0.035 Ω per metre in each conductor. The transmitter is 400 m of cable away from the panel. How much resistance does the cable add to the loop?

2. A loop has a 24 V supply, a 500 Ω sense resistor and 2600 m of 0.5 mm² cable (182 Ω). The transmitter needs 10 V. A technician checks the budget at 20 mA and finds 10.36 V at the transmitter. Is the loop sound?

3. The receiver of a 4 to 20 mA pressure loop reads exactly 0.0 mA. What does this mean?

12 mA supply = pumptransmitter = valvecable = long pipepanel meter counts the flow
See it: what a broken wire looks like

Loop current
The panel shows
Across 250 Ω

A 0 to 10 bar transmitter on a 24 V loop. Set the pressure to 0 and then cut the wire: on 4 to 20 mA the two give different currents, 4 mA and 0 mA. Switch to a 0 to 20 mA scale and try again. The fault levels are those of NAMUR NE 43.

Found this useful?