Lesson 8 of 10 27 min read
Found this useful?

The same contactor on the same compressor fails for the third time. Each time a technician fits a new one, the compressor starts, and the work order is closed with “contactor failed, replaced”. After the third time a manager asks who fitted it, and the answer becomes a warning letter. The fourth failure is already on its way, because nothing that caused the first three has changed. This lesson shows how to go from the broken part to the reason it broke, and how to correct the system so that the failure does not return. #RootCauseAnalysis #FaultTree #Reliability

Learning Objectives

By the end of this lesson, you will be able to:

  1. Distinguish the physical, human and latent causes of a failure, and say why a correction must reach the latent cause
  2. Apply the five whys to a failure and state where the method is weak
  3. Organise possible causes on a cause-and-effect diagram and test each one against evidence on a cause tree
  4. Calculate the top event of a small fault tree with AND and OR gates, and find which basic event to correct first
  5. Choose corrective actions that change the equipment, the settings or the procedure, and that do not depend on blaming a person

Real-World System Problem: A contactor that fails again and again



Compressor 1 of the cold store is started and stopped by a contactor: an electrically operated switch that connects the motor to the supply. The room thermostat decides when cooling is needed, the controller closes the contactor, and the motor runs until the room is cold enough.

The contactor of compressor 1 has been replaced three times in 42 months; the same type on the other machines of the site fails about once in seven years. Each replacement takes an hour and the part is not costly, so each event looked small. Together they are a pattern, and a pattern has a cause.

Replacing the part restored the function three times and corrected nothing. Root cause analysis must find what makes this contactor different from its sisters.

CompressormotorContactorCold roomairControllerThermostat(room air)cooling
The chain that starts and stops compressor 1

Fundamental Theory: From the broken part to the cause



Three levels of cause

Every failure has a chain of causes, and the chain has three levels.

  • The physical cause is what happened to the material: the contacts wore away, the bearing ran dry, the bolt broke by fatigue.
  • The human cause is an action or an omission that led to the physical cause: a setting was left at its default, a grease point was missed, a bolt was not tightened to the stated torque.
  • The latent cause is the condition in the organisation that made the human action likely: no list of settings exists, the grease point is behind a guard, no torque value is written on the job sheet.
Three levels of cause
Failure seen: the compressor does not start
│
▼
Physical cause: what happened to the part
│
▼
Human cause: what was done, or not done
│
▼
Latent cause: why the system allowed it
(the root to correct)

Most reports stop at the first level (“contactor failed”) and some at the second (“fitter error”). A correction at the first level replaces the part and waits for the next failure. One at the second warns the person and waits for the next person to do the same. Only a correction at the third level changes next year. A weed is the same: cut the leaves or the stem and it grows back; only pulling the root ends it.

A failure seldom has one root. “Root cause” is a convenient name for the deepest causes that the site has the power to change.

Keep the failed part and the data

Most evidence is destroyed in the first hour by people doing their job well: they clean, repair and restart. Before or during the repair, keep:

  • The part. Label it with the date, the machine and the position. Do not clean it. The marks on the surface are the record.
  • Photographs of the part in place, of the parts around it and of the panel, before anything is moved.
  • The settings and counters: set points, timers, the hours meter, a start counter if one exists. Write them down before anybody resets them.
  • The data: temperatures, currents and alarms for the hours and days before the failure.
  • What people saw and heard, asked soon and asked as a request for help. A person who expects blame remembers very little.

The five whys

The simplest method asks “why?” of each answer until the answer is something that can be changed. It is usually credited to the Toyota production system, and five is a habit, not a rule. It costs nothing and moves a team past the first answer. Its limits:

  • It follows one path. Most effects have several possible causes, and the asker follows the one that the asker already believes.
  • It stops where the asker stops. A person who knows electrics ends at an electrical cause. A person who has already decided ends at a name.
  • It asks for no evidence. Five guesses in a row read like a proof.
  • It ends easily at a person. “Because the technician did not check” feels like an end. It is where the useful questions begin.

Use the five whys to open an analysis, and require evidence for every answer.

The cause-and-effect diagram

The cause-and-effect diagram (also called a fishbone diagram, or an Ishikawa diagram after Kaoru Ishikawa) answers the first limit of the five whys: the team lists many possible causes before following any. The effect is written at the head, and the possible causes on branches under a few headings. For equipment, six are common: machine, method, material, people, measurement and environment.

MachineMethodMaterial(size of the(settings of(quality andcontactor)the control)batch of part)Contactorfails(fitting and(coil voltage,(heat and dusttightening)start count)in the panel)PeopleMeasurementEnvironment
A cause-and-effect diagram for the contactor

Every item on the diagram is a hypothesis until evidence confirms it or rules it out.

The cause tree

A cause tree joins the two ideas. It branches from the failure into every way it could happen, as the diagram does. Each branch is then tested against the evidence and marked confirmed or ruled out, and only a confirmed branch is taken deeper with the next “why”. A branch is removed not because it seems unlikely, but because a measurement, a label or the failed part says so.

The fault tree

A cause tree looks back at a failure that has happened. A fault tree looks forward at an unwanted event, the top event, and can be calculated. Below it, logic gates join the events that can produce it, down to basic events whose probabilities are known or estimated. The two main gates:

  • An OR gate gives its output when any one of its inputs occurs.
  • An AND gate gives its output only when all of its inputs occur together.

Gate rules for independent events

are the probabilities of the inputs. When all the inputs of an OR gate are small, is close to their sum.

A small example: the wash point of the site has no water if the supply to the pump room fails, or if both of two pumps are failed. In a stated period the supply fails with a probability of 0.01 and each pump is failed with a probability of 0.05.

ORANDPump B0.05Pump A0.05Supply fails0.01No water at the wash point
A small fault tree

The AND gate gives . The OR gate gives , and the simple sum is 0.0125. The supply, alone under an OR gate, contributes four times as much as the two pumps together. A third pump would change almost nothing.

Rates and probabilities on demand

Many paths to a top event have one form: something starts the path (a compressor stops), and a protection that should cover it does not work (the standby does not take the load). The first is a starting event with a rate of times a year. The second has a probability of failure on demand , between 0 and 1 for each call.

For such a path the correct form of the AND gate is a rate:

For an OR gate over several independent paths the rates add, , and the probability of at least one top event in a year is

For a small this is close to . The common mistake here is to multiply two rates, or to multiply “the probability of at least one starting event in the year” by when the starting event comes several times a year. Each call is a new chance for the protection to fail.

Correct the system and do not blame a person

When an analysis reaches a human action, ask: would another competent person, with the same information, tools, time and instructions, probably have done the same? If yes, the person is not the cause. The situation is, and it will produce the same action from the next person.

Blame has a second cost: people who are blamed stop reporting, and the small events and near misses, the cheapest evidence a site has, are no longer written down.

Corrections are not equally strong. From the strongest to the weakest:

  1. remove the cause by a change of design or of a setting,
  2. add a protection that acts by itself (a timer, an interlock, a limit),
  3. add a signal that tells a person in time (a counter, an alarm),
  4. write the step into a procedure or a checklist with a record,
  5. remind or retrain people.

The last is the most common in reports and the weakest, because it depends on memory. A good analysis ends with at least one action from the first three.

Application 1: The contactor of compressor 1



Step 1: Compare the record with the sister parts

Click to reveal the comparison
  1. Failure rate of this contactor. Three failures in 42 months is failures a year, a mean life of 14.0 months. ✅

  2. Against the others. . This contactor fails nearly six times as often as its sisters of the same type. ✅

  3. Regular lives. Random failures would give very unequal lives. Lives of 14, 13 and 15 months suggest wear at a steady pace. Three values cannot prove it, but they point the analysis at wear. ✅

Step 2: The five whys, twice

Click to reveal the two chains
  1. The chain followed after the second failure. Why did the compressor not start? The contactor had failed. Why? It was a poor part, or badly fitted. Action: another make of contactor, and a warning to the technician. The third failure came 15 months later. This chain had two questions, no evidence and a person at the end. ✅

  2. Why did the compressor not start? The contactor did not connect the motor: its contacts were worn away. Evidence: the kept part. ✅

  3. Why were the contacts worn away after 14 months? They had made about as many operations as the contactor is built for. Evidence: even wear on all three poles, and the count of Step 4. ✅

  4. Why so many operations? The compressor starts 3 times an hour, day and night. Evidence: 504 starts in 168 hours. ✅

  5. Why does it start 3 times an hour? The thermostat band is 0.3 K, so the room air crosses the band in minutes. Evidence: the controller setting and the temperature record. This fast starting and stopping is called short cycling. ✅

  6. Why is the band 0.3 K? It is the default of the controller that was installed 42 months ago, and nobody changed it. ✅

  7. Why did nobody change it? No commissioning sheet lists the settings a new controller must have, the site keeps no record of settings, and nothing counts starts. The installer had no value to set and nobody could see the result: a condition of the system, which can be changed. ✅

Step 3: The cause tree with its evidence

Click to reveal the tree
  1. List every branch before following one. The cause-and-effect diagram of the theory section gives six branches. ✅

  2. Test each branch.

    Cause tree: contacts worn away in 14 months
    Contacts worn away in 14 months
    ├─ Contactor too small for the motor
    │ label against motor current: RULED OUT
    ├─ Low coil voltage (contacts chatter)
    │ measured at start: RULED OUT
    ├─ Hot or dusty panel
    │ clean, temperature in limit: RULED OUT
    ├─ Loose terminal
    │ no heat marks: RULED OUT
    ├─ Poor batch of parts
    │ two purchases, same life: RULED OUT
    └─ Too many operations
    504 starts in a week: CONFIRMED
    └─ Band of 0.3 K (short cycling)
    └─ Default setting never changed
    └─ No commissioning sheet,
    no record of settings,
    no start counter

    ✅

  3. The three levels. Physical cause: wear of the contacts by too many operations. Human cause: the band was left at the default. Latent causes: no commissioning sheet, no record of settings, no count of starts, and work orders that record the part and not the cause. ✅

Step 4: Support the physical cause with numbers

Click to reveal the calculation
  1. Running time in one cycle. The air must fall through the band of 0.3 K at 1.2 K an hour.

    ✅

  2. Stopped time in one cycle. h, which is 5 minutes. ✅

  3. Starts. One cycle takes 20 minutes, so there are 3.0 starts an hour and starts a year. ✅

  4. Life of the contactor.

    ✅

  5. A wider band. With a band of 1.5 K the times are 75 minutes running and 25 minutes stopped. One cycle takes 100 minutes: 0.6 starts an hour, 5,040 a year, and a life of years. ✅

  6. What the wider band costs. The room air moves between 3.25 °C and 4.75 °C, inside the allowed 2 °C to 6 °C. The compressor runs percent of the time with either band. In this simple model the wider band costs no extra running. ✅

Step 5: Corrective actions, and a check

Click to reveal the actions and the check
  1. Remove the cause. Set the band to 1.5 K. This is a change of a setting, the strongest kind of correction. ✅

  2. Add a protection that acts by itself. Set a minimum stopped time in the controller. With 10 minutes, even the old band of 0.3 K would give a swing of 0.6 K and 1.5 starts an hour. The compressor maker’s manual states the starts an hour that the compressor allows, and the setting must respect it. ✅

  3. Add a signal. Keep the start counter, and review the starts an hour each month. ✅

  4. Change the procedure. Write a commissioning sheet with the required settings of every controller, record the settings as found and as left, add a cause field to the work order, and keep failed parts until the cause is known. ✅

  5. What is not on the list. No warning and no retraining. Another competent installer, given a controller and no list of settings, would also have left the default. ✅

  6. Check against the record. The calculation predicts a life of 14.3 months, and the three contactors lasted a mean of 14.0. The start counter gave starts an hour, the same as the calculation from the band. Two independent measurements agree with the cause. ✅

  7. Check after the change. There is no need to wait six years. One week after the band is changed the counter should show about starts and not 504. ✅

Application 2: A fault tree for a warm cold room



Cold room above 8 °C for four hoursORANDdoor left open overnight1.00ayearalarm brings nobody0.10ANDduty compressor long stop1.00ayearstandby does not take load0.05ANDlong grid outage0.50ayeargenerator fails0.08shared condenser long stop0.02ayearANDcontroller fails0.10ayearalarm brings nobody0.10
Fault tree: cold room above 8 °C for four hours

Step 1: The rate of each path

Click to reveal the calculation
  1. Door. a year. ✅

  2. Compressors. a year. ✅

  3. Power. a year. ✅

  4. Condenser. No protection, so 0.020 a year. ✅

  5. Controller. a year. ✅

Step 2: The top event

Click to reveal the calculation
  1. Rate. The paths are under an OR gate, so their rates add.

    That is once in 4.5 years on average. ✅

  2. Probability in one year.

    ✅

  3. Five years. The probability of five years with no such event is . Of three sites like this one, two would have at least one such event in five years. ✅

  4. Shares. Door 45.5 percent, compressors 22.7 percent, power 18.2 percent, condenser 9.1 percent, controller 4.5 percent. ✅

Step 3: Which basic event to correct first

Click to reveal the comparison
  1. A fair test. Halve each basic event in turn, leave the others, and see how far the top event falls. ✅

  2. The alarm. It stands in two paths. Halving its failure probability to 0.05 removes a year: the top event falls to 0.165, a gain of 25.0 percent. ✅

  3. The door. Halving the rate of doors left open removes 0.050: the top event falls to 0.170, a gain of 22.7 percent. ✅

  4. The others. The duty compressor or the standby: 11.4 percent each. The grid or the generator: 9.1 percent each. The condenser: 4.5 percent. The controller: 2.3 percent. ✅

  5. Result. Correct the alarm first and the door second. Together (both halved) they bring the top event to 0.140 a year and the yearly probability to 0.131. ✅

Step 4: Check with limits and with the gate rule

Click to reveal the check
  1. Every protection perfect. Set each probability on demand to 0. Only the condenser path remains: 0.02 a year. No tree with this condenser can do better. ✅

  2. No protection at all. Set each probability to 1. The rate is a year, 11.9 times the present value. The protections do most of the work, and they are all items that stand idle until they are called. ✅

  3. The OR gate rule on probabilities. The yearly probabilities of the five paths are , and so on. The OR gate rule on these five values gives 0.197, the same as Step 2. ✅

Verify It in Python



The script calculates the small fault tree of the theory section, the short cycling of the contactor for both bands, and the fault tree of the cold room with the test of halving each basic event. It saves one plot of contactor life against the band and of the five paths.

root_cause.py
"""Short cycling of a compressor contactor, and a small fault tree for a warm cold room."""
import numpy as np
import matplotlib.pyplot as plt
YEAR = 8400.0 # hours in service a year at the site
# ---------- Fault tree gates (independent events) ----------
def gate_and(*p):
return float(np.prod(p))
def gate_or(*p):
return 1.0 - float(np.prod([1.0 - x for x in p]))
print("Small example: no water at the wash point")
both = gate_and(0.05, 0.05)
top = gate_or(0.01, both)
print(f" both pumps failed (AND): {both:.4f}")
print(f" top event (OR): {top:.6f}, sum of the two inputs: {0.01 + both:.6f}")
# ---------- Application 1: the contactor that fails again and again ----------
COOL, WARM = 1.2, 3.6 # K per hour: room cooling (compressor on), warming (off)
LIFE = 30000.0 # electrical life of the contactor in operations (maker's figure)
def cycling(band):
"""On time, off time (minutes), starts an hour and a year, and contactor life in years."""
on, off = band / COOL, band / WARM # hours
starts_hour = 1.0 / (on + off)
starts_year = starts_hour * YEAR
return on * 60.0, off * 60.0, starts_hour, starts_year, LIFE / starts_year
print("Application 1: contactor of compressor 1")
record_months = [14.0, 13.0, 15.0] # service life of the three failed contactors
print(f" record: {len(record_months)} failures in {sum(record_months):.0f} months, "
f"mean life {np.mean(record_months):.1f} months, "
f"{12.0 * len(record_months) / sum(record_months):.3f} failures a year")
print(f" against the 0.15 a year of the other contactors: "
f"{12.0 * len(record_months) / sum(record_months) / 0.15:.1f} times")
for band in (0.3, 1.5):
on, off, sh, sy, life = cycling(band)
print(f" band {band:.1f} K: on {on:.0f} min, off {off:.0f} min, cycle {on + off:.0f} min, "
f"{sh:.1f} starts an hour, {sy:,.0f} a year, life {life:.2f} years "
f"({12 * life:.1f} months)")
print(f" share of the time the compressor runs: {100 * WARM / (COOL + WARM):.0f} % (any band)")
print(f" room limits with the 1.5 K band about 4.0 C: {4.0 - 0.75:.2f} to {4.0 + 0.75:.2f} C")
MIN_OFF = 10.0 # minutes: a minimum off time set in the controller
rise = WARM * MIN_OFF / 60.0 # K gained during the forced off time
on_long = rise / COOL * 60.0 # minutes to cool that rise again
print(f" 0.3 K band with a minimum off time of {MIN_OFF:.0f} min: room swings {rise:.1f} K, "
f"on {on_long:.0f} min, {60.0 / (on_long + MIN_OFF):.1f} starts an hour")
# ---------- Application 2: cold room above 8 C for four hours ----------
# each path: one starting event (times a year) and the protection that must also fail
PATHS = [
("door left open", "alarm brings nobody", 1.00, 0.10),
("duty compressor", "standby does not take", 1.00, 0.05),
("grid outage", "generator fails", 0.50, 0.08),
("shared condenser", "(no protection)", 0.02, 1.00),
("controller fails", "alarm brings nobody", 0.10, 0.10),
]
print("Application 2: cold room above 8 C for four hours")
rates = [f * q for _, _, f, q in PATHS]
F = sum(rates)
for (start, prot, f, q), r in zip(PATHS, rates):
print(f" {start:18s} {f:4.2f} a year x {prot:22s} {q:4.2f} = {r:.3f} a year "
f"({100 * r / F:4.1f} %)")
print(f" top event: {F:.3f} a year, once in {1 / F:.1f} years on average")
print(f" probability of at least one in a year: {1 - np.exp(-F):.3f}")
print(f" probability of none in five years: {np.exp(-5 * F):.3f}")
def top_rate(change):
"""Top event rate with some basic events multiplied by a factor."""
total = 0.0
for start, prot, f, q in PATHS:
total += f * change.get(start, 1.0) * (q * change.get(prot, 1.0))
return total
print(" top event rate if one basic event is halved:")
names = ["door left open", "alarm brings nobody", "duty compressor", "standby does not take",
"grid outage", "generator fails", "shared condenser", "controller fails"]
for name in names:
new = top_rate({name: 0.5})
print(f" {name:22s} {new:.3f} a year (saves {F - new:.3f}, {100 * (F - new) / F:4.1f} %)")
both = top_rate({"door left open": 0.5, "alarm brings nobody": 0.5})
print(f" door and alarm both halved: {both:.3f} a year, "
f"probability in a year {1 - np.exp(-both):.3f}")
perfect = sum(f for _, _, f, q in PATHS if q == 1.0)
bare = sum(f for _, _, f, _ in PATHS)
print(f" limits: every protection perfect {perfect:.2f} a year, no protection at all "
f"{bare:.2f} a year ({bare / F:.1f} times the present value)")
p_year = [1.0 - np.exp(-r) for r in rates]
print(f" check with an OR gate on the yearly probabilities of the five paths: "
f"{gate_or(*p_year):.3f}")
# ---------- Plot ----------
fig, ax = plt.subplots(1, 2, figsize=(10, 4.2))
bands = np.linspace(0.2, 2.0, 100)
ax[0].plot(bands, [cycling(b)[4] for b in bands])
ax[0].scatter([0.3, 1.5], [cycling(0.3)[4], cycling(1.5)[4]])
ax[0].set_xlabel("thermostat band (K)")
ax[0].set_ylabel("contactor life (years)")
ax[0].set_title("Contactor life against the band")
ax[0].grid(True, alpha=0.4)
labels = [f"{s}\n{p}" for s, p, _, _ in PATHS]
ax[1].barh(range(len(PATHS)), rates)
ax[1].set_yticks(range(len(PATHS)))
ax[1].set_yticklabels(labels, fontsize=7)
ax[1].invert_yaxis()
ax[1].set_xlabel("times a year")
ax[1].set_title("Paths to a warm room")
fig.tight_layout()
fig.savefig("root_cause.png", dpi=120)
print("Saved root_cause.png")

Expected output

Small example: no water at the wash point
both pumps failed (AND): 0.0025
top event (OR): 0.012475, sum of the two inputs: 0.012500
Application 1: contactor of compressor 1
record: 3 failures in 42 months, mean life 14.0 months, 0.857 failures a year
against the 0.15 a year of the other contactors: 5.7 times
band 0.3 K: on 15 min, off 5 min, cycle 20 min, 3.0 starts an hour, 25,200 a year, life 1.19 years (14.3 months)
band 1.5 K: on 75 min, off 25 min, cycle 100 min, 0.6 starts an hour, 5,040 a year, life 5.95 years (71.4 months)
share of the time the compressor runs: 75 % (any band)
room limits with the 1.5 K band about 4.0 C: 3.25 to 4.75 C
0.3 K band with a minimum off time of 10 min: room swings 0.6 K, on 30 min, 1.5 starts an hour
Application 2: cold room above 8 C for four hours
door left open 1.00 a year x alarm brings nobody 0.10 = 0.100 a year (45.5 %)
duty compressor 1.00 a year x standby does not take 0.05 = 0.050 a year (22.7 %)
grid outage 0.50 a year x generator fails 0.08 = 0.040 a year (18.2 %)
shared condenser 0.02 a year x (no protection) 1.00 = 0.020 a year ( 9.1 %)
controller fails 0.10 a year x alarm brings nobody 0.10 = 0.010 a year ( 4.5 %)
top event: 0.220 a year, once in 4.5 years on average
probability of at least one in a year: 0.197
probability of none in five years: 0.333
top event rate if one basic event is halved:
door left open 0.170 a year (saves 0.050, 22.7 %)
alarm brings nobody 0.165 a year (saves 0.055, 25.0 %)
duty compressor 0.195 a year (saves 0.025, 11.4 %)
standby does not take 0.195 a year (saves 0.025, 11.4 %)
grid outage 0.200 a year (saves 0.020, 9.1 %)
generator fails 0.200 a year (saves 0.020, 9.1 %)
shared condenser 0.210 a year (saves 0.010, 4.5 %)
controller fails 0.215 a year (saves 0.005, 2.3 %)
door and alarm both halved: 0.140 a year, probability in a year 0.131
limits: every protection perfect 0.02 a year, no protection at all 2.62 a year (11.9 times the present value)
check with an OR gate on the yearly probabilities of the five paths: 0.197
Saved root_cause.png

Common Mistakes



  • Closing the work order with the name of the part. “Contactor failed, replaced” describes the repair, not the cause.
  • Cleaning or scrapping the failed part and resetting the counters before anybody has looked at them.
  • Accepting a chain of five whys in which no answer has evidence. Five guesses are still guesses.
  • Stopping at a person. If another competent person would probably have done the same, the cause is in the situation, and the correction must change it.
  • Choosing retraining or a reminder as the only corrective action: the weakest correction, because it depends on memory.
  • Multiplying the inputs of an AND gate when the events share a cause, or multiplying a yearly probability by a probability on demand when the starting event comes several times a year.

Summary



  • A failure has physical, human and latent causes. A correction that does not reach a latent cause leaves the failure for the next part and the next person.
  • Evidence comes first: the failed part, photographs, settings, counters, data and what people saw, collected before the repair removes them.
  • The five whys follows one path, stops where the asker stops and asks for no evidence. A cause-and-effect diagram lists the other paths; a cause tree tests each one.
  • The contactor of compressor 1 failed every 14 months because a band of 0.3 K gave 3.0 starts an hour and 25,200 a year against a life of 30,000 operations. A band of 1.5 K gives 0.6 starts an hour and a calculated life of 5.95 years.
  • For independent events an AND gate multiplies and an OR gate combines as . A starting event with a rate and a protection with a probability on demand give a path rate of .
  • The cold room tree gave 0.220 top events a year, a probability of 0.197 in one year, with the door and its alarm ahead of the compressors.

Exercises



1. A pump bearing fails after 2,000 hours. The grease in it is found hard and dark. The grease point is behind a fixed guard, and the lubrication route sheet does not list it. Name the physical cause, the human cause and the latent cause, and give one correction of the strongest kind that is possible.

Answer

Physical: the bearing ran with degraded grease and wore. Human: the point was not greased. Latent: the point cannot be reached without removing a guard, and it is missing from the route sheet. Strongest correction: a change of design, for example a grease line brought outside the guard, with the point added to the route sheet.

2. A top event occurs if event A occurs, or event B occurs, or events C and D occur together. The probabilities are 0.02 for A, 0.03 for B, 0.10 for C and 0.20 for D, all independent. Find the probability of the top event.

Answer

AND gate: . OR gate: . The simple sum, 0.07, is close.

3. A cold room controller has a band of 0.5 K. Inside the band the air cools at 1.0 K an hour with the compressor running and warms at 2.0 K an hour with it stopped. Find the starts an hour, the starts in a year of 8,400 hours, and the life of a contactor with an electrical life of 30,000 operations.

Answer

Running 30 minutes, stopped 15 minutes, cycle 45 minutes: 1.33 starts an hour and 11,200 a year. Life years.

4. In the fault tree of Application 2, the site can pay for one of two changes: a generator test programme that reduces the generator’s failure on demand from 0.08 to 0.02, or a second alarm receiver that reduces the alarm’s failure from 0.10 to 0.05. Find the top event rate and the yearly probability for each, and choose.

Answer

Generator: the power path becomes , so a year and . Alarm: the door path becomes 0.050 and the controller path 0.005, so a year and . The alarm gives more, although its improvement is a factor of 2 and the generator’s is a factor of 4, because the alarm stands in the largest path.

5. In Application 2 the standby was assumed to be free all year. Suppose that for 6 weeks of the 50 week year both compressors are needed, so that in those weeks a long stop of either compressor (1.00 a year each) leads to the top event with no protection. For the other 44 weeks the tree is unchanged. Find the new rate of the compressor path, the new top event rate and the yearly probability.

Answer

Hot weeks: a year. Other weeks: a year. The compressor path is 0.284 a year and not 0.050. The top event rate is a year, and . Six weeks in which the redundancy is absent more than double the risk of the whole year.

References



  • P. D. T. O’Connor and A. Kleyner, Practical Reliability Engineering, 5th edition, Wiley, 2012.
  • W. E. Vesely, F. F. Goldberg, N. H. Roberts and D. F. Haasl, Fault Tree Handbook, NUREG-0492, U.S. Nuclear Regulatory Commission, 1981.
  • R. J. Latino and K. C. Latino, Root Cause Analysis: Improving Performance for Bottom-Line Results, 3rd edition, CRC Press, 2006.
  • J. Reason, Managing the Risks of Organizational Accidents, Ashgate, 1997.


© 2021-2026 SiliconWit®. All rights reserved.
Watch it build: a small fault tree
no water at the wash point the top event: the result nobody wants OR any one AND all together AND: p₁ × p₂ OR: 1 − (1 − p₁)(1 − p₂) supply fails 0.01 pump A pump B 0.05 0.05 0.0025 0.0125 supply: 4 × the pumps
  1. A fault tree starts from the top event, the result nobody wants: no water at the wash point.
  2. An OR gate passes the event up when any one of its inputs occurs.
  3. An AND gate passes it up only when all of its inputs occur together.
  4. For independent inputs, AND multiplies the probabilities. OR is close to their sum when they are small.
  5. The supply fails with a probability of 0.01. Each pump is failed with 0.05.
  6. Both pumps: 0.0025. The top event: 0.0125. The supply alone gives four times as much as the pumps.
Predict first

A compressor contactor has failed three times, after 14, 13 and 15 months. Each failed part shows contacts worn evenly on all three poles. The site now fits a contactor of a better make. What do you expect?

physical cause: the parthuman cause: the actionlatent cause: the system correct here
12345 change the design or the settinga protection that acts by itselfa signal in time a procedure with a recordremind or retrain needs more memory
See it: how the band sets the number of starts

Starts an hour
Starts a year (8,400 h)
Contactor life, 30,000 operations

The compressor of Application 1, set to 4.0 °C. Inside the band the air cools at 1.2 K an hour while the compressor runs and warms at 3.6 K an hour while it is stopped, so it runs 75 percent of the time whatever the band. A wider band, or a minimum stopped time, gives longer runs and fewer starts. The stock allows 2 °C to 6 °C. Time runs at about two minutes of the room for each tenth of a second.

See it: which basic event to correct first

Top event, a year
At least one in a year
Gain against 0.220

Halve one basic event, or several:

The five paths of Application 2, each a starting event a year times the chance that its protection fails on demand. The paths sit under one OR gate, so their rates add. Halve one basic event at a time, or several, and watch the top event. The alarm stands in two paths, so halving it moves two bars.

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. A bolt on a fan support broke by fatigue. The fitter did not tighten it to a stated torque, and the job sheet for that work gives no torque value. Which correction reaches the root?

2. A chiller has a thermostat band of 0.5 K. Inside the band the water cools at 1.0 K an hour while the compressor runs and warms at 2.0 K an hour while it is stopped. It is in service 8,400 hours a year, and its contactor is built for 30,000 operations. About how long does the contactor last?

3. A duty pump stops for a long time about 2 times a year. Each time, the standby pump fails to take the load with a probability of 0.1. Treating them as independent, how often a year does the site lose water?

Thermostat (room air) Controller Contactor Compressor motor Cold room air cooling
The control loop of compressor 1
Failure seen the compressor does not start Physical cause what happened to the part Human cause what was done, or not done Latent cause why the system allowed it (the root to correct)
Three levels of cause
Contactor fails Machine size of the contactor People fitting and tightening Method settings of the control Measurement coil voltage, start count Material quality and batch of part Environment heat and dust in the panel
A cause-and-effect diagram for the contactor
Contacts worn away in 14 months Contactor too small for the motor label against motor current RULED OUT Low coil voltage (contacts chatter) measured at start RULED OUT Hot or dusty panel clean, temperature in limit RULED OUT Loose terminal no heat marks RULED OUT Poor batch of parts two purchases, same life RULED OUT Too many operations 504 starts in a week CONFIRMED Band of 0.3 K (short cycling) Default setting never changed No commissioning sheet, no record of settings, no start counter latent cause
The cause tree with its evidence
Cold room above 8 °C for four hours 0.220 a year OR AND 0.100 door left open overnight 1.00 a year alarm brings nobody 0.10 AND 0.050 duty compressor long stop 1.00 a year standby does not take load 0.05 AND 0.040 long grid outage 0.50 a year generator fails 0.08 0.020 shared condenser long stop 0.02 a year no protection AND 0.010 controller fails 0.10 a year alarm brings nobody 0.10 path rate = starting rate × chance the protection fails; the OR adds them
Fault tree: cold room above 8 °C for four hours