Reporting Verified Savings

Lesson 10 of 10 25 min read
Found this useful?

A report reaches a finance manager with one line: “the project saved 18 percent”. She asks what was measured, what it was compared with, over which months, and how far the true figure could be from 18. The report answers none of these, so she holds the payment, and a project that worked is recorded as one that could not be proved. Inside a company, the next project is then refused because nobody believed the last report. This lesson shows how to write a one-page savings report that separates what was measured from what was estimated and states the saving with its range. #SavingsReport #MeasurementAndVerification #EnergySavings

Learning Objectives

By the end of this lesson, you will be able to:

  1. Assemble a one-page savings report from the plan and the record of the reporting period
  2. Calculate monthly and yearly avoided energy and its value, with the expanded uncertainty
  3. State a result and its range in one plain sentence
  4. Report a trend in the record, and say what it shows and what it does not prove
  5. Rewrite an overclaim as a sentence that the data support

Real-World System Problem: Two savings that must be signed for



Two projects of this course have reached the end of a reporting period. The drive on the booster pump has run for twelve months, with an energy meter and a flow meter at its measurement boundary. The whole-site measure has run for 230 days, and its saving is determined at the utility meter with a baseline model.

Each now needs a savings report. Its readers, a finance manager who must approve a payment and possibly an auditor who was never on the site, cannot check a meter. They can check whether the report follows the agreed plan, whether its numbers follow from its data, and whether its words claim more than its numbers.

A saving is a comparison with what would have happened, so no report can show it as a reading. A good report shows which part is a reading and which a calculation, and lets the reader decide.

Energymeter± range× priceIndependentvariablesadjusted baseline − measured± non-routine adjustmentsmeasuredflow, weather, daysBaselinecalculatedmodelone-page report
From the meters to the page

Fundamental Theory: What a savings report must say



The report follows the plan

The report applies the plan and adds nothing to it: the same boundary, meters, formula and price. Where the writer departs from the plan, the report says where and why. A reader who holds the plan and the data file must be able to reach the same number.

Before the numbers go on the page, reconcile the data file with something the reader can check without it. For a sub-meter, the sum of the period’s records must equal the difference between the meter’s register readings at the start and at the end; a shortfall is missing data that the file hides. For a utility meter, the daily readings summed between two bill reading dates must match the kWh on the bills, within about 1 percent. State in the report that both checks were made, with their results.

The eight parts

The International Performance Measurement and Verification Protocol (IPMVP) and ISO 50015 each describe what a savings report should contain. The list here is this course’s own summary, and the current edition of the document named in the contract decides.

  1. Identity. The project, the plan it follows, and the dates of the reporting period.
  2. What was measured. Each quantity, its meter and its total for the period.
  3. What was calculated. The adjusted baseline energy, with the model and the conditions it was given.
  4. Adjustments. The routine adjustment made by the model, and each non-routine adjustment on its own line.
  5. The saving. In energy first, with its range. Then in money, with the price used.
  6. What was estimated and what was left out. Agreed values, interactive effects, and anything outside the boundary.
  7. Events. Changes on the site, faults, missing data, and anything in the record that the reader would want to know.
  8. Data and signatures. Where the data file is kept, who prepared the report and who accepted it.
Data file Prepared by Accepted byProject, plan, periodEstimated or left outEvents during the periodSAVING kWh, with rangecurrency units, with rangeMeasured meters, totalsCalculated adjusted baselineAdjustments routine, non-routine
The one-page report

The sentence that states the result

The centre of the report is one sentence, and most reports write it badly. It needs five things.

The result sentence

Over [period], [the boundary] used [saving] less than it would have used [in the same conditions] without the measure, and the true figure is probably between [low] and [high].

“Probably” has a meaning here: the range is the saving plus or minus the expanded uncertainty , which covers about 95 cases in 100, as a weather forecast of 20 to 24 degrees claims less than a single number would. The report says which sources of uncertainty the range includes.

A total can hide a trend

A yearly total is one number. The record behind it, twelve months or 365 days, can show what the total hides: a saving that grows, or one that is slowly lost.

The record is better at showing a change than at fixing a level. A meter’s error is nearly the same in every month, so it shifts all months together and cancels when one month is compared with another: a change of a few percent between months can be real even when the yearly saving is known only to 13 percent.

A trend in the record is an event, and it belongs in the report. The record shows that something changed and when, not the cause.

Application 1: The first-year report for the pump drive



Step 1: Month by month

Click to reveal the monthly savings
  1. Month 1 by hand. The baseline model is a straight line, so the mean flow of the month gives the mean baseline power.

    The avoided energy is kWh, worth currency units. ✅

  2. All months. The last two columns divide by the running hours: the mean power with the drive, and the saving for each running hour.

    MonthBaseline (kWh)Avoided (kWh)ValuePower (kW)Saving (kW)
    15792292,7481.4010.916
    26162322,7841.4620.883
    36042332,7961.4330.900
    46132232,6761.5080.862
    56352322,7841.4960.861
    65562082,4961.4780.883
    75692132,5561.4680.878
    85511992,3881.5030.850
    95862042,4481.5360.820
    106132132,5561.5270.813
    115841942,3281.5620.777
    126001902,2801.6020.742

    ✅

  3. The year. Running hours 3,028.1, mean flow 12.02 m³/h. Baseline 7,106 kWh, measured 4,536 kWh.

    This is 36.2 percent of the adjusted baseline. ✅

Step 2: The uncertainty of the yearly saving

Click to reveal the range
  1. Four terms, each in kWh. Baseline power: . Energy meter: . Flow, through the slope of the model: . Hours: . ✅

  2. Combine by root sum of squares.

    The relative precision is percent. ✅

  3. Range. 2,218 to 2,922 kWh. In money, , so 26,616 to 35,064 currency units. ✅

  4. Against the plan. The plan expected 2,650 kWh. The result is 80 kWh lower (3.0 percent), and 2,650 is well inside the range. For the hours and flow of this year the plan’s figures give kWh, so on equal terms the result is 108 kWh low. On the yearly total alone, the project has done what was expected. ✅

Step 3: What the monthly record shows

Click to reveal the trend
  1. The saving for each running hour. In months 1 to 7 its mean is 0.884 kW, with a scatter of 0.020 kW from month to month. This agrees with the 0.883 kW of the plan. ✅

  2. From month 8 it falls every month. 0.850, 0.820, 0.813, 0.777 and 0.742 kW. Month 12 is 16.0 percent below the mean of the first seven months, a fall of seven times the monthly scatter. ✅

  3. The flow did not cause it. The mean flow was 12.03 m³/h in months 1 to 7 and 12.01 in months 8 to 12. The mean power with the drive rose from 1.464 kW to 1.602 kW in month 12, by about 22 W a month, at an unchanged flow. ✅

  4. Check a second way. Fit the measured power against flow in months 1 to 7: kW. In months 8 to 12 the measured power lies above this line by 0.026, 0.057, 0.077, 0.116 and 0.145 kW. Over the hours of those months that is 107 kWh, or 1,279 currency units, and it accounts for the 108 kWh of Step 2. ✅

  5. What the record shows. From month 8 the pump has needed more power each month to deliver the same flow. If the month 12 level stayed for 3,000 hours, about 435 kWh a year would be lost, one sixth of the expected saving. That figure is a condition, not a forecast. ✅

  6. What the record does not prove. It does not give the cause. A strainer that is blocking, a worn impeller, a pressure set point that somebody raised and a meter that is drifting all produce this record. The first two are losses of saving. The third is a change to a static factor and would need a non-routine adjustment. The fourth is an error. Somebody must go to the pump. One visit separates them: compare the energy meter with a portable power meter (the fourth cause), read the pressure set point against the plan (the third), then open the strainer. ✅

  7. The hidden truth of the data. The generator raises the power with the drive by 2 percent each month from month 8, to imitate a strainer that is slowly blocking. The writer of a real report does not know this, and must not write it as a finding. ✅

kW0.92x0.90x0.88xxx0.883 planned0.86x x0.84x0.82x x0.78x0.74xmonth123456789..12
Saving for each running hour, month by month

Step 4: The report

Click to reveal the one-page report
  1. The page. Fields with dots are filled in on site.

    Savings reportVariable speed drive on the booster pump
    Plan and periodPlan dated … Months 1 to 12 after commissioning, … to …
    MeasuredElectrical energy at the pump’s supply: 4,536 kWh. Running hours: 3,028.1. Mean flow: 12.02 m³/h (monthly means 11.52 to 12.44, inside the model’s range)
    CalculatedAdjusted baseline energy 7,106 kWh, from the model kW at the measured flow and hours
    AdjustmentsRoutine: the baseline follows the flow and the hours of each month. Non-routine: none. No change to a static factor was reported. Pressure set point read as … on …
    Saving, energy2,570 kWh avoided, 36.2 percent of the adjusted baseline. Range 2,218 to 2,922 kWh at about 95 percent, from the uncertainties of the meters and the hours as the plan states them
    Saving, money30,840 currency units at the plan’s 12.00 per kWh. Range 26,616 to 35,064
    Against the planExpected 2,650 kWh. The result is 3.0 percent lower and agrees with the plan within its range
    Estimated or left outThe baseline energy is calculated, not measured. The meter uncertainties are the plan’s values and were not tested. No demand charge saving and no interactive effect is claimed. Missing data: … hours
    EventsFrom month 8 the mean power with the drive rose each month, from 1.464 kW to 1.602 kW in month 12, at an unchanged flow. The saving for each running hour fell from 0.884 kW to 0.742 kW. The cause is not identified. An inspection of the pump, its strainer and the pressure set point is requested
    ChecksSum of the 12 monthly records 4,536 kWh; meter register … at the start and … at the end, difference … kWh. Energy meter compared with a portable power meter on …: … percent
    DataFile … Meter serial numbers and calibration dates as in the plan
    SignaturesPrepared by … Date … Accepted by … Date …

    The page reports a good year and a problem, and keeps them apart. ✅

Application 2: The report for the whole-site measure



Step 1: The saving and its range

Click to reveal the numbers
  1. Avoided energy.

    At 12.00 per kWh it is worth 166,284 currency units. ✅

  2. Which uncertainty to report. The simple form gives kWh (10.8 to 12.1 percent). The fuller form gives kWh from unrounded values. The report uses the fuller one, because the simple form treats the fitted coefficients as exact. A reader who asks for ASHRAE Guideline 14 gets one more line: its fractional savings uncertainty, with the residuals’ autocorrelation of 0.088, is 3.8 percent at 68 percent confidence, far inside its limit of 50 percent, and 7.4 percent at 95 percent, inside the range reported here. ✅

  3. Range. 12,768 to 14,946 kWh, which is 10.6 to 12.4 percent. In money, 153,216 to 179,352 currency units. The relative precision is percent. ✅

  4. The sentence. “Over the 230 days after the measure was fitted, the site used about 13,900 kWh less electricity than it would have used in the same weather and on the same working days without the measure. The true figure is probably between 12,800 and 14,900 kWh. At the agreed price that is about 166,000 currency units, probably between 153,000 and 179,000.” ✅

Step 2: The report

Click to reveal the one-page report
  1. The page.

    Savings reportWhole-site measure
    Plan and periodPlan dated … Days 500 to 729 (230 days), … to …
    MeasuredElectrical energy at the utility meter: 107,014 kWh. Outdoor temperature each day. The calendar
    CalculatedAdjusted baseline energy 120,871 kWh, from kWh a day (RMSE 27.30 kWh) at the weather and working days of the period. Cooling degree days were 0 to 9.9 a day, inside the baseline’s 0 to 11.0
    AdjustmentsRoutine: weather and day of the week, by the model. Non-routine: none. No change to a static factor was reported
    Saving, energy13,857 kWh avoided, 11.46 percent of the adjusted baseline. Range 12,768 to 14,946 kWh (10.6 to 12.4 percent) at about 95 percent
    Saving, money166,284 currency units at 12.00 per kWh. Range 153,216 to 179,352
    Estimated or left outThe range covers the scatter of the baseline model and the uncertainty of its coefficients. It does not cover the error of the utility meter or any dependence between the errors of one day and the next. No demand charge saving is claimed. The period is 230 days and is not scaled to a year
    Events…
    ChecksDaily readings summed between the bill reading dates of … and …: … kWh, against … kWh on the bills. Model tested on days 365 to 499, before the measure: bias 0.53 percent
    DataDaily file … Utility meter number …
    SignaturesPrepared by … Date … Accepted by … Date …

    ✅

  2. Why the result is not scaled to a year. At 60.2 kWh a day, 365 days would give 21,990 kWh. The 230 days were cooler than a full year, and a cooling measure saves more in warm weather, so that figure describes no year that happened. A yearly figure for normal weather is a normalised saving: a different calculation, which must be named in the plan. ✅

  3. Check with the script. The script fits the model again from the data and prints 13,857 kWh, 414 and 544 kWh, 1,089 kWh, the same ranges and 21,990 kWh. ✅

The wording of a report



Three pairs of words must stay apart in every report.

Measured against estimated. A metered kWh is measured, a baseline is calculated from a model, and agreed hours are estimated. For the lighting change of this course the honest line is “18,144 kWh a year from measured power and agreed hours, and about 5,600 kWh of cooling energy, estimated”, never one “measured” total of the two.

Gross against net of adjustments. When a 9 kW process load was added to the site, the saving before adjustment was 5,577 kWh, the non-routine adjustment was 8,280 kWh and the saving after adjustment was 13,857 kWh. A report shows all three lines.

Energy against money. State kWh first, then the price, then the money. The power factor correction bank of this course saves about 172,880 currency units a month and almost no kWh, and a report that called it an energy saving would be wrong.

Three overclaims are common. Each has a better sentence.

OverclaimWhat is wrongBetter sentence
”The drive saved 31,800 currency units.”It is the proposal’s figure, stated as a result, with no range”In twelve months the pump used 2,570 kWh less than its baseline for the same flow and hours (range 2,218 to 2,922), worth 30,840 currency units at the agreed price."
"The measure cut the site’s energy by 22.8 percent.”It compares raw meter readings, so cooler weather is counted as saving”After adjustment for weather and working days, the avoided energy is 11.5 percent of the adjusted baseline, probably between 10.6 and 12.4 percent."
"The project will save 21,990 kWh every year.”It scales 230 cool days to a year and promises the future”In the 230 days measured, 13,857 kWh were avoided. A year with other weather will give another figure.”

Avoid “guaranteed”, “proved” and “actual saving”. A saving is an estimate with a range, however good the meters are.

Verify It in Python



The script generates the twelve months of the pump drive with a fixed seed, calculates the monthly and yearly savings, the uncertainty and the trend, and then rebuilds the whole-site result with both forms of its uncertainty. It saves one figure: the saving for each running hour by month, and the reported savings with their ranges.

savings_report.py
"""Savings reports: twelve months of the pump drive, and the whole-site measure."""
import numpy as np
import matplotlib.pyplot as plt
PRICE = 12.00 # currency units per kWh, from the plan
# ---------- Part 1: project A, first year with the drive ----------
A0, B1 = 1.625, 0.0600 # baseline model of the plan: kW = A0 + B1 x Q
EXPECTED = 2650.0 # kWh a year, from the plan
rng = np.random.default_rng(12)
month = np.arange(1, 13)
hours = np.round(250.0 + rng.normal(0, 12.0, 12), 1) # running hours, from the record
flow = np.round(12.0 + rng.normal(0, 0.25, 12), 2) # mean flow while running, m3/h
rise = 1.0 + 0.02 * np.clip(month - 7, 0, None) # built in: see the lesson
p_true = (1.462 + 0.12 * (flow - 12.0)) * rise * (1.0 + rng.normal(0, 0.006, 12))
meas = np.round(p_true * hours, 0) # kWh on the energy meter
base = np.round((A0 + B1 * flow) * hours, 0) # adjusted baseline, whole kWh
avoid = base - meas
p_meas = meas / hours # mean power with the drive, kW
rate = avoid / hours # saving for each running hour, kW
print("Project A, months 1 to 12")
print(" month hours flow baseline measured avoided money kW meas kW saved")
for k in range(12):
print(f" {month[k]:>3} {hours[k]:>6.1f} {flow[k]:>5.2f} {base[k]:>8.0f} {meas[k]:>8.0f} "
f"{avoid[k]:>7.0f} {avoid[k] * PRICE:>6.0f} {p_meas[k]:>7.3f} {rate[k]:>8.3f}")
H, B, M = hours.sum(), base.sum(), meas.sum()
S = B - M
qbar = (flow * hours).sum() / H
print(f" year: hours {H:.1f}, mean flow {qbar:.2f}, baseline {B:.0f}, measured {M:.0f} kWh")
print(f" avoided energy {S:.0f} kWh = {100 * S / B:.1f} %, {S * PRICE:.0f} currency units")
u_terms = {
"baseline power, 2 %": 0.02 * B,
"energy meter, 2 %": 0.02 * M,
"flow, 2 %": B1 * 0.02 * qbar * H,
"hours, 1 %": 0.01 * S,
}
u = np.sqrt(sum(v ** 2 for v in u_terms.values()))
U = round(2 * u)
for name, v in u_terms.items():
print(f" u from {name:<20}{v:>6.1f} kWh")
print(f" combined u {u:.0f} kWh, expanded U {U} kWh = {U * PRICE:.0f} currency units "
f"({100 * U / S:.1f} %)")
print(f" range {round(S) - U} to {round(S) + U} kWh, "
f"{(round(S) - U) * PRICE:.0f} to {(round(S) + U) * PRICE:.0f} currency units")
print(f" expected {EXPECTED:.0f} kWh: measured is {S - EXPECTED:+.0f} kWh "
f"({100 * (S - EXPECTED) / EXPECTED:+.1f} %)")
print(f" at {H:.0f} hours and {qbar:.2f} m3/h the plan expects "
f"{(A0 + B1 * qbar - 1.462) * H:.0f} kWh")
early, late = month <= 7, month >= 8
print("The trend")
print(f" months 1 to 7: mean power {p_meas[early].mean():.3f} kW, "
f"saving {rate[early].mean():.3f} kW (scatter {rate[early].std(ddof=1):.3f})")
print(f" month 12: power {p_meas[-1]:.3f} kW, saving {rate[-1]:.3f} kW "
f"({100 * (rate[-1] / rate[early].mean() - 1):+.1f} %)")
print(f" mean flow: months 1 to 7 {flow[early].mean():.2f}, months 8 to 12 {flow[late].mean():.2f} m3/h")
slope = np.polyfit(month[late], p_meas[late], 1)[0]
print(f" slope of measured power over months 8 to 12: {slope * 1000:+.0f} W a month")
c = np.polyfit(flow[early], p_meas[early], 1) # power against flow, months 1 to 7
excess = p_meas - np.polyval(c, flow)
print(f" second way: power = {c[1]:.3f} + {c[0]:.3f} x Q in months 1 to 7")
print(" excess power by that line, months 8 to 12 (kW): "
+ ", ".join(f"{x:+.3f}" for x in excess[late]))
lost = (excess[late] * hours[late]).sum()
print(f" energy above that line in months 8 to 12: {lost:.0f} kWh = {lost * PRICE:.0f} currency units")
print(f" if the month 12 excess stayed for 3,000 hours: {excess[-1] * 3000:.0f} kWh a year")
# ---------- Part 2: the whole-site measure ----------
def building_daily(seed=23, days=730):
rng = np.random.default_rng(seed)
d = np.arange(days)
temp = 21.0 + 4.5 * np.sin(2 * np.pi * (d - 20) / 365.0) + rng.normal(0, 1.6, days)
weekday = (d % 7) < 5
cdd = np.clip(temp - 18.0, 0.0, None)
energy = 310.0 + 42.0 * cdd + np.where(weekday, 180.0, 0.0) + rng.normal(0, 28.0, days)
energy[500:] *= 0.88
return d, temp, weekday, energy # kWh a day
d, temp, weekday, energy = building_daily()
cdd = np.clip(temp - 18.0, 0.0, None)
X = np.column_stack([np.ones(d.size), cdd, weekday.astype(float)])
Xb, Xr = X[:365], X[500:]
coef, *_ = np.linalg.lstsq(Xb, energy[:365], rcond=None)
rmse = np.sqrt(np.sum((energy[:365] - Xb @ coef) ** 2) / (365 - 3))
m = Xr.shape[0]
Bs, Ms = (Xr @ coef).sum(), energy[500:].sum()
Ss = Bs - Ms
ones = np.ones(m)
u_simple = rmse * np.sqrt(m)
u_full = rmse * np.sqrt(m + ones @ Xr @ np.linalg.inv(Xb.T @ Xb) @ Xr.T @ ones)
Us = round(2 * u_full)
print("Whole-site measure, days 500 to 729")
print(f" baseline {coef[0]:.1f} + {coef[1]:.2f} x CDD + {coef[2]:.1f} x weekday, RMSE {rmse:.2f} kWh")
print(f" CDD in the period: 0 to {cdd[500:].max():.1f} a day; baseline period 0 to {cdd[:365].max():.1f}")
print(f" adjusted baseline {Bs:.0f}, measured {Ms:.0f}, avoided {Ss:.0f} kWh = {100 * Ss / Bs:.2f} %")
print(f" u simple {u_simple:.0f} kWh (U {2 * u_simple:.0f}); with the coefficients u {u_full:.0f} kWh, U {Us}")
lo, hi = round(Ss) - Us, round(Ss) + Us
print(f" range {lo} to {hi} kWh = {100 * lo / Bs:.1f} to {100 * hi / Bs:.1f} %, "
f"relative precision {100 * Us / Ss:.1f} %")
print(f" money {round(Ss) * PRICE:.0f}, range {lo * PRICE:.0f} to {hi * PRICE:.0f}, "
f"U {Us * PRICE:.0f} currency units")
print(f" saving over its standard uncertainty: {Ss / u_full:.1f}")
print(f" a day: {Ss / m:.1f} kWh; a 365 day year at that rate: {365 * Ss / m:.0f} kWh (not reported)")
# ---------- Plot ----------
fig, ax = plt.subplots(2, 1, figsize=(8, 8))
ax[0].bar(month, rate)
ax[0].axhline(0.883, color="gray", linewidth=0.8)
ax[0].set_xlabel("month of the reporting period")
ax[0].set_ylabel("saving for each running hour (kW)")
ax[0].set_title("Pump drive: the saving month by month (line: 0.883 kW expected)")
ax[1].errorbar([0, 1], [EXPECTED, S], yerr=[0, U], fmt="o", capsize=6)
ax[1].errorbar([2], [Ss / 10], yerr=[Us / 10], fmt="s", capsize=6)
ax[1].set_xticks([0, 1, 2])
ax[1].set_xticklabels(["pump, expected", "pump, measured", "whole site (kWh / 10)"])
ax[1].set_xlim(-0.5, 2.5)
ax[1].set_ylabel("avoided energy (kWh)")
ax[1].set_title("Reported savings with their expanded uncertainty")
fig.tight_layout()
fig.savefig("savings_report.png", dpi=120)
print("Saved savings_report.png")

Expected output

Project A, months 1 to 12
month hours flow baseline measured avoided money kW meas kW saved
1 249.9 11.52 579 350 229 2748 1.401 0.916
2 262.6 12.04 616 384 232 2784 1.462 0.883
3 258.9 11.77 604 371 233 2796 1.433 0.900
4 258.7 12.44 613 390 223 2676 1.508 0.862
5 269.4 12.22 635 403 232 2784 1.496 0.861
6 235.5 12.24 556 348 208 2496 1.478 0.883
7 242.5 11.99 569 356 213 2556 1.468 0.878
8 234.2 12.15 551 352 199 2388 1.503 0.850
9 248.7 12.16 586 382 204 2448 1.536 0.820
10 262.0 11.91 613 400 213 2556 1.527 0.813
11 249.7 11.88 584 390 194 2328 1.562 0.777
12 256.0 11.97 600 410 190 2280 1.602 0.742
year: hours 3028.1, mean flow 12.02, baseline 7106, measured 4536 kWh
avoided energy 2570 kWh = 36.2 %, 30840 currency units
u from baseline power, 2 % 142.1 kWh
u from energy meter, 2 % 90.7 kWh
u from flow, 2 % 43.7 kWh
u from hours, 1 % 25.7 kWh
combined u 176 kWh, expanded U 352 kWh = 4224 currency units (13.7 %)
range 2218 to 2922 kWh, 26616 to 35064 currency units
expected 2650 kWh: measured is -80 kWh (-3.0 %)
at 3028 hours and 12.02 m3/h the plan expects 2678 kWh
The trend
months 1 to 7: mean power 1.464 kW, saving 0.884 kW (scatter 0.020)
month 12: power 1.602 kW, saving 0.742 kW (-16.0 %)
mean flow: months 1 to 7 12.03, months 8 to 12 12.01 m3/h
slope of measured power over months 8 to 12: +22 W a month
second way: power = 0.067 + 0.116 x Q in months 1 to 7
excess power by that line, months 8 to 12 (kW): +0.026, +0.057, +0.077, +0.116, +0.145
energy above that line in months 8 to 12: 107 kWh = 1279 currency units
if the month 12 excess stayed for 3,000 hours: 435 kWh a year
Whole-site measure, days 500 to 729
baseline 306.6 + 41.61 x CDD + 182.1 x weekday, RMSE 27.30 kWh
CDD in the period: 0 to 9.9 a day; baseline period 0 to 11.0
adjusted baseline 120871, measured 107014, avoided 13857 kWh = 11.46 %
u simple 414 kWh (U 828); with the coefficients u 544 kWh, U 1089
range 12768 to 14946 kWh = 10.6 to 12.4 %, relative precision 7.9 %
money 166284, range 153216 to 179352, U 13068 currency units
saving over its standard uncertainty: 25.5
a day: 60.2 kWh; a 365 day year at that rate: 21990 kWh (not reported)
Saved savings_report.png

In the upper plot the bars stand near the planned 0.883 kW for seven months and then fall each month. In the lower plot the measured saving of the pump lies below the expected point, with the expected value inside its range.

Common Mistakes



  • Reporting one number with no range. State the saving, its expanded uncertainty and what the uncertainty includes.
  • Adding measured and estimated quantities into one total. Give each its own line and label it.
  • Reporting only the yearly total. Give the monthly figures, and report any trend or step as an event.
  • Explaining a trend without a visit to the site. The record shows that something changed. It does not show what.
  • Scaling a short reporting period to a year, or quoting the proposal’s figure as the result.
  • Changing the price, the formula or the period from those of the plan without saying so.

Summary



  • A savings report follows the plan and states: what was measured, what was calculated, the adjustments, the saving in kWh and in money with its range, what was estimated or left out, the events, and where the data are.
  • In its first year the pump drive avoided 2,570 kWh (range 2,218 to 2,922), worth 30,840 currency units, which agrees with the planned 2,650 kWh.
  • The monthly record showed the saving for each running hour falling from 0.884 kW to 0.742 kW from month 8. The report states this as an event with no cause given, and asks for an inspection.
  • The whole-site measure avoided 13,857 kWh in 230 days, 11.46 percent, with a range of 12,768 to 14,946 kWh, worth 166,284 currency units.
  • Keep measured apart from estimated, gross apart from net of adjustments, and energy apart from money.

Exercises



1. A reporting period has an adjusted baseline of 48,000 kWh and a measured energy of 43,900 kWh. The standard uncertainty of the saving is 600 kWh and the price is 12.00 currency units per kWh. Write the result sentence with its numbers.

Answer

Saving kWh, which is 8.5 percent. kWh, so the range is 2,900 to 5,300 kWh (6.0 to 11.0 percent), a relative precision of 29 percent. “Over the period the site used about 4,100 kWh less than it would have used in the same conditions without the measure, probably between 2,900 and 5,300 kWh, worth 49,200 currency units (34,800 to 63,600).”

2. Use the plan of the pump drive. In a later month the pump runs 245.0 hours at a mean flow of 12.30 m³/h, and the meter records 391 kWh. Find the avoided energy and the saving for each running hour, and compare it with the planned 0.883 kW.

Answer

Baseline: kWh. Avoided: kWh. For each running hour: kW, which is 13 percent below 0.883 kW. One month alone does not show a trend, so it must be compared with the months before it.

3. For six months a motor’s saving for each running hour is 0.90, 0.89, 0.91, 0.86, 0.82 and 0.78 kW, with 250 running hours in each month. The plan expected 0.90 kW. Find the avoided energy against the plan, and say what the report must contain.

Answer

Avoided: kWh against a planned kWh, which is 4.4 percent low. The total looks acceptable, but the last month is 13.3 percent below the mean of the first three (0.90 kW) and the fall has continued for three months. The report states the trend as an event, gives no cause that was not found on site, and asks for an inspection.

4. A draft report says: “Our lighting project saved 23,727 kWh, measured.” The power was measured, the 4,200 hours were agreed, and 5,583 kWh of the total is an estimated cooling effect. An earlier calculation gave the lighting saving an expanded uncertainty of 3,701 kWh. Rewrite the sentence.

Answer

“The lighting change saves 18,144 kWh a year, from measured power and agreed hours, probably between 14,443 and 21,845 kWh. A further saving of about 5,600 kWh a year in cooling energy is estimated from two stated assumptions and was not measured.” The two figures are not added into one measured total.

References



  • Efficiency Valuation Organization, International Performance Measurement and Verification Protocol (IPMVP): Core Concepts, current edition.
  • ASHRAE, Guideline 14-2014: Measurement of Energy, Demand, and Water Savings, ASHRAE, 2014.
  • ISO 50015:2014, Energy management systems: Measurement and verification of energy performance of organizations: General principles and guidance.
  • B. L. Capehart, W. C. Turner and W. J. Kennedy, Guide to Energy Management, 8th edition, Fairmont Press, 2016.


© 2021-2026 SiliconWit®. All rights reserved.
Energy meter Independent variables flow, weather, days Baseline model calculated measured adjusted baseline − measured ± non-routine adjustments ± range × price one-page report
From the meters to the page
Project, plan, period Measured meters, totals Calculated adjusted baseline Adjustments routine, non-routine SAVING kWh, with range currency units, with range Estimated or left out Events during the period Data file Prepared by Accepted by
The one-page report
0.74 0.78 0.82 0.86 0.90 kW saved for each running hour 1 2 3 4 5 6 7 8 9 10 11 12 month 0.883 planned falls every month from month 8
Saving for each running hour, month by month
Predict first

A pump drive was expected to save 2,650 kWh in its first year. The report gives 2,570 kWh, with a range of 2,218 to 2,922 kWh. Is the pump in good order?

probably between 2,218 and 2,922 kWh result 2,570 2,0002,5003,000 plan 2,650 kWh avoided by the pump drive in its first year
See it: a good year that hides a fault

Yearly saving
Range, about 95 percent
Month 12, each running hour

The pump drive of Application 1: the running hours, flows and baseline of the lesson's twelve months, with the uncertainties of the plan. The lesson's data have a rise of 2 percent a month, which imitates a strainer that is slowly blocking. Raise it and watch the yearly verdict: the plan's 2,650 kWh stays inside the range even when month 12 saves only half of what was planned.

one line: wrong two lines: honest 23,72718,1445,583 "measured"measuredestimated kWh a year, lighting change

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. A reporting period has an adjusted baseline of 62,000 kWh and a measured energy of 57,300 kWh. The standard uncertainty of the saving is 700 kWh. Which range belongs in the result sentence?

2. A motor's saving for each running hour falls in each of the last four months of the year, while its yearly total agrees with the plan within its range. Nobody has visited the motor yet. What goes into the events row of the report?

3. The power factor correction bank of this course saves about 172,880 currency units a month and almost no kWh. The energy price is 12.00 currency units per kWh. How does the report state its saving?

Watch it build: the result of the pump drive
Over 12 months, the pump and drive used less than without 2,2002,6003,000 2,570 kWh 2,570 2,2182,922 probably: ± U = 2 × 176 = 352 kWh,about 95 cases in 100 plan 2,650 The plan lies inside the range:the total agrees with the plan. Saving per hour: 0.884 → 0.742 kWMonth 12 is 16 % lower: an event
  1. One sentence carries the result. The saving: 7,106 kWh adjusted baseline less 4,536 measured is 2,570 kWh.
  2. Probably means ± U: 2 × 176 = 352 kWh, so 2,218 to 2,922 kWh.
  3. The plan expected 2,650 kWh, well inside the range: the total agrees with the plan.
  4. The record behind the total: the saving per hour fell from 0.884 to 0.742 kW. Report it.