Resistance Thermometers: Pt100 and Pt1000

Lesson 3 of 10 28 min read
Found this useful?

A cold room controller shows 4 °C all night, and in the morning the lettuce is frozen and the vaccines must be thrown away. The sensor was good and the controller was good. The fault was 30 metres of cable between them, which added 2 Ω to a measurement where 0.39 Ω means one degree. This lesson shows how a platinum resistance thermometer turns temperature into resistance, how much error the wiring adds, and how a third or fourth wire removes it. You will calculate each error in ohms and in degrees, and you will state the uncertainty of a converted reading. #Instrumentation #Pt100 #TemperatureMeasurement

Learning Objectives

By the end of this lesson, you will be able to:

  1. Calculate the resistance of a Pt100 or Pt1000 at a given temperature, and the temperature from a measured resistance
  2. Judge when the linear approximation is good enough and when the quadratic is needed
  3. Calculate the error from lead wires in a two-wire and a three-wire connection
  4. Estimate the self-heating error from the measuring current
  5. State the uncertainty of a temperature from the tolerance class and the readout

Real-World System Problem: A cold room that reads warm



A cold room for vegetables, milk or vaccines is held near 4 °C. Many products in it are damaged below 0 °C and spoil faster above 8 °C, so the permitted window is only a few degrees wide. The air temperature is measured by a Pt100 probe in the room. The controller is in a plant room or an office, and in this example the cable between them is 30 m long.

A Pt100 changes by about 0.39 Ω for each degree. The copper cable has a resistance too, about 1.05 Ω in each wire. An instrument that cannot tell the cable from the sensor adds the cable to the reading, like a scale that weighs a parcel together with its heavy box. The room appears several degrees warmer than it is, the controller cools it until the false reading says 4 °C, and the real air is below zero.

The display does not show the error: the reading is steady, has two decimal places, and is wrong. The only defence is to know how the sensor and its connection work, and to calculate the error before the cable is pulled.

Pt100probeEvaporator(cold air)Controllerreads ohmsCOLDROOM(airnear4°C)doorwarm air30 m copper cable1.05Ωineachwire
The cold room, the probe and the long cable

Fundamental Theory: Platinum as a thermometer



Why resistance rises with temperature

In a metal, electric current is carried by electrons that move through a lattice of atoms. When the metal is warmer, the atoms vibrate more and the electrons collide with them more often. The resistance rises. For a pure metal the rise is close to a straight line over a wide range of temperature, so a measurement of resistance is a measurement of temperature.

Platinum is the standard choice for three reasons. It can be made very pure, so one sensor behaves like the next. It does not corrode or oxidise in normal use, so it stays the same for years. And its resistance curve is smooth and well known. A sensor made this way is called a resistance temperature detector (RTD) or a platinum resistance thermometer.

The name of the sensor states its resistance at 0 °C. A Pt100 has at 0 °C. A Pt1000 has . Both use the same platinum and follow the same curve, multiplied by ten for the Pt1000.

The Callendar-Van Dusen equation

The standard IEC 60751 gives the resistance of industrial platinum as a function of temperature. For temperatures from 0 °C to 850 °C it is a quadratic.

Resistance of platinum at or above 0 °C (IEC 60751)

Here is the temperature in °C, is the resistance at that temperature, and is the resistance at 0 °C. The coefficients and come from the standard and are the same for every Pt100 and Pt1000 made to it.

The term with is negative, so the curve bends slightly downward: each degree adds a little less resistance than the degree before it. Below 0 °C the standard adds one more term, with , inside the bracket. This lesson works at and above 0 °C, where that term is not used. For a freezer the term is still very small: if you ignore it, the quadratic and its inverse are wrong by 0.001 °C at −20 °C and 0.01 °C at −40 °C. Below about −50 °C (0.02 °C) use the full equation.

To find temperature from a measured resistance, solve the quadratic for and take the root that gives when .

Temperature from resistance, at or above 0 °C

Sensitivity

The sensitivity is the slope of the curve: how many ohms the sensor gains for one degree.

For a Pt100 at 0 °C this is per °C, and it falls slowly as the temperature rises. This one number converts every resistance error in the measuring chain into a temperature error:

Remember the size of it. On a Pt100, an extra 0.39 Ω anywhere in the circuit is an error of one whole degree.

The linear approximation and its error

Many instruments and many quick calculations use a straight line in place of the quadratic. The line is drawn through the two points 0 °C and 100 °C. Its slope is described by the mean coefficient per °C, which is why a standard Pt100 is often called a “385” sensor.

The line meets the curve at 0 °C and 100 °C. Between those points it reads a little high. Above 100 °C it reads low, and the error grows quickly.

True temperatureResistance (Pt100)Linear resultError of the linear result
4 °C101.562 Ω4.06 °C+0.06 °C
50 °C119.397 Ω50.38 °C+0.38 °C
100 °C138.505 Ω100.01 °C+0.01 °C
200 °C175.856 Ω197.03 °C−2.97 °C
400 °C247.092 Ω382.06 °C−17.94 °C
600 °C313.708 Ω555.09 °C−44.91 °C

For a cold room at 4 °C the linear result is wrong by 0.06 °C, which is small against the tolerance of the sensor. For an oven at 200 °C it is wrong by 3 °C, which is not acceptable. The honest rule is: the straight line is a tool for 0 to 100 °C, and the quadratic is the method everywhere else.

Tolerance classes

No real sensor sits exactly on the standard curve. IEC 60751 sorts sensors into classes by how far they may be from it. The tolerance is a limit, in °C, that grows with the distance from 0 °C. In these formulas is the temperature without its sign.

ClassTolerance (IEC 60751)At 4 °CAt 100 °C
AA±0.11 °C±0.27 °C
A±0.16 °C±0.35 °C
B±0.32 °C±0.80 °C
C±0.64 °C±1.60 °C

Class B is the common industrial grade. Each class applies only inside a stated temperature range, which depends on how the sensor is built, so check the datasheet. The tolerance describes a new sensor. It does not include the wiring, the instrument, or drift after years of use.

Two-wire connection: the leads are in the measurement

To measure a resistance, the instrument passes a small known current through it and measures the voltage. With two wires, the same pair carries the current and senses the voltage. The instrument cannot separate the sensor from the wires, so it measures all three in series.

RL1RL2RtsourceImeterVINSTRUMENTcablePROBEmeasured resistance = Rt + RL1 + RL2
Two-wire: both lead resistances are added

Let be the resistance of the sensor and , the resistances of the two leads. The error in ohms is , always positive, so a two-wire Pt100 always reads warm.

Many instruments accept a fixed offset to cancel the leads. This helps but does not cure: copper itself changes by about 0.39 percent per °C (a typical value), so the lead resistance moves with the weather and with the heat in the cable route, and the offset is correct on one day only.

Three-wire connection: measure one lead and subtract it

The three-wire connection has one wire to one end of the sensor (lead 1) and two wires to the other end (leads 2 and 3). The current flows out through lead 1 and returns through lead 3. Lead 2 carries almost no current, so there is no voltage drop along it, and it reports the voltage at the far end of the sensor.

RL1RL2RL3Rt1 I2 sense3 IINSTRUMENTcablePROBEV12=I(RL1+Rt)V23=IRL3
Three-wire: lead 2 senses, leads 1 and 3 carry current

The instrument takes two voltages. Between terminals 1 and 2 it sees the sensor and lead 1. Between terminals 2 and 3 it sees lead 3 alone. It subtracts the second from the first:

If the two current-carrying leads have the same resistance, the bracket is zero and the leads vanish from the result. That is the one assumption of the three-wire method: equal lead resistances. It is a good assumption when the three wires are cores of one cable, with the same length, the same cross-section and the same temperature. It fails when one terminal is loose or corroded, or when a repair has added a different piece of wire to one core. The error left is the difference between the two leads, not their sum.

Four-wire connection: no assumption at all

The four-wire connection uses one pair of wires for the current and a separate pair for the voltage. The voltage pair is connected directly at the sensor and carries almost no current, so no lead resistance appears in the voltage at all.

RL1RL2RL3RL4RtI outV +V -I retINSTRUMENTcablePROBEV/I=Rt(no lead term, leads may differ)
Four-wire: separate pairs for current and voltage

The leads may be long, thin and unequal, and the result is still . Four-wire is the method for laboratories, for calibration and for any measurement where 0.1 °C matters. Three-wire is the usual industrial compromise, because it saves one core and removes most of the error.

Self-heating

The measuring current heats the sensor, because any current in a resistance releases power:

The sensor then sits slightly above the temperature of the air it is meant to measure. The rise depends on how easily the heat leaves the probe, which is described by a dissipation constant in mW per °C:

The dissipation constant is not in the standard. It depends on the probe and on the medium: it is low in still air, higher in moving air and much higher in water. A typical figure for a small sheathed probe in still air is about 5 mW per °C, and this lesson uses that value as typical. The maker’s datasheet gives the real one.

For a Pt100 at 1 mA near 4 °C, and the rise is . That is negligible. At 5 mA the power is 25 times larger, 2.5 mW, and the rise is 0.5 °C. The error grows with the square of the current, which is why measuring currents are kept at 1 mA or less.

Pt100 against Pt1000

A Pt1000 has ten times the resistance and ten times the sensitivity, about 3.9 Ω per °C. The cable is the same, so the same lead resistance now causes one tenth of the temperature error. This is the main advantage of the Pt1000: a two-wire connection becomes usable over moderate distances, which suits building controls and battery-powered devices.

The cost is self-heating. At the same 1 mA, a Pt1000 releases ten times the power of a Pt100, about 1.0 mW, and rises by about 0.2 °C in still air. A Pt1000 is therefore measured at a lower current, typically 0.1 mA, where the rise is 0.002 °C and the voltage signal is still as large as that of a Pt100 at 1 mA.

Pt100Pt1000
Resistance at 4 °C101.56 Ω1015.6 Ω
Sensitivity at 4 °C0.390 Ω per °C3.90 Ω per °C
Error from 2.10 Ω of leads, two-wire5.38 °C0.54 °C
Self-heating at 1 mA (typical, still air)0.02 °C0.20 °C
Usual connectionthree-wire or four-wiretwo-wire, short to moderate runs

Where to put the probe, and how fast it responds

A correct resistance is still a wrong answer if the probe is in the wrong air. In a cold room, fit the air probe in the return air to the evaporator, or at product height in the body of the room: away from the door, where warm air enters, from the evaporator outlet, where the air is several degrees colder, from walls and from lamps. If the question is the temperature of the product, not of the air, use a second probe in a product simulator: a small sealed bottle of liquid, often glycol, that warms and cools about as slowly as the product does.

A sheathed probe does not follow the air at once, because its sheath and filling must warm or cool first, as a cup of tea takes time to cool in a cold room. For a sudden change of air temperature from to , the indication follows a first-order curve with a time constant :

After one time constant the probe has covered 63 percent of the change, and after three it has covered 95 percent. A typical 6 mm sheathed probe has a time constant of some tens of seconds in moving air and a few seconds in moving water. The maker states the response time for defined test conditions. With (typical), a door opening that lifts the air from 4 °C to 10 °C shows as only 7.2 °C after 30 s. A slow probe hides short events. That is often acceptable, because the product is slower still, but it must be a choice, not an accident.

Application 1: Lead-wire error of a cold room Pt100



Step 1: Resistance and sensitivity at 4 °C

Click to reveal the resistance and the slope
  1. Resistance. Put into the quadratic.

    The sensor has a resistance of 101.562 Ω at 4 °C. ✅

  2. Sensitivity.

    Near 4 °C, each degree is worth 0.3904 Ω. ✅

Step 2: The two-wire error

Click to reveal the two-wire error
  1. Resistance of one lead.

    Each wire adds 1.05 Ω. ✅

  2. Error in ohms. Both leads are in series with the sensor.

    The instrument sees . ✅

  3. Error in degrees.

    The instrument indicates about 9.4 °C when the air is at 4 °C. ✅

  4. What the controller does with it. A controller that holds its indication at 4 °C will hold the real air at about . The room freezes while the display shows the setpoint. ✅

  5. Why a fixed offset is not enough. If the cable route is 20 °C warmer in the afternoon than when the offset was set, the copper gains (with the typical copper coefficient of 0.00393 per °C). That is a further of error that changes with the weather. ✅

Step 3: What three wires remove, and what they assume

Click to reveal the three-wire result
  1. With equal leads. The instrument measures . With the bracket is zero.

    The whole 5.38 °C is removed, and a change of cable temperature is removed with it, because both leads change together. ✅

  2. The assumption. The method assumes that the two leads that carry current have equal resistance. It does not measure both. It measures one and trusts that the other is the same. ✅

  3. With leads that differ by 0.10 Ω. A slightly corroded terminal or one extra joint is enough to cause this.

    The error is 0.26 °C. Its sign depends on which lead is the larger one. ✅

  4. Compare with the sensor. The class B tolerance at 4 °C is . A mismatch of only 0.10 Ω adds an error almost as large as the tolerance of the sensor itself. ✅

Step 4: Check the answer a second way

Click to reveal the check
  1. Exact conversion in place of the slope. Step 2 divided by the slope, which treats the curve as straight over 5 °C. Convert with the full quadratic instead.

    The indication is 9.38 °C, an error of . It agrees with the slope method. ✅

  2. Self-heating at 1 mA. , and with the typical 5 mW per °C the rise is 0.02 °C. It is about 260 times smaller than the two-wire error and can be ignored here. ✅

  3. The script. The Python script below prints 101.562 Ω, 0.3904 Ω per °C, an error of +5.38 °C for two wires and +0.256 °C for three wires with a 0.10 Ω mismatch. ✅

Check it at commissioning. Test the cable and the instrument apart from the sensor. At the probe head, disconnect the Pt100 and connect a precision 100.00 Ω resistor (0.01 percent) in its place, wired the same way. The instrument must show 0.00 °C within its own limit plus 0.03 °C for the resistor (0.01 Ω at 0.391 Ω per °C).

  • A reading near +5.4 °C means the input is still set to two-wire, or a core is missing.
  • A reading a few tenths of a degree off on a three-wire input means unequal leads or a poor terminal: clean, tighten and test again.
  • A reading that is low and moves when the head is touched means water in the head. Leakage of 100 kΩ across the sensor takes away 0.10 Ω, about a quarter of a degree, so use a sealed head and cable gland in a cold room.

Then refit the sensor and check the whole chain at the ice point, as described under “Instrument it”.

Application 2: From a measured resistance to a temperature with its uncertainty



Step 1: Solve the quadratic

Click to reveal the conversion
  1. The bracket.

    The value is negative because the resistance is above . ✅

  2. Under the square root.

    The square root is . ✅

  3. Temperature.

    The sensor is at 4.99 °C. ✅

Step 2: The uncertainty

Each limit below is a maker’s limit with no other information, so it is treated as a rectangular distribution: the standard uncertainty is the limit divided by .

Click to reveal the uncertainty
  1. Sensor tolerance at 4.99 °C.

    The sensor contributes 0.188 °C. ✅

  2. Readout, converted to degrees. The sensitivity at 4.99 °C is per °C. It is the sensitivity coefficient that turns ohms into degrees.

    The readout contributes 0.074 °C. ✅

  3. Combined standard uncertainty. The two sources are independent, so they add by root sum of squares.

    The combined standard uncertainty is 0.202 °C. ✅

  4. Expanded uncertainty.

    The result is written as (). ✅

Step 3: Check the answer a second way

Click to reveal the check
  1. Substitute back. . The temperature returns the measured resistance. ✅

  2. Compare with the straight line. . The linear result is 0.07 °C high, as the theory table predicts near this temperature, so the two methods agree to within the known error of the line. ✅

  3. Which term dominates. The sensor holds percent of the variance. A readout ten times better would lower only from 0.40 °C to 0.38 °C. ✅

Verify It in Python



The script holds the IEC 60751 equation and its exact inverse. It reproduces both applications, the self-heating figures and the table of linear errors, and it plots the linear error against temperature and the lead-wire error against cable length.

pt100_cold_room.py
"""Pt100 in a cold room: resistance, lead-wire error, self-heating, uncertainty."""
import numpy as np
import matplotlib.pyplot as plt
# IEC 60751 coefficients for standard platinum (valid from 0 to 850 degC)
A = 3.9083e-3 # per degC
B = -5.775e-7 # per degC squared
ALPHA = 0.00385 # per degC, mean coefficient from 0 to 100 degC
def resistance(t, r0=100.0):
"""Resistance in ohm at t degC (t at or above 0 degC)."""
return r0 * (1.0 + A * t + B * t**2)
def temperature(r, r0=100.0):
"""Exact inverse of the quadratic, for r at or above r0."""
return (-A + np.sqrt(A**2 - 4.0 * B * (1.0 - r / r0))) / (2.0 * B)
def temperature_linear(r, r0=100.0):
"""The short approximation t = (R - R0) / (R0 * alpha)."""
return (r - r0) / (r0 * ALPHA)
def sensitivity(t, r0=100.0):
"""Slope dR/dt in ohm per degC."""
return r0 * (A + 2.0 * B * t)
# ---------- Application 1: instrument B at 4 degC ----------
T_ROOM = 4.0
R_LEAD = 30.0 * 0.035 # ohm, one lead of 30 m
r4 = resistance(T_ROOM)
s4 = sensitivity(T_ROOM)
print("Application 1: Pt100 at 4 degC, 30 m leads")
print(f" resistance at 4 degC: {r4:.3f} ohm")
print(f" sensitivity at 4 degC: {s4:.4f} ohm per degC")
print(f" one lead: {R_LEAD:.2f} ohm, two leads: {2 * R_LEAD:.2f} ohm")
r_two = r4 + 2.0 * R_LEAD
print(f" two-wire: instrument sees {r_two:.3f} ohm, "
f"indicates {temperature(r_two):.2f} degC, "
f"error {temperature(r_two) - T_ROOM:+.2f} degC")
print(f" two-wire error from the slope: {2 * R_LEAD / s4:.2f} degC")
d_cu = 2.0 * R_LEAD * 0.00393 * 20.0
print(f" leads 20 degC warmer: {d_cu:.3f} ohm more, {d_cu / s4:.2f} degC more")
MISMATCH = 0.10 # ohm, difference between two leads
r_three = r4 + MISMATCH
print(f" three-wire, leads differ by {MISMATCH:.2f} ohm: "
f"error {temperature(r_three) - T_ROOM:+.3f} degC")
print(" four-wire: error 0.00 degC from the leads")
r4k = resistance(T_ROOM, 1000.0)
print(f" Pt1000 two-wire: {r4k:.2f} ohm, slope "
f"{sensitivity(T_ROOM, 1000.0):.3f} ohm per degC, error "
f"{temperature(r4k + 2 * R_LEAD, 1000.0) - T_ROOM:+.3f} degC")
# ---------- Self-heating ----------
DISSIPATION = 5.0 # mW per degC, typical probe in still air
print("Self-heating (dissipation constant 5 mW per degC, typical)")
for name, r_s, i_ma in (("Pt100", r4, 1.0), ("Pt100", r4, 5.0),
("Pt1000", r4k, 1.0), ("Pt1000", r4k, 0.1)):
p_mw = (i_ma * 1e-3) ** 2 * r_s * 1e3
print(f" {name:>6} at {i_ma:.1f} mA: {p_mw:.4f} mW, "
f"rise {p_mw / DISSIPATION:.4f} degC")
# ---------- Application 2: 101.95 ohm to temperature ----------
R_MEAS = 101.95
t_meas = temperature(R_MEAS)
print("Application 2: measured 101.95 ohm (four-wire)")
print(f" quadratic: {t_meas:.3f} degC, linear: "
f"{temperature_linear(R_MEAS):.3f} degC")
print(f" check: resistance at {t_meas:.3f} degC is "
f"{resistance(t_meas):.3f} ohm")
tol = 0.30 + 0.005 * abs(t_meas)
u_sensor = tol / np.sqrt(3.0)
s_meas = sensitivity(t_meas)
a_read = 0.05 / s_meas
u_read = a_read / np.sqrt(3.0)
u_c = np.hypot(u_sensor, u_read)
print(f" class B tolerance: {tol:.3f} degC, u = {u_sensor:.3f} degC")
print(f" readout 0.05 ohm = {a_read:.3f} degC, u = {u_read:.3f} degC")
print(f" combined u_c = {u_c:.3f} degC, expanded U (k = 2) = {2 * u_c:.2f} degC")
print(f" sensor share of the variance: {100 * u_sensor**2 / u_c**2:.0f} %")
# ---------- Error of the linear approximation ----------
print("Error of the linear approximation")
for t in (4.0, 50.0, 100.0, 200.0, 300.0, 400.0, 600.0):
r = resistance(t)
print(f" {t:5.0f} degC: {r:8.3f} ohm, linear gives "
f"{temperature_linear(r):7.2f} degC, error "
f"{temperature_linear(r) - t:+6.2f} degC")
# ---------- Plot ----------
t = np.linspace(0.0, 600.0, 601)
fig, ax = plt.subplots(2, 1, figsize=(8, 7))
ax[0].plot(t, temperature_linear(resistance(t)) - t)
ax[0].axhline(0.0, color="gray", linewidth=0.8)
ax[0].set_xlabel("true temperature (degC)")
ax[0].set_ylabel("linear approximation error (degC)")
ax[0].set_title("Error of t = (R - 100) / 0.385 for a Pt100")
length = np.linspace(0.0, 50.0, 51)
r_l = length * 0.035
ax[1].plot(length, 2.0 * r_l / s4, label="Pt100, two-wire")
ax[1].plot(length, 2.0 * r_l / sensitivity(T_ROOM, 1000.0),
label="Pt1000, two-wire")
ax[1].plot(length, 0.0 * length, label="four-wire")
ax[1].set_xlabel("lead length each way (m), 0.5 mm2 copper")
ax[1].set_ylabel("lead-wire error at 4 degC (degC)")
ax[1].set_title("Lead-wire error against cable length")
ax[1].legend()
fig.tight_layout()
fig.savefig("pt100_cold_room.png", dpi=120)
print("Saved pt100_cold_room.png")

Expected output

Application 1: Pt100 at 4 degC, 30 m leads
resistance at 4 degC: 101.562 ohm
sensitivity at 4 degC: 0.3904 ohm per degC
one lead: 1.05 ohm, two leads: 2.10 ohm
two-wire: instrument sees 103.662 ohm, indicates 9.38 degC, error +5.38 degC
two-wire error from the slope: 5.38 degC
leads 20 degC warmer: 0.165 ohm more, 0.42 degC more
three-wire, leads differ by 0.10 ohm: error +0.256 degC
four-wire: error 0.00 degC from the leads
Pt1000 two-wire: 1015.62 ohm, slope 3.904 ohm per degC, error +0.538 degC
Self-heating (dissipation constant 5 mW per degC, typical)
Pt100 at 1.0 mA: 0.1016 mW, rise 0.0203 degC
Pt100 at 5.0 mA: 2.5391 mW, rise 0.5078 degC
Pt1000 at 1.0 mA: 1.0156 mW, rise 0.2031 degC
Pt1000 at 0.1 mA: 0.0102 mW, rise 0.0020 degC
Application 2: measured 101.95 ohm (four-wire)
quadratic: 4.993 degC, linear: 5.065 degC
check: resistance at 4.993 degC is 101.950 ohm
class B tolerance: 0.325 degC, u = 0.188 degC
readout 0.05 ohm = 0.128 degC, u = 0.074 degC
combined u_c = 0.202 degC, expanded U (k = 2) = 0.40 degC
sensor share of the variance: 87 %
Error of the linear approximation
4 degC: 101.562 ohm, linear gives 4.06 degC, error +0.06 degC
50 degC: 119.397 ohm, linear gives 50.38 degC, error +0.38 degC
100 degC: 138.505 ohm, linear gives 100.01 degC, error +0.01 degC
200 degC: 175.856 ohm, linear gives 197.03 degC, error -2.97 degC
300 degC: 212.051 ohm, linear gives 291.04 degC, error -8.96 degC
400 degC: 247.092 ohm, linear gives 382.06 degC, error -17.94 degC
600 degC: 313.708 ohm, linear gives 555.09 degC, error -44.91 degC
Saved pt100_cold_room.png

The lower plot is a straight line through zero for each sensor: the lead-wire error of a two-wire connection grows in proportion to the cable length, and the Pt1000 line has one tenth of the slope. At 100 °C the linear error is 0.01 °C and not exactly zero, because the standard’s rounded value is very slightly different from the slope the quadratic gives.

Common Mistakes



  • Using two wires on a Pt100 over a long cable because “it is only a resistor”. The leads are resistors too. Calculate divided by 0.39 Ω per °C before choosing the cable.
  • Believing that three wires remove the lead error under all conditions. They remove it only when the two current-carrying leads are equal. Mixed cable sizes, an added joint or one corroded terminal bring a part of the error back.
  • Using at 200 °C or above. The straight line is 3 °C low at 200 °C and 18 °C low at 400 °C. Use the quadratic.
  • Setting a Pt1000 input for a Pt100 sensor, or the reverse. The indication is then far outside any real temperature, which at least makes the mistake visible. Check the sensor type in the instrument before you check anything else.
  • Raising the measuring current to get a larger signal. Self-heating grows with the square of the current, and in still air a few milliamperes can add half a degree.
  • Reading the tolerance class as the accuracy of the whole measurement. The class covers the new sensor only. The leads, the readout, the placement and drift are added to it.

Summary



  • A platinum resistance thermometer turns temperature into resistance. A Pt100 is 100 Ω at 0 °C and gains about 0.39 Ω per °C. A Pt1000 is ten times both.
  • IEC 60751 gives at and above 0 °C. Invert the quadratic for exact work. The linear form is good to about 0.4 °C between 0 and 100 °C and fails above that.
  • A two-wire connection adds both lead resistances: 2.10 Ω and 5.38 °C for 30 m of 0.5 mm² copper on a Pt100.
  • A three-wire connection leaves only the difference between two leads, and assumes they are equal. A four-wire connection leaves nothing and assumes nothing.
  • Self-heating is divided by the dissipation constant. Keep the current at 1 mA or less for a Pt100 and lower for a Pt1000.
  • The class B tolerance dominates the uncertainty of a good installation: about ±0.4 °C () near 5 °C.

Exercises



1. Find the resistance of a Pt100 at 25 °C and its sensitivity at that temperature. Use per °C and per °C².

Answer

. The sensitivity is per °C.

2. A two-wire Pt100 at 4 °C is connected by 12 m of 0.5 mm² copper each way, at per metre. The sensitivity at 4 °C is per °C. Find the error in ohms and in °C.

Answer

Each lead is , so the error is . In degrees it is . Even a short cable gives an error several times the class B tolerance.

3. A four-wire instrument indicates for a Pt100. Find the temperature by the quadratic and by the linear approximation, and the error of the linear result.

Answer

Quadratic: , the square root is , and . Linear: . The linear result is 0.28 °C high.

4. In a three-wire Pt100 connection at 4 °C, one of the two current-carrying leads has a corroded terminal that adds . The leads are otherwise equal. Find the error in °C. Does the length of the cable change the answer?

Answer

The three-wire method leaves the difference between the two leads: , high or low according to which lead has the bad terminal. The cable length does not matter, because the equal part of the leads cancels and only the difference remains.

5. A Pt1000 at 4 °C () is measured with 0.5 mA. The probe has a dissipation constant of 5 mW per °C in still air. Find the power and the self-heating error. What current would keep the error below 0.01 °C?

Answer

, so the rise is . For 0.01 °C the power must be below 0.05 mW, so or less.

6. A class A Pt100 (tolerance ) measures 4 °C through a three-wire connection. The readout is accurate to , and the two current-carrying leads may differ by up to . Treat all three limits as rectangular. The sensitivity is per °C. Find the expanded uncertainty () and name the largest term.

Answer

Sensor: , . Readout: , . Lead mismatch: , . Combined: , so . The sensor is the largest term, but the lead mismatch is almost as large: with a class A sensor, the wiring begins to matter as much as the sensor.

References



  • IEC 60751:2022, Industrial platinum resistance thermometers and platinum temperature sensors, International Electrotechnical Commission.
  • J. P. Bentley, Principles of Measurement Systems, 4th edition, Pearson, 2005.
  • R. S. Figliola and D. E. Beasley, Theory and Design for Mechanical Measurements, 6th edition, Wiley, 2015.
  • JCGM 100:2008, Evaluation of measurement data: Guide to the expression of uncertainty in measurement, Joint Committee for Guides in Metrology.


© 2021-2026 SiliconWit®. All rights reserved.
Cold room (air near 4 °C) Evaporator (cold air) Pt100 probe door warm air 30 m copper cable 1.05 Ω in each wire Controller reads ohms
Instrument cable Probe source I RL1 meter V RL2 Rt measured resistance = Rt + RL1 + RL2
Instrument cable Probe 1 I RL1 2 sense RL2 3 I RL3 Rt V12 = I (RL1 + Rt) V23 = I RL3
Instrument cable Probe I out RL1 V + RL2 V - RL3 I ret RL4 Rt V / I = Rt (no lead term, leads may differ)
Watch it build: the Pt100 curve and the straight line
0200400600 °C 100300Ω Pt100: R(t)bends a little down 0.391 Ω per °C slope = sensitivity 0.39 Ω = 1 °Canywhere in the circuit the 385 linethrough 0 and 100 °C −45 °C line reads low above 100600 °C reads 555 °C 4 °C: +0.06 °C200 °C: −2.97 °C
  1. The Pt100 curve: 100 Ω at 0 °C, bending slightly down as the temperature rises.
  2. Its slope is the sensitivity: 0.391 Ω per °C at 0 °C.
  3. So 0.39 Ω of extra resistance anywhere in the circuit reads as one whole degree.
  4. The shortcut: a straight line through 0 °C and 100 °C, 0.385 Ω per °C.
  5. Above 100 °C the line reads low: at 600 °C it gives 555 °C, 45 °C low.
  6. At 4 °C the line is 0.06 °C high, which is small; at 200 °C it is 3 °C low.
Predict first

A Pt100 sits in air at 4 °C, where its resistance is 101.56 Ω. It is joined to the instrument by two copper wires of 1.05 Ω each, and the instrument cannot tell the wires from the sensor. What temperature does it show?

See it: what the leads add

Resistance of one lead
Sensor, Rt
Instrument sees
Indicated temperature
Error
Class B tolerance

Solid lines carry the measuring current. Dashed lines only sense the voltage and carry almost no current, so their resistance does not matter. The indicated temperature comes from the exact inverse of the Callendar-Van Dusen equation, as in the lesson. Below 0 °C the standard's extra term is included. The lead mismatch is the difference between leads 1 and 3 of the three-wire connection: a corroded terminal or one extra joint. The tolerance is that of a new class B sensor at the room temperature. The copper is taken at 20 °C: 0.0175 Ω mm² per metre.

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. A Pt100 at 4 °C has a three-wire connection over 30 m. Each lead has 1.05 Ω. A corroded terminal then adds 0.10 Ω to lead 1 only. The sensitivity is 0.3904 Ω per °C. What is the error?

2. A two-wire Pt100 on 30 m of cable reads 5.38 °C too warm, because the leads add 2.10 Ω. The sensor is changed to a Pt1000 on the same cable. What is the error now?

3. To cure the same two-wire Pt100 (30 m of 0.5 mm² copper, error 5.38 °C), someone proposes a thicker cable of 1.5 mm². What is the error with the thick cable?

sensor101.56 Ωlead1.05 Ωlead1.05 Ω 103.66 Ω = 9.4 °C The air is 4 °C.
See it: a door opens, and the probe is slow

Highest indication
Part of the change hidden
95 percent of a change after

The grey line is the air, 4 °C, lifted to 10 °C while the door is open. The dark line is what the probe indicates. The lesson's case is τ = 40 s and a door open for 30 s.

Found this useful?