Resistance of platinum at or above 0 °C (IEC 60751)
Here
A cold room controller shows 4 °C all night, and in the morning the lettuce is frozen and the vaccines must be thrown away. The sensor was good and the controller was good. The fault was 30 metres of cable between them, which added 2 Ω to a measurement where 0.39 Ω means one degree. This lesson shows how a platinum resistance thermometer turns temperature into resistance, how much error the wiring adds, and how a third or fourth wire removes it. You will calculate each error in ohms and in degrees, and you will state the uncertainty of a converted reading. #Instrumentation #Pt100 #TemperatureMeasurement
By the end of this lesson, you will be able to:
A cold room for vegetables, milk or vaccines is held near 4 °C. Many products in it are damaged below 0 °C and spoil faster above 8 °C, so the permitted window is only a few degrees wide. The air temperature is measured by a Pt100 probe in the room. The controller is in a plant room or an office, and in this example the cable between them is 30 m long.
A Pt100 changes by about 0.39 Ω for each degree. The copper cable has a resistance too, about 1.05 Ω in each wire. An instrument that cannot tell the cable from the sensor adds the cable to the reading, like a scale that weighs a parcel together with its heavy box. The room appears several degrees warmer than it is, the controller cools it until the false reading says 4 °C, and the real air is below zero.
The display does not show the error: the reading is steady, has two decimal places, and is wrong. The only defence is to know how the sensor and its connection work, and to calculate the error before the cable is pulled.
In a metal, electric current is carried by electrons that move through a lattice of atoms. When the metal is warmer, the atoms vibrate more and the electrons collide with them more often. The resistance rises. For a pure metal the rise is close to a straight line over a wide range of temperature, so a measurement of resistance is a measurement of temperature.
Platinum is the standard choice for three reasons. It can be made very pure, so one sensor behaves like the next. It does not corrode or oxidise in normal use, so it stays the same for years. And its resistance curve is smooth and well known. A sensor made this way is called a resistance temperature detector (RTD) or a platinum resistance thermometer.
The name of the sensor states its resistance at 0 °C. A Pt100 has
The standard IEC 60751 gives the resistance of industrial platinum as a function of temperature. For temperatures from 0 °C to 850 °C it is a quadratic.
Resistance of platinum at or above 0 °C (IEC 60751)
Here
The term with
To find temperature from a measured resistance, solve the quadratic for
Temperature from resistance, at or above 0 °C
The sensitivity is the slope of the curve: how many ohms the sensor gains for one degree.
For a Pt100 at 0 °C this is
Remember the size of it. On a Pt100, an extra 0.39 Ω anywhere in the circuit is an error of one whole degree.
Many instruments and many quick calculations use a straight line in place of the quadratic. The line is drawn through the two points 0 °C and 100 °C. Its slope is described by the mean coefficient
The line meets the curve at 0 °C and 100 °C. Between those points it reads a little high. Above 100 °C it reads low, and the error grows quickly.
| True temperature | Resistance (Pt100) | Linear result | Error of the linear result |
|---|---|---|---|
| 4 °C | 101.562 Ω | 4.06 °C | +0.06 °C |
| 50 °C | 119.397 Ω | 50.38 °C | +0.38 °C |
| 100 °C | 138.505 Ω | 100.01 °C | +0.01 °C |
| 200 °C | 175.856 Ω | 197.03 °C | −2.97 °C |
| 400 °C | 247.092 Ω | 382.06 °C | −17.94 °C |
| 600 °C | 313.708 Ω | 555.09 °C | −44.91 °C |
For a cold room at 4 °C the linear result is wrong by 0.06 °C, which is small against the tolerance of the sensor. For an oven at 200 °C it is wrong by 3 °C, which is not acceptable. The honest rule is: the straight line is a tool for 0 to 100 °C, and the quadratic is the method everywhere else.
No real sensor sits exactly on the standard curve. IEC 60751 sorts sensors into classes by how far they may be from it. The tolerance is a limit, in °C, that grows with the distance from 0 °C. In these formulas
| Class | Tolerance (IEC 60751) | At 4 °C | At 100 °C |
|---|---|---|---|
| AA | ±0.11 °C | ±0.27 °C | |
| A | ±0.16 °C | ±0.35 °C | |
| B | ±0.32 °C | ±0.80 °C | |
| C | ±0.64 °C | ±1.60 °C |
Class B is the common industrial grade. Each class applies only inside a stated temperature range, which depends on how the sensor is built, so check the datasheet. The tolerance describes a new sensor. It does not include the wiring, the instrument, or drift after years of use.
To measure a resistance, the instrument passes a small known current
Let
Many instruments accept a fixed offset to cancel the leads. This helps but does not cure: copper itself changes by about 0.39 percent per °C (a typical value), so the lead resistance moves with the weather and with the heat in the cable route, and the offset is correct on one day only.
The three-wire connection has one wire to one end of the sensor (lead 1) and two wires to the other end (leads 2 and 3). The current flows out through lead 1 and returns through lead 3. Lead 2 carries almost no current, so there is no voltage drop along it, and it reports the voltage at the far end of the sensor.
The instrument takes two voltages. Between terminals 1 and 2 it sees the sensor and lead 1. Between terminals 2 and 3 it sees lead 3 alone. It subtracts the second from the first:
If the two current-carrying leads have the same resistance, the bracket is zero and the leads vanish from the result. That is the one assumption of the three-wire method: equal lead resistances. It is a good assumption when the three wires are cores of one cable, with the same length, the same cross-section and the same temperature. It fails when one terminal is loose or corroded, or when a repair has added a different piece of wire to one core. The error left is the difference between the two leads, not their sum.
The four-wire connection uses one pair of wires for the current and a separate pair for the voltage. The voltage pair is connected directly at the sensor and carries almost no current, so no lead resistance appears in the voltage at all.
The leads may be long, thin and unequal, and the result is still
The measuring current heats the sensor, because any current in a resistance releases power:
The sensor then sits slightly above the temperature of the air it is meant to measure. The rise depends on how easily the heat leaves the probe, which is described by a dissipation constant
The dissipation constant is not in the standard. It depends on the probe and on the medium: it is low in still air, higher in moving air and much higher in water. A typical figure for a small sheathed probe in still air is about 5 mW per °C, and this lesson uses that value as typical. The maker’s datasheet gives the real one.
For a Pt100 at 1 mA near 4 °C,
A Pt1000 has ten times the resistance and ten times the sensitivity, about 3.9 Ω per °C. The cable is the same, so the same lead resistance now causes one tenth of the temperature error. This is the main advantage of the Pt1000: a two-wire connection becomes usable over moderate distances, which suits building controls and battery-powered devices.
The cost is self-heating. At the same 1 mA, a Pt1000 releases ten times the power of a Pt100, about 1.0 mW, and rises by about 0.2 °C in still air. A Pt1000 is therefore measured at a lower current, typically 0.1 mA, where the rise is 0.002 °C and the voltage signal is still as large as that of a Pt100 at 1 mA.
| Pt100 | Pt1000 | |
|---|---|---|
| Resistance at 4 °C | 101.56 Ω | 1015.6 Ω |
| Sensitivity at 4 °C | 0.390 Ω per °C | 3.90 Ω per °C |
| Error from 2.10 Ω of leads, two-wire | 5.38 °C | 0.54 °C |
| Self-heating at 1 mA (typical, still air) | 0.02 °C | 0.20 °C |
| Usual connection | three-wire or four-wire | two-wire, short to moderate runs |
A correct resistance is still a wrong answer if the probe is in the wrong air. In a cold room, fit the air probe in the return air to the evaporator, or at product height in the body of the room: away from the door, where warm air enters, from the evaporator outlet, where the air is several degrees colder, from walls and from lamps. If the question is the temperature of the product, not of the air, use a second probe in a product simulator: a small sealed bottle of liquid, often glycol, that warms and cools about as slowly as the product does.
A sheathed probe does not follow the air at once, because its sheath and filling must warm or cool first, as a cup of tea takes time to cool in a cold room. For a sudden change of air temperature from
After one time constant the probe has covered 63 percent of the change, and after three it has covered 95 percent. A typical 6 mm sheathed probe has a time constant of some tens of seconds in moving air and a few seconds in moving water. The maker states the response time for defined test conditions. With
Resistance. Put
The sensor has a resistance of 101.562 Ω at 4 °C. ✅
Sensitivity.
Near 4 °C, each degree is worth 0.3904 Ω. ✅
Resistance of one lead.
Each wire adds 1.05 Ω. ✅
Error in ohms. Both leads are in series with the sensor.
The instrument sees
Error in degrees.
The instrument indicates about 9.4 °C when the air is at 4 °C. ✅
What the controller does with it. A controller that holds its indication at 4 °C will hold the real air at about
Why a fixed offset is not enough. If the cable route is 20 °C warmer in the afternoon than when the offset was set, the copper gains
With equal leads. The instrument measures
The whole 5.38 °C is removed, and a change of cable temperature is removed with it, because both leads change together. ✅
The assumption. The method assumes that the two leads that carry current have equal resistance. It does not measure both. It measures one and trusts that the other is the same. ✅
With leads that differ by 0.10 Ω. A slightly corroded terminal or one extra joint is enough to cause this.
The error is 0.26 °C. Its sign depends on which lead is the larger one. ✅
Compare with the sensor. The class B tolerance at 4 °C is
Exact conversion in place of the slope. Step 2 divided by the slope, which treats the curve as straight over 5 °C. Convert
The indication is 9.38 °C, an error of
Self-heating at 1 mA.
The script. The Python script below prints 101.562 Ω, 0.3904 Ω per °C, an error of +5.38 °C for two wires and +0.256 °C for three wires with a 0.10 Ω mismatch. ✅
Check it at commissioning. Test the cable and the instrument apart from the sensor. At the probe head, disconnect the Pt100 and connect a precision 100.00 Ω resistor (0.01 percent) in its place, wired the same way. The instrument must show 0.00 °C within its own limit plus 0.03 °C for the resistor (0.01 Ω at 0.391 Ω per °C).
Then refit the sensor and check the whole chain at the ice point, as described under “Instrument it”.
The bracket.
The value is negative because the resistance is above
Under the square root.
The square root is
Temperature.
The sensor is at 4.99 °C. ✅
Each limit below is a maker’s limit with no other information, so it is treated as a rectangular distribution: the standard uncertainty is the limit divided by
Sensor tolerance at 4.99 °C.
The sensor contributes 0.188 °C. ✅
Readout, converted to degrees. The sensitivity at 4.99 °C is
The readout contributes 0.074 °C. ✅
Combined standard uncertainty. The two sources are independent, so they add by root sum of squares.
The combined standard uncertainty is 0.202 °C. ✅
Expanded uncertainty.
The result is written as
Substitute back.
Compare with the straight line.
Which term dominates. The sensor holds
The script holds the IEC 60751 equation and its exact inverse. It reproduces both applications, the self-heating figures and the table of linear errors, and it plots the linear error against temperature and the lead-wire error against cable length.
"""Pt100 in a cold room: resistance, lead-wire error, self-heating, uncertainty."""import numpy as npimport matplotlib.pyplot as plt
# IEC 60751 coefficients for standard platinum (valid from 0 to 850 degC)A = 3.9083e-3 # per degCB = -5.775e-7 # per degC squaredALPHA = 0.00385 # per degC, mean coefficient from 0 to 100 degC
def resistance(t, r0=100.0): """Resistance in ohm at t degC (t at or above 0 degC).""" return r0 * (1.0 + A * t + B * t**2)
def temperature(r, r0=100.0): """Exact inverse of the quadratic, for r at or above r0.""" return (-A + np.sqrt(A**2 - 4.0 * B * (1.0 - r / r0))) / (2.0 * B)
def temperature_linear(r, r0=100.0): """The short approximation t = (R - R0) / (R0 * alpha).""" return (r - r0) / (r0 * ALPHA)
def sensitivity(t, r0=100.0): """Slope dR/dt in ohm per degC.""" return r0 * (A + 2.0 * B * t)
# ---------- Application 1: instrument B at 4 degC ----------T_ROOM = 4.0R_LEAD = 30.0 * 0.035 # ohm, one lead of 30 mr4 = resistance(T_ROOM)s4 = sensitivity(T_ROOM)print("Application 1: Pt100 at 4 degC, 30 m leads")print(f" resistance at 4 degC: {r4:.3f} ohm")print(f" sensitivity at 4 degC: {s4:.4f} ohm per degC")print(f" one lead: {R_LEAD:.2f} ohm, two leads: {2 * R_LEAD:.2f} ohm")r_two = r4 + 2.0 * R_LEADprint(f" two-wire: instrument sees {r_two:.3f} ohm, " f"indicates {temperature(r_two):.2f} degC, " f"error {temperature(r_two) - T_ROOM:+.2f} degC")print(f" two-wire error from the slope: {2 * R_LEAD / s4:.2f} degC")d_cu = 2.0 * R_LEAD * 0.00393 * 20.0print(f" leads 20 degC warmer: {d_cu:.3f} ohm more, {d_cu / s4:.2f} degC more")MISMATCH = 0.10 # ohm, difference between two leadsr_three = r4 + MISMATCHprint(f" three-wire, leads differ by {MISMATCH:.2f} ohm: " f"error {temperature(r_three) - T_ROOM:+.3f} degC")print(" four-wire: error 0.00 degC from the leads")r4k = resistance(T_ROOM, 1000.0)print(f" Pt1000 two-wire: {r4k:.2f} ohm, slope " f"{sensitivity(T_ROOM, 1000.0):.3f} ohm per degC, error " f"{temperature(r4k + 2 * R_LEAD, 1000.0) - T_ROOM:+.3f} degC")
# ---------- Self-heating ----------DISSIPATION = 5.0 # mW per degC, typical probe in still airprint("Self-heating (dissipation constant 5 mW per degC, typical)")for name, r_s, i_ma in (("Pt100", r4, 1.0), ("Pt100", r4, 5.0), ("Pt1000", r4k, 1.0), ("Pt1000", r4k, 0.1)): p_mw = (i_ma * 1e-3) ** 2 * r_s * 1e3 print(f" {name:>6} at {i_ma:.1f} mA: {p_mw:.4f} mW, " f"rise {p_mw / DISSIPATION:.4f} degC")
# ---------- Application 2: 101.95 ohm to temperature ----------R_MEAS = 101.95t_meas = temperature(R_MEAS)print("Application 2: measured 101.95 ohm (four-wire)")print(f" quadratic: {t_meas:.3f} degC, linear: " f"{temperature_linear(R_MEAS):.3f} degC")print(f" check: resistance at {t_meas:.3f} degC is " f"{resistance(t_meas):.3f} ohm")tol = 0.30 + 0.005 * abs(t_meas)u_sensor = tol / np.sqrt(3.0)s_meas = sensitivity(t_meas)a_read = 0.05 / s_measu_read = a_read / np.sqrt(3.0)u_c = np.hypot(u_sensor, u_read)print(f" class B tolerance: {tol:.3f} degC, u = {u_sensor:.3f} degC")print(f" readout 0.05 ohm = {a_read:.3f} degC, u = {u_read:.3f} degC")print(f" combined u_c = {u_c:.3f} degC, expanded U (k = 2) = {2 * u_c:.2f} degC")print(f" sensor share of the variance: {100 * u_sensor**2 / u_c**2:.0f} %")
# ---------- Error of the linear approximation ----------print("Error of the linear approximation")for t in (4.0, 50.0, 100.0, 200.0, 300.0, 400.0, 600.0): r = resistance(t) print(f" {t:5.0f} degC: {r:8.3f} ohm, linear gives " f"{temperature_linear(r):7.2f} degC, error " f"{temperature_linear(r) - t:+6.2f} degC")
# ---------- Plot ----------t = np.linspace(0.0, 600.0, 601)fig, ax = plt.subplots(2, 1, figsize=(8, 7))ax[0].plot(t, temperature_linear(resistance(t)) - t)ax[0].axhline(0.0, color="gray", linewidth=0.8)ax[0].set_xlabel("true temperature (degC)")ax[0].set_ylabel("linear approximation error (degC)")ax[0].set_title("Error of t = (R - 100) / 0.385 for a Pt100")length = np.linspace(0.0, 50.0, 51)r_l = length * 0.035ax[1].plot(length, 2.0 * r_l / s4, label="Pt100, two-wire")ax[1].plot(length, 2.0 * r_l / sensitivity(T_ROOM, 1000.0), label="Pt1000, two-wire")ax[1].plot(length, 0.0 * length, label="four-wire")ax[1].set_xlabel("lead length each way (m), 0.5 mm2 copper")ax[1].set_ylabel("lead-wire error at 4 degC (degC)")ax[1].set_title("Lead-wire error against cable length")ax[1].legend()fig.tight_layout()fig.savefig("pt100_cold_room.png", dpi=120)print("Saved pt100_cold_room.png")Expected output
Application 1: Pt100 at 4 degC, 30 m leads resistance at 4 degC: 101.562 ohm sensitivity at 4 degC: 0.3904 ohm per degC one lead: 1.05 ohm, two leads: 2.10 ohm two-wire: instrument sees 103.662 ohm, indicates 9.38 degC, error +5.38 degC two-wire error from the slope: 5.38 degC leads 20 degC warmer: 0.165 ohm more, 0.42 degC more three-wire, leads differ by 0.10 ohm: error +0.256 degC four-wire: error 0.00 degC from the leads Pt1000 two-wire: 1015.62 ohm, slope 3.904 ohm per degC, error +0.538 degCSelf-heating (dissipation constant 5 mW per degC, typical) Pt100 at 1.0 mA: 0.1016 mW, rise 0.0203 degC Pt100 at 5.0 mA: 2.5391 mW, rise 0.5078 degC Pt1000 at 1.0 mA: 1.0156 mW, rise 0.2031 degC Pt1000 at 0.1 mA: 0.0102 mW, rise 0.0020 degCApplication 2: measured 101.95 ohm (four-wire) quadratic: 4.993 degC, linear: 5.065 degC check: resistance at 4.993 degC is 101.950 ohm class B tolerance: 0.325 degC, u = 0.188 degC readout 0.05 ohm = 0.128 degC, u = 0.074 degC combined u_c = 0.202 degC, expanded U (k = 2) = 0.40 degC sensor share of the variance: 87 %Error of the linear approximation 4 degC: 101.562 ohm, linear gives 4.06 degC, error +0.06 degC 50 degC: 119.397 ohm, linear gives 50.38 degC, error +0.38 degC 100 degC: 138.505 ohm, linear gives 100.01 degC, error +0.01 degC 200 degC: 175.856 ohm, linear gives 197.03 degC, error -2.97 degC 300 degC: 212.051 ohm, linear gives 291.04 degC, error -8.96 degC 400 degC: 247.092 ohm, linear gives 382.06 degC, error -17.94 degC 600 degC: 313.708 ohm, linear gives 555.09 degC, error -44.91 degCSaved pt100_cold_room.pngThe lower plot is a straight line through zero for each sensor: the lead-wire error of a two-wire connection grows in proportion to the cable length, and the Pt1000 line has one tenth of the slope. At 100 °C the linear error is 0.01 °C and not exactly zero, because the standard’s rounded value
1. Find the resistance of a Pt100 at 25 °C and its sensitivity at that temperature. Use
2. A two-wire Pt100 at 4 °C is connected by 12 m of 0.5 mm² copper each way, at
Each lead is
3. A four-wire instrument indicates
Quadratic:
4. In a three-wire Pt100 connection at 4 °C, one of the two current-carrying leads has a corroded terminal that adds
The three-wire method leaves the difference between the two leads:
5. A Pt1000 at 4 °C (
6. A class A Pt100 (tolerance
Sensor:
A Pt100 sits in air at 4 °C, where its resistance is 101.56 Ω. It is joined to the instrument by two copper wires of 1.05 Ω each, and the instrument cannot tell the wires from the sensor. What temperature does it show?
Solid lines carry the measuring current. Dashed lines only sense the voltage and carry almost no current, so their resistance does not matter. The indicated temperature comes from the exact inverse of the Callendar-Van Dusen equation, as in the lesson. Below 0 °C the standard's extra term is included. The lead mismatch is the difference between leads 1 and 3 of the three-wire connection: a corroded terminal or one extra joint. The tolerance is that of a new class B sensor at the room temperature. The copper is taken at 20 °C: 0.0175 Ω mm² per metre.
Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.
1. A Pt100 at 4 °C has a three-wire connection over 30 m. Each lead has 1.05 Ω. A corroded terminal then adds 0.10 Ω to lead 1 only. The sensitivity is 0.3904 Ω per °C. What is the error?
2. A two-wire Pt100 on 30 m of cable reads 5.38 °C too warm, because the leads add 2.10 Ω. The sensor is changed to a Pt1000 on the same cable. What is the error now?
3. To cure the same two-wire Pt100 (30 m of 0.5 mm² copper, error 5.38 °C), someone proposes a thicker cable of 1.5 mm². What is the error with the thick cable?
The grey line is the air, 4 °C, lifted to 10 °C while the door is open. The dark line is what the probe indicates. The lesson's case is τ = 40 s and a door open for 30 s.
No comments yet. Questions, results from your own build, a better way to explain it: all welcome.
Kept on this device only. Nothing is sent anywhere.
Tip: select words in the lesson, or tap a figure or an equation, to put a note right there.
The lesson has changed and these words are no longer in it. Your notes are kept, with the words you chose.