Sizing a System from the Load

Lesson 5 of 10 24 min read
Found this useful?

A workshop owner buys “a 10 kW solar system” because the seller had one in stock. In the first week the inverter trips each time the compressor starts, the battery is empty before sunrise, and at noon the array could give far more than anybody uses. Each part works as its label says. Nobody asked what the workshop runs, for how long, and at what hour. A system is sized from the load, and this lesson shows how to write the load down and how to work back from it to the array, the battery and the inverter. #SolarSizing #LoadAnalysis #BatterySizing

Learning Objectives

By the end of this lesson, you will be able to:

  1. Build a load table with power, hours and energy, and split the daily energy into a day share and a night share
  2. Calculate the array size from the worst month and a stated performance ratio
  3. Calculate the battery size from the night energy, the days of autonomy and the allowed depth of discharge
  4. Choose the inverter size from the peak load and the starting surge
  5. Explain what an array or a battery that is too large costs, and which checks a first sizing still needs

Real-World System Problem: A workshop that must run every day



The site of this course is a workshop and office near the equator, with benches of small tools, a welder and an air compressor. Some loads never stop: a refrigerator, the network equipment, the security lights at night. The grid is unreliable, and a standby generator covers long failures.

The owner wants solar energy to carry an ordinary day, and the battery to carry the evening work and the night. Three sizes answer three questions about the load. The array in kWp: how much energy in a day? The battery in kWh: how much of it is used without sun? The inverter in kW: how much power at one moment? (A house that lives on rainwater is the same: the roof, the tank and the tap.)

A size that is too small fails on the first bad day; one that is too large is paid for and not used. The load table decides both.

Array? kWpBattery? kWhLoadenergyhourspeakHybridinverter? kW
Three sizes, three questions about the load

Fundamental Theory: From the load to three sizes



The load table

A load table has one line for each load or group of loads. Each line gives the power in kW, the hours of use in a day, and the hours of the clock at which the load runs. The daily energy of a line is the power multiplied by the hours:

with in kWh, in kW and in hours. The daily energy of the site, , is the sum of all lines.

Two points decide whether the table is true. The first is the power. A nameplate gives the largest power the machine can take, and many machines take less most of the time: a refrigerator runs its compressor for part of each hour, an air compressor stops when its tank is full. The table needs the mean power over the hours of use, best measured with an energy meter left on the circuit for a week.

The second is the hours, which people underestimate. A light that “is only on in the evening” is often on for six hours.

Day share and night share

The table must also say when each load runs. Energy used while the sun is on the array goes straight through the inverter to the load; energy used at night must first be stored, and storage is the expensive part of the system.

In this course the sun is on the array from 06:30 to 18:30. The energy used in those hours is the day share, ; the energy used from 18:30 to 06:30 is the night share, . Two sites with the same daily energy can need very different batteries: an office that closes at 17:00 needs a small one, a bakery that works from 02:00 a large one.

A load that can be moved into the day is worth moving. A pump that fills a tank, or a compressor that fills a receiver, stores energy more cheaply than a battery.

Peak load and surge

The inverter must supply the largest power of the day, not the mean. The peak load, , is the largest sum of loads running at the same moment: lower than the connected load (the sum of all lines), because not everything runs together, and far above the mean power.

Motors add a second demand. At starting, a motor takes several times its running power for a fraction of a second to a few seconds: the surge. The starting factor depends on the motor and how it is started, and the maker’s data decides. An inverter has a continuous rating and a short overload rating, and the surge must fit inside the second.

The array from the worst month

An array of nameplate power gives in a day. is the insolation on the array plane in kWh/m² a day (the peak sun hours), and the performance ratio, the share of the nameplate energy that reaches the load side of the inverter. Nameplate power is at standard test conditions (STC), which a hot roof never meets; the performance ratio holds that loss with the others.

Array size from the daily energy

is the energy that the array must give in a day (kWh), the peak sun hours of the worst month, and a stated performance ratio. This course uses for sizing.

The worst month is used because the load must be carried in every month; an array sized on the yearly mean is short for half of the year.

The array must give a little more than the load, because the night share passes through the battery, which returns less than it receives. With a round-trip efficiency :

The battery from the night energy

The battery must hold the energy used without sun, and three things make its nameplate larger than that energy. The inverter loses a few percent, so the battery gives more than the load receives. The battery loses energy on the way out; this course takes the losses on charge and on discharge as equal, so the efficiency of one direction is . And a battery is not used from full to empty: the allowed depth of discharge, , is the share of the nameplate energy used in a cycle.

Battery size from the energy without sun

is the nameplate energy (kWh). is the load energy in one period without sun (kWh), the number of such periods the battery must carry, the inverter efficiency. The capacity in Ah is , with the nominal voltage of the battery.

With a grid or a generator behind the site, the period is one night and . With nothing behind it, the designer chooses the days of autonomy, the days with no sun at all that the battery must carry, and the period is a whole day of load.

The inverter from peak and surge

The continuous rating must be above the peak load with a margin, because loads grow and an inverter at its limit runs hot. A margin of 20 to 25 percent is a common choice, not a rule.

The surge check is separate: the largest motor’s power times its starting factor, plus the other loads running at that moment, must be inside the short overload rating. When the site runs from the battery, the same power must come out of the battery, so its current limit is part of the check.

What over-sizing costs

It is tempting to make everything larger “to be safe”. Each margin has its own cost.

An array that is too large gives energy nobody can use. With the load supplied and the battery full, the inverter holds the array back and the extra energy is spilled. Export has some value where it is allowed and paid, none where it is not. A large array may also push more current into the battery and more power into the inverter than they accept.

A battery that is too large is the most expensive mistake, because the battery is the most expensive part for each kWh. Cycled over a small part of its range, it ages by the calendar before it has delivered its energy. It also needs an array large enough to fill it, or it stays partly charged for weeks.

An inverter that is too large costs more and works at a small share of its rating, where it is less efficient.

Load tableInverterBattery:autonomy, DoDArray:worst month, PRdaily energynight energypeak and surge
The order of a first sizing

The checks after the first sizing

The three formulas give a first size. Before anything is bought, check these points:

  • The modules must form strings that stay inside the voltage limits of the inverter with cold cells and with hot cells. See modules, strings and shading.
  • The array must be able to fill the battery on a worst-month day and still carry the day load.
  • The charge current from the array and the discharge current at peak load must be inside the limits of the battery.
  • The ratio of array power to inverter power must be acceptable. See maximum power point tracking and inverters.
  • The battery must be tested on a real day shape, not only on the night energy, because the array stops covering the load before sunset.

Application 1: The load table and the three sizes



Step 1: The load table

Click to reveal the calculation
  1. Energy of each line. Power multiplied by hours, split at 06:30 and 18:30.

    LoadkWHourskWhDayNight
    Always on0.3024.07.23.63.6
    Security lights0.2012.02.40.02.4
    Inside lights0.256.01.50.51.0
    Office equipment0.4014.05.64.01.6
    Bench tools0.6013.58.15.72.4
    Welder3.001.03.03.00.0
    Air compressor2.201.02.22.20.0
    Total6.9530.019.011.0

    ✅

  2. Daily energy. kWh a day, with kWh and kWh. The night share is 37 percent. ✅

  3. Peak load. Between 11:00 and 11:30 the welder and the compressor run together with the always-on loads, the office equipment and the bench tools:

    The connected load is 6.95 kW; the lights are off at that hour, so the peak is lower. ✅

  4. Mean and load factor. The mean power is kW. The load factor, mean divided by peak, is : the inverter must be five times the mean load. ✅

kW6.5welder and compressortogether for 30 minutes4.33.5evening work1.751.30.50.3h06:301218:3024
The load of the site through one day (not to scale)

Step 2: The array

Click to reveal the calculation
  1. For the load only.

    ✅

  2. With the loss in the battery. The night share passes through the battery.

    ✅

  3. Modules. , so 17 modules; two equal strings need an even number: 18 modules, 9.9 kWp, the array of the site. ✅

  4. Margin. The site has percent above the need with the battery loss, and 11.4 percent above the load alone. ✅

Step 3: The battery

Click to reveal the calculation
  1. Efficiency of one direction. . ✅

  2. Energy from the cells for one night.

    ✅

  3. Nameplate energy. The battery is used between 10 and 90 percent, so .

    ✅

  4. Capacity. Ah. The next unit is 300 Ah, 15.36 kWh with 12.29 kWh usable: the battery of the site, with a margin over the night energy of percent. ✅

Step 4: The inverter

Click to reveal the calculation
  1. Continuous rating. kW. The next size is 8 kW, the inverter of the site. ✅

  2. Surge. The worst start is the compressor at 11:00, with the welder and the other loads running. The other loads take kW.

    The assumed overload rating is kW for a few seconds. The start fits, with little to spare. ✅

  3. Battery current. If the battery alone carries the peak, it gives kW, which is A, inside the 150 A limit. The start at 10.9 kW would ask for 219 A, above the continuous limit. At 11:00 the array carries most of the load; on a dark day it would not, and then the short peak rating in the battery data sheet decides. ✅

  4. Ratio of array to inverter. . ✅

Step 5: Check the sizes against the energy of a day

Click to reveal the check
  1. Worst month. The array as built gives kWh. The need is 30.96 kWh. The surplus is 2.4 kWh, the 7.9 percent margin. ✅

  2. Mean day. The array gives kWh for the same need, so 9.9 kWh, 24 percent of what it can give, is not needed: exported if the grid allows it, spilled if not. ✅

  3. The battery in Ah. One night takes Ah from a battery of 300 Ah, which is 77 percent. The allowed window is 80 percent. ✅

  4. The script. The Python script below builds the table from the hours of the clock at 5-minute steps and gives the same totals: 30.0, 19.0 and 11.0 kWh, and a peak of 6.50 kW. ✅

Application 2: The same load with no grid and no generator



Step 1: The battery for two days

Click to reveal the calculation
  1. Energy from the cells. The period without sun is now two whole days of load.

    ✅

  2. Nameplate.

    which is Ah. ✅

  3. Units. , so 6 units: 1,800 Ah and 92.16 kWh. This is 6 times the battery of the site. ✅

  4. Price. currency units, against 460,800 for the site battery. The two days of autonomy cost 2,304,000 currency units more. ✅

6543211Hybrid site: one night, 15.36 kWhOff-grid: two days without sun, 92.16 kWh
One night of storage against two days of autonomy

Step 2: The array that refills it

Click to reveal the calculation
  1. Energy to put back. The battery gave 60 kWh to the load. The array must give kWh to return it, which is 16.30 kWh a day over four days. ✅

  2. Array.

    ✅

  3. Modules. , so 26 modules, 14.3 kWp: 8 more than the site has, and more than the two trackers of the 8 kW inverter are likely to accept. A second charge controller or a different inverter is needed; the data sheets decide. ✅

  4. The inverter. The peak and the surge have not changed, so the inverter rating for the load stays at 8 kW. ✅

Step 3: What the autonomy costs

Click to reveal the calculation
  1. An ordinary day. On a mean day the 14.3 kWp array can give kWh for a need of 31.0 kWh: almost half is spilled on most days of the year. ✅

  2. The battery on an ordinary day. One night takes 11.82 kWh of 92.16 kWh, 13 percent. Five of the six units are there only for the dark days. ✅

  3. The same two days on fuel. Assume the generator runs at 7.5 kW into the load and the battery charger. For 60 kWh it runs hours.

    At 180 currency units a litre this is 4,212 currency units. ✅

  4. Compare. . The extra battery costs as much as the fuel for 547 dark periods of two days. ✅

Verify It in Python



The script builds the load table at 5-minute steps, prints the load of each block of the day, sizes the three parts for both applications, and plots the load through the day.

size_from_load.py
"""Size the array, the battery and the inverter of the site from its load table."""
import math
import numpy as np
import matplotlib.pyplot as plt
DT = 5.0 / 60.0
h = np.arange(0, 24, DT)
night = (h + 1e-9 < 6.5) | (h + 1e-9 >= 18.5)
# name, power (kW), list of (start hour, end hour); a window may pass midnight
LOADS = (
("Always on: refrigerator, network", 0.30, [(0.0, 24.0)]),
("Security lights", 0.20, [(18.5, 6.5)]),
("Inside lights", 0.25, [(16.5, 22.5)]),
("Office equipment", 0.40, [(8.5, 22.5)]),
("Bench tools", 0.60, [(8.0, 13.0), (14.0, 22.5)]),
("Welder", 3.00, [(10.5, 11.5)]),
("Air compressor", 2.20, [(11.0, 12.0)]),
)
def is_on(windows):
"""True at each 5-minute step in which the load runs."""
on = np.zeros(len(h), dtype=bool)
for a, b in windows:
t = h + 1e-9
on |= ((t >= a) & (t < b)) if a < b else ((t >= a) | (t < b))
return on
# ---------- Application 1, part 1: the load table ----------
print("Application 1: the load table")
print(" load kW hours kWh day night")
profile = np.zeros(len(h))
connected = 0.0
for name, kw, windows in LOADS:
on = is_on(windows)
profile += kw * on
connected += kw
print(f" {name:32s} {kw:5.2f} {on.sum() * DT:6.1f} {kw * on.sum() * DT:5.1f} "
f"{kw * (on & ~night).sum() * DT:5.1f} {kw * (on & night).sum() * DT:5.1f}")
E_DAY, E_NIGHT = profile[~night].sum() * DT, profile[night].sum() * DT
E_LOAD, P_PEAK = profile.sum() * DT, profile.max()
print(f" total {E_LOAD:.1f} kWh a day: {E_DAY:.1f} between 06:30 and 18:30, "
f"{E_NIGHT:.1f} between 18:30 and 06:30")
k = profile.argmax()
print(f" connected {connected:.2f} kW, peak {P_PEAK:.2f} kW at {int(h[k])}:{round(60 * (h[k] % 1)):02d}, "
f"mean {E_LOAD / 24:.2f} kW, load factor {E_LOAD / 24 / P_PEAK:.3f}")
edges = [0] + [i for i in range(1, len(h)) if abs(profile[i] - profile[i - 1]) > 1e-9] + [len(h)]
print(" the load through the day:")
for a, b in zip(edges[:-1], edges[1:]):
m0, m1 = round(a * 5), round(b * 5)
print(f" {m0 // 60:02d}:{m0 % 60:02d} to {m1 // 60:02d}:{m1 % 60:02d} {profile[a]:.2f} kW")
# ---------- Application 1, part 2: array, battery, inverter ----------
H_WORST, H_MEAN, PR = 4.5, 5.5, 0.75
P_MOD = 0.55 # kWp of one module at STC
ETA_INV, ETA_RT = 0.97, 0.92
ETA_ONE = math.sqrt(ETA_RT)
V_NOM, AH_UNIT, DOD = 51.2, 300.0, 0.80 # used from 10 % to 90 %
PRICE_PER_KWH = 30000.0 # stated battery price per kWh of nameplate
print("Application 1: sizing")
kwp0 = E_LOAD / (H_WORST * PR)
e_arr = E_DAY + E_NIGHT / ETA_RT
kwp1 = e_arr / (H_WORST * PR)
n_mod = math.ceil(kwp1 / P_MOD)
print(f" array, load only: {E_LOAD:.0f} / ({H_WORST} x {PR}) = {kwp0:.2f} kWp")
print(f" with the battery loss on the night energy: {E_DAY:.0f} + {E_NIGHT:.0f} / {ETA_RT} = "
f"{e_arr:.2f} kWh, {kwp1:.2f} kWp, {kwp1 / P_MOD:.1f} modules, so {n_mod}")
SITE_KWP = 18 * P_MOD
print(f" as built: 18 modules, {SITE_KWP:.1f} kWp, margin {100 * (SITE_KWP / kwp0 - 1):.1f} % on the load "
f"and {100 * (SITE_KWP / kwp1 - 1):.1f} % with the battery loss")
print(f" energy as built: worst month {SITE_KWP * H_WORST * PR:.1f} kWh a day, "
f"mean {SITE_KWP * H_MEAN * PR:.1f}; not needed on a mean day "
f"{SITE_KWP * H_MEAN * PR - e_arr:.1f} kWh, "
f"{100 * (SITE_KWP * H_MEAN * PR - e_arr) / (SITE_KWP * H_MEAN * PR):.0f} %")
cells = E_NIGHT / ETA_INV / ETA_ONE
nominal = cells / DOD
print(f" battery: one-way efficiency {ETA_ONE:.4f}; from the cells {E_NIGHT:.0f} / {ETA_INV} / "
f"{ETA_ONE:.4f} = {cells:.2f} kWh")
print(f" nameplate {cells:.2f} / {DOD} = {nominal:.2f} kWh, {1000 * nominal / V_NOM:.0f} Ah "
f"at {V_NOM} V; as built {AH_UNIT:.0f} Ah, {V_NOM * AH_UNIT / 1000:.2f} kWh, "
f"usable {DOD * V_NOM * AH_UNIT / 1000:.2f}, margin "
f"{100 * (DOD * V_NOM * AH_UNIT / 1000 / cells - 1):.1f} %")
MARGIN, START = 1.20, 3.0 # stated margin; stated starting factor
P_INV, OVERLOAD, I_BAT = 8.0, 1.5, 150.0 # overload factor is a stated example
others = P_PEAK - 2.20
surge = others + START * 2.20
print(f" inverter: {P_PEAK:.1f} x {MARGIN} = {P_PEAK * MARGIN:.1f} kW, as built {P_INV:.0f} kW, "
f"DC to AC ratio {SITE_KWP / P_INV:.2f}")
print(f" compressor start: {others:.1f} + {START:.0f} x 2.2 = {surge:.1f} kW against "
f"{OVERLOAD * P_INV:.0f} kW for a few seconds")
print(f" battery current: peak {1000 * P_PEAK / ETA_INV / V_NOM:.0f} A, "
f"start {1000 * surge / ETA_INV / V_NOM:.0f} A, continuous limit {I_BAT:.0f} A")
# ---------- Application 2: off-grid, two days of autonomy ----------
DAYS, RECOVER = 2, 4
print("Application 2: off-grid with two days of autonomy")
cells2 = DAYS * E_LOAD / ETA_INV / ETA_ONE
nominal2 = cells2 / DOD
units = math.ceil(1000 * nominal2 / V_NOM / AH_UNIT)
kwh2 = units * V_NOM * AH_UNIT / 1000
kwh1 = V_NOM * AH_UNIT / 1000
print(f" from the cells {DAYS} x {E_LOAD:.0f} / {ETA_INV} / {ETA_ONE:.4f} = {cells2:.2f} kWh, "
f"nameplate {nominal2:.2f} kWh, {1000 * nominal2 / V_NOM:.0f} Ah")
print(f" {units} units of {AH_UNIT:.0f} Ah: {kwh2:.2f} kWh, {kwh2 / kwh1:.0f} times the site battery")
print(f" price {PRICE_PER_KWH * kwh2:,.0f} against {PRICE_PER_KWH * kwh1:,.0f}: "
f"{PRICE_PER_KWH * (kwh2 - kwh1):,.0f} more")
refill = DAYS * E_LOAD / ETA_RT / RECOVER
kwp2 = (e_arr + refill) / (H_WORST * PR)
n2 = math.ceil(kwp2 / P_MOD)
n2 += n2 % 2
print(f" array: refill {DAYS * E_LOAD:.0f} / {ETA_RT} over {RECOVER} days = {refill:.2f} kWh a day; "
f"({e_arr:.2f} + {refill:.2f}) / ({H_WORST} x {PR}) = {kwp2:.2f} kWp, "
f"{n2} modules, {n2 * P_MOD:.1f} kWp")
print(f" on a mean day that array gives {n2 * P_MOD * H_MEAN * PR:.1f} kWh for a need of {e_arr:.1f}")
GEN_KW, DIESEL = 7.5, 180.0
hours = DAYS * E_LOAD / GEN_KW
litres = 0.9 * hours + 0.27 * DAYS * E_LOAD
print(f" the same {DAYS * E_LOAD:.0f} kWh by generator at {GEN_KW} kW: {hours:.0f} h, {litres:.1f} L, "
f"{litres * DIESEL:,.0f} currency units; the extra battery equals "
f"{PRICE_PER_KWH * (kwh2 - kwh1) / (litres * DIESEL):.0f} such events")
# ---------- Plot ----------
fig, ax = plt.subplots(figsize=(8, 4.5))
ax.step(h, profile, where="post")
ax.axvspan(0, 6.5, color="gray", alpha=0.2)
ax.axvspan(18.5, 24, color="gray", alpha=0.2, label="18:30 to 06:30")
ax.set_xlabel("hour of the day")
ax.set_ylabel("load (kW)")
ax.set_title("Load of the site through one day")
ax.set_xlim(0, 24)
ax.legend()
fig.tight_layout()
fig.savefig("size_from_load.png", dpi=120)
print("Saved size_from_load.png")

Expected output

Application 1: the load table
load kW hours kWh day night
Always on: refrigerator, network 0.30 24.0 7.2 3.6 3.6
Security lights 0.20 12.0 2.4 0.0 2.4
Inside lights 0.25 6.0 1.5 0.5 1.0
Office equipment 0.40 14.0 5.6 4.0 1.6
Bench tools 0.60 13.5 8.1 5.7 2.4
Welder 3.00 1.0 3.0 3.0 0.0
Air compressor 2.20 1.0 2.2 2.2 0.0
total 30.0 kWh a day: 19.0 between 06:30 and 18:30, 11.0 between 18:30 and 06:30
connected 6.95 kW, peak 6.50 kW at 11:00, mean 1.25 kW, load factor 0.192
the load through the day:
00:00 to 06:30 0.50 kW
06:30 to 08:00 0.30 kW
08:00 to 08:30 0.90 kW
08:30 to 10:30 1.30 kW
10:30 to 11:00 4.30 kW
11:00 to 11:30 6.50 kW
11:30 to 12:00 3.50 kW
12:00 to 13:00 1.30 kW
13:00 to 14:00 0.70 kW
14:00 to 16:30 1.30 kW
16:30 to 18:30 1.55 kW
18:30 to 22:30 1.75 kW
22:30 to 24:00 0.50 kW
Application 1: sizing
array, load only: 30 / (4.5 x 0.75) = 8.89 kWp
with the battery loss on the night energy: 19 + 11 / 0.92 = 30.96 kWh, 9.17 kWp, 16.7 modules, so 17
as built: 18 modules, 9.9 kWp, margin 11.4 % on the load and 7.9 % with the battery loss
energy as built: worst month 33.4 kWh a day, mean 40.8; not needed on a mean day 9.9 kWh, 24 %
battery: one-way efficiency 0.9592; from the cells 11 / 0.97 / 0.9592 = 11.82 kWh
nameplate 11.82 / 0.8 = 14.78 kWh, 289 Ah at 51.2 V; as built 300 Ah, 15.36 kWh, usable 12.29, margin 3.9 %
inverter: 6.5 x 1.2 = 7.8 kW, as built 8 kW, DC to AC ratio 1.24
compressor start: 4.3 + 3 x 2.2 = 10.9 kW against 12 kW for a few seconds
battery current: peak 131 A, start 219 A, continuous limit 150 A
Application 2: off-grid with two days of autonomy
from the cells 2 x 30 / 0.97 / 0.9592 = 64.49 kWh, nameplate 80.61 kWh, 1574 Ah
6 units of 300 Ah: 92.16 kWh, 6 times the site battery
price 2,764,800 against 460,800: 2,304,000 more
array: refill 60 / 0.92 over 4 days = 16.30 kWh a day; (30.96 + 16.30) / (4.5 x 0.75) = 14.00 kWp, 26 modules, 14.3 kWp
on a mean day that array gives 59.0 kWh for a need of 31.0
the same 60 kWh by generator at 7.5 kW: 8 h, 23.4 L, 4,212 currency units; the extra battery equals 547 such events
Saved size_from_load.png

Common Mistakes



  • Sizing from the sum of nameplate powers. The array and the battery follow energy, which is mean power multiplied by real hours. Only the inverter follows power, and it follows the peak that occurs together, not the sum.
  • Sizing the array on the yearly mean of peak sun hours. The load must be carried in the worst month.
  • Forgetting when the energy is used. The same 30 kWh a day needs a small battery if it is used at noon and a large one if it is used at night.
  • Dividing the night energy by the nameplate of the battery. The inverter loss, the battery loss and the depth of discharge all stand between the nameplate and the load.
  • Treating sunset as the start of the battery’s night. The array stops covering the load before sunset and starts again after sunrise.
  • Checking only the running power of a motor against the inverter. The start decides whether the inverter trips.

Summary



  • A load table gives each load its mean power, its hours and its place on the clock. For the site it totals 30 kWh a day, with 11 kWh between 18:30 and 06:30 and a peak of 6.5 kW.
  • The array follows the daily energy, the worst month and a stated performance ratio: 9.17 kWp with the battery loss, built as 18 modules, 9.9 kWp.
  • The battery follows the energy used without sun, divided by the inverter efficiency, the one-way battery efficiency and the depth of discharge: 14.78 kWh for one night, built as 300 Ah, 15.36 kWh.
  • The inverter follows the peak load with a margin, and must pass the starting surge of the largest motor: 8 kW for a peak of 6.5 kW and a start of 10.9 kW.
  • Two days of autonomy without a grid or a generator need 6 times the battery and 26 modules, and most of both stand unused on an ordinary day.
  • A first sizing is then checked for string voltage, battery current and a real day shape.

Exercises



1. A small farm office has a water pump of 0.75 kW that runs 6 hours a day, lights of 0.12 kW for 5 hours and a refrigerator with a mean power of 0.15 kW for 24 hours. Find the daily energy.

Answer

kWh a day.

2. Size an array for 8.7 kWh a day at a site with 4.0 peak sun hours in the worst month and a performance ratio of 0.75. How many modules of 450 W are needed?

Answer

kWp. , so 7 modules, 3.15 kWp.

3. A site uses 3.2 kWh between sunset and sunrise. The inverter efficiency is 0.95, the round-trip efficiency of the battery is 0.90 and the battery is used over 80 percent of its nameplate. Find the nameplate energy for one night and the capacity at 25.6 V.

Answer

One-way efficiency . From the cells: kWh. Nameplate: kWh, which is Ah.

4. The peak load of a site is 2.4 kW. It includes a pump motor of 0.75 kW with a starting factor of 4. Find the continuous inverter rating with a margin of 25 percent, and the power at the moment the pump starts with everything else running.

Answer

Continuous: kW. Start: kW, which must be inside the short overload rating of the inverter.

5. The site of exercise 1 uses 8.7 kWh a day and must run off-grid with three days of autonomy. Use the efficiencies and the depth of discharge of exercise 3. Find the nameplate energy of the battery, and its price at 30,000 currency units for each kWh. Compare with the battery for one night from exercise 3.

Answer

From the cells: kWh. Nameplate: kWh, at a price of 1,086,000 currency units. The battery for one night is 4.44 kWh and 133,100 currency units. Three days of autonomy cost 8.2 times as much.

References



  • R. A. Messenger and A. Abtahi, Photovoltaic Systems Engineering, 4th edition, CRC Press, 2017.
  • G. M. Masters, Renewable and Efficient Electric Power Systems, 2nd edition, Wiley, 2013.
  • D. Linden and T. B. Reddy (editors), Handbook of Batteries, 3rd edition, McGraw-Hill, 2002.


© 2021-2026 SiliconWit®. All rights reserved.
Predict first

The workshop has machines and lights whose powers add up to 6.95 kW. About how much energy does it use in a day?

arraybatteryinverter roof: energy in a daytank: energy without suntap: power now kWpkWhkW
Try it: from the load to the array, the battery and the inverter

Array, worst month, PR 0.75
Battery, 51.2 V units of 300 Ah
Inverter, peak + 20 percent

The loads are the table of the site in Application 1, added at 5-minute steps. The slider moves the end of the office equipment, the bench tools and the inside lights together. The array covers the day share plus the night share divided by the round-trip efficiency 0.92, from the worst month; off-grid it must also refill the battery within four days. The battery covers the energy without sun through the inverter (0.97) and one direction of the battery (√0.92), used over 80 percent of its nameplate. Only the peak sizes the inverter.

One nightTwo dark days 460,800 currency units2,764,800 currency units used only on dark days The extra 2,304,000 buys fuel for 547 such spells.

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. A guest house uses 15 kWh between sunset and sunrise. The inverter efficiency is 0.97, the round-trip efficiency of the battery is 0.92, and the battery is used over 80 percent of its nameplate. What nameplate energy does the battery need for one night?

2. The peak load of a farm is 4.0 kW, and it includes a pump of 1.5 kW with a starting factor of 3. Everything else is running when the pump starts. What power must the inverter's short overload rating cover?

3. A clinic uses 12 kWh in the day and 8 kWh at night. The battery round-trip efficiency is 0.92. The roof gets 4.0 peak sun hours in the worst month and 5.5 as the yearly mean. The sizing performance ratio is 0.75. Which array do you choose?

Watch it build: from the load to the array and the battery
day 19night 1130 kWh Array Battery 4.5 h × 0.753.375 kWh a dayfor each kWp 30.96 ÷ 3.375= 9.17 kWp18 modules, 9.9 ÷ 0.92 11 ÷0.97 ÷0.959÷0.80 = 14.781 unit, 15.36 kWh No grid, 2 days:80.61 kWh6 units
  1. The load table gives 30 kWh a day: 19 kWh while the sun is up, 11 kWh at night.
  2. In the worst month each kWp gives 4.5 h × 0.75 = 3.375 kWh a day.
  3. The night share passes the battery (÷ 0.92): 30.96 kWh, so 9.17 kWp. Built: 18 modules, 9.9 kWp.
  4. The battery: 11 kWh ÷ 0.97 ÷ 0.959 ÷ 0.80 = 14.78 kWh. One 300 Ah unit holds 15.36 kWh.
  5. With no grid and two days without sun, the same rule needs 80.61 kWh: six units.
Array ? kWp energy in a day Hybrid inverter ? kW power at one moment Load energy hours peak Battery ? kWh energy without sun
Three sizes, three questions about the load
Load table Array worst month, PR daily energy Battery autonomy, DoD night energy Inverter peak + margin, surge peak and surge
The order of a first sizing
0 06:30 12:00 18:30 24 0 0.5 1.3 1.75 3.5 4.3 6.5 clock, h load, kW welder and compressor together for 30 minutes welder 3.0 compressor 2.2 evening work 1.55, then 1.75 night 0.5 0.3 30.0 kWh: 19.0 by day, 11.0 by night
The load of the site through one day
Hybrid site: one night, 15.36 kWh 1 Off-grid: two days without sun, 92.16 kWh 1 2 3 4 5 6 needed: 80.61 kWh, 5.25 units one unit: 300 Ah × 51.2 V = 15.36 kWh
One night of storage against two days of autonomy