A technician who is called to site for every high reading soon stops answering, and then the one reading that mattered is missed. A manager who sees one low energy day claims a saving, and the next week it has gone. Both people lack the same thing: a rule that says how far a reading moves when nothing has changed. A control chart is that rule, drawn on the readings themselves. This lesson shows how to set its limits from your own data, how often it will give a false alarm, and how to find a small change that no single reading shows. #ControlCharts #EWMA #ProcessMonitoring

Learning Objectives

By the end of this lesson, you will be able to:

  1. Distinguish common cause variation from a special cause in a series of readings
  2. Calculate the centre line and limits of an individuals chart from the mean moving range
  3. State the false alarm rate of a chart and what autocorrelated readings do to it
  4. Build an EWMA chart that finds a small sustained shift
  5. Explain why the residuals of a baseline are charted and not the raw energy

Real-World System Problem: Was yesterday’s energy normal?



A building used 742 kWh yesterday and 498 kWh the day before. Nobody can say from these two numbers whether anything is wrong. Yesterday was a hot working day and the day before was a Sunday. The energy of a building moves every day with the weather and the calendar, and a little more for reasons that nobody will ever trace.

The site has a second question. An energy-saving measure was installed on day 500 of the record. The supplier says it saves 12 percent. A change of 12 percent is smaller than the difference between a Sunday and a Monday, so no single day will show it. The owner wants to know on which day the data alone would have shown that something changed.

Both questions need the same two steps. First remove the part of the movement that has a known driver, with a baseline model. Then put what remains on a chart whose limits say how large the unexplained movement normally is.

ΣChartEnergy meterBaselinemodelOutdoor tempand weekdayactual kWh+-residualpredicted kWh
From the meter and the weather to a chart

Fundamental Theory: Limits that come from the process



Two kinds of variation

Every measured process moves. The movement that is always present, from many small causes that nobody can separate, is called common cause variation. A process that shows only this movement is called stable, or in control. Its next value cannot be predicted exactly, but the range in which it will fall can be.

A special cause is something that was not there before: a door seal that failed, a compressor that tripped, a setpoint that somebody changed, a saving measure that was installed. A special cause is worth a visit. Common cause variation is not.

A control chart is a time plot of the readings with three horizontal lines: a centre line at the mean, and an upper and a lower control limit three standard deviations from it. A point outside the limits is a signal that a special cause is likely.

● signalUCL●●CL●●●●●●●●LCL1234567891011
An individuals chart with one signal

The individuals chart

When there is one value for each period (one daily mean, one daily energy), the chart is called an individuals chart. Its centre line is the sample mean of the readings of a period that you believe was normal.

The standard deviation is not taken from the usual formula for . It is taken from the moving range, the absolute difference between each reading and the one before it:

For independent normal readings, the mean range of two readings is standard deviations. So the standard deviation is estimated as , and three of them make mean moving ranges.

Individuals chart

The constant is with for ranges of two readings.

The moving range is used because it looks only at neighbours. If the mean shifted once during the period, grows and hides the shift inside wide limits. The moving range sees the shift only once, so the limits stay close to the short-term variation.

Limits come from the process, not from the specification

A cold room for vaccines must stay between 2 °C and 8 °C. Those are specification limits, what the product needs; control limits say what the room normally does.

If the room normally gives daily means between 3.99 °C and 4.04 °C, a daily mean of 4.5 °C is far inside the specification and is also a clear sign that something changed. A chart with the specification drawn as its limits would stay silent until the stock was already at risk.

How often the chart gives a false alarm

For independent readings with a normal distribution, 99.73 percent of the values lie within three standard deviations of the mean. So a stable process still puts about 0.27 percent of its points outside the limits, which is about one point in 370. With one point a day, expect one false alarm a year. With one point a minute, expect about four a day.

Many sensors multiply this. A site with 50 daily charts has a chance of percent of at least one false alarm on any day, about 49 in a year: one a week. People learn to ignore an alarm that is wrong every week. So decide first how many false alarms the whole site can accept, then set each chart from that. For one false alarm a month across 50 daily charts, each chart may give one in points, which needs limits at 3.4 standard deviations in place of 3. Wider limits find a change later, which is one more reason to add the EWMA chart below for small changes.

That rate is true only for independent readings. Sensor readings taken close together are not independent: each one is near the one before it. This is autocorrelation, and it damages the chart in a specific way. Neighbouring readings differ very little, so the mean moving range is small and the limits are narrow. But over an hour the reading travels much further than it does between neighbours, so it leaves those narrow limits again and again.

Run rules

A sustained small shift can leave every point inside the limits and still show itself by a pattern. Extra rules, called run rules, look for such patterns. This lesson uses two rules:

  • one point beyond a control limit,
  • eight successive points on the same side of the centre line.

The second rule works because a stable process puts each point above or below the centre line with a chance of one half, like a coin. Eight on one side by chance has a probability of for any chosen eight points.

Textbooks list more rules. Each added rule finds some real changes sooner and adds its own false alarms: the two rules above together give a false alarm about once in 151 points of a stable process, not once in 370. Use few rules, and say which ones you used.

The EWMA chart for small shifts

The individuals chart judges each point alone and forgets it; to find a small shift, a chart must remember. The exponentially weighted moving average (EWMA) does this:

Here is the new reading, is the previous EWMA value, and is a weight between 0 and 1. The start value is the centre line. With , each new point has a weight of 20 percent and the history has 80 percent. Random movement in opposite directions cancels inside , and a sustained shift accumulates.

Because is an average, it moves less than the readings, and its limits are closer.

EWMA chart, steady-state limits

is the standard deviation of the individual readings and is the width of the limits. Common choices are and . With them, , so the limits are at one standard deviation of the individual readings.

These limits are the steady-state form. For the first few points the exact limits are a little narrower.

Individual values+3σ●●●0●●●●●●●●● ●●●-3σshiftEWMA of the same values+σ0-σ
A small shift: single points stay inside, the EWMA leaves

The EWMA has a cost: it reacts late to one large sudden value, which enters with a weight of only . The two charts are partners, the individuals chart for a large sudden change and the EWMA chart for a small sustained one.

The average run length (ARL) puts numbers on this: the mean number of points from the start of a shift to the first signal. With no shift, it is the mean number of points between false alarms. For independent normal readings:

Shift, in standard deviationsIndividuals chart, 3-sigmaEWMA, ,
0 (false alarms)370560
0.515544
14410.8
26.33.8

The EWMA gives fewer false alarms and finds a shift of half a standard deviation more than three times sooner. For a shift of two standard deviations the two charts are close.

Chart the residuals, not the raw values

A control chart assumes that the mean of a stable process is constant. Daily energy does not: it rises in the hot season and falls every weekend, so a chart of raw energy signals the weather and the calendar, which you already know about.

The cure is to chart the residual of a baseline model:

The baseline removes what the weather and the weekday explain. What remains has a mean of zero while the building behaves as it did in the baseline period, and a mean different from zero when the building itself has changed.

What to do with a signal

A signal is a reason to look, not a proof. The reverse also holds: a sensor that stops sending, or repeats one value, keeps its chart quiet. Give every charted sensor a separate alarm for missing or frozen data, or the quiet chart will be read as a healthy machine.

Application 1: Daily mean temperature of a cold room



Step 1: Limits from the 14 days

Click to reveal the limits
  1. Centre line. The mean of the 14 daily means is . ✅

  2. Moving ranges. There are 13 differences between neighbouring days. The first is and the last is . Their mean, from the unrounded daily means, is

    The printed three-decimal values give 0.0096, which is the same within rounding. ✅

  3. Standard deviation. . ✅

  4. Limits.

    The lower limit is and the upper limit is . ✅

Step 2: Read the chart before adding anything

Click to reveal the reading of the chart
  1. Points beyond the limits. Day 0, at , is above the upper limit of . The other 13 days are inside. ✅

  2. Is day 0 a special cause? Nothing in the log explains it. With no cause found, the point is marked as unexplained and it stays in the data. ✅

  3. Check the assumption behind the limits. The ordinary standard deviation of the 14 means is , almost twice the moving-range value of 0.0086. The lag-1 autocorrelation of the daily means is 0.46. Neighbouring days are more alike than independent days would be, so the limits are somewhat too narrow. ✅

  4. Judge the limits honestly. Textbooks ask for 20 to 25 points or more before limits are trusted. With 14 points these limits are provisional. They are used below, and should be recalculated once a month of normal days exists. ✅

Step 3: The disturbed day

Click to reveal the effect of the trip
  1. Rise. In 60 minutes with the compressor off the air rises by above its normal cycle. ✅

  2. Recovery. The compressor removes that rise in minutes. The excursion is a triangle 6.0 °C high on a base of 80 minutes. ✅

  3. Amount added to the day’s mean. The area of the triangle is spread over the 1440 minutes of the day.

    The mean of day 10 becomes . ✅

  4. Does the chart signal? is above the upper limit of . It is standard deviations above the centre line. The chart signals without any doubt. ✅

  5. Shortest hold the chart detects. For a hold of minutes the added amount is . Day 10 reaches the upper limit when this equals .

    A hold of 25 minutes or more on day 10 is detected. During a 25 minute hold the air rises by only 2.5 °C. ✅

Step 4: Check with the wrong limits and with the script

Click to reveal the check
  1. Include the disturbed day in the limits. This is the mistake of calculating limits from a period that was not normal. The mean moving range grows from 0.00968 to 0.0353, and the limits become to , 3.6 times wider. ✅

  2. Result. Day 10 at still signals, but its margin above the limit has fallen from 0.139 to 0.059 °C. A smaller disturbance would have hidden itself. ✅

  3. The same chart on raw readings. The script reproduces the hand values above. It also puts the 20,160 minute readings on an individuals chart: 60.8 percent of them are beyond the limits. On the 336 hourly means, 7 points (2.1 percent) are beyond the limits, about eight times the 0.27 percent of independent readings. ✅

Application 2: Finding a saving in the residuals of an energy baseline



Step 1: Fit the baseline and form the residuals

Click to reveal the baseline
  1. Least squares on days 0 to 364.

    The base load is 306.6 kWh a day, each cooling degree day adds 41.61 kWh, and a working day adds 182.1 kWh. ✅

  2. Quality of the fit. With and fitted parameters, . ✅

  3. Residuals. For every one of the 730 days, residual = actual minus predicted. In the baseline period their mean is 0.00 kWh, as least squares with a constant term always gives. ✅

Step 2: Limits from the baseline residuals

Click to reveal the limits
  1. Mean moving range of the 365 baseline residuals. , so . This is close to the RMSE of 27.3 kWh, which is a sign that the residuals are close to independent. ✅

  2. Individuals chart. Centre line 0, limits . ✅

  3. EWMA chart. Centre line 0, start value .

    With these settings the EWMA limits are at one standard deviation of the residuals. ✅

  4. Test the limits on the baseline year. No residual of the 365 is beyond ±77.1 kWh. The EWMA is beyond ±25.7 kWh on 2 days (days 238 and 359). This is the “count the false alarms on a quiet period” check, and every chart needs it before it is trusted. With an ARL of 560, about false alarms are expected in a year, and 2 is within ordinary chance. Ten would mean that the limits are too narrow for this data. ✅

Step 3: Chart days 365 to 729

Click to reveal what the charts show
  1. Before the measure, days 365 to 499. The residual mean is +3.6 kWh: the baseline still predicts the building well. The individuals chart signals on days 441 and 460, both above the upper limit. No cause is known, so they are recorded as unexplained. The EWMA chart gives no signal in these 135 days. ✅

  2. Individuals chart after day 500. The first point beyond a limit is day 505, with a residual of . ✅

  3. EWMA chart after day 500. The EWMA passes the lower limit on day 502, with . ✅

  4. Run rule. All residuals from day 500 are below zero, so the eighth successive point below the centre line arrives on day 507. ✅

  5. Size of the shift. The residual mean of days 500 to 729 is a day. The mean predicted energy of those days is 525.5 kWh, so the shift is percent. ✅

Step 4: Check the shift and try a smaller saving

Click to reveal the check
  1. Expected shift. A saving of 12 percent on a predicted 525.5 kWh is a day. The observed shift of 60.2 kWh agrees within 3 kWh. In units of the residual standard deviation the shift is . ✅

  2. A saving of 3 percent. The script rescales the same data to a saving of 3 percent, a shift of about half a standard deviation. The individuals chart first signals on day 625, which is 125 days late. The EWMA chart signals on day 519, after 19 days. These are single cases; the average run lengths of the table, 155 and 44 points, say what to expect on average. ✅

  3. Raw energy on a chart. The script also puts the raw energy of the baseline year on an individuals chart. Its limits are 317 to 834 kWh, and 45 of the 365 days are beyond them with no fault present. ✅

Verify It in Python



The script generates both data sets, builds the limits for the cold room, adds the disturbed day, then fits the energy baseline and runs both charts on its residuals. It saves one plot with the three charts.

control_charts.py
"""Individuals and EWMA control charts: cold room daily means, building energy residuals."""
import numpy as np
import matplotlib.pyplot as plt
def cold_room_minutes(seed=11, days=14):
rng = np.random.default_rng(seed)
n = days * 1440
t = np.empty(n); temp = 4.0; on = False; out = []
for i in range(n):
minute = i % 1440
# door openings are more likely in working hours
door = (480 <= minute < 1020) and (rng.random() < 0.035)
if temp >= 5.0: on = True
if temp <= 3.0: on = False
temp += (-0.30 if on else 0.10) + (0.35 if door else 0.0)
t[i] = temp + rng.normal(0.0, 0.05) # sensor noise, 0.05 °C
return t
def building_daily(seed=23, days=730):
rng = np.random.default_rng(seed)
d = np.arange(days)
temp = 21.0 + 4.5 * np.sin(2 * np.pi * (d - 20) / 365.0) + rng.normal(0, 1.6, days)
weekday = (d % 7) < 5 # day 0 is a Monday
cdd = np.clip(temp - 18.0, 0.0, None) # cooling degree days, base 18 °C
energy = 310.0 + 42.0 * cdd + np.where(weekday, 180.0, 0.0) + rng.normal(0, 28.0, days)
# an energy-saving measure is installed on day 500: 12 percent less from then on
energy[500:] *= 0.88
return d, temp, weekday, energy # kWh a day
D2 = 1.128 # mean range of two normal readings, in units of sigma
LAM, L = 0.2, 3.0 # EWMA weight and limit width
def individuals_limits(x):
"""Centre line, mean moving range, lower and upper limit of an individuals chart."""
centre = x.mean()
mr_bar = np.abs(np.diff(x)).mean()
half = 3.0 / D2 * mr_bar # 3/1.128 = 2.66
return centre, mr_bar, centre - half, centre + half
def ewma(x, start, lam=LAM):
z = np.empty(x.size)
prev = start
for i, v in enumerate(x):
prev = lam * v + (1.0 - lam) * prev
z[i] = prev
return z
def first_run(x, centre, length=8):
"""Index at which `length` successive points on one side of the centre is completed."""
side = np.sign(x - centre)
run = 0
for i in range(x.size):
run = run + 1 if (i > 0 and side[i] == side[i - 1]) else 1
if run >= length:
return i
return None
# ---------- Application 1: daily mean temperature of the cold room ----------
minutes = cold_room_minutes()
daily = minutes.reshape(14, 1440).mean(axis=1)
centre, mr_bar, lcl, ucl = individuals_limits(daily)
sigma_mr = mr_bar / D2
print("Application 1: cold room, 14 daily means (degC)")
print(" " + " ".join(f"{v:.3f}" for v in daily[:7]))
print(" " + " ".join(f"{v:.3f}" for v in daily[7:]))
print(f" centre {centre:.4f}, mean moving range {mr_bar:.5f}, sigma {sigma_mr:.5f}")
print(f" limits {lcl:.4f} to {ucl:.4f}")
print(f" days beyond the limits: {np.where((daily > ucl) | (daily < lcl))[0].tolist()}")
dev = daily - centre
r1 = (dev[1:] * dev[:-1]).sum() / (dev ** 2).sum()
print(f" sample standard deviation s {daily.std(ddof=1):.5f}, lag-1 autocorrelation {r1:.2f}")
WARM, COOL = 0.10, 0.30 # degC per minute, compressor off and on
HOLD = 60.0 # minutes the compressor is held off on day 10
rise = WARM * HOLD
recover = rise / COOL
added = 0.5 * rise * (HOLD + recover) / 1440.0
disturbed = daily.copy()
disturbed[10] += added
print(f" hold {HOLD:.0f} min: rise {rise:.1f} degC, recovery {recover:.0f} min, "
f"added to the day's mean {added:.4f} degC")
print(f" day 10: {daily[10]:.4f} becomes {disturbed[10]:.4f}, "
f"{(disturbed[10] - centre) / sigma_mr:.1f} sigma above the centre line")
hold_min = np.sqrt((ucl - daily[10]) * 2.0 * 1440.0 / (WARM * (1.0 + WARM / COOL)))
print(f" shortest hold that puts day 10 above the upper limit: {hold_min:.1f} min")
c2, m2, l2, u2 = individuals_limits(disturbed)
print(f" limits if day 10 is wrongly included: {l2:.4f} to {u2:.4f} "
f"(mean moving range {m2:.5f})")
# the same chart on readings that are not independent
for name, x in (("minute readings", minutes),
("hourly means", minutes.reshape(-1, 60).mean(axis=1))):
c, m, lo, hi = individuals_limits(x)
out = int(((x > hi) | (x < lo)).sum())
print(f" {name}: {out} of {x.size} beyond the limits ({100.0 * out / x.size:.1f} %)")
# ---------- Application 2: residuals of the energy baseline ----------
d, temp, weekday, energy = building_daily()
cdd = np.clip(temp - 18.0, 0.0, None)
X = np.column_stack([np.ones(d.size), cdd, weekday.astype(float)])
b, *_ = np.linalg.lstsq(X[:365], energy[:365], rcond=None)
predicted = X @ b
resid = energy - predicted
rmse = np.sqrt((resid[:365] ** 2).sum() / (365 - 3))
print("Application 2: building energy, baseline from days 0 to 364")
print(f" model: {b[0]:.1f} + {b[1]:.2f} CDD + {b[2]:.1f} weekday, RMSE {rmse:.1f} kWh")
_, mr_res, _, _ = individuals_limits(resid[:365])
sigma = mr_res / D2
lim_i = 3.0 * sigma
lim_e = L * sigma * np.sqrt(LAM / (2.0 - LAM))
print(f" first-year residuals: mean {abs(resid[:365].mean()):.2f}, mean moving range "
f"{mr_res:.2f}, sigma {sigma:.2f} kWh")
print(f" individuals limits +/-{lim_i:.1f} kWh, EWMA limits +/-{lim_e:.1f} kWh")
z1 = ewma(resid[:365], 0.0)
print(f" first year beyond the limits: individuals "
f"{int((np.abs(resid[:365]) > lim_i).sum())}, EWMA {int((np.abs(z1) > lim_e).sum())} "
f"(days {np.where(np.abs(z1) > lim_e)[0].tolist()})")
day2 = d[365:]
r2 = resid[365:]
z2 = ewma(r2, 0.0)
sig_i = day2[np.abs(r2) > lim_i]
sig_e = day2[np.abs(z2) > lim_e]
print(f" days 365 to 499: individuals signals on days {sig_i[sig_i < 500].tolist()}, "
f"EWMA signals on days {sig_e[sig_e < 500].tolist()}")
fi, fe = sig_i[sig_i >= 500][0], sig_e[sig_e >= 500][0]
print(f" first signal after day 500: individuals day {fi} (residual {resid[fi]:.1f}), "
f"EWMA day {fe} (z {z2[fe - 365]:.1f})")
post = resid[500:]
print(f" eight successive residuals below zero completed on day "
f"{500 + first_run(post, 0.0)}")
print(f" residual mean: days 365 to 499 {resid[365:500].mean():+.1f}, "
f"days 500 to 729 {post.mean():+.1f} kWh")
print(f" mean predicted energy, days 500 to 729: {predicted[500:].mean():.1f} kWh, "
f"shift is {100.0 * post.mean() / predicted[500:].mean():.1f} %")
print(f" 12 % of the predicted energy: {0.12 * predicted[500:].mean():.1f} kWh")
# a smaller saving of 3 percent, made from the same data
small = energy.copy()
small[500:] = small[500:] / 0.88 * 0.97
rs = (small - predicted)[365:]
zs = ewma(rs, 0.0)
si = day2[(np.abs(rs) > lim_i) & (day2 >= 500)]
se = day2[(np.abs(zs) > lim_e) & (day2 >= 500)]
print(f" with a 3 % saving: individuals day {si[0]}, EWMA day {se[0]}")
# raw energy on an individuals chart, for comparison
c, m, lo, hi = individuals_limits(energy[:365])
out = int(((energy[:365] > hi) | (energy[:365] < lo)).sum())
print(f" raw energy, first year: limits {lo:.0f} to {hi:.0f} kWh, "
f"{out} of 365 days beyond them")
# ---------- Plot ----------
fig, ax = plt.subplots(3, 1, figsize=(8, 10))
ax[0].plot(np.arange(14), disturbed, "o-")
for v in (lcl, centre, ucl):
ax[0].axhline(v, color="gray", linewidth=0.8, linestyle="--")
ax[0].set_xlabel("day")
ax[0].set_ylabel("daily mean (degC)")
ax[0].set_title("Cold room: individuals chart with the disturbed day 10")
ax[1].plot(day2, r2, ".", markersize=4)
for v in (-lim_i, 0.0, lim_i):
ax[1].axhline(v, color="gray", linewidth=0.8, linestyle="--")
ax[1].axvline(500, color="black", linewidth=0.8)
ax[1].set_ylabel("residual (kWh)")
ax[1].set_title("Energy residuals: individuals chart")
ax[2].plot(day2, z2)
for v in (-lim_e, 0.0, lim_e):
ax[2].axhline(v, color="gray", linewidth=0.8, linestyle="--")
ax[2].axvline(500, color="black", linewidth=0.8)
ax[2].set_xlabel("day")
ax[2].set_ylabel("EWMA of residual (kWh)")
ax[2].set_title("Energy residuals: EWMA chart")
fig.tight_layout()
fig.savefig("control_charts.png", dpi=120)
print("Saved control_charts.png")

Expected output

Application 1: cold room, 14 daily means (degC)
4.055 4.037 4.015 4.004 3.997 4.000 4.013
3.997 4.006 4.006 4.011 4.007 4.008 4.024
centre 4.0128, mean moving range 0.00968, sigma 0.00858
limits 3.9870 to 4.0385
days beyond the limits: [0]
sample standard deviation s 0.01618, lag-1 autocorrelation 0.46
hold 60 min: rise 6.0 degC, recovery 20 min, added to the day's mean 0.1667 degC
day 10: 4.0107 becomes 4.1773, 19.2 sigma above the centre line
shortest hold that puts day 10 above the upper limit: 24.5 min
limits if day 10 is wrongly included: 3.9308 to 4.1186 (mean moving range 0.03532)
minute readings: 12262 of 20160 beyond the limits (60.8 %)
hourly means: 7 of 336 beyond the limits (2.1 %)
Application 2: building energy, baseline from days 0 to 364
model: 306.6 + 41.61 CDD + 182.1 weekday, RMSE 27.3 kWh
first-year residuals: mean 0.00, mean moving range 29.00, sigma 25.71 kWh
individuals limits +/-77.1 kWh, EWMA limits +/-25.7 kWh
first year beyond the limits: individuals 0, EWMA 2 (days [238, 359])
days 365 to 499: individuals signals on days [441, 460], EWMA signals on days []
first signal after day 500: individuals day 505 (residual -81.6), EWMA day 502 (z -27.0)
eight successive residuals below zero completed on day 507
residual mean: days 365 to 499 +3.6, days 500 to 729 -60.2 kWh
mean predicted energy, days 500 to 729: 525.5 kWh, shift is -11.5 %
12 % of the predicted energy: 63.1 kWh
with a 3 % saving: individuals day 625, EWMA day 519
raw energy, first year: limits 317 to 834 kWh, 45 of 365 days beyond them
Saved control_charts.png

Common Mistakes



  • Using the specification or an alarm value as the control limit. The limits must be calculated from readings of a normal period of this process.
  • Calculating the limits from a period that contains the fault. The fault widens the limits and hides itself, as the check in Application 1 shows.
  • Charting raw readings taken every minute. They are autocorrelated, the limits are far too narrow, and most points signal. Chart hourly or daily means and check that neighbours are close to independent.
  • Treating every signal as a fault. A 3-sigma chart signals about once in 370 points with nothing wrong, and more often when run rules are added.
  • Charting raw energy across seasons. The chart then reports the weather. Chart the residuals of a baseline.

Summary



  • Common cause variation is always present and needs no action. A special cause is a change with a reason, and the control chart exists to separate the two.
  • The individuals chart has its centre line at and its limits at , where 2.66 is .
  • For independent normal readings a 3-sigma chart gives a false alarm about once in 370 points. Autocorrelated readings give many more.
  • The EWMA chart with and has limits at one standard deviation of the individual values and finds small sustained shifts much sooner.
  • When a known driver moves the reading, chart the residuals of a baseline model. On the building data the EWMA of the residuals showed the 12 percent saving two days after it began.

Exercises



1. A pump’s discharge pressure is read once a day for ten days, in bar: 6.2, 6.4, 6.1, 6.3, 6.5, 6.2, 6.0, 6.3, 6.4, 6.1. Find the centre line and the limits of an individuals chart.

Answer

bar. The nine moving ranges are 0.2, 0.3, 0.2, 0.2, 0.3, 0.2, 0.3, 0.1, 0.3, with a mean of 0.233 bar. The limits are , so 5.63 bar and 6.87 bar.

2. A stable process with independent readings is charted once an hour with 3-sigma limits and no run rules. How many false alarms are expected in a year of 8760 hours, and what is the mean time between them in days?

Answer

false alarms a year. One in 370 points is one every 370 hours, which is 15.4 days.

3. The residuals of a baseline have kWh. (a) Find the steady-state EWMA limits for , and for , . (b) With and , the next residuals are kWh. Does the EWMA signal?

Answer

(a) kWh and kWh. (b) The EWMA values are . None is beyond , so there is no signal yet, although seven successive residuals are below zero.

4. In the cold room of Application 1 (limits 3.9870 to 4.0385 °C), the compressor is held off for 40 minutes on day 8, whose undisturbed mean is 4.006 °C. Find the new daily mean and say whether the chart signals.

Answer

Rise °C, recovery min, base 53.3 min. Added amount °C. The new mean is 4.080 °C, above the upper limit of 4.0385 °C, so the chart signals.

5. A baseline predicts a mean of 480 kWh a day, and its residuals are independent and normal with kWh. A measure saves 5 percent. On an individuals chart of the residuals with 3-sigma limits, what is the probability that any one day is beyond the lower limit, and how many days pass on average before the first such signal?

Answer

The shift is kWh, which is 1.2 standard deviations. A day is below the lower limit when its standard normal value is below , with a probability of 0.036. The mean wait is days.

References



  • D. C. Montgomery, Introduction to Statistical Quality Control, 8th edition, Wiley, 2019.
  • D. C. Montgomery and G. C. Runger, Applied Statistics and Probability for Engineers, 7th edition, Wiley, 2018.
  • D. J. Wheeler and D. S. Chambers, Understanding Statistical Process Control, 2nd edition, SPC Press, 1992.


© 2021-2026 SiliconWit®. All rights reserved.
Energy meter Outdoor temp and weekday Baseline model Σ Chart actual kWh + predicted kWh − residual residual = actual minus predicted
From the meter and the weather to a chart
UCL CL LCL signal 1 2 3 4 5 6 7 8 9 10 11 example
An individuals chart with one signal
Individual values +3σ 0 -3σ EWMA of the same values +σ 0 -σ first point beyond a limit shift example values λ = 0.2, L = 3
A small shift: single points stay inside, the EWMA leaves
Predict first

A saving measure lowers the daily energy of a building by half of one standard deviation of its ordinary day to day movement. Which chart shows the change first?

See it: two charts, one shift

Individuals: first signal
EWMA: first signal
False alarms before the shift
Estimate of σ, days 0 to 19
Individuals limits
EWMA limits

The 120 daily values are an illustration made by a seeded generator: independent values with a standard deviation of 25 kWh, such as the residuals of a baseline. They are not the lesson's data. From the start day the mean falls by the size you set, as a saving measure would make it fall. The thin stepped line is that true mean. Both charts take their centre line and their estimate of σ from days 0 to 19 only, by the moving range method, so the limits never see the shift. The EWMA uses the lesson's λ = 0.2 and L = 3 and starts at the centre line. A ring marks the first point beyond a limit after the shift. Points beyond a limit before the shift are false alarms. With only 20 days, the estimate of σ is itself uncertain: press New data and watch it change.

Watch it build: an individuals chart
4.024.00 day 0713 CL UCLLCL 14 daily means, centre 4.0128 mean moving range 0.00968 limits 3.9870 and 4.0385 specification: 2 to 8 °C 4.5 °C: in spec, out of control
  1. The 14 daily means of the cold room. The centre line is their mean, 4.0128 °C.
  2. Each moving range is the step from one day to the next. Their mean is 0.00968 °C.
  3. Limits at 4.0128 ± 2.66 × 0.00968: 3.9870 and 4.0385 °C. Day 0, at 4.055, is beyond.
  4. The specification, 2 to 8 °C, is 75 times taller than this whole chart, far off the drawing.
  5. A day at 4.5 °C is well inside the specification and far above the upper limit: something changed.
2 °C4 °C8 °C specification: what the product allows normal: 3.99 to 4.04 °Cthis day: 4.5 °C Inside the specification. Outside the normal. Go and look.
UCLCLLCL 8 below in a row By chance alone: about 8 times in 1,000.

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. The residuals of a baseline have a mean of zero and a mean moving range of 4.5 kWh. What are the limits of an EWMA chart with λ = 0.2 and L = 3?

2. The mean of a process shifts by one standard deviation and stays there. The readings are independent and normal. How long does an individuals chart with 3-sigma limits wait, on average, for its first point beyond a limit?

3. A stable process with independent normal readings is charted for 120 days on an individuals chart with 3-sigma limits. Nothing changes. What is the chance of at least one point beyond the limits?