Simulator · Monitoring

Cold room hold time

The power fails at 2 a.m. How long until the stock is lost?

Found this useful?

Air passes 8 °C
Stock passes 8 °C
At the cursor
Heat leaking in
Predict first

The power fails in two identical cold rooms. One is full, one is nearly empty. Which keeps its stock safe for longer?

Design check
Try this
  1. Take almost all the stock out. How long before the air passes 8 °C now?
  2. Keep the door shut during the cut. How many hours does that buy?
  3. Find the insulation that holds the shop room's stock safe for a whole day.
How the numbers are worked out

Two parts warm up: the air (with shelves and the inner skin of the panels) and the stock. Heat comes in through the panels at U × A × (outside − air), with U = 0.022 W/m·K divided by the insulation thickness, and with the warm air that enters at each door opening (a third of the room's air each time). The air warms the stock through its surface, about 8 W/m²·K. Both are worked out minute by minute. The stock is one lump, so its middle stays colder than its surface for a while: real cartons warm from the outside in.

This is why a monitored cold room carries a probe in the product, not only one in the air: the air tells you the power is off; the product tells you how long you have. The lesson cold room energy balance works through the heat loads.